Innovative Ductless Mini Split Solution
Submittal Data: UMAT24HP230V1AD Job Name Purchaser Submitted To Unit Designation
GENERAL FEATURES
24,000 BTUH Slim Duct Heat Pump System
Location Engineer For Reference Schedule No.
Date Construction
Approval
-Multi-Speed Fan -Medium Static Pressure Capability -Flexible Return Air From Bottom Or Rear -Internal Condensate Drain Pump -Sentry Condensate Overflow Protection -XK-60 Wired Remote Controllers -Gold Fin Condenser Coating -5 yr. Limited Parts Warranty
AHRI Certified Ref No: 7630812
-7 year Limited Compressor Warranty
System Ratings Fan Motor
Cooling Rated Capacity Capacity Range Power Input (Max) SEER EER Heating at 47° F Rated Capacity Capacity Range Power Input (Max) HSPF COP Heating at 17° F Rated Capacity
Operating Range Cooling Heating
23,800 BTU/H 7,400-29,000 BTU/H 2,500 W 16.0 10.7 27,200 BTU/H 8,200-32,400 BTU/H 2,750 W 10.0 3.4 16,700 BTU/H
(Max) (Min) (Max) (Min)
Refrigerant Piping Data Gas Pipe Size (OD) Liquid Pipe Size (OD) Connection Method MAX Refrigerant Pipe Length MIN Refrigerant Pipe Length MAX Refrigerant Pipe Elevation
115℉ (46 C) 0℉ (-18 C) 75℉ (24 C) 0℉ (-18 C) 5/8-in 3/8-in Flared 98-ft 10-ft 49-ft
Indoor Unit Data Output Power FLA
1/5HP 1.3 A
Airflow 570/820 CFM Cooling Wet (Lo/Hi) 570/820 CFM Heating Dry (Lo/Hi) Sound Pressure Level 40/47 db(A) Cooling (Min/Max) 40/47 db(A) Heating (Min/Max) Dehumidication 0.9 pt/hr 39-in Condensate Drain Lift (Height) Power Supply 208/230 V, 1 Phase, 60 Hz Normal Operational Voltage 187 - 253 V Voltage Range 18-2 AWG Interconnecting Cable Wire Size 2.0A MCA 15A MOCP/Breaker Size Outdoor Unit Data Compressor DC Inverter Driven Rotary Refrigerant Type R410A Fan Motor Output Power 1/6HP FLA 1.5 A Sound Pressure Cooling/Heating 57/57 db(A) Power Supply Normal Operational Voltage Voltage Range MCA MOCP/Breaker Size
© Gree Corporation 2015
V0.0
208/230 V, 1 Phase, 60 Hz 187 - 253 V 24.0A 40A
Submittal Data: UMAT24HP230V1AD
24,000 BTUH Slim Duct Heat Pump System
FAN PERFORMANCE CURVES
EXTENDED RATINGS COOLING PERFORMANCE
HEATING PERFORMANCE
© Gree Corporation 2015
V0.0
Submittal Data: UMAT24HP230V1AD
24,000 BTUH Slim Duct Heat Pump System
MINIMUM SPACING REQUIREMENTS
Units: inch (mm)
INDOOR
Units: inch (mm)
OUTDOOR
© Gree Corporation 2015
V0.0
DIMENSIONAL SPECIFICATIONS INDOOR UNIT DIMENSIONS & WEIGHTS
UMAT24HP230V1AD Units: inch (mm) A B C D E F G H I J
Net Weight Shipping Weight
Liquid Line Valve Gas Line Valve Drain Connector
75 lbs 86 lbs
OUTDOOR UNIT DIMENSIONS & WEIGHTS
152 lbs 163 lbs
Liquid Line Valve Gas Line Valve
3/8-in OD Flared 5/8-in OD Flared 1-in OD
38.625 (980) 16.75 (427) 31.125 (790) 24.0 (610) 15.5 (395)
3/8-in OD Flared 5/8-in OD Flared
Notes: 1. Recommended Communication Cable Type 18-2 AWG Stranded Copper THHN 600V Wire 2. Power wiring cable size must comply with applicable national and local codes. 3. Test conditions are based on AHRI 210/240. Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.
© Gree Corporation 2015
(1101) (517) (820) (1159) (1279) (558) (1002) (160) (235) (268)
Units: inch (mm)
A B C D E
Net Weight Shipping Weight
43.375 20.375 32.25 45.625 50.38 22.0 39.5 6.25 9.3 10.5
V0.0