Transcript
Innovative Ductless Mini Split Solution
Submittal Data: UMAT30HP230V1AC Job Name Purchaser Submitted To Unit Designation
GENERAL FEATURES -Multi-Speed Fan -4-way Discharge Air -Internal Condensate Drain Pump -Wireless Remote Controllers -Power Failure Recovery -Sentry Condensate Overflow Protection -Decorative Grille ( Part# UMAT30GRILLE -Sold Separately) -5 yr. Limited Parts Warranty -7 year Limited Compressor Warranty System Ratings Cooling Rated Capacity 28,200 BTU/H Capacity Range 8,800-31,400 BTU/H Power Input (Max) 3,700 W SEER 20.0 EER 10.4 Heating at 47° F Rated Capacity 31,200 BTU/H Capacity Range 8,200-33,600 BTU/H Power Input (Max) 3,500 W HSPF 9.0 COP 3.7 Heating at 17° F Rated Capacity 16,700 BTU/H
Operating Range Cooling Heating
(Max) (Min) (Max) (Min)
Refrigerant Piping Data Gas Pipe Size (OD) Liquid Pipe Size (OD) Connection Method MAX Refrigerant Pipe Length MIN Refrigerant Pipe Length MAX Refrigerant Pipe Elevation
115℉ (46 C) 0℉ (-18 C) 75℉ (24 C) 0℉ (-18 C) 5/8-in 3/8-in Flared 98-ft 10-ft 49-ft
30,000 BTUH Ceiling Cassette Heat Pump System
Location Engineer For Reference Schedule No.
Date Construction
Approval
AHRI Certified Ref No: 7630984
Fan Motor
Indoor Unit Data Output Power FLA
1/5HP 0.9 A
Airflow 587/880 CFM Cooling Wet (Lo/Hi) 587/880 CFM Heating Dry (Lo/Hi) Sound Pressure Level 40/49 db(A) Cooling (Min/Max) 40/49 db(A) Heating (Min/Max) Dehumidication 1.42 pt/hr 39-in Condensate Drain Lift (Height) Power Supply 208/230 V, 1 Phase, 60 Hz Normal Operational Voltage 187 - 253 V Voltage Range 18-2 AWG Interconnecting Cable Wire Size 1.5A MCA 15A MOCP/Breaker Size Outdoor Unit Data Compressor DC Inverter Driven Rotary Refrigerant Type R410A Fan Motor Output Power 1/6HP FLA 1.5 A Sound Pressure Cooling/Heating 58/58 db(A) Power Supply Normal Operational Voltage Voltage Range MCA MOCP/Breaker Size
© Gree Corporation 2015
V0.0
208/230 V, 1 Phase, 60 Hz 187 - 253 V 24A 40A
Submittal Data: UMAT30HP230V1AC
30,000 BTUH Ceiling Cassette Heat Pump System
EXTENDED RATINGS COOLING PERFORMANCE
HEATING PERFORMANCE
© Gree Corporation 2015
V0.0
Submittal Data: UMAT30HP230V1AC
30,000 BTUH Ceiling Cassette Heat Pump System
MINIMUM SPACING REQUIREMENTS
Units: inch (mm)
INDOOR
Units: inch (mm)
OUTDOOR
© Gree Corporation 2015
V0.0
DIMENSIONAL SPECIFICATIONS INDOOR UNIT DIMENSIONS & WEIGHTS
A 37.375 (950)
B 32.75 (833)
Net Weight Shipping Weight
71 lbs 97 lbs
C 30.75 (780)
D 26.75 (680)
E 6.25 (160)
F 9.5 (240)
G 36.125 (917)
UMAT30HP230V1AC Units: inch (mm)
H 8.5 (215)
Liquid Line Valve Gas Line Valve Drain Connector
OUTDOOR UNIT DIMENSIONS & WEIGHTS
3/8-in OD Flared 5/8-in OD Flared 1-in OD Units: inch (mm)
A B C D E
Net Weight Shipping Weight
I 39.125 (993)
159 lbs 180 lbs
Liquid Line Valve Gas Line Valve
38.625 (980) 16.75 (427) 31.125 (790) 24.0 (610) 15.5 (395)
3/8-in OD Flared 5/8-in OD Flared
Notes: 1. Recommended Communication Cable Type 18-2 AWG Stranded Copper THHN 600V Wire 2. Power wiring cable size must comply with applicable national and local codes. 3. Test conditions are based on AHRI 210/240.
www.greecomfort.com
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.
© Gree Corporation 2015
V0.0