Transcript
CPH Series S ubmittal D ata F orm
3- to 6-Ton Self-Contained Packaged Heat Pump with R-410A
Job Name Location Purchaser Order No. Engineer Unit No. Model No. Unit Designation Performance Data Certified By:
Standard Features • • • • • • • • • • • •
Chlorine-free R-410A refrigerant High-efficiency scroll compressor Copper tube/aluminum fin coils Contactor with lugs High-capacity, steel-cased filter dryer Single-point entry 24-volt terminal strip Convertible Easy to service Built-in filter rack with standard 2” filters Bottom utility entry ARI Certified; ETL Listed
Cabinet Features
• Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish • Full Perimeter Rail • Curb Fit
Contents
Performance Data Accessories List Certified Dimensions Individual Accessories Dimensions
* Complete warranty details available at www.goodmanmfg.com.
SF-CPH36-72 www.goodmanmfg.com
6/10
Supersedes 10/09
Job Name
Location
Performance Data Cooling Performance Tota Capacity
MBH
Sensible Capacity
MBH
Outdoor Design TMP
ºF DB / WB
Air Temp entering Evaporator Coil
ºF
Power Input Required
kW
(less blower motor) Heating Performance Total Heating Capacity
kW BTU/h
Supply Air Blower Performance Total Supply Air
CFM
Ext. Static Pressure
IWG
Blower Speed
RPM
Power Output Required
BHP
Motor Ratings
HP
Power Input Required
kW Electrical Data
Power Supply Total Unit Amps
Amps
Max Overcurrent Device: Fuse
2
Breaker
Amps
www.goodmanmfg.com SF-CPH36-72
Job Name
Location
Accessories List (Detailed specifications begin on page 6.) Item #
Description
Fits Model Sizes
Package Dimensions (“)
Ship Weight (lbs.)
14CURB3672B
Roof Curb – 14” Tall
3-6 tons
16 x 6 x 76
119
25FD3672
25% Manual Fresh Air Damper
3-6 tons
13 x 15½ x 27
11
25MFD3672
25% Motorized Fresh Air Damper
3-6 tons
13 x 15½ x 27
12
BRD3672
Horizontal Barometric Relief Damper
3-6 tons
15 x 15 x 20
8
CDK4872
Concentric Duct Kit
4-6 tons
25 x 48 x 16
35
DNECONGS3672B
Downflow Economizer
3-6 tons
43 x 20 x 24
75
DNECONGS3672B-NR
Downflow Economizer w/o Barometric Relief
3-6 tons
43 x 20 x 24
75
DNSQRRND4872B
Downflow Square-to-Round Adapter 18” Round
4-6 tons
13 x 33 x 10
11
DNBBS3672B
Burglar Bar Sleeves Includes Supply & Return
3-6 tons
41 x 18 x 13
45
GHRC-1
Hurricane Restraint Clip
HAILGD04
Condenser Coil Hail Guard
HA-02
High-Altitude Kit
HSKT072B
High-Static Kit
HZECONGS3672B
Horizontal Economizer
All Models
10 x 5 x 4
4
6 tons
41 x 37 x 3
27
All Models
5.4 x 4.6 x 4.1
1.7
6 tons
20 x 7¼ x 8¾
40
3-6 tons
16½ x 21½ x 36
75
LAKT01
Low-Ambient Kit
3-6 tons
6x6x6
3
LPM-05
LP Conversion Kit
3-6 tons
4¼ x 6¼ x 4½
1
PE36722B
Power Exhaust 208/230v CPX Unit
3-6 tons
37 x 18 x 16
35
PE36724B
Power Exhaust 460v CPX Unit
3-6 tons
37 x 18 x 16
35
SF-CPH36-72
www.goodmanmfg.com
3
Job Name
Location
Dimensions — 3- to 5-T on Models APPENDIX C UNIT DIMENSIONS 47 1/2” 73 1/4”
38 13/16”
73 13/16” 48 3/16”
11”
17”
7 3/8” RETURN
12”
4 7/8”
19 7/16”
25”
SUPPLY RETURN
DRAIN THRU CURB LOCATION
5 7/8”
6 1/4”
EMBOSS FOR THRU THE BASE UTILITIES
SUPPLY 27 3/8”
Horizontasl Discharge Horizontal Discharge
4 1/2”
NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package.
8 3/16”
7 1/2”
47 1/2”
BOTTOM VIEW OF UNIT
Vertical Vertical Discharge Discharge 30
4
www.goodmanmfg.com SF-CPH36-72
Job Name
Location
Dimensions— 6-Ton Models
APPENDIX C UNIT DIMENSIONS
47¹/₂” 47 1/2” 73¹/₄” 73 1/4”
42¹³/₁₆” 38 13/16”
7374¹/₁₆” 13/16” 48 3/16” 48³/₁₆”
11”
17”
77³/₈” 3/8” RETURN
12”
4⁷/₈” 4 7/8”
19 7/16” 19⁷/₁₆”
25”
SUPPLY RETURN
DRAIN THRU CURB LOCATION
5 7/8” 5⁷/₈”
6 1/4”
Horizontal Discharge
EMBOSS FOR THRU THE BASE UTILITIES
SUPPLY 27 3/8” 27³/₈”
Horizontasl Discharge
44¹/₂” 1/2”
NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package.
88³/₁₆” 3/16”
7 1/2” 7¹/₂”
47 1/2” 47¹/₂”
Vertical BOTTOM VIEWDischarge OF UNIT Vertical Discharge 30
SF-CPH36-72
www.goodmanmfg.com
5
Job Name
Location
Roof Curb — #14CURB3672B 3-D View
Top View Insulated Panels
1.625 TYP.
70.75 O.D. 3
3
32.875
14 14.625
70¾
40¼
S/A 14 x 20 Supply Opening
20
20
37 40.25 I.D. O.D.
16.000
14
31⅝ x 14 Return Opening
3
O 1.750
15/6 ¾
14
31.625
R/A
15.250
14 1⅜
67.5 I.D.
Specifications • • • • •
18-Gauge Construction 1 x 4 Wood Nailer attached to top of the curb Shipped knocked down with all hardware Gasket included Bed-Rail style corners
Note: outside duct dimension should be ½” less than opening dimensions above.
No Curb Adapter Required when Replacing Carrier & Bryant Models No curb adapter is required when replacing an existing Carrier or Bryant RTU with a Goodman RTU in these situations; the footprints and locations of the return and supply duct work match. New Unit
Existing Carrier
Existing Bryant
3 to 6 Tons CPC, CPG, CPH
48/50 TJ, LJ, DJ, QJ 48/50 TM, HJ 004 - 007
580C-D, 558C-D, 548C-D 580F, 558F, 581B 036 - 072
6
www.goodmanmfg.com SF-CPH36-72
Job Name
Location
Manual Fresh Air Damper — #25FD3672 Motorized Fresh Air Damper — #25MFD3672
Specifications Manual Damper • • • •
Provides up to 25% fresh air Locking selection knob provides constant opening Painted to match the unit Fits all 3- to 5-ton package units in all fuels
Motorized Damper • • • •
24 VAC Damper motor with spring return Fully assembled and factory wired Painted to match the unit Fits all 3- to 5-ton package units in all fuels
SF-CPH36-72
www.goodmanmfg.com
7
Job Name
Location
Downflow Economizer — #DNECON**3672B
Specifications • • • • • • • • •
Fully modulating Up to 100% fresh air Integral barometric relief Hoods painted to match unit Honeywell economizer control Single adjustable enthalpy control convertible to dual enthalpy Adjustable minimum fresh air Factory wired Fits all 3- to 5-ton models
8
www.goodmanmfg.com SF-CPH36-72
Job Name
Location
Horizontal Economizer — #HZECON**3672B
Specifications • • • •
Fully modulating Up to 100% fresh air Honeywell economizer control Single adjustable enthalpy control convertible to dual enthalpy • Adjustable minimum fresh air • Factory wired • Fits all 3- to 5-ton models
SF-CPH36-72
www.goodmanmfg.com
9
Job Name
Location
Barometric Relief Damper — #BRD3672
Hurricane Restraint Clip — GHRC-1
Specifications • • • •
14-gauge construction Location and quantity of clips dictated by unit need Clips are fastened to the unit and curb using sheet-metal screws Seismic angle is fastened with approved fastener
10
www.goodmanmfg.com SF-CPH36-72
Job Name
Location
Concentric Duct Kit — #CDK36 / #CDK4872
Commercial T-Bar Ceiling
Light Commercial T-Bar Ceiling
Specifications • • • • •
All-aluminum diffuser with aluminum return air egg crate Built-in anti-sweat gasket Molded fiberglass transition (through five tons) Built-in hanging supports Diffuser box constructed of fiberglass duct board (through 7½ tons) or sheet metal
Hanging Support from the Diffuser Turing Vane to Ensure Proper Airflow Aluminum Egg Crate
Molded Fiberglass Transition
SF-CPH36-72
www.goodmanmfg.com
11
Job Name
Location
3-Ton Square-to-Round — #DNSQR36
4- to 6-Ton Square-to-Round — #DNSQR4872
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2009 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
12
www.goodmanmfg.com SF-CPH36-72