Transcript
SDR-75 series
75W Single Output Industrial DIN RAIL with Power Supply ■
SE
SPECIFICATION MODEL
OUTPUT
www.tuv.com ID 2000000000
SDR-75-24
SDR-75-48
12V
24V
48V
RATED CURRENT
6.3A
3.2A
1.6A
CURRENT RANGE
0 ~ 6.3A
0 ~ 3.2A
0 ~ 1.6A
RATED POWER
75.6W
76.8W
76.8W
PEAK CURRENT
9.375A
4.69A
2.34A
PEAK POWER Note.6
112.5W (3 sec.)
RIPPLE & NOISE (max.) Note.2 100mVp-p
100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V ? 1.0%
48 ~ 55V ? 1.0%
LINE REGULATION
? 0.5%
? 0.5%
? 0.5%
LOAD REGULATION
? 1.0%
? 1.0%
? 1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC
VOLTAGE RANGE
80ms/230VAC Note.7 88 ~ 264VAC
3000ms, 60ms/115VAC at full load
20ms/115VAC at full load 124 ~ 370VDC [DC input operation possible by connecting AC/L(+),AC/N(-)]
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
88.5%
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
1.4A/115VAC 30A/115VAC
LEAKAGE CURRENT
<1mA / 240VAC Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-powr on to recover
OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & ISOLATION RESISTANCE EMC EMC EMISSION
(Note 4)
EMC IMMUNITY MTBF DIMENSION PACKING NOTE
47
SDR-75-12
HOLD UP TIME (Typ.)
OTHERS
IF
DC VOLTAGE
12 ~ 14V VOLTAGE TOLERANCE Note.3 ? 1.0%
INPUT
Bauar t gepruft Sicherheit egel ma ge od o s be wac g
PQ
M
89%
90%
0.85A/230VAC 50A/230VAC
150 ~ 170% rated power, constant current limiting with auto-recovery within 3 seconds, and then shut down o/p voltage after 3 seconds, re-powr on to recover 14 ~ 17V 29 ~ 33V Protection type : Shut down o/p voltage, re-power on to recover
56 ~ 65V
100℃±10℃ (RTH2) detect on main of power transistor Protection type : Shut down o/p voltage, re-powr on to recover after temperature goes down -30 ~ +70℃ (Refer to "Derating Curve") 20 ~ 95% RH non-condensing -40 ~ +85℃, 10 ~ 95% RH ±0.03%/℃ (0 ~ 60℃ Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved, design refer to GL ;(meet EN60204-1) I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH Compliance to EN55022 (CISPR22). EN61204-3 Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47 approved 481.9K hrs min. MIL-HDBK-217F (25℃) 32*125.2*102mm (W*H*D) 0.51Kg; 28pcs/15.3Kg/1.22CUFT
℃ File Name:SDR-75-SPEC 2015-10-29
SDR-75 series
75W Single Output Industrial DIN RAIL with Power Supply Mechanical Specification
Unit:mm
102
Case No.
125.2 TB2 32
DC OK +V ADJ.
1 2 TB1 3
1 2 3 4
Terminal Pin No. Assignment (TB1)
35
Pin No. 1 2 3
Assignment FG AC/N OR DC(-) AC/L OR DC(+)
Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Block Diagram
I/P
Assignment DC OUTPUT -V DC OUTPUT+V
fosc : 85KHz EMI FILTER & RECTIFIERS
POWER SWITCHING
RECTIFIERS & FILTER
+V -V O.C.P.
O.L.P. FG O.T.P.
PWM & PFC CONTROL
DETECTION CIRCUIT O.V.P.
File Name:SDR-75-SPEC 2015-10-29
SDR-75 series
75W Single Output Industrial DIN RAIL with Power Supply Peak Loading (1)
(2)
112.5W
112.5W
75W
37.5W 100 sec.
3 sec.
15 sec. 3 sec.
Derating Curve
Output derating VS input voltage
Others
150
100 90
For 3 sec. (typ.)
125
12V Others
75
80 70
230VAC Input only
Continuous
LOAD (%)
LOAD (%)
100
12V
60
-30 -25
60 50 40
0
10
20
30
40
50 55 60
AMBIENT TEMPERATURE (℃)
70 (VERTICAL)
88
100
110
135
155
230
264
INPUT VOLTAGE (V) 60Hz
File Name:SDR-75-SPEC 2015-10-29