Motor Protection Circuit Breaker Series 8527/2
E7
> For protection of Ex e and Ex d motors > Protects cables and plant equipment
E7
> Adjustable thermal overload release, phase failure sensitive > Electromagnetic instantaneous release
E7
> Robust enclosure made of glass fibre reinforced polyester resin > Optionally with – undervoltage release – shunt release – ammeter – auxiliary contacts
E7
www.stahl.de
E7 E7
Series 8527/2 E7
02966E00
E7 Motor protection circuit breakers of Series 8527 are used where high short circuit currents are to be controlled and to protect both Ex e and Ex d motors. These switches are suitable to protect cables and the installation and can basically be used without a back-up fuse at 400 V. Breakers are operated by rotary handles enabling next to secure switching also to identify clearly switch settings.
E7 E7
ATEX / IECEx / GOST Zone
0
For use in
1
2
x
x
20
21
22
x
x
E7 E7 E7 E7
WebCode 2013-02-27·EK00·III·en
8527A
E7 Load Disconnect Switches and Motor Starters
E7/1
Motor Protection Circuit Breaker Series 8527/2 Selection Table Version
without accessories L1 L2 L3 1 3 5
I> I> I>
2 4 6 T1 T2 T3
Motor protection circuit breakers without accessories Series 8527
Current adjustment range
Auxiliary contacts
Order number
Weight
0.1 ... 0.16 A 0.1 ... 0.16 A 0.16 ... 0.25 A
without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO without 1 NC + 1 NO
8527/21-01-0001 8527/22-01-0201 8527/21-02-0001 8527/22-02-0201 8527/21-03-0001 8527/22-03-0201 8527/21-04-0001 8527/22-04-0201 8527/21-05-0001 8527/22-05-0201 8527/21-06-0001 8527/22-06-0201 8527/21-07-0001 8527/22-07-0201 8527/21-08-0001 8527/22-08-0201 8527/21-09-0001 8527/22-09-0201 8527/21-10-0001 8527/22-10-0201 8527/21-11-0001 8527/22-11-0201 8527/21-12-0001 8527/22-12-0201 8527/23-13-0002 8527/24-13-0202 8527/23-14-0002 8527/24-14-0202
2.591 2.610 2.608 2.630 2.610 2.630 2.574 2.595 2.600 2.620 2.653 2.670 2.633 2.650 2.630 2.650 2.600 2.620 2.600 2.620 2.500 2.520 2.400 2.420 4.200 3.520 3.500 3.520
0.25 ... 0.4 A 0.4 ... 0.63 A 0.63 ... 1 A 1 ... 1.6 A 1.6 ... 2.5 A 2.5 ... 4 A 4 ... 6.3 A 6.3 ... 9 A 9 ... 12.5 A 12.5 ... 16 A 16 ... 20 A 20 ... 22.5 A On request:
E7/2
• Circuit breakers for the current adjustment range 25 ... 63 A (Type 8525) • Further accessories e. g. shunt release, ammeter, additional auxiliary contacts (2 NC + 2 NO)
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en
Motor Protection Circuit Breaker Series 8527/2
E7
Selection Table Version
with undervoltage trip D1
L1 L2 L3 1 3 5
E7
U<
I> I> I>
D2
Current adjustment range Motor protection circuit breakers with undervoltage release Series 8527
0.1 ... 0.16 A
0.16 ... 0.25 A
0.25 ... 0.4 A
0.4 ... 0.63 A
0.63 ... 1 A
1 ... 1.6 A
1.6 ... 2.5 A
Rated operational voltage Ue
Auxiliary contacts
230 V AC 50 / 60 Hz
2 4 6 T1 T2 T3
Order number
Weight
without 1 NC + 1 NO
8527/21-01-1061 8527/22-01-1261
kg 2.610 2.610
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-01-1071 8527/22-01-1271
2.610 2.610
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-01-1091 8527/22-01-1291
2.610 2.610
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-02-1061 8527/22-02-1261
2.630 2.630
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-02-1071 8527/22-02-1271
2.630 2.630
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-02-1091 8527/22-02-1291
2.630 2.630
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-03-1061 8527/22-03-1261
2.630 2.630
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-03-1071 8527/22-03-1271
2.630 2.630
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-03-1091 8527/22-03-1291
2.630 2.630
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-04-1061 8527/22-04-1261
2.595 2.595
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-04-1071 8527/22-04-1271
2.595 2.595
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-04-1091 8527/22-04-1291
2.595 2.595
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-05-1061 8527/22-05-1261
2.620 2.620
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-05-1071 8527/22-05-1271
2.620 2.620
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-05-1091 8527/22-05-1291
2.620 2.620
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-06-1061 8527/22-06-1261
2.670 2.670
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-06-1071 8527/22-06-1271
2.670 2.670
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-06-1091 8527/22-06-1291
2.670 2.670
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-07-1061 8527/22-07-1261
2.650 2.650
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-07-1071 8527/22-07-1271
2.650 2.650
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-07-1091 8527/22-07-1291
2.650 2.650
E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7 E7
2013-02-27·EK00·III·en
Load Disconnect Switches and Motor Starters
E7/3
Motor Protection Circuit Breaker Series 8527/2 Selection Table Version
with undervoltage trip D1
L1 L2 L3 1 3 5
U<
I> I> I>
D2
Motor protection circuit breakers with undervoltage release Series 8527
Current adjustment range
Rated operational voltage Ue
Auxiliary contacts
Order number
Weight
2.5 ... 4 A
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-08-1061 8527/22-08-1261
kg 2.650 2.650
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-08-1071 8527/22-08-1271
2.650 2.650
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-08-1091 8527/22-08-1291
2.650 2.650
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-09-1061 8527/22-09-1261
2.620 2.620
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-09-1071 8527/22-09-1271
2.620 2.620
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-09-1091 8527/22-09-1291
2.620 2.620
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-10-1061 8527/22-10-1261
2.620 2.620
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-10-1071 8527/22-10-1271
2.620 2.620
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-10-1091 8527/22-10-1291
2.620 2.620
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-11-1061 8527/22-11-1261
2.520 2.520
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-11-1071 8527/22-11-1271
2.520 2.520
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-11-1091 8527/22-11-1291
2.520 2.520
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-12-1061 8527/22-12-1261
2.420 2.420
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-12-1071 8527/22-12-1271
2.420 2.420
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-12-1091 8527/22-12-1291
2.420 2.420
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/23-13-1062 8527/24-13-1262
4.220 3.520
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/23-13-1072 8527/24-13-1272
4.220 3.520
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-13-1092 8527/24-13-1292
4.220 3.520
230 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/23-14-1062 8527/24-14-1262
3.520 3.520
400 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/23-14-1072 8527/24-14-1272
3.520 3.520
500 V AC 50 / 60 Hz
without 1 NC + 1 NO
8527/21-14-1092 8527/24-14-1292
3.520 3.520
4 ... 6.3 A
6.3 ... 9 A
9 ... 12.5 A
12.5 ... 16 A
16 ... 20 A
20 ... 22.5 A
E7/4
2 4 6 T1 T2 T3
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en
Motor Protection Circuit Breaker Series 8527/2 Explosion Protection Global (IECEx) Gas Dust Europe (ATEX) Gas Dust
Certificates and approvals Certificates Technical data Mechanical data Degree of protection Enclosure material Mounting / installation Mounting orientation Cable entries Standard
E7 IECEx BVS 08.0047 Ex d e IIC T* IECEx PTB 06.0090 (see type 8146/5) Ex tD A21 IP65 T** (see type 8146/5) DMT 02 ATEX E 026 E II 2 G Ex d e IIC T* PTB 01 ATEX 1024 (see type 8146/5) E II 2 D Ex tD A21 IP65 T** (see type 8146/5) Adjustment range
T*
T**
8527/21, 8527/22
0.1 ... 0.25 A 0.25 ... 12.5 A 12.5 ... 16 A
T6 T5 T4
80 °C 95 °C 130 °C
8527/23
0.1 ... 12.5 A
T6
80 °C
8527/24
16 ... 22.5 A
T5
95 °C
E7 E7
IECEx, ATEX, Canada (CSA), Kazakhstan (GOST-K), Russia (GOST-R), Belarus (GOST-B)
IP66 acc. to IEC/EN 60529 Polyester resin, glass-fibre-reinforced, dark grey, similar to RAL 7024 Surface resistance ( 109 Ω, impact strength ) 7 J, flame-resistant, self-extinguishing according to IEC-92-1, UL 94, ASTM D 635-77
E7
arbitrary
E7
Type
Accessories
8527/21
without with without with without with
8527/23; 8527/24 8527/25; 8527/26 0.1 ... 12.5 A
1)
without with 12.5 ... 22.5 A without with M25 x 1.5 for cables Ø 12 ... 17 mm M32 x 1.5 for cables Ø 10 ... 18 mm
Switch insert Electrical data Rated operational voltage Rated operational current
E7
Type
8527/22
Wire Leads
E7
8161 Screw connections M25 x 1.5 M32 x 1.5 2 3 2 3 2 1 2
M25 x 1.5 1 1 1 -
2 3 1
1 1 -
2 2
8290 Stopping plug
E7 E7 E7
1) auxiliary contacts, undervoltage release, shunt release 8527/21 directly to fitted components 8527/22 Main contacts 1.5 ... 6 mm2 finely stranded 1.5 ... 10 mm2 solid Auxiliary contact 0.75 ... 1.5 mm2 finely stranded 0.75 ... 2.5 mm2 solid 8527/23 on terminals 0.5 ... 6 mm2 finely stranded 8527/24 0.5 ... 10 mm2 solid 8527/25 8527/26 Please note: Compare cable diameter with cable diameter range of cable entry
E7 E7 E7
max. 690 V AC, 50 / 60 Hz 0.1 ... 22.5 A
E7 2013-02-27·EK00·III·en
Load Disconnect Switches and Motor Starters
E7/5
Motor Protection Circuit Breaker Series 8527/2 Technical data Contact Switching Capacity
Service life electrical mechanical Main contacts Short circuit protection
according to the selected adjustment range (AC) 230 V
400 V
500 V
690 V
7.0 kW
12.4 kW
16 kW
22 kW
105 operations 105 operations 3-pole Adjustment ran- Highest rated current of the short circuit fuse if ICC > ICS ge from ... to at 230 V AC at 400 V AC at 440 V AC at 500 V AC ICS 0.1 A ... 0.16 A up to 1.0 A ... 1.6 A
gG, aM
ICS
gG, aM
ICS
gG, aM
ICS
gG, aM
60 kA
35 A / 40 A
40 kA
at 690 V AC ICS
gG, aM
40 kA
25 A
10 kA
40 kA
50 A
7 kA
40 A
Short-circuit proof, no fuse needed up to ICC = 100 kA
1.6 A ... 2.5 A 2.5 A ... 4.0 A 4.0 A ... 6.3 A
70 kA 50 A
6.3 A ... 9.0 A
50 kA 80 A
30 kA
80 A
5 kA
50 A
9.0 A ... 12.5 A
75 kA
80 A
45 kA 80 A
27 kA
80 A
4.5 kA
50 A
12.5 A ... 16.0 A
60 kA
100 A
40 kA 100 A
22 kA
100 A
4 kA
50 A
16.0 A ... 20.0 A
55 kA
100 A
35 kA 100 A
22 kA
100 A
3.5 kA
50 A
20.0 A ... 22.5 A
50 kA
125 A
30 kA 125 A
20 kA
125 A
3 kA
50 A
ICS = Rated short-circuit breaking capacity ICC = Projected short circuit current at the installation location Thermal overcurrent release
according to the adjustment range of the switch, selectable on the switch see tripping characteristic curve
Electromagnetic quick release
Ambient conditions Ambient temperature range Mechanical data Switching handle
Auxiliary contacts Device version Electrical data Rated operational voltage Ue Rated operational current
E7/6
Adjustment range
Operate value set at factory
0.16
...
0.63 A
7.5
...
12.0 In
1.0
...
2.5 A
9.0
...
14.0 In
2.5
...
4.0 A
10.0
...
15.0 In
4.0
...
6.3 A
10.0
...
15.0 In
9.0
...
22.5 A
12.5
...
17.5 In
-20 ... +40 °C
Labelling: 0 - I; can be locked with 3 padlocks in 0-position Colour: Standard: Handle black, protective collar black Special version: Handle red, protective collar yellow (for EM-STOP function) optional: without; 1 NC + 1 NO; 2 NCs + 2 NOs max. 500 V AC AC-15: 24 V / 2.5 A; 230 V / 2 A; 400 V / 1 A DC-13: 24 V / 2.5 A; 60 V / 2.5 A; 110 V / 0.6 A; 220 V / 0.25 A
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en
Motor Protection Circuit Breaker Series 8527/2 Technical data Undervoltage release Electrical data Function Pick-up voltage Drop-out Power consumption Inrush Holding Shunt release Electrical data Function Pick-up voltage Relative duty cycle Power consumption Inrush Holding Ammeter Device version Electrical data Movement Measuring range Overload capacity
E7 in case of voltage interruption, circuit-breaker triggers; this prevents unwanted restarting, e.g. of a motor ) 0.85 x Uc 0.7 ... 0.35 x Uc
E7
0.9 VA 0.9 VA
E7
for remote tripping of circuit-breakers by applying actuating voltage ) 0.85 x Uc Switches off automatically via integrated contact switch
E7
24 ... 60 V: 14.4 ... 90 VA; 110 ... 240 V: 13 ... 61 VA; 220 ... 415 V: 17.6 ... 62.3 VA Switches off automatically via integrated contact switch Type 8405; dimensions 64 mm x 64 mm
E7
Moving iron: class 2.5; direct measuring; overload scale 1:2 according to the adjustment range of the switch 2 x Ie 25 s, 50 x Ie 1 s
E7 E7 E7 E7 E7 E7 E7 E7 E7 2013-02-27·EK00·III·en
Load Disconnect Switches and Motor Starters
E7/7
Motor Protection Circuit Breaker Series 8527/2 Adjustment ran- Tripping time of the motor protection switch with ge of the motor 4 5 protection switch 3
6
7.2
8
times rated current, 3-pole from cold state. A ... A
s
s
s
s
s
s
0.1 ... 0.16
15.0
9.0
6.5
4.8
3.7
3.2
0.16 ... 0.25
16.0
10.0
6.8
5.2
4.0
3.6
0.25 ... 0.4
16.0
9.7
6.5
5.0
3.8
3.3
0.4 ... 0.63
17.0
10.2
7.3
5.7
4.4
3.9
0.63 ... 1.0
17.5
10.2
7.2
5.5
4.2
3.8
1.0 ... 1.6
17.0
10.0
7.1
5.6
4.4
4.0
1.6 ... 2.5
18.0
10.3
7.5
5.9
4.7
4.2
2.5 ... 4.0
18.4
11.5
8.1
6.4
5.0
4.6
4.0 ... 6.3
19.0
12.0
8.5
6.7
5.3
4.9
6.3 ... 9.0
18.2
11.5
7.9
6.0
4.5
3.8
9.0 ... 12.5
19.0
11.5
8.0
6.0
4.6
4.0
12.5 ... 16.0
19.5
11.5
7.5
5.4
4.0
3.3
16.0 ... 20.0
20.0
11.5
7.8
5.7
4.2
3.5
20.0 ... 22.5
20.0
10.4
7.0
5.0
3.7
3.2
11050E00
1) 2) 3) 4) 5)
E7/8
11051E00
Multiples of the rated operational current Tripping time 2-pole 3-pole Electromagnetic release
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en
Motor Protection Circuit Breaker Series 8527/2
E7 E7 E7 E7 E7 E7 11052E00
11053E00
E7 E7 E7 E7 E7 11054E00
1) 2) 3) 4) 5)
11055E00
Multiples of the rated operational current Tripping time 2-pole 3-pole Electromagnetic release
E7 E7 E7
2013-02-27·EK00·III·en
Load Disconnect Switches and Motor Starters
E7/9
Motor Protection Circuit Breaker Series 8527/2
1) 2) 3) 4) 5)
E7/10
11056E00
11057E00
11058E00
11059E00
Multiples of the rated operational current Tripping time 2-pole 3-pole Electromagnetic release
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en
Motor Protection Circuit Breaker Series 8527/2
E7 E7 E7 E7 E7 E7 11060E00
11061E00
E7 E7 E7 E7 E7 11062E00
1) 2) 3) 4) 5)
11063E00
Multiples of the rated operational current Tripping time 2-pole 3-pole Electromagnetic release
E7 E7 E7
2013-02-27·EK00·III·en
Load Disconnect Switches and Motor Starters
E7/11
Motor Protection Circuit Breaker Series 8527/2 Dimensional Drawings (All Dimensions in mm) - Subject to Alterations
04793E00
8527/21
04794E00
8527/22
04795E00
8527/23; 8527/24
04796E00
8527/25; 8527/26 Cable entries Type 8527/21 8527/22 8527/23; 8527/24 8527/25; 8527/26 0.1 ... 12.5 A 12.5 ... 22.5 A
Accessories without with without with without with
Cable glands 8161 M25 x 1.5 M32 x 1.5 A+B -A, B, C -A+B -A, B, C --A+B C A+B
Stopping plugs 8290 M25 x 1.5 C -C -C --
without with without with
A+B A, B, C -C
C -C --
--A+B A+B
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.
E7/12
Load Disconnect Switches and Motor Starters
2013-02-27·EK00·III·en