Submittal Data: UMAT18HP230V1AD Job Name Purchaser Submitted To Unit Designation
GENERAL FEATURES
18,000 BTUH Slim Duct Heat Pump System
Location Engineer For Reference Schedule No.
Date Approval
Construction
-Multi-Speed Fan -Medium Static Pressure Capability -Flexible Return Air From Bottom Or Rear -Internal Condensate Drain Pump -Sentry Condensate Overflow Protection -XK-60 Wired Remote Controllers -Gold Fin Condenser Coating -5 yr. Limited Parts Warranty
AHRI Certified Ref No: 7630507
-7 year Limited Compressor Warranty
System Ratings Fan Motor
Cooling Rated Capacity Capacity Range Power Input (Max) SEER EER Heating at 47° F Rated Capacity Capacity Range Power Input (Max) HSPF COP Heating at 17° F Rated Capacity
Operating Range Cooling Heating
17,100 BTU/H 5,400-19,800 BTU/H 1,750 W 16.0 11.0 18,800 BTU/H 4,700-23,200 BTU/H 1,900 W 9.5 3.3 10,900 BTU/H
(Max) (Min) (Max) (Min)
Refrigerant Piping Data Gas Pipe Size (OD) Liquid Pipe Size (OD) Connection Method MAX Refrigerant Pipe Length MIN Refrigerant Pipe Length MAX Refrigerant Pipe Elevation
115℉ (46 C) 0℉ (-18 C) 75℉ (24 C) 0℉ (-18 C) 1/2-in 1/4-in Flared 66-ft 10-ft 49-ft
Indoor Unit Data Output Power FLA
Airflow Cooling Wet (Lo/Hi) Heating Dry (Lo/Hi) Sound Pressure Level Cooling (Min/Max) Heating (Min/Max) Dehumidication Condensate Drain Lift (Height)
1/10HP 0.6 A 362/585 CFM 362/585 CFM 28/40 db(A) 28/40 db(A) 0.66 pt/hr
39-in
Power Supply 208/230 V, 1 Phase, 60 Hz Normal Operational Voltage 187 - 253 V Voltage Range 18-2 AWG Interconnecting Cable Wire Size 1.0A MCA 15A MOCP/Breaker Size Outdoor Unit Data Compressor DC Inverter Driven Rotary Refrigerant Type R410A Fan Motor Output Power 1/6HP FLA 1.5 A Sound Pressure Cooling/Heating 56/56 db(A) Power Supply 208/230 V, 1 Phase, 60 Hz Normal Operational Voltage 187 - 253 V Voltage Range 17.0A MCA 25 A MOCP/Breaker Size
© Gree Corporation 2015
V0.0
Submittal Data: UMAT18HP230V1AD
18,000 BTUH Slim Duct Heat Pump System
FAN PERFORMANCE CURVES
EXTENDED RATINGS COOLING PERFORMANCE
HEATING PERFORMANCE
© Gree Corporation 2015
V0.0
Submittal Data: UMAT18HP230V1AD
18,000 BTUH Slim Duct Heat Pump System
MINIMUM SPACING REQUIREMENTS
Units: inch (mm)
INDOOR
Units: inch (mm)
OUTDOOR
© Gree Corporation 2015
V0.0
DIMENSIONAL SPECIFICATIONS INDOOR UNIT DIMENSIONS & WEIGHTS
UMAT18HP230V1AD Units: inch (mm) A B C D E F G H I J
Net Weight Shipping Weight
Liquid Line Valve Gas Line Valve Drain Connector
73 lbs 84 lbs
OUTDOOR UNIT DIMENSIONS & WEIGHTS
Net Weight Shipping Weight
37.25 24.375 29.0 35.125 40.88 28.375 29.0 4.875 8.0 10.5
1/4-in OD Flared 1/2-in OD Flared 1-in OD Units: inch (mm)
Liquid Line Valve Gas Line Valve
106 lbs 115 lbs
1/4-in OD Flared 1/2-in OD Flared
Notes: 1. Recommended Communication Cable Type 18-2 AWG Stranded Copper THHN 600V Wire 2. Power wiring cable size must comply with applicable national and local codes. 3. Test conditions are based on AHRI 210/240. Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.
© Gree Corporation 2015
(945) (618) (738) (892) (1037) (721) (738) (125) (203) (266)
V0.0