Transcript
3231350/3
Issue 3
SX75 Series Process Controller
Installation and Maintenance Instructions
Printed in the UK
Copyright 2006
GENERAL INDEX 1. SAFETY INFORMATION ..................................... page 1 PRODUCT OVERVIEW 2. FUNCTIONS OF KEYS AND DISPLAYS ........... page 3 3. DIMENSIONS INSTALLATION ............................ page 6 4. ELECTRICAL WIRING ........................................ page 7 5. PASSWORD PROTECTION ............................. page 15 6. PROGRAMMING INSTUCTIONS FUNCTIONS MENU CONFIGURATION SETTING OF PARAMETERS (see enclosed leaflet)
7. OPERATING INSTUCTIONS (second leaflet) FUNCTIONS MENU CHANGING NUMERIC VALUES SET POINT - MODIFY - RECALL - LOCAL / REMOTE OPERATION - AUTOMATIC / MANUAL OPERATION - TUNING - AUTOTUNE
8. EVENT OUTPUTS ............................................. page 16 9. OPERATING MODE .......................................... page 18 10.TECHNICAL DATA ............................................ page 19
1. SAFETY INFORMATION All personnel using this product must carefully read this manual prior to operation. Your attention is drawn to Safety Information Leaflet IM-GCM-10. If
these controllers are handled improperly or not used as specified, the result may: cause danger to the life and limb of the user or a third party. damage to the controller and other items belonging to the owner. hinder the performance of the controller.
1.1 WIRING NOTES Every effort has been made during the design of the controller to ensure the safety of the user, but the following precautions must be followed:
Maintenance personnel must be suitably qualified in working with equipment containing hazardous live voltages. Ensure correct installation. This Controller is designed for installation in an enclosure which provides adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed. Consideration should be given to prevention of access to the power terminationís by unauthorised personnel. Safety may be compromised if the installation of the product is not carried out as specified in this manual. Isolate the Controller from the mains supply before opening the unit. The controller is designed as an installation category II product, and is reliant on the building installation for over-current protection and primary isolation. Wiring should be carried out in accordance with IEC 364 or equivalent. Fuse rated at 0.5A/250V should be fitted in all phases of the Controllerís supply. Fuses should not be fitted in the protective earth conductor. The integrity of the installation protective earth system must not be compromised by the disconnection or removal of other equipment. The Mains cable connections at the rear of the controller, must be retained in position (by tie wrapping Etc.). This will prevent the high voltage cables at the rear of the controller from touching the SELV (Safe Extra Low Voltage) connections, in the unlikely event of the terminals coming loose. A disconnecting device (switch or circuit breaker) must be included in the building installation. This must be in close proximity to the equipment and within easy reach of the operator. There must be a 3mm contact separation in all poles. It must be marked as the disconnecting device for the controller. It must not interrupt the protective earth conductor. It must not be incorporated into a mains supply cord. The requirements for the disconnecting device are specified in IEC 947-1 and IEC 947-3 or equivalent. The Controller must not be located in such a way that the disconnecting device is made difficult to operate.
1
1.2 SAFETY REQUIREMENTS AND ELECTROMAGNETIC COMPATIBILITY NOTES This product is CE marked. It conforms to the council directive 89/336/EEC and the directive 92/31EEC, which modifies the directive 89/336/EEC (Electromagnetic Compatibility) by meeting the standards EN50081-2 (Industrial emission) and EN50082- 2 (Industrial immunity). And the council directives 73/23/EEC (Low Voltage) as amended by article 13 of the directive 93/68/EEC, by meeting the standard EN 61010-1.
This product may be exposed to interference above the limits of EN 50082-1 if:
The product or its wiring is located near a radio transmitter. Excessive electrical noise occurs on the mains supply. Cellular telephones and mobile radios may cause interference if used within approximately three metre of the product or its wiring. The actual separation necessary will vary according to the power of the transmitter. AC power line protectors should be installed if mains supply noise is likely, Protectors can combine filtering , suppression, surge and spike arrestors.
1.3 PRODUCT OVERVIEW The SX75 is a panel mounted microprocessor controller having auto tune, 4 programmable set point control, universal inputs and outputs incorporating PID and fuzzy logic algorithms for close control of industrial processes. Type SX75+ additionally has re-transmit and serial communicators.
2
2. FUNCTION OF KEYS AND DISPLAYS Auto-tune in course
Active Remote Set Active serial communication
Set Point Number
275.8 275.8
50
4
output Y3 ON
Measured Vaue X
Set point W Manual operation Main output % Y1 Main output Y1 ON Main output Y1 (increases - Heat) Main output Y1F (decreases - cool)
output Y2 ON Set point Functions (menu)
Increment digit
Face seal IP54
Select digit
Withdrawal screw
Confirm data Automatic / Manual
Front cover
NUMERIC INDICATORS X, W, Y, N° Measured Value X The value of measure X is expressed in engineering units. (green) If value over range If value under range - In parameters: displays parameter values - In configuration: displays the values of EFGH configuration code (see enclosed leaflet)
8888 ____ 8888 ----
275.8
Set point W (green)
275.8 Output Y1
Displays the operating Set point (Local or Remote) - In parameters: displays the parameter codes - In configuration: displays the values of ILMN configuration code (see enclosed leaflet)
(green) Displays the value of main output Y1 from 0...100%
50 Set Point Number
(from - 100 to 100% for Y1 with dual action) - In configuration: Displays Co Dispalys current set point number
(green)
4 3
2. FUNCTION OF KEYS AND DISPLAYS LEDS FOR OUTPUT STATE Lit with output Y1 ON Not lit with continuous or dual action discontinuous output
Output Y1 (red) 1
Output Y1 (red)
Output Y1F (red)
Output Y2 (red)
Lit with output
Y1 "ON" (increasing valve motor drive position)
Lit with output
Y1 "ON" (decreasing valve motor drive position)
Y1 (heat) "ON" - dual action
Y1 (cool) "ON" - dual action
Lit with output Y2 ON
2
Output Y3 (red)
Lit with output Y3 ON
3
LEDS FOR OPERATING STATE Manual (green)
Lit in Manual operation
MAN
Remote (green)
Lit when the Remote Set point is operating (if off, the operating Set point is the Local one)
REM
Auto-Tune (green)
Lit when Auto-Tune function is activated
AT
Serial comm. (green)
Permanently lit when the serial communication is enabled to write. Flashes with signal in transit
SCI
Loop Break Alarm
275.8 275.8
4
50
With output Y3 active and configured as Loop Break Alarm, the front displays X and W will flash (see p. 15)
4
2. FUNCTION OF KEYS AND DISPLAYS KEYS Set Point
configuration: 1 Local used for: modifying the Local Set point 1 Local + 1 Remote used for: modifying the Local Set point changing from Local to Remote Set point and vice versa (see enclosed leaflet) 1 Local + 4 storable used for: modifying the Local Set point to recall the Local operating Set point recalling the 4 memorized Set points (see enclosed leaflet)
Digit selection
Increment digit
Functions
Enter
Auto/Man
Selects the digit to be modified (see enclosed leaflet) In Manual operation, decrements the value of main output Y1 Increments the value of the flashing digit, from 0
9 In manual operation increments the value of main output Y1 Permits access to menu of functions to be programmed Enter or Scroll of values and modes of operation
Keys for modifying numeric values of any data
Keys for data programming and processing
Change from Automatic to Manual operation and vice versa
5
3. DIMENSIONS - INSTALLATION 3.1 - Overall dimensions (in compliance with DIN 43700) 48
W
F
-
14
+
150
60 min. 65 min. with protection IP65
96 110 min. 150 min. with protection IP65
A/M
Ring with hook and locking screw
Front cover projection
Advised thickness 1 ÷ 16
92
+0.8
45
Wiring protection plate
+0.6
Panel apertures
3.2 - Panel installation A Panel fitting
B Fixing with ring
Install away from: heat sources corrosive gases dusty environments
Knurl for hook hold
Holding hooks
!
AMBIENT Temperature: 0 ÷ 50°C Humidity : 30 ... 85uR%
Seal ring fitting
C Screw locking
Locking screws
D Plate for engineering units
275.8 275.8
4
if different from °C, remove and apply label
50 °F
!
Do NOT force
labels supplied
cross-screwdriver
6
Pa
%
kPa
HR%
MPa
mV
l/m
V
m3/h
mA
Nm3/h
A
CO%
kW
O2%
psi
m
Bar
rh
4. ELECTRICAL WIRING A ● Terminal board
B ● Freeing the terminals 1 Lift the plate to free the location pin
All screw terminals M3.5 Location pin
Wiring protection plate
2 Rotate downwards
Plate screw
D ● Protecting the terminal board
C ● Wirring connections Cable wires section N°
With eyelet terminals
2
6.9 max.
With fork terminals 1
6.9 max.
1 Rotate upwards
7
0.25 ÷ 2.5 AWG 22 ÷ 14
2 Depress the plate to engage the pin
With tinned wire
2
6÷7
Recommended
7
4. ELECTRICAL WIRING Although this controller is designed to resist the heaviest disturbances present in industrial environments (level IV of standard (IEC 801-4), it is advised to read the safety information section 1. Also note the precautions below:-
!
Precautions
Advised conductor course Power supply and output channels
!
D E
Single out supply line from power line
D E
Keep away from electromagnetic contactors and powerful motors
Serial communication A Analogic inputs B Logic inputs and analogic signals C
A
B
C
E
A
B
C
E
Channel for low level signal conductors
Input D Outputs E
Wiring diagram TX
RX
3
3
i
4
A
Measuring input X
B
9
B
10
J, L, K, S
Pt100 (1)
7
11
21
12
IL1
22
IL2
23
Y3
IL3
24
Y2
0%
+ 24 Vdc (2)
wire transmitter
mA Volt
4
Logic inputs
6
4
20 mA
2
COM
2
5
Remote set input X
1
5 100% +
8 Retransmission Y4 output (SX75+)
8
25
(-)
26
Y1
27
Y1F
28
(-)
29
Y1
(+)
Single power supply 100...240 Vac - 50/60 Hz
1
Event outputs
7
13 14 15 16 17 18 19 20
A Relay A Relay 2nd channel (cool)
Valve motor drive
9
Serial communication (SX75+)
Continuous mA, V Logic 0/18 Vdc
6 Main output
4. ELECTRICAL WIRING Schema 1 Singledipower collegamento supply
11 12
Standard: 100 to 240 Vac - 15% + 10% 250 Vac max. Single power supply
Power consumption4VA
2 "X" measuring input A - For thermocouples J-L-K-S-R
Respect polarities
7
Always use a compensated cable suitable for the type of thermocouple used
9
Earth screen at one end only
Line: max. 150 W
B - For RTD Pt100 A
For 3-wire connection, use cables of same section (min. 1 sq.mm)
7
B
9
B
10
For 2-wire connection, use cables of adequate section (min. 1.5 sq.mm.) Note: with a 15 m. probe-controller distance and a 1.5 sq.mm. section cable, the error is about 1°C.
for 3-wire connection only Line: 20 W max. for wire
For 2-wire transmitter
C - Continuous, mA, Volt Auxiliary supply for transmitter
+24 Vdc
6
4
20 mA
+24 Vdc
6
6
X i
7 Input mA, Volt
7 Rj
Transmitter
9 Rj = 30 W per mA Rj = 10 KW per Volt
For 3 or 4-wire transmitter
+24 Vdc
7 Rj
X
9
9 Transmitter
com.
9
Rj
i
4. ELECTRICAL WIRING Schema 3 • Remote di collegamento Set point input Rin = 30 Ω per mA Rin = 330 KΩ per V
In current
4..20 mA
In voltage
0..10Vdc
5 Remote Set point mA, Volt Rin
NOT galvanically isolated
!
25
4 • Logic inputs External contacts COM H C1 H C2 H C3
IL1 IL2 IL3
21 22 23
Closing of contacts C1, C2, C3, for two seconds permits the selection AUTO or MAN, Local or Remote Set point and recalling the 4 memorized Set points
24
5 • Input potentiometer position (Valve motor drive)
From 100Ω to 10KΩ max
0% 0%
100%
25
y.1.
26
y.h.
27
Total stroke
Useful stroke
100%
See section 6: Setting of parameters and descriptions ref. Pot.1 on separate leaflet.
10
4. ELECTRICAL WIRING 6 Auxiliary Relays for Valve Motor Drive actuators Live Y1
Relay 1
VMD signal from SX75 controller
VMD signal to actuator
Y1
Relay 2 Neutral
Neutral
When using SX75 controllers to directly drive VMD electric actuators damage to the controllers internal relays might occur due to switching the relatively heavy electrical loads. Auxiliary relays should therefore always be installed between the controller and the valve drive actuator. This will protect the controller from switching the actuators high current loads, avoid introducing high current loops within the proximity of the controller, and provide an easily replaceable switching element outside of the controller. This advice is in line with that recommended by other manufacturers of similar equipment and is considered to be good working practice.
11
4. ELECTRICAL WIRING 6 Main output Y1
16 Y1 Y1F
Relay
17
Relay 2nd channel (cool)
18 Y1
19 20
Continuous 4..20mA (0..10Vdc)
Output options 1. 2 relays for switched single or dual action (Heating/cooling) or 3 position VMD (Valve motor drive). 2. Continuous 4-20mA output or (0-10Vdc) or logic output 0/18Vdc.
Logic output 0/18Vdc
A Single with Relay
Y1
16
Load
17
Normally open contact rating 5A/250Vac V~
for resistive loads (transition 2 x 10 (coeff.5) min. at 5A/250Vac)
B single in current
Y1
19 20
C single in voltage
Y1
19 20
Load 450 W max.
Continuous output 4..20mA galvanically isolated
Continuous output 0..10Vdc 500 W galvanically min. isolated
Load
! NOTE: Internal switch must be set 1
D single logic
Y1
19 20
Load V~
Output 0/18Vdc (20mA max.) galvanically isolated
Relay or static contactor
12
2 3
1 Continuous output 4...20mA Default 2 Continuous output 0...10Vdc 3 Logic output 0...18Vdc
4. ELECTRICAL WIRING 6 Main output Y1 (continued) E Valve motor drive
16
Y1
17
Y1
18
Increase relay V~ Decrease relay
M ~
F Dual action relay NA Y1F
17
V~
18
Load resistive loads 5A \ 250 Vac
G Continuous dual action
Two normally open interlocked relays (Switch actions increase, stationary, decrease) rating 5A 250Vac for resistive loads.
For controllers with dual action output Y1 (example: Heat-Cool), an extra output Y1F with Relay is available for the cooling action. If a continuous output is desired for cooling, use the retransmission output Y4 (option) configured for retransmission of the signal: Y1F (cool). Possible combinations for Y1 dual are: Terminals 16 - 17 19 - 20 16-17 19 - 20 Y1 s (Heat) R R L L C C R C L Y1 t (Cool) R L* R L* L* R C C C 17 - 18 28 - 29 Terminals where: R = Relay L = Logic C = continuous (mA or Volt) *version on request
Load 500 W min.
28 29
Y4
Retransmission output Y1F (option) galvanically isolated 4...20mA, 10Vdc max. or 0...10Vdc, 20mA max.
For Y1 cool, R is the extra relay of Y1, while C is the retransmission output Y4 configured to retransmit Y1 cool: 4...20mA or 0...10 Volt. Output feature of dual action controllers Heat 100%
Cool - 100% Y1F limit (0
-100%)
Cool
!
See retransmission output Y4 (SX75+ only)
Y1C limit (0
100%)
Dead band
-100%
Heat 0 0
Y1F = output cool Y1C = output heat
13
100%
4. ELECTRICAL WIRING 6 Event outputs Y2 and Y3 (see p.15) Y3 Y2
13
Load
14 15
Normally open contacts, capacity 5A/250Vac for resistive loads (transitions 2x10 (coeff.5) min. at 5A/250Vac)
V~
Load
7 Retransmission output Y4 (SX75+ only) Load 500 W min.
Y4
Galvanically isolated 4..20mA, 10Vdc max. or 0..10Vdc, 20mA max.
28 29
Retransmission output Y1F (option) Retransmission: of input signal X of Set point W of output Y1F (Cool)
Passing from 4..20mA (standard) to 0..10Vdc, by moving a JUMPER inside the controller
!
A 4
20 mA
V 0
10 Vdc
8 Serial communication (SX75+ only)
Transmission
Zener Reception 2,7 V
1 2 3 4
TX
Interface 20mA closed loop passive and galvanically isolated or RS485 port
RX
Note Zener 2,7 V Only for 20mA closed loop
14
5. PASSWORD PROTECTION In order to prevent tampering or inadvertent alterations of the configuration or of some important parameters at the programming stage, 2 passwords have to be entered.
w
5.1 Access to configuration password (3333) 3333) )
wWw
Enter password of access to configuration
pAssWwS w(see enclosed leaflet)) NO
OK YES
3333
Return to normal function
Introduction into configuration code
5.2 Access to programming group 3 parameters password
pAssWwS w NO
OK YES
Enter password to access the 3rd group (see enclosed leaflet)
Return to normal function
Introduction into the 3rd group advanced parameters
15
(1111) 1111) )
1111
6•PROGRAMMING INSTRUCTIONS • SX75 SERIES CONTROLLERS PARAMETERS GROUP 2 - CONTROL FUNCTIONS
FUNCTIONS MENU GROUP 1 - SETPOINTS
DISPLAY
275. 8 275. 8 4 50
Measured Value
during normal operation
Function value
during programming
Set point
during normal operation
Function mnemonic
during programming
pAss Press F for group 3
s.p. 1
1 Set point
s.p2. 2
KEYS
Integral time 0.0 to 100.0 minutes
t.i.
2nd Set point
p.b.
A.par
s.p3. 3 s.p4. 4
Enter Function
s1.u u
To scroll through the menu, press Normal Operation
s1.d d
View Set point
s. p . t
for serial comms SX75+ only
y3Hy Start Configuration Procedure
Derivative time 0.0 to 10.00 min.
t.d.
Fuzzy intensitity 0.0 to 90.0% 50
A.tu.
Autotune function 0 Disabled 1 Enabled
f.Err
Fuzzy scale amplitude 0.5 to 999.9%
f.1nt.
Fuzzy intensity 0.0 to 90.0%
For time proportional output
t.y.
Cycling time Y1
t.c.
(only for time proportional output.)
dy.
(only for heat/cool time proportional output.)
pot.1
Y3 Hysteresis 0.01 to 10.00% span
Calibrate potentiometer feedback
Calibrate minimum position of valve
Addr
Accept calibration point
pot.h
Device Number 0…63
Calibrate maximum position of valve
s.Cb . r .
Accept calibration point
s.Cp . a
Note: 1 If
or is not pressed within 10 seconds the instrument will time-out back to the process variable.
CONFIGURATION
Baud rate 0 to 4 (see note 2)
if not configured at the power-up the main diplay will show:
Follow
Enter the first block of 4 configuration codes -E, F, G, H
9999
Enter the second block of 4 configuration codes I, L, M, N
9999 Co
°C - °F selection (Applies to EF configuration codes 00 to 62 only) 0 =°C 1 =°F EF =74…87 Number of decimal places EF (Applies to configuration codes 74 to 87 only) 1
sc.hi
Configurable input scale high value
Note:
E 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 7 7 8 8 8 8
Input type, scale range (1) -200…600°C RTD Pt100 IEC 751
Conf.
-200…600°C -99.9...300,0°C
Conf -99,9...300.0°C Thermocouple J Fe Cu 45%Ni IEC 584
0...600°C Conf. within 0...600°C
Thermocouple L Fe-Const DIN 43710
0...600°C Conf.
Thermocouple K Cromel-Alumel IEC 584
0...600°C 0...1200°C
Conf.
0...1200°C
Thermocouple S Pt10%RhPt IEC 584
Conf.
Thermocouple R Pt13%RhPt IEC 584
Conf.
0...1600°C
4...20 mA
Conf.
eng. units
0...20 mA
Conf.
eng. units
0...1 Vdc
Conf.
eng. units
0...10 Vdc 4...20 mA
eng. units Conf. Conf. eng. units with √
0...20 mA
Conf. eng. units with √
0...1 Vdc
Conf. eng. units with √
0...10 Vdc
Conf. eng. units with √
0...1600°C 0...1600°C 0...1600°C
F 0 2 0 2 0 2 0 2 0 2 0 2 0 2 4 5 6 7 4 5 6 7
I 0 1 2 3 4 5 6 7 8
Disabled Deviation with startup inhibition
Active high Active low Active outside
Band
Active inside Active high
Process
Advance to group 3 parameters
Y3 Event safety action 0 = disabled 1 = closed contact 2 = open contact
0 1 2 3 4
Parity None Odd Even None* None*
0 1 2 3 4
Protoc. User User User Modbus Jbus
1 st group 2 nd group
0022
2 A.par
Parameter protection code
Visible and modification 2 Visible but NO MODIFICATION 1 NOT VISIBLE 0
factory set parameters
CONFIGURATION CODE
Event Y2 type
Y1 Safety ( H = 6 or 7)
Y2 Event safety action 0 = disabled 1 = closed contact 2 = open contact
Security Access
Type of control output Y1 (2) Relay (On - Off with hysteresis Relay with time-proportioning Logic 0/24 Vdc with time-proportioning 4…20 mAdc 0…10 Vdc Valve motor drive Relay with time-proportioning Logic 0/24 Vdc with time-proportioning 4…20 mAdc 0.…10 Vdc
* Only for Heat-Cool applications
* * * *
G 0 1 2 3 4 5 6 7 8 9
Type of control action and safety position Y1(3)
Reverse
Safety Safety
0%
Safety
100% (Yh) 100% (Yh)
Reverse
Safety Safety
Direct Reverse Direct Reverse Direct
Safety Safety Safety Safety Safety
-100% (Yh2) Conf (4) Conf (4) Off Off
Direct Reverse Direct
0%
-100% (Yh2)
* *
H NOTES: 5 For Pt100 and thermocouple inputs with 0 configurable scale, it advised to select the largest range possible. The minimum 1 span should be no less than 25% of the 2 maximum range. Note: within the selected 3 range, it is possible to limit the set point low and high limit settings (Spl l and Spl h). 4 For mA and Volts inputs, low and high scale 5 values can be configured in engineering units 6 between -999 and 9999. The minimum scale span is 100 steps. The v alues can be 7 expressed in units (xxxx), in tenth (xxx.x), 8 hundredths (xx.xx), or thousandths x.xxx). 9 6 A switch located inside the controller 9
* Only for Heat-Cool applications
4230
First block of 4 configuration code E,F,G,H Second block of 4 configuration code I,L,M,N
!
Active low Active high
Deviation
Active low
Exiting the configuration process you will access group 3 parameters to modify, if necessary, Set point limits, maximum power output etc…
Disabled Deviation with startup inhibitor
Active high Active low Active outside
Band
Active inside Active high Active low
Process
Active high Active low
Deviation Loop - Break - Alarm
L 0 1 2 3 4 5 6 7 8 9
8 Selecting H(6,7) it is possible to set the safety value assumed by parameter say 1 in event of an input signal failure.
9999 - 9999 that means the instrument IS NOT CONFIGURED
Y Co
You can configure your instrument by entering the 8 characters code
provides selection of analogue outputs. See paragraph 4.6 of the IMI 7 The safety state is the value assumed by Y1 in event of input signal failure it is the value defining the upper limit of Y1. Safety states with * (H-4) or (H-5) impose the maximum limit to Cool action.
if at the power-up you see
7500
Event Y3 type
Y1 Safety ( H = 6 ou 7)
sa.y1
sa.y2
Parity 0 to 4 (see note 3)
Retransmission output Y4
sa.y1
0
1
Baude Rate 9600 * 4800 2400 1200 600
!
Configurable input scale low value
1n.5h
Input shift -50 to 50 digit
Serial communications User SX75+ only
0:5
4 Parameters Y2 and Y3 event alarms will not appear if configuration code I=0 (Y2) and L=0 (Y3)
Enter correct password to start configuration process (3333 )
Maximum power output (heat) 10 to 100% 100 Maximum power output (cool) 10 to 100% 100
0
Hysteresis 0.1 to 10.0% span
Hy.
Minimum power output (heat) 0 to 100% 0
Time constant of the input filter 0 to 30 secs
Note: If the controller is configured as an ON/OFF controller the whole group 2 parameters will be occulted and replaced by:
3 Allowable event alarm set points depend upon the type of alarm configuration • Deviation alarm : -300 to +300 • Band alarm: 0 to 300 • Independent: on full scale
10 0 Remote Bias sc.Io…sc.hi
t.fil
sa.y3 Note: 1 Set points will only be shown if configuration code N=3 2 If slope gradient = 0 there will be a step change between set points
sc.1o
yh. 2
s.C1 .
0
Addr
sc.dd
yh.
For serial communication SX75+ model only Serial Communications status 0= OFF; 1= ON
View instrument Device number 0 … 63
ERROR Return to normal OK operation YES Entering the configuration process
yl.
Time Sampling 0 to 30 sec. (0 = 0.5 sec.)
0
Cool relative gain 0.1 to 3.0 1:0
rcr
Remote Ratio —100 to 100
sc.Io
3
The valve is driven to minimum position
0 to 200 sec
Dead band 0.0 to 5.0% output 1:0
d.b.
Y3 Event alarm set point (see note 3)
pot.1
Cycling time Y2
s.p.r.2 s.p.r.3
Fuzzy scale on change on error 0.10 to 99.99% 10:00
1:0
Only for Heat/Cool controller (configuration G = 6 to 9)
30
t.san
Valve movement sensitivity 0.1 to 10%
End of the scale
0
60
30 0 to 200 sec
t.c2. 2
f.der
Set point limit high
s.p.r.1
20:0
Time for full valve travel 15 to 600 sec.
Set point limit low Beginning of the scale
Remote set point operation 0 = Remote 1 = Remote + local
1
1:00
0:50
Serial Communication status enabled to write
F =2
0:20
S.P.L. h
Security access for parameters (see note) 0000 to 0022 0022
50
Slope down during transition of the Set point 0.0 to 100.0 step/min. 0:0 (see note 2)
y HYYy
5:0
300
63
F=0
Slope up between the Set point 0.0 to 100.0 step/min. 0:0 (see note 2)
Y2 Hysteresis 0.01 to 10.00% span
y35.p
Addr
C-f
f.1nt.
Derivative time 0.00 to 10.00 minutes
300
View Configuration code
7500 Co
Con.2
4th Set point (See Note 1) 40
0:50
4230
Con.1
t.d.
y25.p
Modify or view Parameters
Conf
pAss
3rd Set point (See Note 1) 30
Y2 Event alarm set point(see note 3)
Run Auto - Tune function
par.
Integral time 0.0 to 100.0 min.
t.i.
Increment value
s..pl . 1 .
Yes
5:0
1:0
20
From configuration process
Error: return to normal operation
Proportional band 0.5 to 999.9%
5:0
10
Enter correct Password 1111 Press F for normal operation
Only for valve motor drive output (configuration G = 5)
Proportional band 0.5 to 999.9%
p.b.
st
Digit select
tune QWt une
GROUP 3 - ADVANCED FUNCTIONS
None (5) Retransmission measurement X 4…20 mA
Retransmission Set point W Retransmission Y1
0…10Vdc (6)
Retransmission measurement X Retransmission Set point W Retransmission Y1 Cool
Type of Set point 1 Local Standard
1 Local and Remote 4…20 mA 1 Local and Remote 0…10 Vdc 1 Local + 4 stored
9 Configuration code M applies to SX75+ models only. 10 To change from 4...20 mA to 0...10V alter the jumper switch position.
M 0 1 2 3 4 5 6 N 0 1 2 3
PARAMETERS DESCRIPTION
Entering parameters
Second group of parameters
The output relay contacts are
When configuration phase is completed, the controller can display all the parameters of functions that may be entered to their desired values. To simplify the exercise the parameters have been divided into three groups . Group 1 covers the parameters related to the set point. Group 2 covers control parameters. The third group, which is protected by the password 1111, are the advanced parameters. These include the security access, the fuzzy control parameters, the parameters for the serial communication, all the limiting functions and safety states functions.
Hy
Hysterisis of relay output Y1 (G = 0) The hysterisis is a zone within which an output does not change and maintains the state previously assumed. In order to obtain a change in the state of variable X it is necessary to go outside this zone. The amplitude of this hysterisis zone is expressed as an amplitude % of the configured scale. The output contacts are to be found between terminals 16 and 17. p.b. Proportional band (G = 1 to 9) The band within which the modulation of the output in direct proportion to the difference between the set point W and the measured value. It is calculated as a % of the input span. t.i. Integral time (G = 1 to 9) This is the time used by a single integral action to repeat the proportional action. This action is expressed in minutes. t.d. Derivative time (G = 1 to 9) This is the time taken for a single proportional action to attain the same level as the P + D output. This action is expressed in minutes. f.int Percentage intensity of fuzzy action (G = 1 to 9). The main control output is composed of the sum of two control algorithms, Fuzzy and PID. This parameter permits the balancing as a % of the proportion of the fuzzy algorithm in relation to that of the PID. With most applications the default value of 50% would be suitable. tc Cycle time of the output Y1 (G = 1,2,6,7) This parameter is expressed in seconds and defines the total time of the On/Off states of the main output Y1 modulated in % of the PID + Fuzzy algorithm. e.g. If Y1 = 20% and t.c. = 30”, the On state = 6” and that of the Off = 24”. If G = 1 or 6, the output relay contacts are between terminals 16 and 17. If G = 2 or 7, the logic output as a voltage is available between the terminals 19(+) and 20(-). tc 2 Cycle time for “cooling output” Y1 (G = 6 to 9 and M = <> 3, <> 6). This parameter is expressed in seconds and defines the total time of the On/Off states of the cold output Y1 modulated in % of algorithm PID + Fuzzy. e.g. If Y = -20% and tc2 = 30”, the On state = 6” and that of the
between the terminals 17 and
First group of parameters s.p..1 Stored set point 1 (N = 3) s.p..2 Stored set point 2 (N = 3) s.p..3 Stored set point 3 (N = 3) s.p..4 Stored set point 4 (N = 3) The memorised set points are the preset values for operation, recalled through logic inputs, serial transfer or the front keyboard. When one of these set values is recalled the small auxiliary display on the front of the instrument shows the set number recalled. sl. u. Rate of change for increase of the main set point SP. Any new value of the main set point SP greater than that previously entered set point will change at the rate entered into this parameter. The slope is expressed in digits/minute. sl. d. Rate of change for decrease of the main set point SP. Any new value of the main set point SP less than that previously entered set point will change at the rate entered into this parameter The slope is expressed in digits/minute. yY2sp Set point of event output Y2 (I = 1 to 8) y2Hy Hysterisis of event output Y2 (I = 1 to 8) Hysterisis is a zone within which an output does not change and maintains the state previously assumed. In order to obtain a change in the state of the measured value X it is necessary to go outside this zone. The amplitude of this hysterisis zone is expressed as an amplitude % of the configured scale.
y3sp Set point of output event Y3 (L = 1 to 8) See y2sp y3Hy Hysterisis of output event Y3 (L = 1 to 8) See y2hy
flyout_section.pmd
Off = 24”.
1
18.
d.b.
The dead band between the heating and cooling outputs (G = 6 to 9) If the variable X coincides with the set point sp1 and the output positions itself at 0% the system will tend to pass continually between hot and cold and vice versa. The parameter involved defines that the command at the output of the controller, whether it is hot or cold, will only be forwarded if it is greater than that written in the same parameter.
rcr Relative gain of the “cooling” output (G = 6 to 9). This is a parameter that determines the amplitude of the proportional band of the cold with respect to that of the hot: pbf = pb / rcr pbf = Proportional band output Y1 “cold” pb = Proportional band output Y1 “hot” ty
Time for full valve travel (G = 5) for VMD. This is the time used (expressed in seconds) for the control valve to travel from its lower limit to its upper limit. As a control algorithm of the “floating” type, this parameter is fundamental to a correct positioning of the control valve.
dy
Pressing the A/M button again, the controller stores the “100%” position. At this point the calibration operation is concluded and to terminate press the “> enter” button. During the calibration phase it is useful to time the valve travel time for the ty parameter.
Resolution of positioning or dead zone (G = 5). This parameter expressed in actuator run %, defines the minimum movement required for the servomotor. All the commands given by the control algorithm with lower amplitudes than the value written in the dy parameter, will not be executed.
pot.1 Procedure for calibration of the feedback potentiometer. Only for VMD control (G=5) This calibration is performed if the A/M button is pressed. When the value on the display remains steady the VMD control valve has reached its lower run limit. Pressing the A/M button again, the controller stores the “0%” position and drives the control valve to its maximum position. When the value on the display remains steady the VMD control valve has reached its upper limit.
These four parameters are related to serial communication, they only appear during the setting up phase of the instrument (SX75+ only) and do not relate to the configuration. splI Low limit value for the main set point SP1 splh High limit value for the main set point SP1
Third group of parameters AparSecuity access to parameter groups This function is used to set the level of access allowed for groups 1 and 2. - 0 Group not visible - 1 Group visible, without any facility to modify parameter contents. - 2 Group visible, with facility to modify parameter contents. Atu Auto Tune With this parameter the controllers autotune function can be enabled or disabled. On entering “0” the tuning function is disabled and the “tune” parameter is no longer available in the main menu. f.err Span of fuzzy operational zone (G = 1 to 9) This parameter defines the zone of operation for the fuzzy algorithm and is calculated in % of scale. The optimum value of this zone can be calculated using the following formula : f.err = 4 x p.b. f.der Fuzzy derivative (G = 1 to 9). This parameter defines the speed of the process to be controlled. It is expressed as “ % scale/minute” and its optimum value can be calculated with the formula : f.der = 4 x p.b./t.i. pb = Proportional band expressed as a percentage ti = Integral time expressed in minutes. t.san Sampling time (G = 1 to 9) This parameter determines the sampling time and is variable between 1 and 30 seconds max. The optimum sampling time is relative to the speed of the process to be controlled and is given by : t.san = t.i. x 60 / f.err pb =Proportional band expressed in % of scale ti =Integral time expressed in minutes. This is automatically calculated during auto-tune. sCI Enable or disable serial communications (SX75+ only) Addr Recognition address of serial communication (SX75+ only) sCbr Baud rate of serial communication (SX75+ only) sCpa Parity control of serial communication (SX75 only)
7/12/02, 4:43 PM
yl
Low limit of output Y1 (G=1 to 4) from 0% to 100%. The value entered into this paramenter determines the lowest limit for output Y1. The safety position (configuration H) can override this.
yh
High limit of output Y1 (G= 1 to 9) from 0% to 100%. The value entered into this parameter determines the highest limit for the output Y1. The safety position (Configuration H) can
The main control set point sp1 may only be freely entered between the two parameters spll and splh. spr1 Selects the operation of the RSP "Remote set point" (N = 1,2). The target set point can equal the RSP or the target set point can equal the local set point offset by the RSP. - 0 Target set point = remote set point - 1 Target set point = remote set point + local set point spr2 RSP Range This parameter is used to select the range for the remote set point (N=1,2). A value from -100 to +100 can be entered. The value for SPr2 is a percentage of the input span. A positive value will give direct action to the RSP. To calculate the value for SPr2 use the formula below. SPr2 =
override this. yl.2 High limit of output Y2 (G= 1 to 9) from 0% to 100%. The value entered into this parameter determines the highest limit for the output Y2. The safety position (Configuration H) can override this. tfil Input Filter This parameter can be used to stabilize the measured value. The value entered in this parameter defines the time constant of the digital filter used on the measured value X. Given an instantaneous variation between 0% and 100%, measured value X will reach 63.2% in the time indicated in the parameter tfil. The affect of the time constant tfil on the measured value X
RSP range x 100 Input scale range
Input scale range is the value from the lowest input scale value (Sclo) to the highest input scale value (Schi). See RSP example. spr3The datum point for the remote set point (N=1, 2) value between Sclo and Schl can be entered. The value entered will represent the minimum RSP input signal (0Vdc or 4mA), ie the start point.
Insh Input Shift This parameter allows the user to adjust the measured value reading. The value entered in the parameter will be used as the offset from the measured value. The settings are +/50 digits. say2 Safety state of event Y2 (l = 1 to 8) If the measured value signal fails, event output Y2 can be set to: - 0 Function excluded. Normal operation of alarm respected. - 1 Output held in the On state. - 2 Output held in the Off state say3 Safety state of event Y3 (l = 1 to 8) If the measured value signal fails event output Y3 can be set to: - 0 Function excluded. Normal operation of alarm respected. - 1 Output held in the On state. - 2 Output held in the Off state.
7 • OPERATING INSTRUCTIONS • SX75 SERIES CONTROLLERS FUNCTIONS MENU
SET POINT Procedure to recall a Set point from memory
Modify Set Point
Remote Set point status
DISPLAY
Serial Communication status
Measured value
during normal operation
Function value
during programming
275. 8
Auto-Tune status
275. 8 4 50
Memory Set point Number window
Set point
during normal operation
Function mnemonic
during programming
During normal operation
Least significant digit will flash
0250
Set point value will flash
250
s.pr . . Accept Set point 1 as target Set point
Increment value Edit Set point
The Set point may now be modified as previously explained
0260
Enter Auto / Manual Function
Modify Set point
sp. 1
Digit select
To scroll through , press Normal Operation
During normal operation
Set point value will flash
250
Remote
Modify Set point
KEYS
Auto/manual status
During normal operation
Set point value will flash
250
Local
sp. 2
Enable remote Set point The REM indicator will, switch on
s.p1 . . Accept Set point 2 as target Set point
Confirm modified Set point
Enable local Set point The REM indicator will switch off
sp.3 3 Accept Set point 3 as target Set point
F
sp.4 4
NOTE: THIS PROCEDURE WILL NOT WORK IF TERMINALS 21 & 24 (IL3) ARE LINKED
Accept Set point 4 as target Set point
View Set point
S.P. t
tune
Note: The above Set points may be modified from the 1st group within the parameter menu.
Run Auto - Tune function
Note: If a Remote Set point is selected, the instrument will store the Local Set point value this will be re-instated Local Set point mode is selected.
To activate displayed set point press
par.
Modify or view Parameters View Configuration code
Conf
4230
Start Configuration Procedure
7500 Co
Note: After the Set point has been modified the new target Set point will be reached after a period of time, depending upon the values entered in the sl.u (Slope up) and sl.d (Slope down) gradient parameters. When using Remote Set point we suggest, to set sl.u and/or sl.d to 0 The target Set point can be viewed at any time from the function menu.
Example
Target Set point =350°
Set point changed .sI.u = 10 digit / min. Initial Set point = 250°C
sp. t Target Set point
t
If slope gradient is equal to zero there will be a step change
AUTOMATIC / MANUAL OPERATION
TUNING AUTO-TUNE
For serial comms View instrument SX75+ model only Device number 0 … 63
Auto-tune should be used when the instrument is first installed to provide approximate values for the FUZZY algorithm, and calculation of proportional, integral and derivative parameters. When the auto-tune cycle has been completed, the values for FUZZY (ferr; fder; t.san) will also be adjusted automatically. It is possible to escape from the auto-tune procedure at any time by pressing any key.
Addr
63 63
AUTO
MAN
AUTO
100% Set point W
Addr
W (X)
W X
Serial Communication status enabled to write
0 100% output Y
sI.u. W=X
YMAN=YAUTO
Y
Set point change or start up
Y
modify Y
YAUTO=YMAN
0
or is not pressed within 10 seconds the instrument 1 If will time-out back to the normal display
Start Auto - Tune Process Fuzzy parameters have been calculated Set point W
Y
with
Time out:
t = 10 minutes
From normal operation (Auto mode)
Dev. > 5% span
Variable X
CHANGING NUMERIC VALUES
Aan.
Auto-Tune in operation Output Y1
To enter Manual mode
It is possible to modify any numeric value by changing each digit in
Ymax: 100% or
yh
Ymin: 0%
Example: to change 250 to 260
0250
press to select the required digit. Each successive press of this button moves the flashing digit one place to the left.
From normal operation (Manual mode)
The Auto-tune function is available if the following requirements are met: 1. Parameter A.tu= 1 2. The deviation between set point value and measured value of more than 5% of input span Note• if the heat/cool facility is selected the Auto-tune process will calculate the FUZZY parameters for both heat and cool.
0 2 5 0
0250
Pressing increments the selected digit (for the most significant digit there is a - between 9 and 0)
0
0260
Auto To enter Automatic mode
9
Press to accept the value. The value displayed will be accepted automatically after the 10 seconds. From normal operation (Auto mode) Auto-Tune in operation
tune
275.8
Start Auto-tune process
CONFIGURATION INSTRUCTIONS Note: Before switching the power on, check that the controller is wired correctly (refer to section 4, Electrical wiring).
Example 2. Temperature control
you now proceed to the normal operating mode. This will provide access to the settings of Group 1 (Set point), Group 2 (Control), and Group 3 (Advanced) parameters.
Using an SX75 controller with an RTD Pt100 sensor monitoring the system temperature. The controller provides a Valve Motor Drive output signal to the electric actuator. The actuator travel speed is 0.5mm/s, with a valve travel of 20mm.
proceed as follows
Press
F
repeatedly until the controller displays 'ConF' Press
This indicates that the controller is not configured (the controller will not function without being configured). If it has been configured and you need to change the configuration, see item 5 of this document.
Using the increment key
To configure the controller two sets of code numbers must be entered into the controller. Configuration code group 1, EFGH (Con1), cover the input type, the output type, and the control and safety action. Configuration code Group 2 ILMN (Con2), cover the event alarms, set point, plus re-transmission on SX75+ models.
Press
Refer to the Configuration Code table, on the opposite side of this sheet to select the desired configuration settings. Selected codes should be recorded the "customer configuration and parameter record" sheet. To enter the desired codes proceed as follows:
EF code setting value
1) EFGH Configuration Code (Con1)
G code setting value
Press the enter key
H code setting value
and the digit select key
Configuration code settings:
twice.
, enter the password 3333.
and follow procedure shown from 1a of this section.
Note: the controller will time out from the configuration back to the normal operating mode, if a key is not pressed after 30 seconds.
Example 1. Pressure control
Configuration code EFGH
Using an SX75 controller with a pressure transmitter monitoring system pressure, and the controller is providing a 4-20mA control signal to the control valve.
key.
Application requirements: • Pressure transmitter 0 to 25 barg, producing a 4 - 20 mA output signal. • Control Valve with Electric or Electro-pneumatic positioner accepting a 4 - 20 mA input signal. • Two Event alarms are required. Event Y2 set for active high process alarm at 22 bar. Event Y3 set for active outside band alarm set •
at 5 bar. This process requires only one set point. The local set point is 18 bar
Configuration code settings:
, to increment the displayed value. When the desired value is displayed, press
to advance to G code setting.
E 7
F 4
G 3
H 0
I 5
L 3
M 0
N 0
, to increment the displayed value. When the desired value is displayed, press
to advance to F code setting.
The F code value will be flashing to prompt the user to select the desired value. Press
Parameter Sc.d.d Sc.lo Sc.hi
The E code value will be flashing to prompt the user to select the desired value. , to increment the displayed value. To save the selected EFGH codes, press
. You will now advance to configuration
Description
Customer set Values
Number of decimal places Input scale low value Input scale high value
1 0.0 25.0
H 0
I 6
L 7
M 0
N 3
Description
Customer set Values
°C or °F
0
Description Set point 1 Set point 2 Set point 3 Set point 4 Slope up between SP Slope down between SP Event Alarm 1set point Event Alarm 1 Hysteresis Event Alarm 2set point Event Alarm 2 Hysteresis
Default Value 10 20 30 40 0.0 0.0 300 0.50 300 0.50
Customer set Values 40 60 N/A N/A 0.0 0.0 35 0.5 10 0.5
Description Proportional Band Integral time Derivative time Fuzzy intensity Time for full valve travel Valve movement sensitivity Potentiometer Calibration
Default Value 5.0 5.0 1.00 50 60 1.0 N/A
Customer set Values 5.0 5.0 1.00 50 40 1.0 N/A
Default Value 0022 1 20.0 10.00 3 see Sc.lo see Sc.hi 0 0 0 0
Customer set Values 0022 1 20 4.00 15 0 80 0 0 1 1
Group 3 Advanced parameter settings: Parameter
Description
I code setting value Sl. U Sl. d y2S.P y2Hy y3S.P y3Hy
L code setting value M code setting value N code setting value
2) ILMN Configuration Code (Con2) After the enter key is pressed, the display will show:
9999 Con 2
P.b. t.i. t.d. F.Int.
, to increment the displayed value. When
to advance to M code setting.
the desired value is displayed, press
up between SP down between SP Alarm 1set point Alarm 1 Hysteresis Alarm 2set point Alarm 2 Hysteresis
Default Value 0.0 0.0 300 0.50 300 0.50
Customer set Values 0.0 0.0 22.0 0.5 5.0 0.5
Default Value 5.0 1.0 0.20 50
Customer set Values 20.0 0.3 0.0 50
Default Value 0022 1 20.0 10.00 3 see Sc.lo see Sc.hi 0 100 0 0 0 0
Customer set Values 0022 0 80 99.99 0 0 20 0 100 0 0 1 1
Parameter A.Par A.tu. F.Err F.der t.San S.P.L.l S.P.L.h t.F iL In.Sh Sa.y2 Sa.y3
Group 2 Control parameter settings: Parameter
The N code value will be flashing to prompt the user to select the desired value. Press
Slope Slope Event Event Event Event
Configuration code ILMN
2a) N Code setting (Set point type):
Description Proportional Band Integral time Derivative time Fuzzy intensity
Group 3 Advanced parameter settings:
2b) M Code setting (Retransmission output for SX75+ models): The M code value will be flashing to prompt the user to select the desired value.
Parameter , to increment the displayed value. When the desired value is displayed, press
The L code value will be flashing to prompt the user to select the desired value. Press
A.Par A.tu. F.Err F.der t.San S.P.L.l S.P.L.h yL. yh. t.F iL In.Sh Sa.y2 Sa.y3
, to increment the displayed value. When
to advance to I code setting.
the desired value is displayed, press
2d) I Code setting (Event alarm Y2): The I code value will be flashing to prompt the user to select the desired value. Press To save the selected ILMN codes, press
Description
to advance to L code setting.
2c) L Code setting (Event alarm Y3):
, to increment the displayed value.
Security access Auto Tune enable Fuzzy scale Fuzzy change on difference Sampling time Set point low limit Set point high limit Minimum power output Maximum power output (heat) Input filter time constant Input Shift Y2 Event safety Action Y3 Event safety action
Note: For SX75+ models, the parameters “ S.C.I; Addr; S.C.b.r; S.C.Pa” for serial communication will be present between t.San and S.P.L.l .
.
Note: You will now advance to setting the configuration parameters. See section 3 below. 3) Configuration Parameters NOTE: depending on the configuration codes previously set, some of the configuration parameters are not applicable.
In the normal operating mode, adjust the local set point to 18 bar. Press
, and the digit select key
W
key, then press the
key. Using the increment key
change the set point to 18.
C_F parameter is only shown for RTD and Thermocouples input ranges (Codes EF) Scdd parmeter is only shown for mA / volt inputs types (Codes EF) Sc.lo and Schi parameters are only shown for configurable input scales, Configuration code F = 2. Sa.Y1 Safety action parameter is only shown when configuration code H=6 or H=7.
3a) "C_F" Celsius or Fahrenheit: Use the
key to select 0 for °C or 1 for °F. Press the enter key
to set the
desired scale.
3b) "Sc.dd" Decimal Places: Use the
key to select 1, 2 or 3 decimal places. The default value is 1. Press the enter
to select the desired value.
3c) "Sc.lo" Configurable input scale low value: This will set the low value for for the input scale. Use the increment key to enter the low input scale value. Press the enter key
, to set the desired value.
3d) "Sc.hi" Configurable input scale high value: This will set the high value for the input scale. Use the increment key to enter the low input scale value. Press the enter key
, to set the desired value.
NOTE:The above will not be shown if the input type selected has a fixed scale range. (ie. EF Code = 10, sets an RTD with a fixed range from -99.9 to 300.0) 3e) "SA.yl" Configurable safety position for the control output: Note this is only displayed when configuration code "H" is 6 or 7. Using the increment key
G 5
Group1 Set point parameter settings:
code group 2 ILMN (Con2).
, and the digit select key
S.P. 1 S.P. 2 S.P. 3 S.P. 4 Sl. U Sl. d y2S.P y2Hy y3S.P y3Hy
P.b. t.i. t.d. F.Int. t.y dy. Pot. l
Configuration parameter settings:
, to increment the displayed value.
to advance to E code setting.
1d) E Code setting (Input type and scale part 2):
, and the digit select key
Parameter
Parameter
1c) F Code setting (Input type and scale part 1):
key
F 0
Group 2 Control parameter settings:
The G code value will be flashing to prompt the user to select the desired value.
• • • •
E 1
Group1 Set point parameter settings:
1b) G Code setting (Control output type):
Press
C_F
The following commissioning examples for the SX75 controller will provide guidance to commission similar applications.
The H code value will be flashing to prompt the user to select the desired value.
Press
Event Y3 set for an active high deviation alarm set at 10°C. This process requires only two set points. Set point 1 = 40°C is the standby temperature. Set point 2 = 60°C is the control temperature. (Note Set point’s 3 and 4 can be ignored)
Configuration parameter settings:
1a) H Code setting (Control action and safety position):
When the desired value is displayed, press
•
COMMISSIONING EXAMPLES
Adjustments can only be made if a digit of the code displayed is flashing. The flashing will time out after 30 seconds. To restart a flashing
Press
Configuration Code and parameters: • Temperature sensor with an effective range from 0°C to 100°C. • Control Valve with Valve motor drive electric actuator. • Two Event alarms are required. Event Y2 set for active low process alarm set at 35°C.
Parameter
. The controller will display
9999 Con 1
Press
This will display the two groups of configuration codes that have
5) Modify a completed configuration code: To modify the set onfiguration code from the normal operating display,
9999 Co
display, press the
F
been set. After 10 seconds the display will time out and return to normal operating mode.
9999
50
4) Normal operating mode: The values in group 3 advanced parameters could be set now. However, it is recommended that
To proceed to normal operating mode press the function key
On power up the controller will display
275.8
AT and MAN will be displayed when autotune is in operation.
and the digit select key
to modify the value for the required safety position.
Press the enter key to set the desired value. This now completes the setting of the configuration codes and configuration parameters. The controller will advance to Group 3 of the advanced parameters. Please read below.
fluout_section6_today.pmd
2
7/12/02, 3:56 PM
Description Security access Auto Tune enable Fuzzy scale Fuzzy change on difference Sampling time Set point low limit Set point high limit Input filter time constant Input Shift Y2 Event safety Action Y3 Event safety action
Note: For SX75+ models, the parameters “ S.C.I; Addr; S.C.b.r; S.C.Pa” for serial communication will be present between t.San and S.P.L.l .
8. EVENT / ALARM OUTPUTS Y2 AND Y3 Deviation
Active high Event set point is variable between -300 to +300 steps. This value is with reference to set point W
Active low
Band
Active out
Process
Active in Active high
Event set point is variable between 0 to +300 steps. This value is with reference to set point W
Active low
Y2 & Y3 relay / led status: Event relay off = Event relay on =
Event set point is variable within the input signal scale range
Y2 & Y3 led off Y2 & Y3 led on
Deviation with startup inhibition Active high
Event set point is variable between -300 to +300 steps. This value is with reference to set point W
Active low
16
8. EVENT / ALARM OUTPUTS Y2 AND Y3 Loop-Break-Alarm (control loop defect/interruption)
Any interruption in the connections or any anomaly in the operation of one of the control loops (input or output signals) will cause the output Y3 to be energized after a few minutes and front display X and W will flash. The alarm state will stop when the fault is corrected or if a key is pressed.
275.8 275.8 4
mA °C
!
With ON - OFF action the loop break alarm feature is not available
17
50
Y1
9. OPERATING MODE Operating mode options: a.commands from
b.external contacts on logic inputs External contacts COM
275.8
H C1
275.8 4
50
H C2 H C3
21
IL1
22
IL2
23
IL3
24
c.commands via serial see separate manual 20mA C.L.
275.8 275.8 4
50
RS232 Interface
With external contacts on logic inputs IL1, IL2, IL3 The contacts closing for at least 2 sec. C1, C2, C3, will change the state or Set point of the controller. IL1
C1
IL2
C2
Type of modification
IL3
C3
Version with only Local Set point
Version with Set point (note1) 1 Local + 4 Memorized
Version with Set point 1 Local + 1 Remote
No action
Change from AUTOMATIC to MANUAL
ON ON
Change from MANUAL to AUTOMATIC
ON ON
No action
Local Sp. = Memorized Sp. 1
passage Local Sp. to__Remote Sp.
ON
No action
Local Sp. = Memorized Sp. 2
__
ON
ON
No action
Local Sp. = Memorized Sp. 3
__
ON
ON
No action
Local Sp. = Memorized Sp. 4
__
ON
ON
Passage from REMOTE to LOCAL
No action
ON
Note 1: Is possible to fix the selected Set point holding closed the relative contacts. While they are closed is possible to change from Auto/Man or Man/Auto but it is not possible to change the Set point
18
10. TECHNICAL DATA Accuracy (a25°C amb.)
0.2% ± 1 digit (for input with RTD Pt100 and thermocouples) 0.1% ± 1 digit (for input in current and voltage)
Input "X" (configurable)
Auxiliary inputs
RTD Pt100
Pt100Ω @ 0°C, (IEC 751)
Thermocouples
J-K-S-R (IEC 584), L (DIN 43710)
Continuous current
4..20mA, 0..20mA, Ri 30Ω
Continuous voltage
0..1Vdc, 0..10Vdc, Ri 10KΩ
With configurable scale field
3 of logic type (control of operating and Set point states) 1 Local + 4 storable
Set point
Local/Remote Set point
Control actions
Auto - Tune Auto/Man Station
2 ramps for ascent and descent gradient slope
0.1´100.0 digit/min.
Higher and lower limit
from beginning to end of scale
In current
4..20mA, Ri30Ω
In voltage
0..10Vdc, Ri 330kΩ
Algorithm
On - Off, PID, FUZZY, PID with I and D excludable actions.
Proportional band (P)
0,5..999.9%
Integral action time (I)
0.1..100min., excluded
Derivative action time (D)
0.01..10min., excluded
Cycle time
1..200 sec. (for discontinuous control)
Hysteresis
0.1..10% (for on-off control)
Dead zone
± 0´5,0% for dual action (heat-cool)
Not isolated accuracy: 0.1% at 25°C.
For automatic parameter adjustment (One shot) With bumpless action, AUTO/MAN transfer via keyboard, logic input and serial communication.
19
10. TECHNICAL DATA
Main output Y1 (configurable)
Single or dual, with direct or reverse action Relay with dual action 2 contacts NA, 5A/250Vac, 2x10 coeff.5 Discontinuous transitions Logic 0.18 Vdc, 20mA max. (for static relays) Continuous
Current
4..20mA(450W max.,10 Volts max.)
Voltage
0..10Vdc(450W min. 20 mA max.)
Maximum output
10..100% (1st channel
Relay
2 contacts NA, 5A/250Vac, 2x10(coeff.5) transitions
Action mode
active high (above the set point) active low (below the set point)
Event/ Hysteresis Alarm outputs Y2 - Y3 (configurable) Type of Set point
Special functions Retransmission Current output Y4 (SX75+ only) Voltage Serial commnication (SX75+ only)
galvanically isolated
) -10..-100% (2nd channel
0,1..10% deviation
± 300 steps (with or without inhibited startup)
band
0..300 steps
independent
from beginning to end of scale
Loop-Break-Alarm (control loop defect) 4..20mA(450W max.,10Vdc max.) 0..10Vdc(500W min.,20mA max.)
galvanically isolated
Interface 20mA C.L. passive and galvanically isolated (see manual MIU-CS/E) or RS485 port Access to parameters
Protections Immunity to disturbances
On three levels for: modification, indication only, no access level IV, standard IEC 801-4
All significant data are stored in a non-volatile memory Single power supply
Standard model
100..240V, 48..63Hz, -15% + 10% 250 Vac max
Low voltage model
24V, 48..63Hz, -15% + 10% or 24Vdc ± 15%
Absorbed power
about 4VA
Auxiliary 24Vdc ± 10%, 20mA max. for 2-wire or 3 or 4-wire transmitter power supply
General features
)
Isolation group
C according to VDE 0110
Climatic group
KWF according to DIN 40040
Ambient temperature
0...50°C., humidity 35...85uR%
Protection
Front:IP54 standard (IP65 with Kit AXIP65- 1) Cover: IP30, terminal board IP20
Material
Self-extinguishing UL94V1
Weight
Approx 480 g.
Dimensions
48 x 96, depth 150mm, according to DIN 43700
20