Transcript
B1
A1
B2
G1
G2
SYNCHRO CHECK RELAY DEAD BUS ts
75 mm
U BUS >75% 2x∆V% ON OFF U GEN >75% SYNC OUT SYNC VDB%
∆V% 6
4
10 2
2
∆ϕ 8
6
8 4
12
DELAY 0,6 0,8
16 0,4
1,0
20 0,2
4
8 10
GENERATOR T O O
T O O
S L O W
F A S T
T- Tx T+
12 11 21 24
SYNCHRO CHECK RELAY Type: SYND
TYPE: SYND
A2
100 mm
55 mm
FEATURES
Description: The synchro check relay type SYND is a multifunction unit that can be set to both constant or pulse output as well as to enable or disable synchronization to a “dead bus”. The unit is designed with a micro controller to monitor the bus and the generator voltage, as well as the phase differential between two grids.
•
Multi function check relay
•
Extremely compact
•
Rail mounting for easy cabling on the baseplate
•
Three wire interface to an optional panel indicator
•
Microcontroller and SMD - technic for accurate and reliable function.
•
LED indication of bus and generator status
11
BUS
21
B2 B1
0V
12V
T - T x T+
24
12
For a front panel indication of the function, the SYND can be connected through a simple three wire digital interface to the optional panel indicator type SYPD.
Dead Bus ON: Be careful when this function is selected. Personal injury can occur if the bus is disconnected for maintenance. Too the load of the generator can be excessive. When the Mains Bus voltage is detected to be under the Dead Bus VDB% set limit V the Mains Bus is defined to be dead and the internal relay will pull in if the Generator voltage is above 75% of nominal value. The relay will drop out or stay in according to the function setting on the SYPD as described above.
CPU
G2 GEN. G1
The unit is specially designed for DIN rail mounting on the base of the control box for an easy connection to the two bus systems.
Operation: Dead Bus OFF: When the voltage on the Mains Bus, L1 - L2, and the Generator Bus, L1 - L2, both are above 75% of the nominal value, the SYND will monitor the voltage difference ∆V%. As soon as ∆V is below the set limit, the SYND will start monitoring the phase difference ∆ϕ. If the phase difference ∆ϕ is continuously below the set limit during the elapse of the set delay time td, and the voltages still within the limits, the internal relay will pull in for 100 m sec. if pulse output is selected, or stay in as long as the conditions are within the limits for synchronisation.
FUNCTION DIAGRAM
A1 A2
The SYND ensure the right conditions before the connection of the generator to the bus, in order to avoid damage to the generator and malfunction or damage to the connected equipment.
CONNECTION DIAGRAM Bus
L1 L2 L3
L1 L2 GEN. L3 C1
Supply A1
B1
B2
G1
G2
SYND Control Box
Control Supply 12 11 21 24
T- Tx T+
SYPD Indicator Box
A2
T- Tx T+
C1 Supply
59 Thiim
A/S
Transformervej 31 2730 Herlev - Denmark
Tel.: +45 4485 8000 Fax: +45 4485 8005
Web: www.thiim.com Webshop: shop.thiim.com
SPECIFICATIONS
ORDERING INFORMATION
INPUT Nominal voltage Max. input Input resistance Voltage range Frequency range UBUS low level UGEN. low level UBUS,UGEN. voltage differential UBUS,UGEN. phase angle differential Delay
2 kΩ x Unom. 50 % to 130 % 35 to 70 Hz 75 % fixed 75 % fixed 2 to 10 % / 4 to 20 % adjustable 4 to 20 degrees adjustable 0,2 to 1 sec. adjustable
PERFORMANCE PARAMETERS ELECTRICAL Supply dependence Temp. dependence
< 0.01 % / % ∆U supply < 0.02 % / °C
OUTPUT Sync pulse delay Sync pulse relay Contact rating Mechanical life Sync pulse Output for SYPD indicator
200 ms. to 1sec. adjustable 1 x C/O 6 A, 250 VAC, 1500 W 30 Million cycles 100 ms. or constant B7 0 VDC B8 Digital output B9 12 VDC
SUPPLY AC supply with transformer DC supply
AC voltage, Nominal ± 20 % 24 V (19,2 to 28,8 V) 110 V (88 to 132 V) 230 V (184 to 276 V) 400 V (320 to 480 V) 440 V (352 to 528 V)
45 to 440 Hz (transformer) 4 VA, 3 W
Frequency range Power consumption
EXAMPLE:
Specify from 110 to 500 V Unom. x 1.5
DC Voltage, Nominal -20 % to +33 % 12V (From 9,6 to 16V) 24V (From 16 to 32V)
TYPE Syncho Check Relay
SYND 400 2 B230 A A 5 C
SYND
VOLTAGE BETWEEN PHASES The first three figures of the voltage in Volt e.g. 400 V
400
Followed by: 1 for V = 10.0 to 99.9 2 for V = 100 to 999
1 2
SUPPLY VOLTAGE 18-360 VDC and 20-240 VAC 20 - 28 VAC 99-140 VAC 198-264 VAC 342-484 VAC 374-506 VAC
E400 B024 B110 B230 B400 B460
ADJUSTMENT Trimpot A adjutable
A
HOUSING Rail mounting.(internal transformer)
A
SIZE 55 mm.
5
CODE END
C
GENERAL Temperature range Humidity Dielectric test voltage Weight
- 25 °C to + 55 °C Up to 90 % RH non-condensing Input to AC supply 3750 VAC Coil to relay contacts 3750 VAC 0.28 kg
EMC directive 89/336: Low voltage directive 73/23:
International Standards EN50081 - Emission EN50082 - Immunity EN60255 - Electrical Relays
TYPICAL SETTING ∆V% setting
Set for max. differantial (UBUS - UGEN) voltage in % of UGEN
25 mS ± 15 deg. 0.5 sec. 6 sec. 0.17 Hz 16.5 deg.
C1 closing delay ∆ϕ setting DELAY setting Min. time for 1 rotation 0-360 deg. Max. frequency diff. Max. sync error
Min. time for 1 rotation 0-360 deg. in sec.
=
=
Frequency diff. in Hz
Max. sync error in deg.
50 mS ± 15 deg. 0.5 sec. 6 sec. 0.17 Hz 18 deg.
180 ∆ϕ setting
100 mS ± 10 deg. 0.5 sec. 9 sec. 0.11 Hz 14 deg.
200 mS ± 7 deg. 0.5 sec. 12.86 sec. 0.08 Hz 12.6 deg.
400 mS ± 5 deg. 0.5 sec. 18 sec. 0.06 Hz 13 deg.
x delay setting
1 time for 1 rotation 0-360 deg.
(
∆ϕ setting x 2 = ∆ϕ setting + x C1 closing delay DELAY setting
)
60 We reserve the right to make changes for product improvement.
SYND.INDD - 012013