MUA IID Controller Space Temperature Sensor
U3
U4
D2
COMM
(1)
PAL
RS-485 COMM
COMM PWR
RAM
EPROM TUC-5R PLUS
H.H.
(1 MEG)
YS101816 REV 2
U6
R2
R2
R3 R4
R3
LED1
R4
R5
RLY4
+VREF
COM4-5
D5
P1 LED2
COM4-5
R5
WDOG
Supply Air Temperature
R1
R1
RLY5
TEST POINT 5.11V
INPUTS
ADDRESS
PU1
AIN2
PU2
AIN3
Outside Air Temperature
PU3
AIN4 AIN5 GND
PU4 PU5 PU7
GND
1 2 4 8 16 32 TOKEN NETWORK U10
JP1 U12
TB4
AIN3
PU3
JO3
PU4
JO4
POWER EXPANSION
T’STAT
When Space Humidity Sensor Is Used Pull-up Resistor PU7 Must Be Removed
When OA Humidity Sensor Is Used Pull-up Resistor PU3 Must Be Removed
4 RLY IO. BD.
K3
24VAC
PRESSURE SENSOR
K2
H-
4 ANALOG IN MOD. I/O BD. YS101784
K4
GND
Relay Output Dry Contacts R6 Thru R21 May Be User Configured For The Following: 1 - Heating (Aux. Heating)Stages 2 - Cooling (Compressor) Stages 3 - Gas Reheat Control For Dehumidification 4 - External Heat Enable 5 - Alarm Signal 6 - Override Signal 7 - Occupied Signal 8 - Economizer
K1
H+
H+
JO2
AOUT1
AIN7 GND
Remote Occupied Contact (N.O. Input)
AIN2
GND
AOUT2
250 Ohm Resistor
JO1
PU2
AIN4
AOUT1
Outside Air Humidity
PU1
AIN1
Hood ON/OFF (N.C. Input)
0-5 VDC 0-1 VDC
AIN1
ADD
Relay Output Dry Contacts R2 Thru R5 May Be User Configured For The Following: 1 - Heating (Aux. Heating)Stages 2 - Cooling (Compressor) Stages 3 - Gas Reheat Control For Dehumidification 4 - External Heat Enable 5 - Alarm Signal 6 - Override Signal 7 - Occupied Signal 8 - Economizer
24VAC GND
+VDC
G - Fan ON/OFF Only
OE354 - 4 Analog Input, 1 Analog Output Board
U5
COM1-3
COM1-3
RLY2 D3
R
RLY3
OVR
TMP GND AUX
D4
NORMAL
T SHLD
OE357 - 4 Relay Output Board
W
A R M E R C O O L E R
RLY1
U2
H-
Space Humidty
(0-10VDC or 2-10VDC) External Modulating Heat
JOB NAME
E
250 Ohm Resistor
FILENAME
T (COM)
SS1013MUA2D.CDR X (MIN) D (FULL)
Economizer Actuator
DATE: PAGE
1
03/24/05
C
O
N
DRAWN BY:
T
R
O
L
B. Crews
DESCRIPTION:
SS1013 MUA IID Code Wiring Diagram