Transcript
S M M S i / S HR M i V RF I ndo or Uni t HFGTYUT
MMD-AP0424BH2UL - Medium Static Ducted Model: MMD-AP0424BH2UL
Submittal Data Unit – (s) #:
SMMSi /SHRMi VRF Medium Static Features • • • • • • • • •
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R-410A Capacity
R-410A Refrigerant Eleven sizes from 7,500 to 48,000 Btu/h Standard condensate pump with 10.7” lift capability Quiet operation, as low as 27.5 dB(A) Sound Pressure Rear return Configurable for bottom return. Optional wired or wireless controls Auto or manually set three fan speeds 1 inch track for field supplied filters One year parts limited warranty
Fan System Type x Number . . . . . . . . . . . . . . . . . . . . . . . . . . Centrifugal x 1
Cooling (Btu/h) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42,000
Air Flow Rate CFM (L-M-H) . . . . . . . . . . . . . . .871 - 1165 - 1324
Heating (Btu/h). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47,500
Max Ext. Static Pressure In. WG . . . . . . . . . . . . . . . . . . . . .0.44
Electrical
Motor
Power Source . . . . . . . . . . . . . . . . . .208 / 230V, 1-Phase, 60 Hz
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DC Inverter Driven
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.142 kW
Watts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Full Load Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2 A Minimum Circuit Amps (MCA) . . . . . . . . . . . . . . . . . . . . . . . 2.8 A Maximum Over Current Protection (MOCP) . . . . . . . . . . . . . 15 A Physical Characteristics External Finish . . . . . . . . . . . . . . . . . . Zinc Hot Dipped Steel Plate Dimensions
Sound Pressure Levels Low-Med-High dB(A) . . . . . . . . . . . . . . . . . . . . . . . 36 - 38.5 - 41 Refrigerant Piping Connections Liquid (High Pressure) . . . . . . . . . . . . . . . 3/8" / 9.52 mm (Flare) Gas (Low Pressure). . . . . . . . . . . . . . . . .5/8" / 15.87 mm (Flare)
W xx 53 31 3/16 1/2 D Inches Unit. . . . . . . . . . . . . . . 12 .129/16 9/16 H H xx 53 39 1/5 3/8 W D mm Unit . . . . . . . . . . . . . . . . . . . .320.0 H x 1351.3 W x 800.1 D Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119 lbs. / 53.9 kg
Drainpipe Connection O.D. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 -1/4" / 31.8 mm I.D. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1" / 25.4 mm
Accessories □ Wired Controller w Timer . . . . . . . . . . . . . . . .RBC-AMT32UL
□ Remote Sensor . . . . . . . . . . . . . . . . . . . . . . . . . TCB-TC21LUL
□ 7 Day Prog. Wired Controller . . . . . . . . . . .RBC-AMS51E-ES . . RBC-AMS41UL
□ Fan Guard** . . . . . . . . . . . . . . . . . . . . . . . . . . TCB-IG211BUL
□ Simple Controller . . . . . . . . . . . . . . . . . . . . . . . .RBC-AS21UL
* With Stand Alone Receiver
□ Wireless Remote Kit* . . . . . . . . . . . . . . . . . . . . TCB-AX21UL
** Required with Bottom Return Applications
DIMENSIONAL DRAWING -- INDOOR UNIT Medium Static Ducted Model: MMD--AP0424BH2UL Drain pipe connecting port VP25(Polyvinyl chloride tube): External Dia., 1-1/4” (31.7) Internal Dia., 1” (25.4)
Unit external dimension 31.5"(800)
2"(50)
19.6"(498) 1.6"(41)
Unit external dimension B
2"(50)
1.7"(42)
Supply air duct flange dimensions C 5.5"(140)
Supply Air
1.2"(30)
6.3"(159.9)
5"(127)
15.1"(384)
9.5"(240)
0.3"
2.4"(59)
25.1"(638) 5.2"(131)
1” Air filter track Hanging bolt spacing A
2.2"(57)
Hanging bolt spacing 27.6” (700)
1.6"(41)
Air filter track
Z
12.6"(320)
1"(25)
Outside 8.6"(218.2)
5.8"(147.5)
Return Air Refrigerant pipe connecting port G (Gas side)
1.7"(44) 1.9"(49)
1"(26) Hole for control wire and remote control wiring 7/8"(22.2) Hole for power supply cable
Refrigerant pipe connecting port H (Liquid side)
Bottom Return Accessory fan guard required Hanging bolt
Air filter track
Supply Air
12"(300) or less
6.3"(159) 9.6"(243.2) Outside 9.6"(243.2)
12.6"(320)
Drain connection Drain connection is ABS. If drain piping is PVC, the correct glue must be used
1.2"(30)
Return air flange
2.2"(57)
21.7"(550) or less
10.7"(271) or less
(per local codes)
3.6"(91)
Return Air
Return air duct flange dimensions D
Z view
Space required for installation and servicing Clearance required for maintenance and service Supply Air
Electrical control box
Unit width B
Ceiling opening size
Ceiling opening size E *
17.7"X17.7" (450X450)
5.9"(150) or more 4"(100)
Optional access area B*
4"(100)
5.9"(150) or more
Supply Air
Air filter (locally procured)
access area A*
17.7"X17.7" (450X450)
Ceiling Electrical control box
15.5"(400) (Min.) †
31.5"(800)
Air filter (locally procured)
Return air 1.2"(30) 5.9"(150)
Ceiling Drain pan / Drain pump check cover
Ceiling opening size * 38.6"(980)
Space for removing or replacing the filter F
Space for removing or replacing the filter F
Electrical control box
NOTES: • Access area A is required for maintaining and servicing the electrical box, filter, drain pump, drain pipe, and refrigerant pipe • The filter can be replaced through access area A or B ONLY. • When routing the refrigerant and drain pipe, do not block access to control box and filter. • Filters are field supplied per local code requirements.
Un it :in (m m )
*Required if installation is not above a suspended ceiling. †In case of bottom return: 17.7” (450) min.
Model A MMDAP0074BH2UL, AP0094BH2UL, 24.3" A0124BH2UL (616) 42" AP0154BH2UL, AP0184BH2UL (1066) AP0214BH2UL, AP0244BH2UL, 55.7" AP0304BH2UL, AP0364BH2UL, (1416) AP0424BH2UL, AP0484BH2UL
Copyright 2014 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
B
C
21.7" 13.9" (550) (351.6) 39.4" 31.6" (1000) (801.6)
D
E
18.6" 23.6" (471.6) (550) 36.3" 41.3" (801.6) (1050)
F
G
H
23.6" 0.375" 0.25" (550) (9.5) (6.4) 23.6" 0.50" 0.25" (550) (12.7) (6.4)
53.2" 45.4" 50.1" 55.1" 40.5" 0.625" 0.375" (1350) (1151.6) (1271.6) (1400) (1030) (15.9) (9.5)
Edition Date: 02/14 10/14
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
02 Catalog No:SUBMMD0424BH2UL---01 Replaces: NEW Replace: SUBMMD0424BH2UL-01