Ss_reflib_021404

   EMBED


Share

Transcript

Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan IGM Reference Document Including Modbus and BACnet object Listings This reference document is based on the assumption that the connecting unit is SiteScan 2000 ready and is using the SiteScan 2000 hardware specified within. Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Revision Level Updates: Revision Date B.5 B.6 B.7 B.8 B.9 B.10 B.11 B.12 11/8/00 2/19/01 4/4/02 5/3/02 10/1/02 1/22/03 7/23/03 4/19/04 B.13 5/24/04 B.14 B.16 8/19/20 04 11/22/2 004 5/18/05 B.17 7/1/05 B.18 7/21/05 B.15 Description Added: revision level update chart, HiPulse support, and NPower support Revised NPower definition Added support for HiMod LNA Revised Modbus explanation (Hi Byte / Lo Byte) Corrected NPower table (typing error) Added support for DataMate Added support for STS-2 Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for MM2 Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2. Track issue 3576 – Make BacNet points consistent with Modbus Points. Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and GXT Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for Bacnet and Modbus addressing on STS-2. Added Remote shutdown alarm to LAM. Added Note about Alarms “Bacnet auto discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is for units with or without PDU. Changed breaker status register for STS2 from bits1-8 to 0-7. Added XDC Unit. Added control point note for units with on/off control as follows: Bit 0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these registers as spares. Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Table of Contents Click on the desired page number for instant navigation. Use the "back" arrow on your toolbar to return to the table of contents. OPEN COMMUNICATIONS .................... 7 DEFAULT MAPPING FOR MODBUS & BACNET OBJECTS ..................... 7 MODBUS COMMUNICATIONS ........................................................................................ 9 Connectivity to SiteLink modules using Modbus ..................................................... 9 Implementation Basics .................................................................................................................... 9 Transmission Format ....................................................................................................................... 9 Modbus Packet Format ................................................................................................................ 10 RTU Framing ........................................................................................................................................ 11 BACNET COMMUNICATIONS ...................................................................................... 12 BACnet Protocol Implementation Conformance Statement Rev. 2.1 ................................ 12 LIEBERT ENVIRONMENTAL UNITS ........................................................................................ 16 AIR UNIT - LEVEL 0 – L00 ...................................................................................................................... 17 AIR UNIT – LEVEL 10 – L10 .................................................................................................................. 19 AIR UNIT – STANDARD MICROPROCESSOR – LSM.................................................................... 21 AIR UNIT – ADVANCED MICROPROCESSOR – LAM .................................................................. 23 AIR UNIT – SMALL SYSTEMS – L0B .................................................................................................. 26 AIR UNIT – MINI-MATE 2 – MM2, DATAMATE......................................................................... 28 AIR UNIT – 8 TON MINIMATE – L8T ................................................................................................ 31 ATLAS AIR UNIT – C10 ............................................................................................................................. 34 CHILLER UNIT – CSU3000 – CSU ..................................................................................................... 37 CHILLER UNIT – CSU 3000 W/ECONO – CSE .............................................................................. 39 AIR UNIT - HIROSS MICROFACE .......................................................................................................... 41 AIR UNIT – X-TREME DENSITY COOLANT DISTRIBUTION UNIT– CDU......................... 44 AIR UNIT – X-TREME DENSITY COOLANT PUMPING UNIT– XDP .................................... 46 AIR UNIT – X-TREME DENSITY CHILLER UNIT– XDC............................................................ 49 LIEBERT POWER UNITS ..................................... 52 POWER UNIT – VOLTAGE- CURRENT MONITORING PANEL – VCM................................. 53 POWER UNIT – POWER MONITORING PANEL – PMP ................................................................ 55 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development POWER UNIT – VOLTAGE-CURRENT-FREQ. MONITOR PANEL – VCF ............................ 58 POWER UNIT – POWER MONITORING PANEL (EXT. PROTOCOL) – PM2 ...................... 60 POWER UNIT – STATIC TRANSFER SWITCH PDU – EDS ........................................................ 63 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS ....................... 66 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS-2 ................... 69 LIEBERT UPS UNITS ..................................... 73 UPS UNIT – MULTI MODULE UPS – S600 EXTENDED PROT. – MM4 .......................... 74 UPS UNIT – MULTI MODULE SERIES – MMS .............................................................................. 77 UPS UNIT – SYSTEM CONTROL CABINET – S600 EXT. PROT. – SC4 ............................ 79 UPS UNIT – SYSTEM CONTROL CABINET – SCC ....................................................................... 82 UPS UNIT – SINGLE MODULE SERIES – SMS .............................................................................. 84 UPS UNIT – SINGLE MODULE UPS – S600 EXT. PROT. – SM4 ........................................ 86 UPS UNIT – MULTI-MODULE SICE 7200 & HIPULSE UPS – SMM.............................. 90 UPS UNIT – SYSTEMS CABINET SICE 7200 UPS – SSC ...................................................... 95 UPS UNIT – SINGLE MODULE SICE 7200 & HIPULSE UPS – SSM ............................... 98 UPS UNIT – UPSTATION S – DCU .................................................................................................. 103 UPS UNIT – UPSTATION S3 – US3 ................................................................................................. 106 UPS UNIT – SINGLE MODULE SERIES AP301/302 – SM3 .................................................. 109 UPS UNIT – SINGLE MODULE UPS – NPOWER -- IMP ........................................................ 112 UPS UNIT – SINGLE MODULE UPS – NX -- PNX................................................................... 116 UPS UNIT – HINET – PHN ................................................................................................................... 121 UPS UNIT – NFINITY – PNF................................................................................................................ 123 UPS UNIT – GXT – PGX ...................................................................................................................... 127 UPS UNIT – PSI – PPS ........................................................................................................................... 131 LIEBERT MONITORING MODULES.. 134 CONTACT CLOSURE MODULE – CCM............................................................................................. 135 WATER/LIQUID DETECTION UNIT – WDU ................................................................................... 138 REMOTE AUTOCHANGEOVER – RAC............................................................................................... 139 TEMPERATURE/HUMIDITY MODULE – THM ............................................................................... 141 WATER/LIQUID DETECTION UNIT LDS5000 – WD5 ............................................................. 144 UNIVERSAL MONITOR – UVM ............................................................................................................ 145 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development How to use the Reference Library Charts This document contains a dedicated sheet for each Liebert Unit and associated controller. The title of each chart contains the name of the Liebert Controller used such as L00 for a Level-0 Air unit or PMP for a Power Monitoring Panel for Power Center. The first section, Compatible Hardware, indicates the equipment associated with this particular controller as follows: Liebert Units SiteScan Interface Modules BMS interface Modules Indicates the Environmental, Power, UPS or Monitoring Module by model name that uses this controller. Indicates which SiteScan Hardware Modules can be used with the controller. Take Special note of this box when adding new units to an existing SiteScan system, as some new controllers are only compatible with the new hardware (SiteLink). Indicates which SiteScan Hardware Modules can be used with the controller for interfacing with a third part using BACnet or Modbus protocol. The next section, Available Points, contains six categories providing the following information: Status Points (View) Alarm Points Setpoints (View) Control Points (Set) Trendable Points (Set) Reports Status Information for the listed points that will be presented in SiteScan Alarms that are available to SiteScan Current settings of controllable Setpoints available to SiteScan Setpoints that can be changed with SiteScan Points that can be graphically trended within the SiteScan software Reports that can be triggered within the SiteScan software Page 5 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Liebert Unit ID Chart 3-Letter ID L00 Environmental Products Level 00, Level 1 3-Letter ID SMS L10 Level 2, Level 3, and Level 10 SM3 LAM Level 15 and Level AM/AG, HiMod (LNA) Level SM and Level 0 w/ On/Off Control Small Systems Controller SM4 LSM L0B MM2 US3 MMS SSC IMP PNX NPower (S300 Replacement) NX UPS – ESP2 Protocol PHN HiNet UPS – ESP2 Protocol PNF PGX Nfinity UPS – ESP2 Protocol GXT UPS – ESP2 Protocol PPS PSI UPS – ESP2 Protocol MM4 CSE CSU Chiller SSM XDP SMM THM WDU Xtreme Density Unit Environmental Control Xtreme Density Coolant Distibution Unit Static Switch PDU Static Switch PDU (Single Output Breaker, Prior to 1/99) Static Switch PDU (Dual Output Breaker Option, 1/99 or later) Miscellaneous All IGM Contact Modules CM200 / RCM8 / VSM Remote Autochangeover Module RAC2-8 Temperature / Humidity Module Liquid Detection LDS750 or LDS1000 WD5 Liquid Detection LDS5000 VCF UVM Universal Monitor VCM CDU EDS STS CCM RAC SCC SC4 PMP PM2 Page 6 of 148 Single Module Series UPS - S300, S500, S600 (Prior to 1/98) Single Module Series 30x (latest version) Single Module Series 600 - Extended Protocol (1/98 or later) UPStation S3 UPS Multi Module Series 500-600 UPS (Prior to 1/98) Multi Module Series 600 UPS Extended Protocol (1/98 or later) System Control Cabinet Series 500600 (Prior to 1/98) System Control Cabinet Series 600Extended Protocol (1/98 or later) Single Module Series UPS - SICE 7200 & HiPulse Multi Module Series UPS - SICE 7200 & HiPulse System Control Cabinet - SICE 7200 Small Systems Controller - Mini Mate II, DataMate Atlas Air Environmental Control (LECS15) Chiller w/ Econocoil C10 UPS Products Power Products PDU Precision Power & Datawaves w/ PMP (latest LCD display) All Voltage-Current-Frequency Panels (Old Red LED Display) All Voltage-Current Monitoring Panels (Old Red LED Display) Precision Power & Datawaves w/ PMP (latest LCD display and extended protocol EPROM version 3.290.0, manufactured and shipped after 4/99) Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Open Communications Default Mapping for Modbus & BACnet Objects This model represents the standard configuration for a Liebert Sitelink-12 module. Consecutive register / object mapping is utilized, regardless of the SiteLink-12 population. All ports that do not have a Liebert IGM attached will be assigned "null values" (or zero's) for their corresponding registers. The default “slave ID” or “Device ID” follows the CMnet address of the unit. The address can be visually checked by looking at the address dip-switch or rotary switch settings. However, the address can be changed in software to suit specific needs. How to use this table: The unit or model specific reference sheets assumes that the desired unit is attached to port 1 of the SiteLink module. If the desired unit is attached to a different port, the table below indicates the starting register or object number for the unit. For example: The register for “temperature” for a L00 type unit attached to port 1 is identified as 40001. If an additional L00 type unit were attached to port 2, the “temperature” value would be located in register 40025. The same type unit attached to port 3 = 40049…etc. Modbus Notes: • Modbus Registers start at 40001. • All registers are unsigned integers. BACnet Notes: • BACnet Objects start at 1. • All “Status” and “Alarm” objects are “AI’s” (analog inputs). • The “Control” objects are “AO’s” (analog outputs) Page 7 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Register Offset 1-24 25-48 49-72 73-96 97-120 121-144 145-168 169-192 193-216 217-240 241-264 265-288 Object Type Status Status Status Status Status Status Status Status Status Status Status Status Port Assignment 1 2 3 4 5 6 7 8 9 10 11 12 289-293 294-298 299-303 304-308 309-313 314-318 319-323 324-328 329-333 334-338 339-343 344-348 Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms Alarms 1 2 3 4 5 6 7 8 9 10 11 12 349-351 352-354 355-357 358-360 361-363 364-366 367-369 370-372 373-375 376-378 379-381 382-384 Control Control Control Control Control Control Control Control Control Control Control Control 1 2 3 4 5 6 7 8 9 10 11 12 ** See reference libraries for unit specific objects. Page 8 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Modbus Communications Connectivity to SiteLink modules using Modbus This design specification describes the Modbus communications protocol as supported by the SiteLink module. It includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to help facilitate answering questions regarding supported types, frame format, function code support etc. Implementation Basics Protocol controls the language structure or message format between devices in other words, the rules for communication. The rules for communication include how master and slave devices initiate communications, as well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of the query and response cycles between master and slave devices. The SiteLink module is configured to act as a slave device on a common network. The common network can be point-to-point over EIA-232, where one master communicates to one slave device or in a multidrop configuration over EIA-485, where multiple slaves reside on a common wire or loop. Transmission Format The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud rate, character parity and number of stop bits. See chart below. Physical Port EIA-232 – DB9 DCE EIA-232 – DB9 DCE Transmission Mode RTU Baud Rate Data Bits Parity Bits Stop Bits Default 9600 8 None 1 Yes ASCII Configurable Configurable Configurable No EIA-485 – 2 or 4 wire RTU or ASCII 1200 – 38.4kbd (19.2kbd omit) 1200 – 38.4kbd (19.2kbd omit) Configurable Configurable Configurable No Page 9 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Modbus Packet Format Each Modbus packet consists of the following fields: • Device Address • Function Code • Data Field(s) • Error Check Field Device Address: The address field immediately follows the beginning of the frame and consists of 8-bits (RTU) or 2 characters (ASCII). These bits indicate the user assigned address of the slave device that is to receive the message sent by the attached master device. Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address. Function Code: The function code field tells the addressed slaves what function to perform. Function codes are specifically designed invoke a specific action by the slave device. The function code range is from 1 to 127. However, the SiteLink module primarily uses Function Code 3 (Read Holding Registers), Function Code 6 (Preset Single Register) and Function Code 16 (Preset Multiple Registers). Data Field(s): The data field varies in length depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to pass back data to the master device. Error Check Field: The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted with transmission errors. Page 10 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development RTU Framing The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including next 2 Registers (3 total). Query Sample Slave Address Function Code 02 03 Starting Register “Hi Byte” Starting Register “Lo Byte” Number of Registers “Hi Byte” Number of Registers “Lo Byte” CRC16 CRC16 “Hi Byte” “Lo Byte” 00 32 00 03 E5 FA Count: Bytes of Data Register 40051 Data Hi Lo Register 40052 Data Hi Lo Register 40053 Data Hi Lo CRC16 CRC16 “Hi Byte “Lo Byte” 1B 0D Response Sample Slave Address Function Code 02 03 6 01 58 00 FA 00 54 Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum. Register values: 40051 = 158(hex) = 344(decimal) 40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 84 (decimal) ASCII Framing: Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a synchronizing character which indicates that the transmitting station is ready to receive an immediate reply. ASCII Example Frame Start Slave Address Function Code Data Error Check End of Frame CR Ready for Data LF : 2 Char 2 Char N x 4 Char B3 0D 0A 16-bits 16-bits N x 16-bits Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional) Page 11 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development BACnet Communications BACnet Protocol Implementation Conformance Statement Vendor Name: Liebert Corporation Product Name: SiteLink Module Rev. 2.1 Product Model Number: SiteLink-DC12i, SiteLink-DC4i, SiteLink-12, and SiteLink-4 Product Description: The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12 port and 4 port configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.) Class 1 Class 2 Class 3 BACnet Conformance Class Supported: Class 4 Class 5 x Class 6 BACnet Functional Groups Supported: Clock HHWS PCWS Event Initialization Event Response COV Event Initiation COV Event Response Files Reinitialize Virtual Operator Interface Virtual Terminal Device Communications Time Master Page 12 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development BACnet Standard Application Services Supported: Application Service Initiate Execute Requests Requests AcknowledgeAlarm ConfirmedCOVNotification ConfirmedEventNotification GetAlarmSummary GetEnrollmentSummary SubscribeCOV UnconfirmedCOVNotification UnconfirmedEventNotification AtomicReadFile AtomicWriteFile AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple WriteProperty WritePropertyMultiple DeviceCommunicationControl ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ReinitializeDevice ConfirmedTextMessage TimeSynchronization Who-Has I-Have Who-Is I-Am X X X X X X X X X X VT-Open VT-Closed VT-Data Authenticate Request Key Page 13 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development BACnet Standard Application Services Supported (continued): Supported Dynamically Dynamically Optional Creatable Deleteable Properties X Analog Input X Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-State Input Multi-State Output Notification Class Program Schedule Object Type Data Link Layer: Point-to-Point, EIA-232, baud rates: 9600 & 38,400 Character Set Supported: ANSI X3.4 Segmented Requests Supported Segmented Responses Supported Router Special Functionality: No No No Page 14 of 148 Writable Properties None Present Value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Page 15 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Liebert Environmental Units Page 16 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit - Level 0 – L00 Hardware Compatibility Liebert Units: Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4 SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 1 2 3 4 5 6 7 8 9 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x Alarm Points Communications High Head Pressure 1 High Head Pressure 2 Loss of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Local Alarm High Water Humidifier Pan Notes: 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff Discrete BACnet alarm objects available – use auto-discover for this unit 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40289:11 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 289:11 Page 17 of 148 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance 40010 40011 40012 40013 10 11 12 13 BS10_x BS11_x BS12_x BS13_x Control Points (Set) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance 40350 40350 40351 40351 350 350 351 351 BC02_x BC02_x BC03_x BC03_x Trendable points (Set) Temperature Humidity Reports Trend Status Page 18 of 148 Notes: Multiply desired value by 1000 Multiply desired value by 1000 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – Level 10 – L10 Hardware Compatibility Liebert Units: Modular Plus, Deluxe System/3, Industrial Cooling Series SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Alarm Points Communications High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Compressor 1 Overload Compressor 2 Overload Main Fan Overload Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 1 2 3 4 5 6 7 8 9 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 Page 19 of 148 Notes: 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Short Cycle Loss of Power Inverter Bypass Standby Fan On Loss of Emergency Power Local Alarm 1 Local Alarm 2 Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Setpoint Low Temperature Setpoint High Humidity Setpoint Low Humidity Setpoint Auto-Restart Delay Control Points (Set) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA04_x:05 40010 40011 40012 40013 40014 40015 40016 40017 10 11 12 13 14 15 16 17 BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x 40350 40350 40351 40351 350 350 351 351 BC02_x BC02_x BC03_x BC03_x Trendable Points (Set) Temperature Humidity Reports Trend Status Page 20 of 148 Notes: Multiply desired value by 1000 Multiply desired value by 1000 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – Standard Microprocessor – LSM Hardware Compatibility Liebert Units: Challenger 3000. Deluxe System / 3, ICS , System 4 (Replaces L0A control) SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40014 1 2 3 4 5 6 7 8 9 14 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS14_x Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Local Alarm 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 Page 21 of 148 Notes: 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance 40010 40011 40012 40013 10 11 12 13 BS10_x BS11_x BS12_x BS13_x Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance 40349 40350 40350 40351 40351 349 350 350 351 351 BC01_x BC02_x BC02_x BC03_x BC03_x Trendable Points (Set) Temperature Humidity Reports Trend Status Page 22 of 148 Notes: Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – Advanced Microprocessor – LAM Hardware Compatibility Liebert Units: Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A) HiMod (LNA version) SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40018 1 2 3 4 5 6 7 8 9 18 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Liquid Detected Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem No Water in Humidifier Pan Notes: 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off Discrete BACnet alarm objects available – use auto-discover for this unit 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 Page 23 of 148 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register Compressor 1 Overload Compressor 2 Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Standby Unit On Low Suction Short Cycle Loss of Power Inverter on Bypass Standby Fan On Loss of Emergency Power Local Alarm 1 Local Alarm 2 Off by Remote Shutdown RunTimes (View) Compressor 1 Run Hours Compressor 2 Run Hours Glycol Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Reheat 2 Run Hours Reheat 3 Run Hours Chilled Water Valve Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temp Alarm Setpoint Low Temp Alarm Setpoint High Humd Alarm Setpoint Low Humidity Alarm Setpoint 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 40291:6 40291:7 40291:8 BACnet Instance (Exec. 6 Modules) 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 291:7 291:9 BACnet Instance (Exec. B Modules) BA02:04_x BA02:05_x BA02:06_x BA02:07_x BA02:08_x BA02:09_x BA02:10_x BA03:00_x BA03:01_x BA03:02_x BA03:03_x BA03:04_x BA03:05_x BA03:06_x BA03:07_x BA03:08_x 40019 40020 19 20 BS19_x BS20_x 40021 40022 21 22 BS21_x BS22_x 40010 40011 40012 40013 40014 40015 40016 40017 10 11 12 13 14 15 16 17 BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x Page 24 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40349 40350 40350 40351 40351 40349 40349 349 350 350 351 351 349 349 BC01_x BC02_x BC02_x BC03_x BC03_x BC01_x BC01_x Trendable Points (Set) Temperature Humidity Reports Trend Status Page 25 of 148 Notes: Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000 Bit 2 on=RH off Bit 3 on=RH on Bit 4 on=HL off Bit 5 on=HL on Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – Small Systems – L0B Hardware Compatibility Liebert Units: Datamate, Mini-Mate, Mini-Mate Plus SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Unit On/Off Alarm Points Communications Local Off Remote Off High Temperature Low Temperature High Humidity Low Humidity Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40011 1 2 3 4 5 6 7 8 9 11 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS11_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 289:0 289:1 289:2 289:3 289:4 289:5 289:6 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 40349 349 BC01_x Notes: 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff Setpoints (View) None Control Points (Set) Remote On/Off Page 26 of 148 Bit 0 on=unit off Bit 1 on=unit on Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Trendable Points (Set) Temperature Humidity Reports Trend Status Page 27 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – Mini-Mate 2 – MM2, DataMate Hardware Compatibility Liebert Units: Mini-Mate 2, DataMate SiteScan Interface Modules: SiteLink BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification Dehumidification Econ-o-Cycle Stages % Capacity Unit On/Off Alarm Points Communications Local Off Remote Off High Head Pressure 1 Loss of Airflow Standby Glycol Unit On Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Smoke Detected Loss of Water Standby Unit On Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40018 1 2 3 4 5 6 7 8 9 18 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x 40289:0 40289:1 40289:2 40289:3 40289:5 40289:6 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:8 40290:9 40290:10 289:0 289:1 289:2 289:3 289:5 289:6 289:8 289:9 289:10 290:0 290:1 290:2 290:8 290:9 290:10 BA01_x:00 BA01_x:01 BA01_x02 BA01_x:03 BA01_x:05 BA01_x:06 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:08 BA02_x:09 BA02_x:10 Page 28 of 148 Notes: 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40291:1 40291:2 40291:6 291:1 291:2 291:6 BA03_x:01 BA03_x:02 BA03_x:06 40019 40020 40021 19 20 21 BS19_x BS20_x BS21_x 40010 40011 40012 40013 40014 10 11 12 13 14 BS10_x BS11_x BS12_x BS13_x BS14_x 40015 15 BS15_x 40016 40017 16 17 BS16_x BS17_x Control Points (Set) Remote On/Off Temperature Setpoint Temperature Tolerance 40349 40350 40350 349 350 350 BC01_x BC02_x BC02_x Humidity Setpoint Humidity Tolerance 40351 40351 351 351 BC03_x BC03_x Notes: Alarm Points Short Cycle Loss of Power Local Alarm 1 Run Times (View) Compressor 1 Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Chilled Water Valve Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Alarm Setpoint Low Temperature Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint Reports Trend Status Trendable Points (Set) Temperature Humidity Page 29 of 148 Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 (ModBus & BACNet 2.6 only) Multiply desired value by 1000 (ModBus & BACNet 2.6 only) Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Note: For SSWeb BACnet the format of the BACnet object name is as follows. BS01_x Where x is the port number on the Sitelinks. There may be other point numbers that show up in a BACNet capture, but only the point numbers in the above table will be supported for third-party use. Page 30 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – 8 Ton MiniMate – L8T Hardware Compatibility Liebert Units: Minimate - 8 Ton only SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Humidity Cooling Heating Humidification De-humidification Econ-O-Cycle Stages % Capacity Unit Status (On / Off) Alarm Points Communications Local Off Remote Off High Head Pressure 1 High Head Pressure 2 Loss of Airflow Standby Glycol Unit On Not Used Change Filters High Temperature Low Temperature High Humidity Low Humidity Humidifier Problem Not Used Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40018 1 2 3 4 5 6 7 8 9 18 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS18_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x00 BA02_x01 BA02_x02 BA02_x03 Page 31 of 148 Notes: 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off 1=on / 0=off Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Not Used Not Used Not Used Not Used Smoke Detected Loss of Water Standby Unit On Not Used Short Cycle Loss of Power Not Used Not Used Not Used Local Alarm 1 Local Alarm 2 Run Times (View) Compressor 1 Run Hours Compressor 2 Run Hours Glycol Run Hours Fan Motor Run Hours Humidifier Run Hours Reheat 1 Run Hours Reheat 2 Run Hours Reheat 3 Run Hours Chilled H2O Valve Run Hours Setpoints (View) Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance High Temperature Alarm Setpoint Low Temp Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 40290:10 40291:0 40291:1 40291:2 40291:3 40291:4 40291:5 40291:6 40291:7 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 291:7 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 40019 40020 19 20 BS19_x BS20_x 40021 40022 21 22 BS21_x BS22_x 40010 40011 40012 40013 40014 10 11 12 13 14 BS10_x BS11_x BS12_x BS13_x BS14_x 40015 40016 40017 15 16 17 BS15_x BS16_x BS17_x Page 32 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Control Points (Set) Unit On / Off Temperature Setpoint Temperature Tolerance Humidity Setpoint Humidity Tolerance Reheat Lockout Humidifier Lockout Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40349 40350 40350 40351 40351 40349 40349 349 350 350 351 351 349 349 BC01_x BC02_x BC02_x BC03_x BC03_x BC01_x BC01_x Trendable Points (Set) Temperature Humidity Reports Trend Status s Page 33 of 148 Notes: Bit 0 on=unit off Bit 1 on=unit on Multiply desired value by 1000 Multiply desired value by 1000 Bit 2 on=RH off Bit 3 on=RH on Bit 4 on=HL off Bit 5 on=HL on Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Atlas Air Unit – C10 Hardware Compatibility Liebert Units: Atlas Air; LECS 15 SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Unit Number Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Activation Mode Fan Status Cool 1 Status Cool 2 Status Heat 1 Status Heat 2 Status Humidifier Status De-humidifier Status Cooling Capacity Heating Capacity Active Operation (Days) Active Operation (Hours) Cool Mode (Days) Cool Mode (Hours) Heat Mode (Days) Heat Mode (Hours) Humidifier Mode (Days) Humidifier Mode (Hours) De-humidifier Mode (Days) De-humidifier Mode (Hours) Cool 1 Operating Mode (Days) Cool 1 Operating Mode (Hours) Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x Page 34 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Cool 2 Operating Mode (Days) Cool 2 Operating Mode (Hours) Fan Operation (Days) Fan Operation (Hours) Heat 1Operating Mode (Days) Heat 1Operating Mode (Hours) Heat 2 Operating Mode (Days) Heat 2 Operating Mode (Hours) Humidify Operating Mode (Days) Humidity Operating Mode (Hours) Cool Service (Days) Cool Service (Hours) Filter Service (Days) Filter Service (Hours) Humidifier Service (Days) Humidifier Service (Hours) Temperature Control Status Battery Voltage Level Remote Shutdown Status General Alarm Status Audible Alarm Status Temperature Control Select Alarm Points Communications Faulty Sensor High Temperature Low Temperature High Humidity Low Humidity Loss of Airflow Water Under Floor Cool 1 Low Pressure Alarm Cool 2 Low Pressure Alarm Cool 1 High Pressure Alarm Cool 2 High Pressure Alarm Cool Service Humidifier Service Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40019 40020 40021 40022 40023 40024 19 20 21 22 23 24 BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 Page 35 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Filter Service Humidity Low Level Battery Level Low Loss of Power Spare 1 Spare 2 Setpoints (View) Unit Status (On / Off) Return Air Temperature Return Air Humidity Supply Air Temperature High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Start up Delay Control Points (Set) Unit Status (On / Off) Return Air Temperature Return Air Humidity Supply Air Temperature High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm Start up Delay Trendable Points (Set) Average Return Air Temp. Average Return Air Humidity Average Supply Air Temp. Average Supply Air Humidity Reports Trend Status Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:3 40290:4 40290:5 40290:6 40290:7 40290:8 290:3 290:4 290:5 290:6 290:7 290:8 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 40016 40017 40018 16 17 18 BS16_x BS17_x BS18_x 40349 40350 40351 349 350 351 BC01_x BC02_x BC03_x Page 36 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Chiller Unit – CSU3000 – CSU Hardware Compatibility Liebert Units: Chiller CSU-3000 SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Number of Modules Module 1 Start Module 1 Pump Module 1 Cool Module 2 Start Module 2 Pump Module 2 Cool Module 3 Start Module 3 Pump Module 3 Cool Alarm Points Communications Mod 1 High Head Pressure Mod 2 High Head Pressure Mod 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp. Module 2 High Water Temp. Module 3 High Water Temp. Module 1 Low Water Temp. Module 2 Low Water Temp. Module 3 Low Water Temp. Module 1 No Power Module 2 No Power Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 1 2 3 4 5 6 7 8 9 10 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 Page 37 of 148 Notes: 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Module 3 No Power Module 1 Liquid Detected Module 2 Liquid Detected Module 3 Liquid Detected Local Alarm 1 Local Alarm 2 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:4 40290:5 40290:6 40290:7 40290:8 40290:9 290:4 290:5 290:6 290:7 290:8 290:9 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status Page 38 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Chiller Unit – CSU 3000 w/Econo – CSE Hardware Compatibility Liebert Units: Chiller CSU-3000 SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) System Econ-o-Cycle Number of Modules Module 1 Start Module 1 Pump Module 1 Cool Module 2 Start Module 2 Pump Module 2 Cool Module 3 Start Module 3 Pump Module 3 Cool Module 1 Econ-o-Cycle Module 2 Econ-o-Cycle Module 3 Econ-o-Cycle Alarm Points Communications Mod 1 High Head Pressure Mod 2 High Head Pressure Mod 3 High Head Pressure Module 1 No Water Flow Module 2 No Water Flow Module 3 No Water Flow Module 1 High Water Temp. Module 2 High Water Temp. Module 3 High Water Temp. Module 1 Low Water Temp. Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 1 2 3 4 5 6 7 8 9 10 11 12 13 14 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 Page 39 of 148 Notes: 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=START / 0=STOP 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF 1=ON / 0=OFF Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Module 2 Low Water Temp. Module 3 Low Water Temp. Module 1 No Power Module 2 No Power Module 3 No Power Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:0 40290:1 40290:2 40290:3 40290:4 290:0 290:1 290:2 290:3 290:4 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 Setpoints (Set) None Control Points (Set) None Trendable Points (Set) None Reports Status Page 40 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit - Hiross Microface Hardware Compatibility Liebert Units: Liebert Hiross Microface SiteScan Interface Modules: SiteLink (All) BMS interface Modules: Liebert Hiross Hirolink Available Points SiteScan Availability Modbus Register Status Points (View) Unit On Off Heater Working Hours Humidifier Working Hours Compressor 1 Working Hours Conditioner Working Hours Low Humidity Warning High Humidity Warning Low Temperature Warning High Temperature Warning Humidity Proportional Band Temperature Proportional Band Room Humidity Setpoint Room Temperature Setpoint 1 Compressor 2 Working Hours Free-cooling Working Hours Cooling Ramp Status Dehumidification Status Electrical Heater 2 Status Electrical Heater 1 Status Compressor 1 Humidifier Current Room Humidity Room Temperature Status Compressor 2 Free-cooling Status Page 41 of 148 BACnet Instance Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Smoke Alarm No Power (User Input) Power On (User Input) User Input 2 Triggered User Input 2 Triggered No Connection To Unit 1 Compressor 1 Motor Protection Compressor 2 Motor Protection Fire Alarm Out Of Memory Condenser 1 Fan Failure Condenser 2 Fan Failure Network Ping Subgroup-Id Not Unique Subgroup-Unit 1 Not Connected Subgroup-Unit 2 Not Connected Share Rm. Sensor Failure Warn Share Rm. Sensor Failure Alarm Share Outdoor Temp Sensor Share Glycol Temp Sensor Unit Synch (Short Reset) Humidifier High Temperature Humidifier Overflow Modbus Register Setpoints (View) Room Temperature Setpoint 1 Temperature Proportional Band Room Humidity Setpoint Humidity Proportional Band High Temperature Alarm Setpoint Low Temp Alarm Setpoint High Humidity Alarm Setpoint Low Humidity Alarm Setpoint Page 42 of 148 BACnet Instance Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Control Points (Set) Unit On/Off Humidity Proportional Band Temperature Proportional Band Room Humidity Setpoint Room Temperature Setpoint Modbus Register Trendable Points (Set) Temperature Humidity Reports Trend Status Page 43 of 148 BACnet Instance Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – X-Treme Density Coolant Distribution Unit– CDU Hardware Compatibility Liebert Units: X-Treme Density Coolant Ditribution Unit SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Valve % Open Pump 1 Status Pump 2 Status Fluid Level Fluid Temperature Stop Valve Purge Valve FMS Disable Rate Of Change Local Temp Local Humidity Local Dewpoint Remote Temp Remote Humidity Remote Dewpoint Unit Status Alarm Points Communications Local Off Remote Off Loss Of Flow P1 Loss Of Flow P2 Pump Short Cycle Spare 5 Leak Detected Valve Failure Customer Alarm 1 Fan Fail High Fluid Temp Low Fluid Temp Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 Page 44 of 148 Notes: 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 43=C / 46=F Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Fluid Sensor Problem High Remote Temp Low Remote Temp Remote Sensor Problem High Local Temp Low Local Temp Local Sensor Problem Low Pressure High Fluid Level Low Fluid Level Low Low Level Fluid Level ROC System Purge P1 Emergency Purge FMS Power Loss Loss Of Power Setpoints (View) Temperature Setpoint High Fluid Temp Setpoint Temp Scale High Air Temp Low Air Temp Dewpoint Margin Restart Delay Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 290:2 290:3 290:4 290:5 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 291:3 291:4 291:5 291:6 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 40017 40018 17 18 BS17_x BS18_x 40019 40020 40021 40022 19 20 21 22 BS19_x BS20_x BS21_x BS22_x 40349 40350 40351 49 50 51 BC01_x BC02_x BC03_x Trendable Points (Set) Temperature Humidity Dewpoint Reports Trend Status Page 45 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – X-Treme Density Coolant Pumping Unit– XDP Hardware Compatibility Liebert Units: X-Treme Density Coolant Pumping Unit SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Status Points (View) Valve % Open Pump 1 Status Pump 2 Status Fluid Temperature Chilled Water Temperature Unit Status Scale F or C Local Temperature Local Humidity Local Dewpoint Remote Temperature Remote Humidity Remote Dewpoint 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 1 2 3 4 5 6 7 8 9 10 11 12 13 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x Alarm Points Communications Local Off Remote Off Loss Of Flow P1 Loss Of Flow P2 Pump Short Cycle Condensation Refrigerant Leak Valve Failure Customer Alarm 1 Fan Failure Alarm High Chilled Water Temp Low Chilled Water Temp Failed Chilled Water Sensor High Remote Temp Low Remote Temp 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 Page 46 of 148 Notes: 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 43=C / 46=F Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Remote Sensor Problem 40290:05 290:5 Page 47 of 148 BA02_x:05 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 290:6 290:7 290:8 290:9 290:10 291:0 291:1 291:2 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 40014 14 BS14_x 40015 40016 40017 40018 40019 15 16 17 18 19 BS15_x BS16_x BS17_x BS18_x BS19_x 40349 40350 40351 49 50 51 BC01_x BC02_x BC03_x Alarm Points High Local Temp Low Local Temp Local Sensor Problem Low Pressure High Refrigerant Temp Low Refrigerant Temp Failed Refrigerant Sensor Loss Of Power Setpoints (View) Temperature Setpoint Temperature Scale High Chilled Water Temp High Air Temp Low Air Temp Dewpoint Margin Restart Delay Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin Trendable Points (Set) Temperature Humidity Dewpoint Reports Trend Status Page 48 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Air Unit – X-Treme Density Chiller Unit– XDC Hardware Compatibility Liebert Units: X-Treme Density Chiller Unit SiteScan Interface Modules: SiteLink-12, SiteLink-4 BMS interface Modules: SiteLink-12, SiteLink-4 Available Points SiteScan Availability Status Points (View) Pump 1 Status Pump 2 Status Cooling % Compressor 1A status Compressor 1B status HG Valve1 % Compressor 2A status Compressor 2B status HG Valve2 % Refer Temp 1 Refer Temp 2 CW Temp Unit Status Scale F or C Local Temp Local Humidity Local Dew Point Remote Temp Remote Humidity Remote Dew Point Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x 1=On / 0=Off 1=On / 0=Off 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 N/A N/A N/A N/A N/A N/A N/A N/A N/A BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 Alarm Points Communications Local Off Remote Off Loss Of Flow Pump 1 Loss Of Flow Pump 2 Pump Short Cycle Customer Alarm 1 Condensation Fan Failure Alarm Page 49 of 148 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 1=On / 0=Off 43=C / 46=F Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 40021 40022 40023 N/A N/A N/A BS21_x BS22_x BS23_x Alarm Points High Local Temperature Low Local Temperature Local Sensor Problem High Remote Temperature Low Remote Temperature Remote Sensor Problem High Dewpoint High Head Compressor 1a High Head Compressor 1b High Head Compressor 2a High Head Compressor 2b Low Suction P Tandem 1 Low Suction P Tandem 2 Short Cycle Compressor 1a Short Cycle Compressor 1b Short Cycle Compressor 2a Short Cycle Compressor 2b High Refrigerant Temp 1 Low Refrigerant Temp 1 Failed Refrigerant Sensor 1 High Refrigerant Temp 2 Low Refrigerant Temp 2 Failed Refrigerant Sensor 2 High Chilled Water Temp Low Chilled Water Temp Failed Chilled Water Sensor Valve Failure Loss Of Power Setpoints (View) Temp Setpoint High Temp Setpoint Low Temp Setpoint Page 50 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Control Points (Set) Unit On / Off Temperature Setpoint Dewpoint Margin Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40349 40350 - N/A N/A N/A BC01_x BC02_x - Trendable Points Temperature Humidity Dewpoint Reports Trend Page 51 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Liebert Power Units Page 52 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Voltage- Current Monitoring Panel – VCM Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA Alarm Points Communications Output Undervoltage Output Overvoltage Transformer Overtemp Local Alarm #1 Local Alarm #2 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 1 2 3 4 5 6 7 8 9 10 11 12 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 289:0 289:1 289:2 289:3 289:4 289:5 BA01_x:00 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 Setpoints (View) None Control Points (Set) None Page 53 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current kVA Reports Trend Status Page 54 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Power Monitoring Panel – PMP Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Notes: Divide by 10 for correct value Divide by 10 for correct value Discrete BACnet alarm objects available –use auto-discover for this unit 40289:00 40289:01 40289:02 40289:03 40289:04 289:00 289:01 289:02 289:03 289:04 Page 55 of 148 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Load Alarm Custom Alarm #1 Custom Alarm #2 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B Page 56 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) % Capacity C Ground Current Neutral Current KW KVA Reports Trend Status Page 57 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Voltage-Current-Freq. Monitor Panel – VCF Hardware Compatibility Liebert Units: MPU4000, Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA Frequency Alarm Points Communications Output Undervoltage Output Overvoltage Transformer Overtemp Local Alarm #1 Local Alarm #2 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 1 2 3 4 5 6 7 8 9 10 11 12 13 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 289:0 289:1 289:2 289:3 289:4 289:5 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 Setpoints (View) None Control Points (Set) None Page 58 of 148 Notes: Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) Voltage Out X-Y Voltage Out Y-Z Voltage Out Z-X Voltage Out X-N Voltage Out Y-N Voltage Out Z-N Current Out A Current Out B Current Out C Ground Current Neutral Current kVA Reports Trend Status Page 59 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Power Monitoring Panel (Ext. Protocol) – PM2 Hardware Compatibility Liebert Units: Datawave, Precision Power Center SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Voltage In X-Y Voltage In Y-Z Voltage In Z-X Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C Ground Current Neutral Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Power Factor Kilowatt Hours Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_X BS18_x BS19_x BS20_x BS21_x THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y Page 60 of 148 Notes: Divide by 10 for correct value Divide by 10 for correct value Divide by 100 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: Status Points (View) THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Alarm Points Communications Output Undervoltage Output Overvoltage Output Overcurrent Frequency Deviation Ground Overcurrent Transformer Overtemp Ground Fault Ground Failure Liquid Detected Security Alarm Phase Rotation/Loss Datawave Overtemperature Emergency Shutdown Load On Bypass Local Alarm #1 Local Alarm #2 Output Voltage THD Custom Alarm #1 Custom Alarm #2 Discrete BACnet alarm objects available –use auto-discover for this unit 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 Setpoints (View) None Control Points (Set) None Page 61 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C Ground Current Neutral Current KW KVA Power Factor THD Voltage X THD Voltage Y THD Voltage Z THD Current X THD Current Y THD Current Z K Factor Current X K Factor Current Y K Factor Current Z CREST Factor Current X CREST Factor Current Y CREST Factor Current Z Reports Trend Status Page 62 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Static Transfer Switch PDU – EDS Hardware Compatibility Liebert Units: Static Transfer Switch SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Transfer Count Preferred Source Load On Source 1or 2 Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency KW KVA Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x Page 63 of 148 Notes: 1=Source 1 / 0=Source 2 1=Source 1 / 2=Source 2 Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value 1=Enabled / 0=Disabled Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Communications Logic Failure Equipment Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR1 Shorted SCR2 Open SCR1 Open SCR2 Fan Failure Source 2 Overload Power Supply 2 Fault Frequency Deviation Transfer Inhibit Auto Retransfer Primed Out of Synchronization Source 1 Failure Source 2 Failure Auto Retransfer Failed Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB1 Open Source 2 CB2 Open Output CB3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Custom Alarm 3 Custom Alarm 4 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 Page 64 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Custom Alarm 5 Custom Alarm 6 Custom Alarm 7 Custom Alarm 8 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40292:2 40292:3 40292:4 40292:5 292:2 292:3 292:4 292:5 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C KW KVA Reports Trend Status Page 65 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Static Transfer Switch PDU Dual Output – STS Hardware Compatibility Liebert Units: Static Transfer Switch with w/ & w/o PDU SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Transfer Count Preferred Source Load On Source 1 or 2 Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency KW KVA Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled Dual Output Breaker Status Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x Page 66 of 148 Notes: 1=Source 1 / 0=Source 2 1=Source 1 / 2=Source 2 Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value 1=Enabled / 0=Disabled 1=Enabled / 0=Disabled Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Communications Logic Failure Equipment Overtemp Power Supply 1 Fault Source 1 Overvoltage Source 1 Undervoltage Source 2 Overvoltage Source 2 Undervoltage Source 1 Overload Shorted SCR1 Shorted SCR2 Open SCR1 Open SCR2 Fan Failure Source 2 Overload Power Supply 2 Fault Frequency Deviation Transfer Inhibit Auto Retransfer Primed Out of Synchronization Source 1 Failure Source 2 Failure Auto Retransfer Failed Overload Control Fuse 1 Blown Control Fuse 2 Blown Source 1 CB1 Open Source 2 CB2 Open Output CB3 Open Custom Alarm 1 Custom Alarm 2 Bypass CB4 Closed Bypass CB5 Closed Output CB 3B Open Custom Alarm 4 Custom Alarm 5 Custom Alarm 6 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 292:02 292:03 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA01_x:02 BA01_x:03 Page 67 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Custom Alarm 7 Custom Alarm 8 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40292:4 40292:5 292:4 292:5 BA01_x:04 BA01_x:05 Setpoints (View) Auto Transfer Timer Nominal Voltage Deviation Phase Differential Limit Frequency Deviation Auto Transfer Enabled Control Points (Set) None Trendable Points (Set) Source 1 Voltage A-B Source 1 Voltage B-C Source 1 Voltage C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 2 Voltage A-B Source 2 Voltage B-C Source 2 Voltage C-A Source 2 Current A Source 2 Current B Source 2 Current C KW KVA Reports Trend Status Page 68 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Power Unit – Static Transfer Switch PDU Dual Output – STS-2 Hardware Compatibility Liebert Units: Static Transfer Switch Extended Protocol w/ & w/o PDU SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) PDU Source 1 Voltage A-B PDU Source 1 Voltage B-C PDU Source 1 Voltage C-A PDU Source 1 Frequency Output KVA Output KVA % Output KW Heat Sink Temp 1 Heat Sink Temp 2 Heat Sink Temp 3 Sync Phase Angle Output Neutral Current Output Ground Current PDU Source 2 Voltage A-B PDU Source 2 Voltage B-C PDU Source 2 Voltage C-A PDU Source 2 Frequency Output Power Factor A Output Power Factor B Output Power Factor C Output KWH Output Voltage THD A Output Voltage THD B Output Voltage THD C Output Current THD A Output Current THD B Output Current THD C Output Current K FACTOR A Output Current K FACTOR B Output Current K FACTOR C Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: Not available in SSWeb Not available in SSWeb Not available in SSWeb Not available in SSWeb 40019 19 BS19_x 40018 18 BS18_x Not available in SSWeb Not available in SSWeb Not available in SSWeb Not available in SSWeb Not available in SSWeb Not available in SSWeb Not available in SSWeb Page 69 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS01_x Status Points (View) Output I CREST FACTOR A Output I CREST FACTOR B Output I CREST FACTOR C Source 1 Volts A-B Source 1 Volts B-C Source 1 Volts C-A Source 1 Current A Source 1 Current B Source 1 Current C Source 1 Frequency Source 2 Volts A-B Source 2 Volts B-C Source 2 Volts C-A Source 2 Current A Source 2 Current B Source 2 Current C Source 2 Frequency Total Transfer Count Total Operating Hours CB1 Status CB2 Status CB3 Status CB3A Status CB4 Status CB5 Status CB7 Status CB8 Status Active Source Preferred Source 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40001 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1 40024:0 40024:1 40024:2 40024:3 40024:4 40024:5 40024:6 40024:7 40003 40002 24:0 24:1 24:2 24:3 24:4 24:5 24:6 24:7 3 2 Alarm Points Communications Lost S1 SCR Short S2 SCR Short S1 SCR Open S2 SCR Open Primary Fan Fail Control Module Fail 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 289:00 289:01 289:02 289:03 289:04 289:05 289:06 Notes: Divide by 10 for correct value Divide by 10 for correct value BS24_x:00 BS24_x:01 BS24_x:02 BS24_x:03 BS24_x:04 BS24_x:05 BS24_x:06 BS24_x:07 BS03_x 1=Source 1, 2=Source 2 BS02_x 0=Source 1, 255=Source 2 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 Page 70 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points (Cont’d) PWR Supply DC A Fail PWR Supply DC B Fail PWR Supply SRC 1 AC Fail PWR Supply SRC 2 AC Fail PWR Supply Logic Fail Output Voltage Sense Fail S1 Voltage Sense Fail S2 Voltage Sense Fail S1 SCR Sense Fail S2 SCR Sense Fail S1 Current Sense Fail S2 Current Sense Fail S1 Gate Drive Fail S2 Gate Drive Fail Internal Comm Fail External Comm Fail CB1 Shunt Trip Fail CB2 Shunt Trip Fail CB6 Neutral Open Contactor Neutral Fail Heatsink Overtemp Equipment Overtemp Ambient Overtemp S1 Undervolts S1 Undervolts (RMS) S1 Overvolts S1 Over/Under Frequency S1 Fail S2 Undervolts S2 Undervolts (RMS) S2 Overvolts S2 Over/Under Frequency S2 Fail S1 Overcurrent S2 Overcurrent S1 I-Peak S2 I-Peak Sources Out of Sync Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 289:07 289:08 289:09 289:10 289:11 289:12 289:13 289:14 289:15 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 290:11 290:12 290:13 290:14 290:15 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 291:11 291:12 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:11 BA03_x:12 Page 71 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points (Cont’d) Load On Alternate Source Auto Retransfer Inhibit CB1 (S1) Open CB2 (S2) Open CB4 (S1 BYP) Closed CB5 (S2 BYP) Closed CB3 Output Breaker Open CB3A Output Breaker Open S1 Phase Rotation Error S2 Phase Rotation Error Transfer Inhibited Output Undervoltage History Logs Full Input Contact #1 Input Contact #2 Input Contact #3 Input Contact #4 Input Contact #5 Input Contact #6 Input Contact #7 Input Contact #8 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40291:13 40291:14 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40292:11 40292:12 40292:13 40292:14 40293:00 40293:01 40293:02 40293:03 291:13 291:14 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 292:11 292:12 292:13 292:14 293:00 293:01 293:02 293:03 BA03_x:13 BA03_x:14 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:04 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA04_x:11 BA04_x:12 BA04_x:13 BA04_x:14 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 Trendable Points (Set) KVA KW S1 Amps A S1 Amps B S1 Amps C S1 Frequency S2 Amps A S2 Amps B S2 Amps C S2 Frequency Trendable Points (Set) Status Trend Page 72 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Liebert UPS Units Page 73 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Multi Module UPS – S600 Extended Prot. – MM4 Hardware Compatibility Liebert Units: Series 600MMS SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Total Operating Hours Module Number Total # Battery Discharge Accumulated Battery Time Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 1 2 3 4 5 6 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 7 8 9 10 11 12 13 14 15 16 17 18 19 20 BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Page 74 of 148 Notes: Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 Status Points (View) Accumulated Battery Amp/Hr Accumulated Battery kw/Hr Battery Charge Percent Battery Time Remaining Battery Temperature Alarm Points Communications Battery Discharge Input Failure Hardware Shutdown DC Ground Fault Input CB Open Output CB Open DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Battery Disconnected Control Power Failure Overload Shutdown Inverter Fault Input Current Unbalanced Inverter Out of Sync Reverse Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemp Blower/Fan Failure Overtemperature Shutdown Battery Room Overtemp Battery Test Running Page 75 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Setpoints (View) Overload Alarm DC Overvoltage Alarm Battery Discharging Alarm Low Battery Alarm Battery Shutdown 1 Alarm Battery Shutdown 2 Alarm Control Points (Set) None Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage KVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Input Amps Phase A Input Amps Phase B Input Amps Phase C Reports Trend Status Page 76 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Multi Module Series – MMS Hardware Compatibility Liebert Units: Series 600MMS, Series 600T MS SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage Battery Current KVA KW Frequency % Capacity A % Capacity B % Capacity C Alarm Points 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Communications Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Ambient Overtemperature 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 Notes: Divide by 10 for correct value Discrete BACnet alarm objects available – use auto-discover for this unit 289:00 289:01 289:02 289:03 289:04 289:05 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 Page 77 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Battery Grounded Battery Disconnected Module Cooling Failure Control Power Failure Overload Shutdown Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:06 40289:07 40289:08 40289:09 40289:10 289:06 289:07 289:08 289:09 289:10 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C % Capacity A % Capacity B % Capacity C DC Bus Voltage DC Bus Current kW kVA Reports Trend Page 78 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – System Control Cabinet – S600 Ext. Prot. – SC4 Hardware Compatibility Liebert Units: Series 600 SCC SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Output Frequency Bypass Frequency Total Operating Hours Number of Modules in System System Number Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 1 2 3 4 5 6 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 7 8 9 10 11 12 13 14 15 16 17 18 19 20 BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Page 79 of 148 Notes: Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Communications Output Undervoltage Output Overvoltage Frequency Deviation Bypass CB Open Output CB Open Static Switch Disconnected Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Control Power Failure Module #1 Summary Alarm Module #2 Summary Alarm Module #3 Summary Alarm Module #4 Summary Alarm Module #5 Summary Alarm Module #6 Summary Alarm Bypass Not Available Not OK to Transfer Bypass Ph Rotation Error Manual Reset/Transfer Auto Re-Transfer Primed Overload Transfer Module #1 Offline Module #2 Offline Module #3 Offline Module #4 Offline Module #5 Offline Module #6 Offline Custom Alarm #1 Custom Alarm #2 Custom Alarm #3 Custom Alarm #4 Custom Alarm #5 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 Page 80 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40292:02 40292:03 40292:04 292:02 292:03 292:04 BA04_x:02 BA04_x:03 BA04_x:04 Alarm Points Custom Alarm #6 Custom Alarm #7 Custom Alarm #8 Setpoints (View) Overload Alarm Control Points (Set) None Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C kVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Reports Trend Status Page 81 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – System Control Cabinet – SCC Hardware Compatibility Liebert Units: Series 600 SCC SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C KVA KW Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x Divide by 10 for correct value Discrete BACnet alarm objects available – use auto-discover for this unit Alarm Points Communications Output Overload Emergency Power Off Load On Bypass Static Switch Disabled Output Out of Limits Module #1 Summary Notes: 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 289:00 289:01 289:02 289:03 289:04 289:05 289:06 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 Page 82 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Module #2 Summary Module #3 Summary Module #4 Summary Module #5 Summary Module #6 Summary Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:07 40289:08 40289:09 40289:10 40290:00 289:07 289:08 289:09 289:10 290:00 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage In A-N Voltage In B-N Voltage In C-N Current Out A Current Out B Current Out C % Capacity Phase A % Capacity Phase B % Capacity Phase C KW KVA Reports Trend Status Page 83 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module Series – SMS Hardware Compatibility Liebert Units: Series 300/500/600 Single Module UPS SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage DC Bus Current KVA KW Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Alarm Points Communications Battery Discharge Low Battery Reserve Output Overload Fuse Cleared Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Module Cooling Failure Modbus Register 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 BACnet Instance (Exec. 6 Modules) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 BACnet Notes: Instance (Exec. B Modules) BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x Divide by 10 for correct value BS18_x BS19_x BS20_x BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 Page 84 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Control Power Failure Overload Shutdown Setpoints (View) None Control Points (Set) None Trendable Points (Set) Voltage In A-B Voltage In B-C Voltage In C-A Voltage Out A-B Voltage Out B-C Voltage Out C-A Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C % Capacity Phase A % Capacity Phase B % Capacity Phase C DC Bus Voltage DC Bus Current KW KVA Reports Trend Status Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:00 40290:01 290:00 290:01 BA02_x:00 BA02_x:01 Page 85 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module UPS – S600 Ext. Prot. – SM4 Hardware Compatibility Liebert Units: Series 600 SMS SiteScan Interface Modules: DC1,DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW Critical Bus Frequency % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Input Amps Phase A Input Amps Phase B Input Amps Phase C Bypass Frequency Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 1 2 3 4 5 6 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x BS24_x Page 86 of 148 Notes: Divide by 10 for correct value Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) Bypass Frequency Total Operating Hours Module Number Total # Battery Discharge Accumulated Battery Time Accumulated Battery Amp/Hr Accumulated Battery kW/Hr Battery Charge Percent Battery Time Remaining Battery Temperature Alarm Points Communications Output Undervoltage Output Overvoltage Battery Discharge Frequency Deviation Input Failure Hardware Shutdown DC Ground Fault Input CB Open Bypass CB Open Output CB Open Static Switch Disconnected DC Cap Fuse Blown Low Battery Reserve Output Overload Rectifier Fuse Blown Emergency Power Off Ambient Overtemperature Load On Bypass Static Switch Disabled Battery Disconnected Control Power Failure Inverter Fault Input Current Unbalanced Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:01 BA03_x:02 Page 87 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Bypass Not Available Not OK to Transfer Bypass Ph Rotation Error Manual Reset/Transfer Auto Re-Transfer Primed Overload Transfer Reserve Power Low Battery Shutdown DC Overvoltage Shutdown Battery Cycle Buffer Full Equipment Overtemp Blower/Fan Failure Overtemperature Shutdown Custom Alarm #1 Custom Alarm #2 Custom Alarm #3 Custom Alarm #4 Custom Alarm #5 Custom Alarm #6 Custom Alarm #7 Custom Alarm #8 Battery Room Overtemp Battery Test Running Auto-restart Initiated Auto-restart Failed Setpoints (View) Overload Alarm DC Overvoltage Alarm Battery Discharging Alarm Low Battery Alarm Battery Shutdown 1 Alarm Battery Shutdown 2 Alarm Control Points (Set) None Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40292:00 40293:01 40293:02 40293:03 40293:04 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 292:00 293:01 293:02 293:03 293:04 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04 Page 88 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Trendable Points (Set) Input Voltage A-B Input Voltage B-C Input Voltage C-A Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Amps Phase A Output Amps Phase B Output Amps Phase C DC Bus Voltage Battery Current KVA KW % Capacity Phase A % Capacity Phase B % Capacity Phase C Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Input Amps Phase A Input Amps Phase B Input Amps Phase C Reports Trend Status Page 89 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Multi-Module SICE 7200 & HiPulse UPS – SMM Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Module Number Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 1 2 3 BS01_x BS02_x BS03_x 40004 40005 40006 4 5 6 BS04_x BS05_x BS06_x 40007 40008 40009 40010 40011 7 8 9 10 11 BS07_x BS08_x BS09_x BS10_x BS11_x 40012 40013 40014 40015 40016 40017 40018 40019 12 13 14 15 16 17 18 19 BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x Page 90 of 148 Notes: Divide by 10 for correct value Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) % Battery Charge Battery Temperature Battery Time Remaining Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Byp Phase Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Rectifier Off Rectifier Off Via Display Rectifier Block Rectifier Current Limit Rectifier Overtemperature Rectifier Fuse Failure Inverter Off Inverter Off Via Display Inverter Block Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40020 40021 40022 20 21 22 BS20_x BS21_x BS22_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 Page 91 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Inverter Fuse Failure Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Slow Overvoltage DC Undervoltage Battery Fuse Failure DC Fast Overvoltage Transfer Count Block Overload Shutdown Overtemperature SD Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response Battery Ground Fault BackFeed Fault Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40293:00 40293:01 40293:02 40293:03 40293:04 40293:05 40293:06 40293:07 40293:08 40293:09 40293:10 291:08 291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 293:00 293:01 293:02 293:03 293:04 293:05 293:06 293:07 293:08 293:09 293:10 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04 BA05_x:05 BA05_x:06 BA05_x:07 BA05_x:08 BA05_x:09 BA05_x:10 Page 92 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Alarm Points Synchronization Inhibited ECO – Mode On Setpoints (View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Slew Rate # of Battery Cells Rated Capacity Pre-End Discharge End of Discharge per Cell Maximum Voltage per Cell Year Month Day Hour Minute Second Control Points (Set) Date & Time Sync Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output voltage L3-L1 Page 93 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend Page 94 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Systems Cabinet SICE 7200 UPS – SSC Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Number of Modules in Sys %Battery Charge Battery Temperature Battery Time Remaining Modbus Register 40001 40002 40003 BACnet Instance (Exec. 6 Modules) 1 2 3 BACnet Instance (Exec. B Modules) BS01_x BS02_x BS03_x 40004 40005 40006 4 5 6 BS04_x BS05_x BS06_x 40007 40008 40009 40010 7 8 9 10 BS07_x BS08_x BS09_x BS10_x 40012 40013 40014 40015 40016 40017 40018 40019 12 13 14 15 16 17 18 19 BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x 40020 40021 40022 20 21 22 BS20_x BS21_x BS22_x Page 95 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register Communications Bypass Switch Open Output Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Bypass Ph Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Inverter Non Sync Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Transfer Count Block Overload Shutdown Overtemperature Shutdown Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 40291:05 BACnet Instance (Exec. 6 Modules) 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:05 291:05 291:05 291:05 291:05 291:05 291:05 291:05 BACnet Instance (Exec. B Modules) BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 BA03_x:05 Page 96 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Setpoints ( View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Year Month Day Hour Minute Second Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend Page 97 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module SICE 7200 & HiPulse UPS – SSM Hardware Compatibility Liebert Units: SICE 7200 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Voltage L1-N Output Voltage L2-N Output Voltage L3-N Output Amps L1 Output Amps L2 Output Amps L3 Output Amps Neutral Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Input Voltage L1-L2 Input Voltage L2-L3 Input Voltage L3-L1 Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 %Battery Charge Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 1 2 3 BS01_x BS02_x BS03_x 40004 40005 40006 4 5 6 BS04_x BS05_x BS06_x 40007 40008 40009 40010 40011 7 8 9 10 11 BS07_x BS08_x BS09_x BS10_x BS11_x 40012 40013 40014 40015 40016 40017 40018 40019 40020 12 13 14 15 16 17 18 19 20 BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Page 98 of 148 Notes: Divide by 10 for correct value Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Status Points (View) Battery Temperature Battery Time Remaining 40021 40022 21 22 BS21_x BS22_x Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Bypass Ph Rotation Error Bypass SCR Failure Bypass Off Bypass Off Via Display Load On Bypass Bypass Overtemperature Rectifier Off Rectifier Off Via Display Rectifier Block Rectifier Current Limit Rectifier Overtemperature Rectifier Fuse Failure Inverter Off Inverter Off Via Display Inverter Block Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage Inverter Fuse Failure 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 Page 99 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Output Overvoltage Output Undervoltage Output No Voltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Slow Overvoltage DC Undervoltage Battery Fuse Failure DC Fast Overvoltage Transfer Count Block Overload Shutdown Overtemperature Shutdown Emergency Stop Overload Present Overload Shutdown TO Bad EEPROM Error LRC Par P1 Error LRC Par P2 Error LRC Par P3 Error LRC Alarm History Error LRC Event History Internal Battery Low Error LRC Table Error LRC Panel Can Bus No Response Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 40292:09 40292:10 40293:00 40293:01 40293:02 40293:03 40293:04 40293:05 40293:06 40293:07 40293:08 40293:09 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 40293:10 291:09 291:10 292:00 292:01 292:02 292:03 292:04 292:05 292:06 292:07 292:08 292:09 292:10 293:00 293:01 293:02 293:03 293:04 293:05 293:06 293:07 293:08 293:09 293:10 293:10 293:10 293:10 293:10 293:10 293:10 293:10 293:10 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 BA04_x:09 BA04_x:10 BA05_x:00 BA05_x:01 BA05_x:02 BA05_x:03 BA05_x:04 BA05_x:05 BA05_x:06 BA05_x:07 BA05_x:08 BA05_x:09 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 BA05_x:10 Page 100 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Alarm Points Setpoints (View) Power Rating Configuration Nominal Voltage Low Level Input Voltage Upper Level Input Voltage Low Level Output Voltage Upper Level Output Voltage Nominal Frequency Frequency Tolerance Slew Rate # of Battery Cells Rated Capacity Pre-End Discharge End of Discharge per Cell Maximum Voltage per Cell Year Month Day Hour Minute Second Control Points (Set) Date & Time Sync Trendable Points (Set) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Battery Voltage Page 101 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Trendable Points (Set) Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 Reports Status Trend Page 102 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – UPStation S – DCU Hardware Compatibility Liebert Units: UPStation S SiteScan Interface Modules: DCU BMS interface Modules: Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Status Points (View) Battery Time Remaining Last Battery Test Passed Last Self Test Passed Voltage In Phase A Voltage In Phase B Voltage In Phase C Current In Phase A Current In Phase B Current In Phase C Voltage Out Phase A Voltage Out Phase B Current Out Phase A Current Out Phase B Voltage Bypass Phase A Voltage Bypass Phase B Current Bypass Phase A Current Bypass Phase B VA Inverter Load Percentage Load Inverter Temperature PFC Temperature Battery Temperature Battery Voltage Battery Current Input Frequency Output Frequency Page 103 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Status Points (View) Bypass Frequency Alarm Points Communications Inverter Utility Failure Ambient Overtemperature Battery Test In Progress Input Overvoltage UPS On Bypass Receptacle 1 Off Receptacle 2 Off Receptacle 3 Off Receptacle 4 Off Receptacle 5 Off Receptacle 6 Off Receptacle 7 Off Receptacle 8 Off Outlet Overload Input Frequency Charger Failure Low Battery Inverter Undervoltage Inverter Overvoltage Bypass Power UPS Status Setpoints (View) None Control Points (Set) None Page 104 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points (Set) Voltage In Phase A Voltage In Phase B Voltage In Phase C Current In Phase A Current In Phase B Current In Phase C Voltage Out Phase A Voltage Out Phase B Current Out Phase A Current Out Phase B Voltage Bypass Phase A Voltage Bypass Phase B Current Bypass Phase A Current Bypass Phase B VA Inverter Load Percentage Load Inverter Temperature PFC Temperature Battery Temperature Battery Voltage Battery Current Input Frequency Output Frequency Bypass Frequency Reports Trend Status Page 105 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – UPStation S3 – US3 Hardware Compatibility Liebert Units: UPStation S3 SiteScan Interface Modules: DC1, DC4, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current Out A Current Out B Current Out C DC Bus Voltage DC Bus Current KVA KW Inverter Temperature PFC Temperature Battery Temperature Battery Test Status Input Frequency Bypass Frequency Output Frequency Current In A Current In B Current In C % Capacity Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40016 40017 40018 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40021 40022 40023 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 21 22 23 BS16_x BS17_x BS18_x BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS21_x BS22_x BS23_x 40024 40014 24 14 BS24_x BS14_x 40015 15 BS15_x Page 106 of 148 Notes: Divide by 10 for correct value Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) Inverter Status Utility Status Bypass Status Battery Test in Progress Battery Time Remaining KVA Size Alarm Points Communications Bypass Failure Input Failure Battery Discharging Low Battery Reserve Output Overload Ambient Overtemperature Output Undervoltage Output Overvoltage Input Overvoltage Charge Failure UPS Off Load On Bypass Utility Failed Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40020 40019 20 19 BS20_x BS19_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 290:01 290:02 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N Page 107 of 148 Notes: Countdown starts at 254 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Trendable Points (Set) Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Battery Time Reports Trend Status Page 108 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module Series AP301/302 – SM3 Hardware Compatibility Liebert Units: Single Module UPS AP301/302 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage in A-N Voltage in B-N Voltage in C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Input Frequency Bypass Frequency Output Frequency Last Battery Test Status Inverter Status Model Number KVA Size Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40016 40017 40018 40001 40002 40003 40004 40005 40006 16 17 18 1 2 3 4 5 6 BS16_x BS17_x BS18_x BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 40008 40009 40015 40010 40011 40012 40013 7 8 9 15 10 11 12 13 BS07_x BS08_x BS09_x BS15_x BS10_x BS11_x BS12_x BS13_x 40014 40022 40023 40020 40019 14 22 23 20 19 Page 109 of 148 BS14_x BS22_x BS23_x BS20_x BS19_x Notes: Divide by 10 for correct value Divide by 10 for correct value Divide by 10 for correct value 0=failed / 1= passed 0=off / 1=on Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) Utility Status Bypass Status Battery Test In Progress Battery Time Remaining Alarm Points Communications Bypass Failure Input Failure Battery Discharging Low Battery Reserve Output Overload Ambient Overtemperature Output Undervoltage Output Overvoltage Charger Failure Load On Bypass Utility Failed Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40024 24 BS24_x 0=not present / 1=present 40021 21 BS21_x Countdown timer starts at 254 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 290:00 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 Setpoints (View) None Control Points (Set) None Trendable Points (Set) Bypass Voltage A-N Bypass Voltage B-N Bypass Voltage C-N Voltage In A-N Voltage In B-N Voltage In C-N Voltage Out A-N Voltage Out B-N Voltage Out C-N Current In A Current In B Current In C Current Out A Current Out B Page 110 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Current Out C % Capacity DC Bus Voltage DC Bus Current KW KVA Input Frequency Bypass Frequency Output Frequency Battery Time Reports Trend Status Page 111 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module UPS – NPower -- IMP Hardware Compatibility Liebert Units: NPower SMS SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Voltage A-B Input Voltage B-C Input Voltage C-A Input Frequency Bypass Voltage A-B Bypass Voltage B-C Bypass Voltage C-A Bypass Frequency Battery Voltage Battery Current Battery Temperature Battery Time Remaining Battery Charge Percentage Output Voltage A-B Output Voltage B-C Output Voltage C-A Output Voltage A-N Output Voltage B-N Output Voltage C-N Output Current A Output Current B Output Current C Output kVA A Output kVA B Output kVA C Output kW A Output kW B Modbus Register BACnet Instance (2.6) BACnet SSWEB 40001 40002 40003 1 2 3 BS01_x BS02_x BS03_x 40004 40005 40006 4 5 6 BS04_x BS05_x BS06_x 40007 40008 40009 7 8 9 BS07_x BS08_x BS09_x 40010 40011 40012 10 11 12 BS10_x BS11_x BS12_x 40013 40014 40015 40016 40017 40018 40019 40020 13 14 15 16 17 18 19 20 BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x Page 112 of 148 Notes: Scale by 10 Scale by 10 Scale by 10 Scale by 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) Output kW C Output Frequency Rated kVA Percentage Rated kW Percentage SBS Line Contact On/Off SBS Load Contact On/Off Input Delta Contact On/Off Input Wye Contact On/Off Output Contact On/Off Battery Breaker On/Off Trap Filter Contact On/Off Int. Mbypass Sw. On/Off Ext. Mbypass Sw. On/Off Alarms Points Communications Battery Fuse Failure Rectifier Fuse Fail Trap Fuse Fail Battery Overcharged Bypass Overload Shutdown Inverter Overload Transfer Inverter Fuse Failure Overvoltage Transfer Undervoltage Transfer Inverter Curr.Lim. Transfer EPO Shutdown Rectifier Fail Inverter Fail Hardware Shutdown On Battery Modbus Register BACnet Instance (2.6) BACnet SSWEB 40021 40022 40023 40024 21 22 23 24 BS21_x BS22_x BS23_x BS24_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 289:00 289:01 289:02 289:03 289:04 289:05 289:06 289:07 289:08 289:09 289:10 289:11 289:12 289:13 289:14 289:15 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 Page 113 of 148 Notes: Scale by 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarms Points Input Current Limit Battery CB Open Battery Discharging SBS Overload Phase A SBS Overload Phase B SBS Overload Phase C Inverter Current Limit Inverter Overload Phase A Inverter Overload Phase B Inverter Overload Phase C Low PF Warning Battery Ground Fault EPO Latched SBS Unable Inverter Off By User Battery Low Warning Battery Test Fail User Shutdown Battery Not Charged Load On Bypass Input Contact #1 Input Contact #2 Input Contact #3 Input Contact #4 Input Contact #5 Input Contact #6 Input Contact #7 Input Contact #8 Common Alarm Modbus Register BACnet Instance (2.6) 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 290:00 290:01 290:02 290:03 290:04 290:05 290:06 290:07 290:08 290:09 290:10 290:11 290:12 290:13 290:14 290:15 291:00 291:01 291:02 291:03 291:04 291:05 291:06 291:07 291:08 291:09 291:10 291:11 291:12 BACnet SSWEB Notes: BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 Common alarm includes All other alarms not listed Page 114 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trendable Points Input Volts A-B Input Volts B-C Input Volts C-A Bypass Volts A-B Bypass Volts B-C Bypass Volts C-A Battery Voltage Battery Current Battery Temp (Degrees C) Output Volts A-B Output Volts B-C Output Volts C-A Output Current Phase A Output Current Phase B Output Current Phase C Output kVA Phase A Output kVA Phase B Output kVA Phase C Output kW Phase A Output kW Phase B Output kW Phase C Percent Rated kVA Percent Rated kW Reports Trend & Status Page 115 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – Single Module UPS – NX -- PNX Hardware Compatibility Liebert Units: NX SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Input Frequency Output Frequency Bypass Frequency Inverter Load Status UPS Load On Bypass Status Parallel Load Source Rotary Breaker State Battery Test Result DC-DC Status Inverter Ready Status PF Correction Status Battery Charge Comp Status Battery Test In Progress Battery Voltage Battery Current Battery Charge Percentage Battery Deplete Time Remain Battery Temperature Ambient Temperature Input Voltage Vab Input Voltage Vbc Input Voltage Vca Input Volts A Input Volts B Input Volts C Input Current A Input Current B Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: 40001 BS01_x Scale By 10 40002 40003 BS02_x BS03_x Scale by 10 40004 BS04_x 40005 40006 40007 BS05_x BS06_x BS07_x Page 116 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Status Points (View) Input Current C Input PF A Input PF B Input PF C Bypass Volts A Bypass Volts B Bypass Volts C Output Volts A Output Volts B Output Volts C Output Current A Output Current B Output Current C Output PF A Output PF B Output PF C Output % A Output % B Output % C Output Va A Output Va B Output Va C Output Var A Output Var B Output Var C Output Watts A Output Watts B Output Watts C System Output Va A System Output Va B System Output Va C System Output Var A System Output Var B System Output Var C System Output Watts A System Output Watts B System Output Watts C Crest Factor A Crest Factor B Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: 40008 40009 40010 40011 40012 40013 40014 40015 40016 BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x Scale by 10 Scale by 10 Scale by 10 40017 BS17_x Average of A,B,C 40018 40019 40020 BS18_x BS19_x BS20_x 40021 40022 40023 BS21_x BS22_x BS23_x Page 117 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Status Points (View) Crest Factor C Alarm Points Loss Of Communications Input Switch Open Input Generator Disconnected Main AC Neutral Lost Load On Battery Reserved Load On Joint Mode Load On Bypass Load Has No Power Supplied Bypass – UPS Over Load Bypass – over max xfer number False Operation UPS Overload Alarm Battery Shutdown imminent Inverter Not Sync DC Under Voltage Shutdown Inverter Fault Inverter DC Offset Overrun Inverter Contactor Fail Inverter Over Current Alarm Inverter Communication Fail Rectifier Input Fuse Blown Rectifier Startup Fail Rectifier Fault Rectifier Over Current Alarm Rectifier Communication Fail Control Power Fail Fan Fail Alarm Battery Over Temperature Ambient Over Temperature Rectifier Over Temperature Rectifier Inductor Over Temp Inverter Over Temperature Inverter Inductor Over Temp 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 40291:01 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA03_x:00 BA03_x:01 Page 118 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Alarm Points Battery Converter Over Temp Battery Balancer Over Temp Input Power Failure Alarm Input Brown Out Alarm Input Frequency Deviation Alarm Input Phase Rotation Alarm Bypass SBS Unable Bypass Input Fault Output Over Voltage Alarm Charger Failure Battery Fault Battery Contactor Fail Battery Converter Fail Battery Converter Over Current Battery Balancer Fault Battery Balancer Over Current Parallel System Low Batt Warn Parallel Load Share Fault Parallel System Fault Parallel Connection Error Parallel System Over Load Parallel Transfer To Bypass Parallel Communication Fail Setpoints (View) Device Type Sub Module Number Outlet Circuitry Supported Parallel Module ID Parallel Module # Parallel Redundant Module # Module Mode Nominal VA Nominal Input Voltage Nominal Output Voltage 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40291:11 40291:12 40291:13 40291:14 40291:15 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 40292:06 40292:07 40292:08 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA03_x:11 BA03_x:12 BA03_x:13 BA03_x:14 BA03_x:15 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 BA04_x:06 BA04_x:07 BA04_x:08 40024 BS24_x Page 119 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Setpoints (View) Nominal Bypass Voltage Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal DC Bus #1 Voltage Nominal DC Bus #2 Voltage Battery Float Voltage Auto Restart Delay Battery Low Alarm Time Auto Restart Enable Load Bus Sync Mode Economic Mode UPS Type Offline UPS Type Interactive Has Dual Inputs Control Points (Set) None Trend Points Output Current Phase A Output Current Phase B Output Current Phase C Output % (Avg 3 Phases) Page 120 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – HiNet – PHN Hardware Compatibility Liebert Units: HiNet SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) UPS Load VA UPS Load Watt Input Frequency Output Frequency Load On Inverter UPS Load On Bypass UPS DC-DC Status Battery Voltage Battery Current Battery Charge Percentage Ambient Temperature Input Va Input Vb Input Vc Input Current Ia Input Current Ib Input Current Ic Output Va Output Vb Output Vc Output Current Ia Output Current Ib Output Current Ic Modbus Register BACnet Instance (Exec. 6 Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 BACnet Instance (Exec. B Modules) BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x Page 121 of 148 Notes: Scale By 10 Scale By 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Alarm Points Loss Of Communications Load On Battery Reserved Load On Bypass – Permanent UPS Overload Battery Shutdown imminent Inverter Not Sync Input Power Failure Bypass SBS SCR Open fault Bypass Input Fault Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 40024 BS24_x Setpoints (View) Device Type UPS Sub Module Number UPS Battery Count UPS Outlet Circuitry Supported UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs Setpoints (Set) None Trend Points Load VA Load Watts Input Current A Input Current B Input Current C Output Current A Output Current B Output Current C Page 122 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – NFinity – PNF Hardware Compatibility Liebert Units: Nfinity SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Bypass Frequency Load On Inverter UPS Load On Bypass Battery Test Result Inverter Ready Status Power Factor Correction Stat Battery Charger State Replace Battery Status Battery Test In Progress Battery Charge Status Battery Voltage Battery Charge Percentage Battery Deplete Time Battery Temperature Transformer Temperature Current Redundant PM # Current Active PM # Current Active Batt Mod # Input Va Input Current Ia Bypass Va Bypass Current Ia Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 BS07_x 40008 BS08_x 40009 40010 40011 40012 40013 BS09_x BS10_x BS11_x BS12_x BS13_x 40014 40015 40016 40017 BS14_x BS15_x BS16_x BS17_x Page 123 of 148 Notes: Scale By 10 Scale By 10 Scale By 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Status Points (View) Output Va Output Current Ia Power Module Fail Count Battery Module Fail Count Power Module Warning Count Battery Mod Warning Count Battery Discharge Count Battery Discharge Time Setpoints (View) Device Type Sub Module Number Power Module Number Battery Module Number Battery Count Outlet Circuitry Supported Maximum System Capacity Installed System Capacity Nominal Input Voltage Nominal Output Voltage Nominal Bypass Voltage Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Auto Restart percentage Battery Low Alarm time Battery Auto Test Interval Battery Next Auto Test Time Overload Alarm Threshold Minimum Red Pwr module # Auto Restart Enable Auto Battery Test Enable UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs UPS Has Redundant Control Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40018 40019 BS18_x BS19_x 40020 40021 BS20_x BS21_x 40022 BS22_x Notes: Scale by 10 Scale by 10 Scale by 100 40023 BS23_x 40024 BS24_x Page 124 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Setpoints (Set) None Alarm Points Loss Of Communications Load On Battery Load On Bypass Overload Bypass Fault Bypass Manual Bypass Manual Xfer Prohibited UPS Overload Alarm Shutdown Pending Battery Shutdown imminent Fan Fail Air Filter Bad Transformer Overtemperature Internal Communication Failure New Event Logged Input Power Failure Red Power Module Number Low Device Active Alarm Exist Main Control Module Alarm Redundant Module Alarm Power Module Alarm Battery Module Alarm Main Control Module Fail Redundant Control Module Fail User Interface Module Fail Power Module Failure Battery Module Failure Overtemp Shutdown Overload Shutdown Output Short Shutdown Low Battery Shutdown Remote Shutdown External Signal Shutdown 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40290:11 40290:12 40290:13 40290:14 40290:15 40291:00 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA02_x:11 BA02_x:12 BA02_x:13 BA02_x:14 BA02_x:15 BA03_x:00 Page 125 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Control Points (Set) Delayed Output Off Delayed Output Off then Reboot Delayed Output On Battery Test Command Alarm Silent command Trend Points Load Va Load Watts Input Current Bypass Current Output Current Page 126 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – GXT – PGX Hardware Compatibility Liebert Units: GXT SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Bypass Frequency Load On Inverter UPS Load On Bypass Battery Test Result DC-DC Status Inverter Ready Status Power Factor Correction Stat Battery Charge Comp Status Replace Battery Status Battery Test In Progress Battery Charge Status Battery Voltage Battery Charge Percentage Battery Deplete Time Ambient Temperature Input Voltage Vab Input Voltage Van Bypass Voltage Vab Bypass Voltage Van Output Voltage Vab Output Voltage Van Output Current Ia Output Load % Phase A Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 40008 40009 BS07_x BS08_x BS09_x 40010 40011 40012 40013 40014 40015 40016 40017 BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x Page 127 of 148 Notes: Scale By 10 Scale By 10 Scale By 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Status Points (View) Output VA Phase A Output Var Phase A Output Watt Phase A Input Voltage Vbn Bypass Voltage Vbn Output Voltage Vbn Output Current Ib Output Load % Phase B Output VA Phase B Output Watt Phase B UPS Black Out Count UPS Brown Out Count PhaseA Maximum Input Va PhaseA Minimum Input Va PhaseA Maximum Output Va PhaseA Minimum Output Va Load Circuit Output State Setpoints (View) Device Type UPS Sub Module Number Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40018 40019 40020 BS18_x BS19_x BS20_x 40021 40022 40023 BS21_x BS22_x BS23_x 40024 BS24_x Outlet Circuitry Supported Nominal VA Nominal Input Voltage Nominal Output Voltage Nominal Bypass Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Auto Restart Delay Battery Low Alarm time Auto Restart Enable Audible Alarm Enable Auto Battery Test Enable Page 128 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Setpoints (View) UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs Setpoints (View) None Control Points (Set) Delayed Output Off Delayed Output Off/Reboot Delayed Output On Battery Test Command Alarm Silence Abort Command Alarm Points Loss Of Comm Load On Battery Reserved UPS Overload UPS Shutdown Pending Battery Shutdown Iminent Overtemperature Input Current Unbalance Input Power Failure Input Over Voltage Input Under Voltage Input Frequency Deviation Bypass Input Fault Output Undervoltage Output Overvoltage Shutdown – Overtemp Shutdown – Overload Shutdown – DC Bus OV Shutdown - Output Short Shutdown - L-N Swapped 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 Page 129 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Alarm Points Shutdown Shutdown Shutdown Shutdown Shutdown - Low Battery - By Remote - UV Startup - PFC Startup - External Signal 40290:04 40290:05 40290:06 40290:07 40290:08 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 Trend Points Load VA Load Watts Ouput Current A Output VA A Output VAR A Output Watts A Output Current B Output VA B Output Watts B Page 130 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development UPS Unit – PSI – PPS Hardware Compatibility Liebert Units: PSI SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) UPS Load VA UPS Load Watt UPS Load Percent Input Frequency Output Frequency Load On Inverter Battery Test Result UPS Booster On Status UPS Buck On Status UPS DC-DC Status UPS Battery Charger State Replace Battery Battery Test In Progress UPS Battery Charge Status Battery Voltage Battery Charge Percentage Battery Time Remaining Ambient Temperature Input Va Input Current Ia Output Va Output Current Ia UPS Black Out Count UPS Brown Out Count PhaseA Maximum Input Va PhaseA Minimum Input Va PhaseA Maximum Output Va PhaseA Minimum Output Va Load Circuit Output State Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x 40007 BS07_x 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x BS17_x BS18_x BS19_x BS20_x BS21_x BS22_x BS23_x Page 131 of 148 Notes: Scale By 10 Scale By 10 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Set Points (View) Device Type Sub Module Number Outlet Circuitry Supported Nominal VA Nominal Input Voltage Nominal Output Voltage Nominal Input Current Nominal Input Frequency Nominal Output Frequency Nominal Power Factor Nominal Battery Voltage Battery Last Min Rated Load Battery Float Voltage Auto Restart Delay Ambient Overtemp Alarm Overtemp Failure Threshold Auto Restart Enable Audible Alarm Enable Auto Battery Test Enable UPS Type Is Offline UPS Type Is Interactive UPS Has Dual Inputs Modbus Register BACnet Instance (Exec. 6 Modules) 40024 BACnet Instance (Exec. B Modules) BS24_x Setpoints (Set) None Control Points (Set) Turn Output Off with Delay Delayed Ouput Off/Reboot Delayed Output On Battery Test Command Alarm Silent command Abort previous Command Reset Battery Stats Cmd Reset Stat Counters Cmd Page 132 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Available Points SiteScan Availability Alarm Points Loss Of Comm Load On Battery Reserved UPS Overload UPS Shutdown Pending Battery Shutdown Iminent Overtemperature Input Current Unbalance Input Power Failure Input Over Voltage Input Under Voltage Input Frequency Deviation Bypass Input Fault Output Undervoltage Output Overvoltage Shutdown – Overtemp Shutdown – Overload Shutdown – DC Bus OV Shutdown - Output Short Shutdown - L-N Swapped Shutdown - Low Battery Shutdown - By Remote Shutdown - UV Startup Shutdown - PFC Startup Shutdown - External Signal Modbus Register 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40289:11 40289:12 40289:13 40289:14 40289:15 40290:00 40290:01 40290:02 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA01_x:11 BA01_x:12 BA01_x:13 BA01_x:14 BA01_x:15 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 Trend Points Load VA Load Watts Ouput Current A Output VA A Output VAR A Output Watts A Output Current B Output VA B Output Watts B Page 133 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Liebert Monitoring Modules Page 134 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Contact Closure Module – CCM Hardware Compatibility Liebert Units: CCM200, RCM8, VSM100 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Contact 1 Contact 2 Contact 3 Contact 4 Contact 5 Contact 6 Contact 7 Contact 8 Contact 9 Contact 10 Contact 11 Contact 12 Contact 13 Contact 14 Contact 15 Contact 16 Contact 17 Contact 18 Contact 19 Contact 20 Contact 21 Contact 22 Contact 23 Contact 24 Contact 25 Contact 26 Contact 27 Page 135 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: Status Points (View) Contact 28 Contact 29 Contact 30 Contact 31 Contact 32 Discrete BACnet alarm objects available – use auto-discover for this unit Alarm Points (See Note) Communications 40001:0 1:0 BS01_x:00 Contact 1 Contact 2 Contact 3 Contact 4 Contact 5 Contact 6 Contact 7 Contact 8 Contact 9 Contact 10 Contact 11 Contact 12 Contact 13 Contact 14 Contact 15 Contact 16 Contact 17 Contact 18 Contact 19 Contact 20 Contact 21 Contact 22 Contact 23 Contact 24 Contact 25 Contact 26 Contact 27 40001:1 40001:2 40001:3 40001:4 40001:5 40001:6 40001:7 40001:8 40001:9 40001:10 40002:0 40002:1 40002:2 40002:3 40002:4 40002:5 40002:6 40002:7 40002:8 40002:9 40002:10 40003:0 40003:1 40003:2 40003:3 40003:4 40003:5 1:1 1:2 1:3 1:4 1:5 1:6 1:7 1:8 1:9 1:10 2:0 2:1 2:2 2:3 2:4 2:5 2:6 2:7 2:8 2:9 2:10 3:0 3:1 3:2 3:3 3:4 3:5 BS01_x:01 BS01_x:02 BS01_x:03 BS01_x:04 BS01_x:05 BS01_x:06 BS01_x:07 BS01_x:08 BS01_x:09 BS01_x:10 BS02_x:00 BS02_x:01 BS02_x:02 BS02_x:03 BS02_x:04 BS02_x:05 BS02_x:06 BS02_x:07 BS02_x:08 BS02_x:09 BS02_x:10 BS03_x:00 BS03_x:01 BS03_x:02 BS03_x:03 BS03_x:04 BS03_x:05 Page 136 of 148 Note: The first three status registers are used to report Alarm Points. Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Contact 28 Contact 29 Contact 30 Contact 31 Contact 32 Modbus Register 40003:6 40003:7 40003:8 40003:9 40003:10 BACnet Instance (Exec. 6 Modules) 3:6 3:7 3:8 3:9 3:10 BACnet Instance (Exec. B Modules) BS03_x:06 BS03_x:07 BS03_x:08 BS03_x:09 BS03_x:10 Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status Page 137 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Water/Liquid Detection Unit – WDU Hardware Compatibility Liebert Units: LDS1000, LDS750 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Distance Feet or Meters Alarm Points Communications Cable Fault Liquid Detected Modbus Register (2.6 BACnet Instance) BACnet SSWeb 40001 40002 1 2 BS01_x BS02_x 40289:0 40289:1 40289:2 289:0 289:1 289:2 G701_x G210_x G211_x Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status Page 138 of 148 Notes: 1=feet / 0=meters Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Remote Autochangeover – RAC Hardware Compatibility Liebert Units: RAC2-8 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 Unit 8 Alarm Points Communications Common Alarm 1 Common Alarm 2 Common Alarm 3 Common Alarm 4 Common Alarm 5 Common Alarm 6 Common Alarm 7 Common Alarm 8 Emergency Power Operation EPO All Units High Temperature Low Temperature High Humidity Low Humidity Manual Override Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) Notes: 40001 40002 40003 40004 40005 40006 40007 40008 1 2 3 4 5 6 7 8 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 1=on / 0=0ff 40289:0 40289:1 40289:2 40289:3 40289:4 40289:5 40289:6 40289:7 40289:8 40289:9 40289:10 40290:0 40290:1 40290:2 40290:3 40290:4 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 289:9 289:10 290:0 290:1 290:2 290:3 290:4 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 BA02_x:03 BA02_x:04 Page 139 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Setpoints (View) None Control Points (Set) None Trendable Points (Set) None Reports Status Page 140 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Temperature/Humidity Module – THM Hardware Compatibility Liebert Units: THM100 SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Temperature Sensor 1 Humidity Sensor 1 Temperature Sensor 2 Humidity Sensor 2 Temperature Sensor 3 Humidity Sensor 3 Temperature Sensor 4 Humidity Sensor 4 Temperature Sensor 5 Humidity Sensor 5 Temperature Sensor 6 Humidity Sensor 6 Temperature Sensor 7 Humidity Sensor 7 Temperature Sensor 8 Humidity Sensor 8 Alarm Points Communications High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4 Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x BS14_x BS15_x BS16_x 40289:0 289:0 BA01_x:00 Notes: Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Alarm threshold determined by others Page 141 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) High/Low Temp Sensor 5 High/Low Humidity Sensor 5 High/Low Temp Sensor 6 High/Low Humidity Sensor 6 High/Low Temp Sensor 7 High/Low Humidity Sensor 7 High/Low Temp Sensor 8 High/Low Humidity Sensor 8 Setpoints (View) High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4 High/Low Temp Sensor 5 High/Low Humidity Sensor 5 High/Low Temp Sensor 6 High/Low Humidity Sensor 6 High/Low Temp Sensor 7 High/Low Humidity Sensor 7 High/Low Temp Sensor 8 High/Low Humidity Sensor 8 Control Points (Set) High/Low Temp Sensor 1 High/Low Humidity Sensor 1 High/Low Temp Sensor 2 High/Low Humidity Sensor 2 High/Low Temp Sensor 3 High/Low Humidity Sensor 3 High/Low Temp Sensor 4 High/Low Humidity Sensor 4 High/Low Temp Sensor 5 Page 142 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Modbus Register BACnet Instance (Exec. 6 Modules) Trend Points Temp Sensor 1 Humidity Sensor 1 Temp Sensor 2 Humidity Sensor 2 Temp Sensor 3 Humidity Sensor 4 Temp Sensor 4 Humidity Sensor 4 Temp Sensor 5 Humidity Sensor 5 Temp Sensor 6 Humidity Sensor 6 Temp Sensor 7 Humidity Sensor 7 Temp Sensor 8 Humidity Sensor 8 Page 143 of 148 BACnet Instance (Exec. B Modules) Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Water/Liquid Detection Unit LDS5000 – WD5 Hardware Compatibility Liebert Units: LDS5000 SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) Installed Cable Footage 1 Installed Cable Footage 2 Not Used - Spare Not Used - Spare Leak Det Footage Cable 1 Leak Det Footage Cable 2 Not Used - Spare Not Used - Spare Leakage Current Cable 1 Leakage Current Cable 2 Not Used - Spare Not Used - Spare Feet / Meters Alarm Points Communications Leak Detected Cable 1 Cable Fault Cable 1 Leak Detected Cable 2 Cable Fault Cable 2 Not Used - Spare Not Used - Spare Not Used - Spare Not Used - Spare Setpoints (View) None Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 1 2 3 4 5 6 7 8 9 10 11 12 13 BS01_x BS02_x BS03_x BS04_x BS05_x BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 289:0 289:1 289:2 289:3 289:4 289:5 289:6 289:7 289:8 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 Control Points (Set) Alarm Silence Alarm Reset Trendable Points (Set) None Page 144 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Universal Monitor – UVM Hardware Compatibility Liebert Units: Universal Monitor - UVM SiteScan Interface Modules: SiteLink (All) BMS interface Modules: SiteLink (All) Available Points SiteScan Availability Status Points (View) I/O Extender Card Status Input Contact #1 Status Input Contact #2 Status Input Contact #3 Status Input Contact #4 Status Input Contact #5 Status Input Contact #6 Status Input Contact #7 Status Input Contact #8 Status Input Contact #9 Status Input Contact #10 Status Input Contact #11 Status Input Contact #12 Status Input Contact #13 Status Input Contact #14 Status Input Contact #15 Status Input Contact #16 Status Input Contact #17 Status Input Contact #18 Status Input Contact #19 Status Input Contact #20 Status Input Contact #21 Status Input Contact #22 Status Input Contact #23 Status Input Contact #24 Status Output Contact #1 Status Output Contact #2 Status Output Contact #3 Status Output Contact #4 Status Output Contact #5 Status Output Contact #6 Status Output Contact #7 Status Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) BS01_x 40001 Page 145 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Status Points (View) Output Contact #8 Status Output Contact #9 Status Output Contact #10 Status Output Contact #11 Status Output Contact #12 Status Output Contact #13 Status Output Contact #14 Status Output Contact #15 Status Output Contact #16 Status Sensor #1 High Status Sensor #1 Low Status Sensor #2 High Status Sensor #2 Low Status Sensor #3 High Status Sensor #3 Low Status Sensor #4 High Status Sensor #4 Low Status Sensor #1 Reading Sensor #2 Reading Sensor #3 Reading Sensor #4 Reading Alarm Points Input #1 Alarm Input #2 Alarm Input #3 Alarm Input #4 Alarm Input #5 Alarm Input #6 Alarm Input #7 Alarm Input #8 Alarm Input #9 Alarm Input #10 Alarm Input #11 Alarm Input #12 Alarm Input #13 Alarm Input #14 Alarm Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40002 40003 40004 40005 BS02_x BS03_x BS04_x BS05_x 40289:00 40289:01 40289:02 40289:03 40289:04 40289:05 40289:06 40289:07 40289:08 40289:09 40289:10 40290:00 40290:01 40290:02 BA01_x:00 BA01_x:01 BA01_x:02 BA01_x:03 BA01_x:04 BA01_x:05 BA01_x:06 BA01_x:07 BA01_x:08 BA01_x:09 BA01_x:10 BA02_x:00 BA02_x:01 BA02_x:02 Page 146 of 148 Notes: Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development SiteScan Availability Alarm Points Input #15 Alarm Input #16 Alarm Input #17 Alarm Input #18 Alarm Input #19 Alarm Input #20 Alarm Input #21 Alarm Input #22 Alarm Input #23 Alarm Input #24 Alarm Sensor #1 High Alarm Sensor #1 Low Alarm Sensor #2 High Alarm Sensor #2 Low Alarm Sensor #3 High Alarm Sensor #3 Low Alarm Sensor #4 High Alarm Sensor #4 Low Alarm Loss of Power Low Battery Alarm Battery Unplugged Check Battery Exp board loss of comm Configuration Changed Loss of Comm Setpoints (View) Sensor #1 High Threshold SP Sensor #1 Low Threshold SP Sensor #2 High Threshold SP Sensor #2 Low Threshold SP Sensor #3 High Threshold SP Sensor #3 Low Threshold SP Sensor #4 High Threshold SP Sensor #4 Low Threshold SP Control Points (Set) Sensor High Threshold Sensor Low Threshold Alarm Silence Alarm Reset Trendable Points (Set) Sensor Readings Modbus Register BACnet Instance (Exec. 6 Modules) BACnet Instance (Exec. B Modules) 40290:03 40290:04 40290:05 40290:06 40290:07 40290:08 40290:09 40290:10 40291:00 40291:01 40291:02 40291:03 40291:04 40291:05 40291:06 40291:07 40291:08 40291:09 40291:10 40292:00 40292:01 40292:02 40292:03 40292:04 40292:05 BA02_x:03 BA02_x:04 BA02_x:05 BA02_x:06 BA02_x:07 BA02_x:08 BA02_x:09 BA02_x:10 BA03_x:00 BA03_x:01 BA03_x:02 BA03_x:03 BA03_x:04 BA03_x:05 BA03_x:06 BA03_x:07 BA03_x:08 BA03_x:09 BA03_x:10 BA04_x:00 BA04_x:01 BA04_x:02 BA04_x:03 BA04_x:04 BA04_x:05 40006 40007 40008 40009 40010 40011 40012 40013 BS06_x BS07_x BS08_x BS09_x BS10_x BS11_x BS12_x BS13_x Notes: Sensors 1-4 Sensors 1-4 Sensors 1-4 Page 147 of 148 Revision B.12; 26 Feb. 04 Liebert Monitoring Group - Development Page 148 of 148