Engineering Manual
From 6 to 26 Tons (60 Hz Data)
Vertical Floor Mounted Precision Air Conditioners Dual Compressor DX & Chilled Water Systems!
Stulz Air Technology Systems, Inc. (SATS)
Founded in 1947, STULZ acquired Air Technology Systems (ATS) in March 2001, naming the new company Stulz Air Technology Systems, Inc. (SATS). SATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class "island" manufacturing processes in a modern, 150,000 ft2 facility. The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the precision air conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service.
ISO-9001:2001 Quality Registered Stulz-ATS is committed to satisfying customer expectations by meeting and exceeding customer requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We continually measure our performance to improve the effectiveness of our quality management system.
Precision A/C Applications SATS is dedicated to the manufacturing of supplemental and precision air conditioning products. With an extensive installation base, SATS has earned a solid reputation as a quality supplier and leader in its field.
1-1
CyberTWO™ vertical, floor mounted air conditioning units provide precision temperature and/or humidity control for computer rooms and other critical areas where continuous 24 hrs/day, 365 days/yr operation is required. Designed for front only access, CyberTWO systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications. Typical applications include:
INDUSTRIES:
Telecommunications Internet / Web Hosting Financial / Banking Insurance Legal Services Airlines / Mass Transit Entertainment Government Colleges / Universities
APPLICATIONS:
Computer / LAN Rooms Telecommunications Rooms Co-location Centers ISP (Internet Service Providers) ASP (Applications Service Providers) Copier / Fax Rooms ATM Bank Centers Hospital Operating & Isolation Rooms Laboratories
Table of Contents SECTION - 1 Introduction to SATS .........................................................1-1 Table of Contents .............................................................. 1-2
SECTION - 2 CyberTWO SYSTEMS: Outstanding Advantages ................................................... 2-1 User Oriented Features & Options ................................... 2-2 Available Configurations ................................................ 2-3/4
MODEL NOMENCLATURE: Nomenclature Chart ......................................................... 2-5 Model Nomenclature Specifications .............................. 2-6/7
SECTION - 3 GUIDE SPECIFICATIONS: Standard Features Index ................................................... 3-1 Standard Guide Specifications ......................................3-2/4
SECTION - 6 DIMENSIONAL / INSTALLATION DRAWINGS: Dimensional Drawing Index ............................................. 6-1 Physical Data - Unit Weights (lbs) .................................... 6-2 CyberTWO "VFS" Systems: 6 to 10 Ton, Down-Flow Systems ..................................... 6-3 6 to 10 Ton, Up-Flow Systems .......................................... 6-4 15 to 26 Ton, Down-Flow Systems ................................... 6-5 15 to 26 Ton, Up-Flow Systems ........................................ 6-6 Free-Cool/Alternate Water Source Systems: 6 to 10 Ton, Down-Flow Systems ..................................... 6-7 6 to 10 Ton, Up-Flow Systems .......................................... 6-8 15 to 26 Ton, Down-Flow Systems ................................... 6-9 15 to 26 Ton, Up-Flow Systems ..................................... 6-10 Floor Stand Options: ................................................ 6-11-12
Optional Features Index ................................................... 3-5 Microprocessor Controls Specifications ....................... 3-6/7 Optional Features Guide Specifications ..................... 3-8/12
SECTION - 4 PERFORMANCE / CAPACITY SPECIFICATIONS: Performance Specifications Index .................................... 4-1 DX - Air Cooled Systems ................................................ 4-2/3 DX - Water Cooled Systems .......................................... 4-4/5 DX - Glycol Cooled Systems .......................................... 4-6/7 Free-Cooling & Alternate Water Source Systems ...... 4-8/17
SECTION - 5 ELECTRICAL DATA: (FLA / MCA / MFS) Electrical Data Index ......................................................... 5-1 DX - Compressorized Systems: Air Cooled, Split Systems ................................................. 5-2 Water Cooled Systems ..................................................... 5-2 Glycol Cooled Systems .................................................... 5-2
CyberTWO™ VFS
Free-Cooling & Alternate Water Source: DX with Free-Cooling ........................................................ 5-3 DX with Alternate Water Source ........................................ 5-3
1-2
CyberTWO Systems SUPPLY AIR OUTLET
CyberTWO systems are designed to provide precision temperature and humidity control 24 hrs/day, 365 days/yr. A wide variety of cabinet configurations and options make SATS products the most flexible precision air conditioning line available in the industry. CyberTWO systems require only front service access and are easily installed sideby-side, tucked into a corner or between cabinets. The CyberTWO Series units are especially adaptable to raised floors and are available in both down-flow and up-flow air pattern configurations.
RETURN AIR INLET
Down-Flow Air Patterns
Up-Flow Air Patterns
CyberTWO Systems Offer Outstanding Advantages Flexibility
Microprocessor Controls
A wide variety of cooling methods are available to meet your unique requirements.
Precision temperature and/or humidity control with unrivaled, user-friendly C-6000 series controls, offer a wide range of functions and alarms.
• DX - Air Cooled • DX - Water Cooled • DX - Glycol Cooled (w/ Remote Drycoolers & Pump Packages • Free-Cooling Systems • Alternate Water Source Systems
• •
... and more!
• Chilled Water Air Handling Units
Versatility • Plenum Box Spot Cooling & Ducted systems • Self-Contained & Split systems
100% Front Service Access Designed for 100% Front Only Access, CyberTWO systems require minimal floor space and can be installed side-by-side, tucked into a corner or between cabinets.
Wide Size Range DX systems from 6 to 26 ton capacity in six incremental sizes and Chilled Water systems from 6 to 40 ton capacity in seven incremental sizes.
Non-Proprietary Parts CyberTWO systems incorporate nonproprietary components where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components.
2-1
Featuring: BMS Connection Unit Sequencing
Complete Temperature & Humidity Control • Electrode Canister Steam Humidification • Dehumidification Mode with - Electric Reheat/Heat - Optional Hot Gas Reheat (Energy $aver) - Optional Hot Water & Steam Reheat/Heat
Capacity Modulation Options • • • •
Dual / 2-Stage Scroll Compressor Systems Hot Gas Bypass Systems Multi-stage Reheat/Heat Modulating Chilled Water Valves
Code (UL / CSA) Conformance L LISTED NRT
UL 1995 C
R
- NYC MEA Approved (MEA-163-88-E) - CSA Compliance - MET-C Recognized by Standards Council of Canada
User Oriented Features & Options Scroll Compressors CyberTWO DX A/C's incorporate Dual Scroll Compressor Technology. Scroll Compressors provide higher efficiency, higher reliability and lower sound power than other compressor technologies.
Year Round Operation Option offerings available with CyberTWO air conditioners allow for year-round, 24 hours-a-day system operation in any environment in the world: Low Ambient Control (DX - Air Cooled) • -20°F Variable Fan Speed • -30°F Flooded Head Pressure
Modular Motor Controllers
CyberTWO systems incorporate modular motor controllers with motor circuit breakers in lieu of inconvenient replaceable fuses.
Quiet Operation Low sound power Scroll compressors coupled with low RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation.
Warranty - 2 Year Parts Standard - Optional 5 Year Compressor
Selected Standard Features: 100% Front Access (Saves Up-To 18 ft2 Floor Space)
• • • • • • • • • • •
Main Power Circuit Breaker Modular Motor Controllers (w/ motor circuit breakers) Acoustical / Thermal Insulation Aluminum Fin / Copper Tube Coils Thermal Expansion Valves Refrigerant Sight Glasses Refrigerant Filter / Drier Strainers Liquid Refrigerant Reclaim Valves Insulated Stainless Steel Condensate Drain Pan High / Low Refrigerant Pressure Switches Rotolock Compressor Service Valves
Other Available Options:
CyberTWO (Model VFS-240-DAR-D Shown)
-
2 & 3-way Grilled Plenum Boxes Floor Stands (with & without turning vanes, seismic) Condensate Pumps Smoke Detectors Firestats Water Leak Detectors Special High Efficiency Filtration (4" Filters up-to 60% Dust Spot) High Pressure DX - Water/Glycol Cooled Condenser Regulating Valves Free-Cooling & Alternate Water Source Units Drycoolers & Pump Packages Many more options available (see page 3-5) !
2-2
Application Dependent Configuration Choices AIR COOLED SYSTEMS
WATER COOLED SYSTEMS SELF-CONTAINED WATER COOLED SYSTEMS
SPLIT AIR COOLED Evaporator Air Inlet
OFF
Evaporator Air Inlet
ON
OFF
ON
WCS-( ) (Remote Outdoor Propeller Condenser)
Evaporator Air Outlet
VFS-072 thru 312-DW-( ) VFS-072 thru 312-DAR-( )
Remote Water Source (supplied by others)
Evaporator Air Outlet
(Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern)
(Dual Compressors - Split Evaporator) (Up-Flow or Down-Flow Air Pattern)
GLYCOL COOLED SYSTEMS
FREE-COOLING SYSTEMS
SELF-CONTAINED GLYCOL COOLED SYSTEMS
Evaporator Air Inlet
Evaporator Air Inlet
ON OFF
ON OFF
F( )S-( ) / GPS-( ) (Outdoor Propeller Drycooler & Pump Package)
Evaporator Air Outlet
Evaporator Air Outlet
VFS-072 thru 312-DW/DG-FC-( )
VFS-072 thru 312-DG-( )
(Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern)
(Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern)
ALTERNATE WATER SOURCE SYSTEMS Evaporator Air Inlet
WCS-( ) "At Night" (Remote DX Heat Rejection Source)
Evaporator Air Outlet
Remote Liquid Chiller "By Day" VFS-072 thru 312-DW/DG/DAR-AWS-( ) (supplied by others) (Dual Compressors - Evaporator) (Up-Flow or Down-Flow Air Pattern)
2-3
F( )S-( ) / GPS-( ) (Outdoor Propeller Drycooler & Pump Package)
Flexible Air Pattern Configuration Choices Down-Flow Systems:
Top "Ducted" Return with:
Top "Free" Return with:
RETURN AIR INLET
1
2
SUPPLY AIR OUTLET
Bottom Discharge Into Raised Floor
Floor Stand (Optional)
Bottom Discharge Into Raised Floor
Up-Flow Systems: Top Discharge Through 2 or 3-way Grilled Plenum Box with:
SUPPLY AIR OUTLET
4
3 EVAPORATOR AIR OUTLET
EVAPORATOR AIR INLET
RETURN AIR INLET
Front "Free" Return
Rear "Ducted" Return
Top "Ducted" Discharge with: SUPPLY AIR OUTLET
SUPPLY AIR OUTLET
5
6
RETURN AIR INLET
Front "Free" Return
RETURN AIR INLET
Rear "Ducted" Return
2-4
Model Nomenclature
- "VFS" Systems
Nomenclature
VFS-240-DG-FC-U COS MCS OHS VFS FCS GPS WCS F( )S
D U
= CyberONE System = Modular Cyber System = OverHead System = Vertical Floor System = Floor Console System = Glycol Pump System = Air Cooled Condenser = Air Cooled Fluid Cooler
AWS FC
= Down-Flow Air Pattern = Up-Flow Air Pattern
= "Alternate Water Source" = "Free-Cooling"
Nominal Capacity in 1,000's of BTU/H
- Model Nomenclature Chart
AHU AR AS CAA D( ) G GRC P V F LGA RCU-I S W
= = = = = = = = = = = =
Air Handling Unit Remote (Split) Air Cooled Self-Contained Air Cooled Indoor Centrifugal Condenser Dual (Two) Circuit or Pump System Glycol Cooled Glycol Cooled Remote Condensing Unit Outdoor Propeller Condenser for 0°F Outdoor Propeller Condenser for -20°F Outdoor Propeller Condenser for -30°F Outdoor Propeller Glycol Drycooler Indoor Centrifugal Remote Condensing Unit = Single Pump = Water Cooled
EVAPORATOR AIR OUTLET
EVAPORATOR AIR INLET
VFS-( )-( )-D
VFS-( )-( )-U
Down-Flow Air Patterns
Up-Flow Air Patterns
CyberTWO - Dual Circuit & Chilled Water Floor A/C's 2-5
Model Nomenclature Specifications
DX - EVAPORATOR SECTIONS
Air Cooled Remote Evaporator (Models VFS-( )-DAR) The system shall be a remote (split) air cooled, floor mounted precision air conditioner evaporator. The evaporator section shall house, as a minimum, the evaporator coil, expansion valve, compressor, evaporator blower/ motor and associated electrical and refrigeration components.
The evaporator system shall require only a single point main power supply connection; and the system shall ship from the SATS factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging.
Remote Outdoor Propeller (Models WCS-( )-( )) The system shall be a remote outdoor air cooled condenser with direct-driven propeller fan(s). The condenser cabinet shall house the condenser coil, fan(s) and fan motor(s) and Nema 3R condenser motor control/enabling box. The compressor(s) shall be located with the VFS-( )-AR evaporator section. The condenser shall be sized to provide the total heat of rejection of the system at a 95°F DB ambient temperature for the corresponding CyberTWO model VFS-( )-AR evaporator.
WCS-( )-V: Low Ambient Head Pressure Control down to a minimum ambient temperature of -20°F via Variable Fan Speed Head Pressure Control.
WCS-( )-F: Low Ambient Head Pressure Control down to a minimum ambient temperature of -30°F via Flooded Head Pressure Control.
DX - WATER COOLED SYSTEMS
Integral Self-Contained (Models VFS-( )-DW) The system shall be a dual compressor, self-contained, floor mounted precision air conditioner to include integral water cooled condensers with factory installed head pressure water regulating control valves. Condenser (source) water shall be provided by a cooling tower or some other remote water source. The system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Water Regulating Valves: Head pressure shall be automatically controlled by factory installed 2-way water regulating valves rated for 150 psig w.w.p. (Note: 3-way and high pressure valves are optionally available, page 3-9.)
DX - GLYCOL COOLED SYSTEMS
Integral Self-Contained (Models VFS-( )-DG) The system shall be a dual compressor, self-contained, floor mounted precision air conditioner to include integral glycol cooled condensers with factory installed head pressure glycol regulating control valves.
Condenser (source) glycol solution shall be provided via a CyberAiR model GPS-( )-( ) / F( )S-( ) remote glycol pump package and drycooler system. The evaporator system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Glycol Regulating Valves: Head pressure shall be automatically controlled by factory installed 2-way glycol regulating valves rated for 150 psig w.w.p. (Note: 3-way and high pressure valves are optionally available, page 3-9.)
GLYCOL PUMP PACKAGE & REMOTE DRYCOOLERS
(Single Pump Packages) (Models GPS-( )-S) The system shall be a single pump package designed to provide the total required glycol condenser coolant flow rate at the total rated system pressure drop. The pump packaged shall include, as a minimum; pump, starter/ contactor, main power non-fused disconnect switch, 24 Volt control transformer, A/C unit and drycooler interconnect contacts.
- CyberTWO Systems
The VFS-( )-DAR evaporator section shall be located at some distance from its corresponding SATS model WCS-( ) outdoor air cooled condenser.
Note: The outdoor propeller condensers are model designated as follows:
Nomenclature
"CyberTWO" Model Nomenclature Guide Specifications
(Dual Pump Packages) (Models GPS-( )-D) The system shall be a dual (two), redundant, pump package designed to provide the total required glycol condenser coolant flow rate at the total rated system pressure drop. A coolant sensing flow switch shall be provided for automatic switchover from primary to backup pump operation in the event of a loss of coolant flow. The dual pump package shall include, as a minimum; quantity two (2) equal horsepower pumps, pump starters/contactors, main power nonfused disconnect switch, 24 Volt control transformer, A/C unit and drycooler interconnect contacts.
2-6
Model Nomenclature Specifications Nomenclature
Remote Drycooler (Models WCS-( )-( )) The system shall be a remote outdoor air cooled glycol drycooler (fluid-cooler) sized to provide the total heat of rejection of the system glycol condenser source solution at a ___°F DB ambient temperature. The drycooler shall include, as a minimum; glycol coil, direct-driven propeller fan(s), fan motor starters/ contactors, main power non-fused disconnect switch, drycooler fan cycling control aquastat(s) and field installed 15 gallon expansion tank and airtrol fitting.
- CyberTWO Systems
DX COOLING with "Assist-Mode" FREE-COOLING SYTEMS
(Water/Glycol Economizer Coil)
The evaporator system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. ALTERNATE WATER SOURCE
(Chilled Water by "Day" and DX-Backup by "Night"!) (Models VFS-( )-DAR, DW, DG-AWS) The system shall be a dual compressor floor mounted precision air conditioner to include a combination DX refrigeration cycle and Alternate Water Source cooling cycle. The Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply, when available, as the primary cooling cycle with DX refrigerant cooling as a backup.
(Models VFS-( )-DW/DG-FC) The system shall be a self-contained, floor mounted precision air conditioner to include a combination integral, dual compressor, DX Water/ Glycol Cooled refrigeration cycle and Free-Cooling economizer cycle. The Free-Cooling cycle shall be provided to take advantage of low ambient air temperature conditions to provide compressor-less cooling. Condenser (source) and free-cooling coil glycol solution shall be provided via a CyberAiR model GPS-( )-( ) / WCS-( )-( ) remote glycol pump package and drycooler system. During free-cooling mode, the drycooler capacity shall be increased by reversing the typical drycooler fan(s) cycling sequence of operation to provide maximum cooling effect for the glycol coolant solution.
CyberTWO (Model VFS-120-DAR-D Shown)
2-7
"VFS" Series
"VFS" Model
VFS-072/312-( )
SELECTED STANDARD FEATURES: TEMPERATURE CONTROL • • • •
2-Stage Cooling Mode 2-Stage Electric Reheating / Heating Cooling &/or Heating Only (No Humidity Control) 3-Stage Electric Reheating / Heating
Standard Standard Optional Optional
HUMIDITY CONTROL • Electrode Canister Steam Humidifier • Dehumidification Mode with 2-Stage Electric Reheat
Standard Standard
CONTROLS • C-6000 Graphic Microprocessor w/ Alarms • MIB Gateway BMS/LAN Connection
Standard Optional
CABINET • • • •
Powder Coat Painted Galvanneal Steel Insulated Stainless Steel Condensate Drain Pan 2 lb Density Thermal & Sound Insulation Floor Stand (Varying heights available - see page 3-10 for details.)
Standard Standard Standard Optional
• 4", 30% Dust Spot Efficient Pleated Filters • 4", 60% Dust Spot Efficient Pleated Filters • 2 or 3-way Plenum Box (Up-Flow Units)
Standard Optional Optional
DX-REFRIGERATION CIRCUIT • • • • • • •
HCFC R22 Refrigerant Dual Scroll Compressors w/ Rotolock Service Valves High Efficiency, Aluminum Fin / Copper Tube Coils Thermal Expansion Valves Refrigerant Sight Glasses & Filter/Drier Strainers Refrigerant Service Valves HFC R407C Refrigerant
Standard Standard Standard Standard Standard Standard Optional
BLOWERS/MOTORS • Belt-Drive Evaporator Blower(s) / Motor • Low RPM DWDI Centrifugal Blower(s)
Standard Standard
ELECTRICAL • 3-Phase Power Supply • Multi-Voltage Control Transformer (24V Class 2) • Modular Motor Controllers with Integral Circuit Breakers
----------- See Electrical Tables Section 5 ----------Standard Standard
SAFETY FEATURES • • • •
C-6000 Audible/Visual Local & Remote Alarms Main Power Circuit Breaker, unit mounted High / Low Refrigerant Pressure Switches (DX units) Motor Overload Protection
Standard Standard Standard Standard
SPECIFIC MODEL STANDARD FEATURES: AIR COOLED • Remote Outdoor, Air Cooled Condenser rated for -20°F to 95°F Amb. Oper. • Low Ambient Control to -30°F & High Ambient to 105°F
Standard Optional
WATER/GLYCOL COOLED • 2-way, 150 psig Water / Glycol Regulating Valves • High Pressure &/or 3-way Valves • Coaxial or Brazed-Plate Heat Exchangers
Standard Optional Standard
ALL SPLIT DX SYSTEMS • Liquid Line Solenoid Valves to Prevent Liquid Slugging
Standard
DUAL CIRCUIT DX SYSTEMS • Two (2) Independent Refrigerant Circuits
- Standard Features "Quick-Reference" Table
FILTERS / PLENUMS
Guide Specifications
Selected Standard Features -
Standard
CODE CONFORMANCE • NRTL Conformance Compliance to UL 1995 Standard • CSA / NYC MEA-163-88-E
Standard Standard
3-1
Guide Specifications -
Standard Equipment
Guide Specifications
QUALITY ASSURANCE
Cabinet Construction
(ISO-9001:2001 Registered)
The cabinet and access panels shall be fabricated from heavy gauge galvannealed steel and powder-coat paint processed for decor matching and corrosion protection. The panels shall be lined with 2 lb/ft2 high density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B.
SATS operates in an ISO-9001 registered quality control environment. Each SATS employee is committed to satisfying his or her customer expectations with the highest level of consistent, measurable and continuous quality improvement.
GENERAL GUIDE SPECIFICATION
Electrical System
General Description
The indoor evaporator shall be provided with a unit mounted main power circuit breaker with lockable handle. The circuit breaker shall provide main power lockout during routine maintenance and service. The circuit breaker shall be a thermal magnetic type selected to protect the fast-bus power distribution system, providing short circuit and ground fault system protection.
- Standard Equipment
Remote Stop / Start Included in the system's electrical control circuit shall be a 2-pin terminal connection for remote stop / start of the CyberTWO air conditioner by a remote source. Modular Motor Controllers
The system shall be a floor mounted air conditioner designed and built to provide precision temperature and humidity control. The system shall be complete and factory run-tested before shipment. The system shall be MET Laboratory (an NRTL) listed and labeled in compliance with UL 1995 and CSA C22.2 No. 236. The system shall be MEA NYC approved (MEA-163-88-E). The system shall be manufactured by Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA.
100% Front Access The air conditioner shall require front only access for all routinely maintenanced components. No allowance for side service access shall be required, however, removable side access shall be provided for additional access.
3-2
Main Power - Circuit Breaker
The system shall incorporate modular motor controllers utilizing motor start protectors and circuit breakers eliminating the need for fusing, as well as providing:
Evaporator Coils
• Motor branch circuit short circuit protection • Motor load switching controllers (contactors) • Motor overload protection The system shall incorporate overcurrent and overload protection in accordance with UL 1995 requirements. Each blower motor, compressor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter / contactor. The control circuit shall be a 24 VAC Class 2 low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and grounding wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC).
The DX-evaporator coil shall be an AFrame design to provide maximum coil surface area and minimum depth to provide a high sensible cooling capacity. The coil shall be seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a dual interlaced circuiting design for maximum heat transfer. Coil end plates shall be hot dipped galvanized. The evaporator coil shall be mounted in an insulated stainless steel condensate drain pan.
Guide Specifications -
Thermal Expansion Valves Filter Drier/ Strainers
overloads, internal pressure relief valve, internal discharge gas vibration eliminator and external vibration mounting isolation.
Blowers/Motors
Sight Glasses
Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge.
Scroll Compressors
DX systems shall be provided with two independently circuited high efficiency, high reliability and low sound Scroll compressors. Each compressor shall be complete with rotolock service valves, charging and service schraeder ports, internal vibration isolation, internal thermal
The standard CyberTWO floor A/C includes the C-6000 Advanced Microprocessor Controller, Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/Heat providing precision temperature and humidity control.
C-6000 Microprocessor
The blower(s) shall be belt driven with double width, double inlet housing, forward curved blades and permanently lubricated ball bearings sized for an average 150,000 hours of service life. The blower(s) shall be dynamically and statically balanced to minimize vibration and operate in the Class I range. The blower(s) shall be belt driven with dual belts (3 Hp and higher) sized for 200% of the fan motor horsepower. The blower shall have an adjustable base for belt tensioning and a locking system to prevent the motors from moving. The motor's drive sheaves shall have an adjustable pitch to change the speed of the blowers. The motor shall be 1725 RPM and shall have overload protection and a minimum NEMA service factor of 1.15.
(Microprocessor Controller w/ Alarms) Control shall be provided by SATS' Advanced C-6000 Microprocessor temperature and humidity controller with alarms. The user friendly C-6000 shall provide both local & remote alarm indication, if applicable, for:
High Temperature Low Temperature High Humidity Low Humidity High Head Press. Low Suction Press. Comm. Failure
Dirty Filter Loss of Air Flow Firestat Smoke Detection Leak Detection Sensor Failure
Electrode Canister Steam Humidifier
- Standard Equipment
All refrigeration piping shall be refrigerant grade tubing. Each refrigerant circuit shall include, as a minimum, refrigerant drier/strainer, sight glass with moisture detector, thermal expansion valve with rapid bleed port feature and external equalizer, evaporator coil, compressor, high pressure switch with manual reset and a low pressure switch with automatic reset. Split / Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be brazed, and the entire system shall be pressure tested at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with refrigerant.
Temp & Humid Control
Guide Specifications
DX-Refrigeration System
Standard Equipment
The humidifier shall be an electrode steam canister type. Manually adjustable ON/OFF steam output shall be standard.
Dehumidification Mode A Dehumidification mode with Electric Reheat/ Heat shall be incorporated as standard. (Note: Please refer to pages 3-5 thru 3-12 of this brochure for more specification details on all CyberTWO Temperature and Humidity Control Options.)
3-3
Guide Specifications Guide Specifications
Evaporator Air Patterns DOWN-FLOW: (standard) (VFS-( )-( )-D) The air conditioner shall be configured for a down-flow air pattern with free evaporator return air from the top and conditioned supply air discharge through the bottom of the unit into the raised floor. (Floor Stands are available as option, page 3-10.)
Down-Flow Air Pattern
Standard Equipment
Air Filtration The A/C shall have slide out, 4" deep, class 2 (per U.L. Standard 900) filters. The filters shall be easily accessed through a front access door. The filters shall have an efficiency rating of at least, 30% average as measured by ASHRAE Standard 52-76 test method.
DX - Heat Rejection AIR COOLED Remote Outdoor Air Cooled Condenser
WATER / GLYCOL COOLED Water/Glycol Cooled Condensers Coaxial Tube-In-Tube: (Models VFS-072/120-DW/DG)
Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured, tube-in-tube coaxial condenser; designed and tested for a 450 psig. w.w.p.
- Standard Equipment
(For model WCS-( )-( ))
SS Brazed-Plated:
A remote outdoor air cooled condenser with direct driven propeller fan(s) shall be provided. The condenser shall be suitable for outdoor installation. Each fan shall be provided with a low RPM, nonoverloading direct driven motor. Each evaporator refrigerant circuit shall be directly connected to an independent condenser coil circuit rated for the full heat of rejection of the air conditioner at a 95°F DB ambient air temperature.
Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured brazed plate heat exchanger, with integral sub-cooler, constructed of type 316 stainless steel; designed and tested for a 450 psig. w.w.p.
(Models VFS-180/312-DW/DG)
(Please refer to page 2-4 for available "down-flow" air pattern configurations.)
(A top 1" flanged return air duct connection is optionally available.)
UP-FLOW: (optional) (VFS-( )-( )-U) The air conditioner shall be configured for an up-flow air pattern with free evaporator return air through front filtered grille and conditioned supply air through the top of the unit. SUPPLY AIR OUTLET
Up-Flow Air Pattern
2-Way, 150 psig Regulating Valve (Standard on all VFS-( )-DW/DG)
(Note: Condensers rated for 105°F DB ambient are optionally available, pg 42.)
RETURN AIR INLET
(Please refer to page 2-4 for available "up-flow" air pattern configurations.)
(A 1" flanged duct connection shall be provided as a standard. 2 & 3-way top discharge plenum boxes are available as options, page 3-10.)
3-4
-20°F, Variable Speed Control WCS-( )-V: Low Ambient Head Pressure Control down to a minimum ambient temperature of -20°F via Variable Fan Speed Head Pressure Control. (Note: Low ambient head pressure control down to -30°F DB minimum ambient air temperature via flooded head pressure control is optionally available, page 3-9.)
Each refrigerant circuit's head pressure shall be automatically controlled by a factory installed 2-way water / glycol regulating valve rated for 150 psig. w.w.p. (Note: 3-way and high pressure water/ glycol regulating valves are optionally available, page 3-9.)
Optional Features -
Guide Specifications
OPTION.................................................... page Microprocessor Controls • C-6000 Microprocessor (standard) ....................... 3-6/7 - User Interface ....................................................... 3-6 - Alarms .................................................................. 3-6 - Control Inputs/Outputs .......................................... 3-7 - Security ................................................................ 3-7 - Diagnostics & Services ......................................... 3-7 - Multi Unit Sequencing ........................................... 3-7 • Remote BMS communications ............................. 3-7
Humidity Control Options
• 350 psig Rated System: (optional) ...................... 3-9 - 3-way, 350 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve • 400 psig Rated System: (optional) ...................... 3-9 - 3-way, 400 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve
DX - Capacity Modulation • Snap-Acting, Hot Gas Bypass ............................... 3-9
• Steam Humidifier (standard) .................................. 3-8
High Static Pressure Blowers
• Floor Stands - Seismic Floor Stand ........................................... 3-10 - Turning Vanes ..................................................... 3-10 • 2 or 3-Way Plenum Discharge Box .................... 3-10
Index
3-8 3-8 3-8 3-8 3-8
ACCESSORIES
-
• Dehumidification Cycle - Electric Reheat / Heat (standard) .......................... - Hot Gas Reheat .................................................... - Hot Water Reheat / Heat ...................................... - Steam Reheat / Heat ............................................ - Electric SCR-Fired Reheat / Heat .........................
Free Cooling - Valve Combinations • 150 psig Rated System: (standard) ..................... 3-9 - 3-way, 150 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve
Optional Features
Optional Features Index
• Condensate Pump ............................................... 3-10 • Smoke Detector ................................................... 3-10
• High Static Belt-Drive Blower Upgrade ................... 3-8/9 (Up to 2.0" ext. static pressure)
High Efficiency Filtration (IAQ) • IAQ High Efficiency Filters ....................................... 3-9
Head Pressure Control Options Air Cooled - Low Ambient Control • 0°F Ambient .......................................................... 3-9 • -20°F Ambient ....................................................... 3-9 • -30°F Ambient ....................................................... 3-9
• Firestat ................................................................. 3-10 • Remote Water Detector: - Qty. One, Spot Type ............................................ 3-11 - Qty. Two, Spot Type ............................................. 3-11 - 25 Ft. - Strip/Cable Type ...................................... 3-11 - Water Detector Auxiliary Contact ......................... 3-11 • Acoustical Compressor Sound Jackets ............... 3-11
Energy $aving Cooling Options • Free-Cooling Cycle .............................................. 3-12 • Alternate Water Source Cycle ............................ 3-12
Water/Glycol Cooled - Regulating Valves • 2-way, 150 psig (standard) .................................... 3-9 • 2-way, 350 psig ..................................................... 3-9 • 2-way, 400 psig ..................................................... 3-9 • 3-way, 150 psig ..................................................... 3-9 • 3-way, 350 psig ..................................................... 3-9 • 3-way, 400 psig ..................................................... 3-9
3-5
Microprocessor Controls - C-6000 Guide Specifications
C-6000 Series Controls Advanced Microprocessor Temperature & Humidity Controller with Alarms
windows type structure, in three different modes; Information, Operation, and Service. FIELD CONFIGURABLE: The C-6000 controller is field program configurable and capable of matching the unique needs of any data center, telecommunication or other critical area.
- Microprocessor Control Options
The CyberTWO floor mounted A/C shall be provided with SATS’ C-6000 Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a “user-friendly” operating environment, to allow easy system setup and operation. The C-6000 is a complete microprocessor based control system designed for operating, controlling and monitoring the air conditioning unit. The C-6000 controller shall include a full-featured LCD, Graphical display for visual indication of the units operating conditions. USER INTERFACE
Compressor Evaporator Blower Motor Humidifier Heater Pump
ALARM CONDITIONS
As a standard, the C-6000 temperature and humidity sensor shall be factory unit mounted in the return air stream of the Precision A/C unit, after the filter(s).
Alarm conditions activate an audible and visual indicator. An alarm shall be acknowledged through a button located on the user interface. The C-6000 alerts to the following alarm conditions (if applicable):
(Note: Remote Sensor installation is available as an option.)
SYSTEM SETUP & ADJUSTMENTS The C-6000 shall be completely factory pre-programmed, and therefore, most applications will require no field setup. However, the “default” set points and their ranges are easily adjusted from the C-6000 interface. UNIT STATUS DISPLAY
• Current Dry Bulb Temp Set Point • Current Relative Humidity Set Point • Actual Time
Current Unit Status: The C-6000 LCD Graphic Display shall indicate current unit functions:
3-6
• • • • •
SENSOR LOCATION OPTIONS:
The C-6000 LCD Graphic Display shall indicate current room status:
The User Interface shall feature an easy to read, liquid-crystal, graphical display. The attractive unit mounted interface, allows the operator to visually monitor and customize unit functions and settings. The controller is operated via a 4-key menu-driven
Run Times The historical run-time in hours of the following major components shall be available directly from the C-6000 interface: (if applicable)
• System ON/OFF • Standby Mode • Cooling • Manual Mode • Heating • Day/Night Operation • Humidifying • Service Required • Dehumidifying • Graphical display of room temperature and humidity for the last 24 hours.
High Temperature Low Temperature High Humidity Low Humidity High Head Press. Low Suction Press. Comm. Failure
Dirty Filter Loss of Air Flow Firestat Smoke Detection Leak Detection Sensor Failure
Summary Alarm Contact: A summary alarm dry-contact (n/o or n/c) connection shall be available for remote annunciation of an alarm condition. An additional user-defined custom alarm drycontact shall also be available on most system configurations. Alarm History: The C-6000 controller provides users with a recorded history of the previous 80 alarms, including the time and date of the alarm. CONTROL INPUTS/OUTPUTS The C-6000 is capable of both digital (on/off) and analog input and output device control. Prior to shipment, each Precision A/C unit’s C-6000 is factory program configured to match the unit’s system operational requirements.
Microprocessor Controls - C-6000
An expansion board shall increase the capability by providing and additional 8 digital inputs and 8 digital outputs.
Power Loss Restart In the event of a loss of power to the system, the C-6000 can be configured for Automatic or Manual Restart. The C-6000’s non-volatile memory enables the system to restart when power is restored, without the loss of the “last” stored set points and other system configuration settings. Sequential Load Activation To minimize the total in rush current loads during system startup/restart, the C-6000 controller shall be configured for time-delay sequence startup. The user can designate specific unit restart time-delays, as well as, each unit’s respective electric heater and/or humidifier. Unit restart delay can be adjusted from 0 to 10 minutes. Electric heater and/or humidifier restart delay can be adjusted from 0 to 60 seconds. Start Delay: After a power loss, the C-6000’s Start Delay feature allows the Precision A/C to operate with a delayed start period (adjustable up to 42 minutes).
SECURITY Keypad Lockout The C-6000 includes a 2-level password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function interface.
DIAGNOSTICS AND SERVICE MODE The C-6000 shall incorporate a unique self-diagnostics algorithm that continually tests systems functions and hardware operation. In the event of such a failure, the user will be alerted to the condition via a visual and audible alarm. Control Board The Control Board shall initiate a self-test of the control system.
number of “standby” units can be designated as any number. Automatic timed change over is designated between 1 and 255 hours. Automatic change-on-failure can be user customized by selecting which normally displayed alarms will result in a switchover to the “standby” unit. As well, standby units can be sequenced to maintain temperature and or humidity as needed. It is necessary that the remote sensor option be utilized for this function. The Multi-Unit Sequencing function shall exist inherently within the standard C-6000 controller. Interconnect wiring between the RS-485 data bus ports as well as field configuration from the C-6000 user interface shall be all that is required to incorporate this feature. When BMS communication is required (MIB Gateway), the RS-485 serial port shall be utilized for the MIB interface. The Multi-Unit Sequencing function shall then be accomplished in the same manner as described above but via the MIB Gateway.
Remote BMS Connection MIB GATEWAY
Input Diagnostics All system inputs and output devices shall be continuously monitored for proper operation.
MULTI UNIT SEQUENCING Multi-Unit Sequencing (Up to 6 Units) The C-6000 shall enable a unit sequencing function with automatic time-based switch over as well as change-on-failure switch over for up to 6 units via the standard RS-485 serial port. One unit shall be designated as the “master” with all others being designated as “standby”. The
C-6000 Inputs & Outputs shall be remotely monitored (address readable) and remotely controlled (address writable) via any building management system (BMS)/local area network (LAN) control system that can communicate via a ModBus protocol. Each C-6000 configured for BMS communication shall incorporate an RS-485 Serial Communication Port that is field connected to a factory provided wall mounted ModBus Gateway.
- Microprocessor Control Options
Temperature Anticipation The C-6000 shall incorporate a selfcalibrating and self-adjusting control logic that adjusts the response of the SATS air conditioner to changes in temperature and humidity. The system shall provide premium setpoint accuracy while controlling the room conditions rate of change, minimizing the equipment energy consumption and maximizing the system’s operating life and reliability.
Recovery Delay After a power loss, the C-6000’s Recovery Delay feature allows the Precision AC A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (adjustable up to 42 minutes) to “pull-down” the conditioned space’s load without nuisance alarms during initial startup or power loss restart.
Guide Specifications
Digital (on/off) and Analog (0-10 VDC) Inputs & Outputs The C-6000 I/O Board provides as a standard 10 digital outputs, 8 digital inputs, 7 analog inputs, and 4 analog outputs.
3-7
Optional Features -
Humidity Control CyberTWO floor systems include the C-6000 Microprocessor Controller, Electrode Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/Heat for total temperature and humidity control, as a standard.
Canister Steam Humidification: (standard) The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output setting
A factory mounted and wired electric resistance heater shall be included to provide automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Electric heaters shall be provided with thermal/magnetic circuit breakers which shall protect each conductor. Included shall be one automatic resetting and one manual resettable over-temperature safety device (pilot duty).
The floor A/C shall be provided with a refrigeration based dehumidification mode. Moisture is condensed on the
(Note: Hot Gas Reheat is not available on systems incorporating Free-Cooling or Alternate Water Source, because no method of reheat would be available during non-compressorized FC or AWS operation.)
Hot Gas Reheat: (Models VFS-()-DAR, DW & DG only) Remote Air Cooled Condenser
Scroll Compressor
Hot Gas Reheat Valve Flooded Head Pressure Control Valve Relief Valve
Refrigerant Reclaim Port Liquid Refrigerant Receiver
LP
HP
Sight Glass
Hot Gas Evaporator Cooling Coil Reheat Coil
Feeler Bulb
A factory installed copper tube, aluminum fin heat/reheat coil and 2way control valve shall be provided to control the flow of hot water for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Steam Reheat/Heat A factory installed copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided to control the flow of steam for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. (Note: Steam trap and steam piping specialties shall be provided by others, not by SATS.)
SCR Fired Reheat/Heat
Reheat Options
Dehumidification Cycle: (standard)
reheat coil providing energy free sensible reheating.
Hot Water Reheat/Heat
Heater elements shall be of a safe low-watt density, plated fin-tubular design. Two (2) stages of electric reheat/heat shall be provided as standard.
from 25 to 100% of the full rated humidifier capacity. The humidifier shall incorporate an automatic flush cycle that senses the current consumption of the humidifier and controls mineral concentration of the water. A “Change Cylinder” light shall notify service personnel when the humidification output is below rated requirements and when maintenance is due.
3-8
Electric Heat/Reheat: (standard)
Equalizer Line
- Guide Specifications
However, these standard features can be deleted and/or substituted with alternate features to allow you the flexibility to select the configuration best suited for your unique application.
cooling coil and discharged through the condensate drain. Reheat (electric, hot gas, steam or hot water) shall be provided to offset sensible cooling during the dehumidification cycle.
Equalizer Line
Optional Features
SELECTED OPTIONS
Guide Specifications
Air Flow
Solenoid Valve Refrigerant Drier / Strainer Thermal Expansion Valve
A factory installed copper tube, aluminum fin hot gas reheat coil and valve shall be provided for automatic sensible reheating mode during dehumidification cycle. Hot compressor discharge gas shall be diverted from the condenser to the hot gas
The electric heat/reheat shall be controlled through a “Zero Firing” Silicon Controlled Rectifier (SCR) with an extruded aluminum heat sink and solid state logic system to provide close dry bulb temperature control of the leaving conditioned air temperature. C-6000 proportional (0-10 Vdc) microprocessor controls shall be provided with the SCR Fired Electric Reheat option.
High Static Pressure Belt-Drive Blowers The CyberTWO vertical floor air conditioner shall be provided with a high static pressure belt-driven evaporator blower to provide standard unit CFM @ ____ " e.s.p.
Optional Features -
Blower Motor Horsepower Net Cooling Capacity Electrical Data Discharge Blower Data
Unit Air Flow Rate (CFM) will match the standard data as shown in Section 4 of this manual for each respective unit model.
Filtration
FREE-COOLING SYSTEMS
AIR COOLED - Low Ambient -30°F, Flooded Control Remote Air Cooled Condenser Scroll Compressor
High Pressure Switch Flooded Head Pressure Control Valve
Relief Valve
Liquid Refrigerant Receiver
HP
Evaporator Cooling Coil
LP
Sight Glass
Refrigerant Reclaim Port
Low Pressure Switch
Liquid Line Solenoid Valve Refrigerant Drier / Strainer
Equalizer Line
• • • •
Head Pressure Control
Feeler Bulb
Thermal Expansion Valve
The air cooled system shall incorporate a low ambient flooded head pressure control for year-round system operation down to -30°F DB minimum ambient air temperature.
150 psig Rated System: (standard) • DX Valves = 3-way, 150 psig • FC Valve = 3-way, 400 psig 350 psig Rated System: (optional) • DX Valves = 3-way, 350 psig • FC Valve = 3-way, 400 psig 400 psig Rated System: (optional) • DX Valves = 3-way, 400 psig • FC Valve = 3-way, 400 psig
WATER / GLYCOL COOLED
DX - Capacity Modulation/ Freeze Protecion CyberTWO vertical floor A/C's are available with the following standard and optional high efficiency IAQ conscious filtration:
Air Pattern Type
Filters Avail.
Up-Flow Units: w/ free-front return: F1, F2 w/ ducted rear return: F1, F2 Down-Flow Units: w/ top return:
F1, F2, F3
Filter ratings are based on dust spot efficiency ratings per ASHRAE Test Standard 52-76. (Note: F2 & F3 optional filters create additional static pressure and may require the High Static Pressure BeltDrive Option. Please consult your local SATS sales representative for details.)
DX Water Cooled and Glycol Cooled systems are available with following standard (V1) and optional (V2-V6) head pressure regulating control valves: V1: 2-way, 150 psig (standard) V2: 2-way, 350 psig V3: 2-way, 400 psig V4: 3-way, 150 psig V5: 3-way, 350 psig V6: 3-way, 400 psig
}
3-way valves require front & left side access
Each refrigerant circuit's head pressure shall be controlled by a factory installed ____-way water / glycol regulating valve rated for ____ psig. w.w.p.
The CyberTWO floor A/C shall incorporate a snap acting hot gas bypass system to provide modulation of the unit’s cooling capacity and evaporator coil freeze protection under low load conditions. Remote Air Cooled Condenser
Scroll Compressor
High Pressure Switch
Evaporator Cooling Coil
HP LP
Low Pressure Switch
Feeler Bulb
Equalizer Line
F1: 4", 30% Eff. Filters (standard) F2: 4", 60% Eff. Filters F3: 2", 30% Pre / 4", 60% Eff. Final Filters
SNAP-ACTING, Hot Gas Bypass (Models VFS-()-DAR, DW & DG only)
- Guide Specifications
Each circuit shall include factory installed crankcase heaters, cold-start relays, liquid refrigerant receivers with receiver liquid level sight glass and head pressure regulating valves for flooded condenser operation.
DX Water/Glycol Cooled systems with Free-Cooling are available with the following standard and optional DX head pressure and Free-Cooling valve combinations:
Optional Features
(Note: Due to the probable change in standard unit blower motor horsepower for the High Static Belt-Drive Blower option, please consult your local SATS sales representative for the following unit specification changes:
Guide Specifications
Flooded Head Pressure Control Valve Hot Gas Regulator Valve (Optional) Relief Valve
Refrigerant Liquid Refrigerant Reclaim Port Receiver
Sight Glass
Liquid Line Solenoid Valve
Refrigerant Drier / Strainer
Thermal Expansion Valve
3-9
Optional Features Optional Features
AWS Control Valves
Guide Specifications
Note: For additional floor stand heights, please contact your local SATS sales representative.
Additional Floor Stand Options: Seismic Zone-4 Rate: The adjustable floor stand shall be certified rated for seismic zone-4 installation. Alternate Water Source cooling shall be controlled by the following standard and optional control valves: V1: 3-way, 400 psig (standard) V2: 2-way, 400 psig (optional)
- Guide Specifications
Standard Valve Control: A ____-way modulating AWS cooling control valve rated for a maximum ____ psig w.w.p. shall be factory installed. Precision cooling control shall be accomplished via an analog control signal to the proportionally actuating control valve.
Turning Vanes: Turning vanes shall be factory provided for field installation to each unit's floor stand.
Adjustable Floor Stand
The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers. The condensate pump shall be rated for 145 GPH at 40 ft. of head with a shut-off at 50 ft. of head.
Smoke Detector
Top Discharge Plenum Box (Up-Flow units only)
Evaporator Air Outlet
ACCESSORIES
stop/start terminals, shall open the A/ C's control circuit, thereby shutting the A/C down in the event of a condensate overflow.
A 2 or 3-way (please specify) plenum discharge box shall be provided. The plenum box shall include doubledeflecting, adjustable grilles. The plenum box shall ship separately for rigging purposes.
Condensate Pump (Factory Mounting Available)
A photo-electric smoke detector shall be factory installed in the CyberTWO evaporator section on the suction side of the evaporator blower. The smoke detector shall be rated for high air velocity applications, and shall shut down the air conditioner upon sensing smoke in the return air stream. Optional Auxiliary Contact: An auxiliary dry-contact (n/o) terminal connection shall be provided for remote notification of a smoke detection alarm.
Firestat A _____ " high adjustable floor stand shall be provided to allow for ease of installation of the CyberTWO A/C onto a raised floor. The floor stand shall be field installed. Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height
3-10
Adjustable Height
Turning Vane Availability
Minimum Maximum
4.0" (Upflow Units Only)
3.5"
4.5"
Not Available
6.0"
5.0"
7.0"
Not Available
12.0"
11.0"
15.0"
Optional
15.0"
14.0"
18.0"
Optional
18.0"
17.0"
21.0"
Optional
24.0"
23.0"
26.0"
Optional
A condensate pump shall be factory installed within the CyberTWO system for automatic removal of condensate and humidifier flush water (if applicable). The condensate pump shall include an internal overflow safety float switch which, when wired to the A/C's remote
The air conditioner shall be provided with a factory wired and mounted firestat. The firestat shall shut down the air conditioner upon sensing a high return air temperature.
Optional Features Single (one) - Spot Type Detector:
Optional Auxiliary Contact: An auxiliary dry-contact (n/o) terminal connection shall be provided for remote notification of a water detection alarm.
Compressor Sound Jackets (VFS-( )-DW/DG-() Only!) Quantity 1-(one) remote spot type water/leak detector per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations.
Quantity 2-(two) remote spot type water/leak detectors per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. 25 Ft. - Strip/Cable Type Detector:
Low Entering Condenser Water Kit For Water/Glycol systems that require entering condenser water temperatures from 65°F to 45°F, the system shall be provided with a factory installed in-line liquid refrigerant receiver to help reduce the negative effect the low condenser source can have on the evaporator. A compressor crankcase heater shall also be provided standard with this option. (Compressor Sound Jackets are not available with this option due to the crankcase heater).
- Guide Specifications
Dual (two) - Spot Type Detectors:
Each compressor shall be provided with a factory installed acoustical sound jacket. Each sound jacket shall have a snap closure system for ease of removing and reinstallation during maintenance. Each sound jacket shall have a Noise Reduction Coefficient NRC of 85 per ASTM C-423 and a Sound Transmission Loss STC of 11 per ASTM E-90.
Optional Features
Remote Water Detectors
Guide Specifications
A 25 Ft. in length remote strip/cable type water/leak detector shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations.
3-11
Optional Features
(Water/Glycol Economizer Coil) A Free-Cooling economizer cycle shall be provided to take advantage of low ambient air temperature conditions to provide compressor-less cooling. The air conditioner shall have three modes of operation: Remote Drycooler (Optional)
Primary Mode:
The free-cooling coil shall be closely sized to match the DX mode sensible cooling capacity to increase the number of hours that the system can operate in the free-cooling mode, thereby increasing the operating savings of the installation.
Secondary / Backup Mode:
100%, 2-Stage DX Cooling Mode:
Pump (Optional) 3-Way Mixing Modulating Valve
Free-Cooling Coil
T
DX1 - Cooling Coil
DX1 3-Way Head Pressure Control Valve
HP
Water / Glycol Cooled Condenser Coil
LP
Equalizer Line
- Free-Cooling & Alternate Water Source
Free-Cooling Aqua-Stat
Scroll Compressor
Feeler Bulb
Expansion Valve
Refrigerant Reclaim Port Sight Glass
Refrigerant Drier / Strainer
"Assist" FC + 1-Stage DX Mode: When outdoor air temperatures are between approximately 35°F to 65°F and cooling is required, the C-6000 microprocessor controller's "assistmode" free-cooling program algorithm shall analyze input data from factory provided and installed ambient temperature sensors, aquastat and return room air temperature and relative humidity sensors. Based on this data, the C--6000 shall automatically activate partial precooling mode in conjunction with one stage of DX cooling. This "precooling" effect decreases the hours of compressor operation, thereby increasing the operating savings of the installation. 100% Free-Cooling Mode: When outdoor air temperatures are below approximately 35°F and space cooling is required, all source coolant shall be diverted from the DX - Water / Glycol Cooled refrigerant condenser to a chilled water/glycol coil (free-
3-12
cooling coil & control valve). To maximize the cooling effect for the coolant solution during the freecooling mode, the drycooler capacity shall be increased by reversing the typical drycooler fan(s) cycling sequence of operation.
When outdoor air temperatures are above 65°F, or at any time when the free-cooling mode cannot handle the space cooling or dehumidification load, the C-6000 shall automatically switch to 100%, 2-stage DX - water / glycol cooled compressorized cooling mode.
Alternate Water Source (Chilled Water by "Day" and DX-Backup by "Night" !) An Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply when available as the primary cooling cycle, with dual compressor, DX refrigerant cooling as a backup. The air conditioner shall have two cooling systems: Remote Liquid Chiller (by others)
Alternate Water Source Cooling Coil
Pump (by others) Flow Switch
AWS Control Valve
FS
Alternate Water Source Aqua-Stat T
Remote Air Cooled Condenser Scroll Compressor
Flooded Head Pressure Control Valve Relief Valve
Refrigerant Reclaim Port Receiver
LP
HP
Sight Glass
DX - Cooling Coil
Equalizer Line
Guide Specifications
Free-Cooling "Assist-Mode" Option
- Free-Cooling/Alternate Water Source
Feeler Bulb
Solenoid Valve Refrigerant Drier / Strainer Expansion Valve
The primary mode of cooling shall be a chilled water / glycol circuit with alternate water source cooling coil and 3-way modulating (0-10 Vdc) control valve rated for 400 psig. w.w.p.
The secondary/backup mode of cooling shall be a dual compressor, DX refrigerant circuit. The C-6000 microprocessor's Alternate Water Source program algorithm shall analyze input data from factory provided and installed water flow switch, aquastat and return room air temperature, and relative humidity sensors. Based on this data, the C6000 microprocessor shall automatically control the sequencing of the primary AWS chilled water to and from the secondary/backup dual compressor DX modes of operation. If chilled water is available, the system shall operate like a chilled water unit, without the compressors operating. When the water temperature is too high, or the water flow rate is not sufficient, the air conditioner shall automatically switch to the dual compressor, DX refrigerant cycle. (Note: DX Air Cooled with AWS cooling is shown for illustration purposes only. DX Water and Glycol Cooled with AWS cooling are also available.)
Performance/Capacity Specifications - Index MODEL TYPE .......................................... page Air Cooled • Air Cooled Systems - VFS-072/312-DAR ................................................ 4-2 - Remote Air Cooled Condenser Data ...................... 4-3
Water Cooled • Water Cooled Sytems - VFS-072/312-DW ................................................. 4-4 - Water Cooled Condenser Data .............................. 4-5
Glycol Cooled • Glycol Cooled Sytems - VFS-072/312-DG .................................................. 4-6 - Glycol Cooled Condenser Data ............................. 4-7 - Remote Drycooler/Pump Data .............................. 4-7
DX Free Cooling • DX Glycol Cooled w/ Free Cooling - VFS-072/312-DG-FC ............................................. 4-8 - Glycol Cooled Condenser Data ............................. 4-9
• DX Air Cooled w/ Alternate Water Source - VFS-072/312-DAR-DWS ..................................... 4-12 - Remote Air Cooled Condenser Data .................... 4-13
Index
DX Alternate Water Source Cooling
-
• DX Water Cooled w/ Free Cooling - VFS-072/312-DW-FC .......................................... 4-10 - Water Cooled Condenser Data ............................. 4-11
Performance/Capacity Specifications
Index
• DX Water Cooled w/ Alternate Water Source - VFS-072/312-DW-AWS ...................................... 4-14 - Water Cooled Condenser Data ............................ 4-15 • DX Glycol Cooled w/ Alternate Water Source - VFS-072/312-DG-AWS ....................................... 4-16 - Glycol Cooled Condenser Data ........................... 4-17
4-1
Air Cooled Performance Data
"VFS" Model
6 to 26 Ton "VFS"
( )-072-DAR
( )-096-DAR
( )-120-DAR
( )-180-DAR
( )-240-DAR
( )-312-DAR
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible
- Air Cooled (6 to 26 Ton Systems)
75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
70,915 67,020
97,935 92,500
122,825 111,200
185,450 173,650
241,420 215,410
287,260 250,390
67,570 64,745
93,435 89,185
117,130 107,670
176,580 169,340
230,230 211,055
273,826 243,640
65,470 63,135
90,560 86,685
113,495 104,975
171,340 165,145
223,785 206,330
265,460 238,480
69,585 69,585
96,590 95,245
120,150 116,560
181,075 179,590
235,105 228,900
278,670 267,170
66,470 66,470
92,325 91,585
114,730 112,590
173,265 172,460
224,735 222,675
265,720 259,240
64,510 64,510
89,530 89,160
111,165 110,155
168,305 167,655
218,155 217,430
257,640 253,415
Reheat/Heat - Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 61,795 107,785
79,700
122,675
139,530
HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 300 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc)
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
4-15 5.1 Kw
163,130 138,650 5.0 13.8 --------
164,410 194,160 142 157 --------------------
(Standard)
4-15 5.1 Kw
Cycling Cycling Modulating (0-10 Vdc)
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890
2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760
3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815
5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020
5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800
7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880
3/ 14.6 394
3/ 19.8 442
3/ 24.3 422
3/ 24.3 506
Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm
4-2
3/ 9.7 386
3/ 14.6 343
Air Cooled -
( )-072-DAR
( )-096-DAR
( )-120-DAR
( )-180-DAR
( )-240-DAR
( )-312-DAR
Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,785
Scroll, (2) 3,890
Scroll, (2) 4,950
Scroll, (2) 7,759
Scroll, (2) 10,448
Scroll, (2) 12,812
Total Heat of Rej.
92,991 Btu/h
131,494 Btu/h
163,488 Btu/h
250,800 Btu/h
328,337 Btu/h
394,083 Btu/h
Connection Sizes - Copper, Refrigerant: Liquid Line, (Qty.) Hot Gas Line, (Qty.)
(Please refer to CyberTWO "VFS" IOM Manual for proper interconnecting refrigerant line sizing.)
1/2" OD, (2) 5/8" OD, (2)
1/2" OD, (2) 5/8" OD, (2)
1/2" OD, (2) 5/8" OD, (2)
5/8" OD, (2) 7/8" OD, (2)
5/8" OD, (2) 1-1/8 OD, (2)
5/8" OD, (2) 1-1/8 OD, (2)
Condensate Drain, (w/ pump)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
Remote Air Cooled Condenser Data: WCS-( ) - (Remote Outdoor Propeller Fan(s), Air Cooled Condenser for Model VFS-( )-DAR Evaporator Section) Model @ 95°F Amb.
WCS-008
WCS-010
WCS-012
WCS-020
WCS-025
WCS-028
Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.)
8,640 1/2 Hp, (1)
7,780 1/2 Hp, (1)
7,080 1/2 Hp, (1)
15,400 1.0 Hp, (2)
23,000 1.5 Hp, (2)
22,450 1.5 Hp, (2)
1/3 Hp, (1)
1/3 Hp, (1)
1/3 Hp, (1)
____
____
____
164
+
Motor Hp, (Qty.) Net Weight (lbs)
179
195
536
580
630
Refrigerant Connections - Copper Hot Gas Line, (Qty.) 7/8" OD, (2) Liquid Line, (Qty.) 5/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-3/8" OD, (2) 1-1/8" OD, (2)
1-3/8" OD, (2) 1-1/8" OD, (2)
Model @ 105°F Amb.
WCS-010
WCS-015
WCS-016
WCS-028
WCS-036
WCS-041
7,780 1/2 Hp, (1)
15,700 1.0 Hp, (2)
15,600 1.0 Hp, (2)
22,450 1.5 Hp, (2)
20,700 1.5 Hp, (2)
33,675 1.5 Hp, (3)
1/3 Hp, (1)
____
____
____
____
____
174
Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) + Motor Hp, (Qty.) Net Weight (lbs)
510
518
630
730
900
Refrigerant Connections Hot Gas Line, (Qty.) 1-1/8" OD, (2) Liquid Line, (Qty.) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-3/8" OD, (2) 1-1/8" OD, (2)
1-5/8" OD, (2) 1-3/8" OD, (2)
1-5/8" OD, (2) 1-3/8" OD, (2)
Low Ambient Control Std Minimum Op. Amb. Head Press. Method
-20°F Variable Speed
-20°F Variable Speed
-20°F Variable Speed
-20°F Variable Speed
-20°F Variable Speed
-20°F Variable Speed
-30°F(Flooded)
-30°F(Flooded)
-30°F(Flooded)
-30°F(Flooded)
-30°F(Flooded)
-30°F(Flooded)
Optional Min. Op. Amb
- Air Cooled (6 to 26 Ton Systems)
20x25x4, (3)
Performance Data
"VFS" Model
Remote Condenser Data (6 to 26 Ton "VFS")
Compressors are located with the model VFS-( )-DAR Evaporator Section
4-3
Water Cooled Performance Data
"VFS" Model
( )-072-DW
6 to 26 Ton "VFS" ( )-096-DW
( )-120-DW
( )-180-DW
( )-240-DW
( )-312-DW
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible
- Water Cooled (6 to 26 Ton Systems)
75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
78,245 70,325
107,525 97,990
134,380 117,420
194,200 170,840
266,500 223,315
313,200 262,975
74,645 68,105
102,660 94,835
128,280 114,105
185,100 165,600
254,175 217,746
298,440 256,460
72,315 66,275
99,565 92,355
124,420 111,475
179,270 161,650
246,560 213,170
289,410 251,145
76,190 73,500
105,540 101,910
131,100 124,110
189,535 180,125
258,940 238,330
303,540 281,450
72,770 71,060
100,900 98,430
125,260 120,390
180,820 174,215
247,070 232,000
289,225 273,950
70,500 69,550
97,860 96,205
121,475 118,100
175,045 170,685
239,655 227,695
280,410 268,110
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 44,305 52,440
58,655
90,750
102,170
HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 250 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc)
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
4-15 5.1 Kw
123,200 138,650 5.0 13.8 --------
164,410 194,160 142 157 --------------------
(Standard)
4-15 5.1 Kw
Cycling Cycling Modulating (0-10 Vdc)
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890
2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760
3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815
5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020
5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800
7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880
3/ 14.6 394
3/ 19.8 442
3/ 24.3 422
3/ 24.3 506
Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm
4-4
3/ 9.7 386
3/ 14.6 343
Water Cooled ( )-072-DW
( )-096-DW
( )-120-DW
( )-180-DW
( )-240-DW
( )-312-DW
Scroll, (2) 3,865
Scroll, (2) 6,315
Scroll, (2) 8,523
Scroll, (2) 10,289
Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,174
Scroll, (2) 3,042
Water Cooled Condenser Data - Based on 0% Glycol Solution Total Heat of Rej.
95,482 Btu/h
135,100 Btu/h
167,617 Btu/h
258,040 Btu/h
337,181 Btu/h
402,707 Btu/h
GPM @ 85°F EWT / 95°F LWT Unit Press. Drop (Ft. of H2O)
19.1 GPM 24.2 Ft.
27.0 GPM 20.6 Ft.
33.5 GPM 31.3 Ft.
51.6 GPM 24.4 Ft.
67.4 GPM 32.7 Ft.
80.5 GPM 37.5 Ft.
Condenser Type
Coaxial
Coaxial
Coaxial
Plate-Finned
Plate-Finned
Plate-Finned
Head Pressure Control Standard Control
2-way, 150 psig Water Regulating Valves, (factory installed)
Optional Control
Refer to page 3-11 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options!
Performance Data
"VFS" Model
Condenser Data (6 to 26 Ton "VFS")
Connection Sizes - Copper 7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet Condenser In/Out
1/4" OD 1-1/8" OD
1/4" OD 1-3/8" OD
1/4" OD 1-3/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
Remote Water Source
Remote Water Source
(supplied by others) Evaporator Air Inlet
OFF
(supplied by others)
EVAPORATOR AIR OUTLET
ON
EVAPORATOR AIR OUTLET
- Water Cooled (6 to 26 Ton Systems)
Condensate Drain, (w/ pump)
EVAPORATOR AIR INLET
Evaporator Air Outlet
EVAPORATOR AIR INLET
VFS-072 thru VFS-312-DW-D Self-Contained, DX - Water Cooled (Down-Flow Air Pattern)
VFS-072 thru VFS-312-DW-U Self-Contained, DX - Water Cooled (Up-Flow Air Pattern)
DX - Water Cooled with "Free Cooling" Option Performance Data <<< Please see page 4-10 for DX - Water Cooled with "Free Cooling" Option Performance Data. >>>
4-5
Glycol Cooled Performance Data
"VFS" Model
( )-072-DG
6 to 26 Ton "VFS" ( )-096-DG
( )-120-DG
( )-180-DG
( )-240-DG
( )-312-DG
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible
- Glycol Cooled (6 to 26 Ton Systems)
75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
69,610 65,460
95,490 91,030
119,725 109,440
174,540 159,760
237,750 208,890
280,370 246,790
66,390 63,120
91,100 87,675
114,150 105,850
166,350 154,340
226,750 202,950
267,365 240,020
64,320 61,340
88,280 85,175
110,560 103,125
161,050 150,275
219,760 198,300
259,155 234,880
68,265 67,535
94,310 93,415
117,220 114,340
171,060 166,575
231,520 221,275
272,120 262,990
65,245 64,955
90,150 89,720
111,940 110,315
163,275 160,500
221,000 214,500
259,580 254,970
63,225 63,225
87,445 87,445
108,420 107,810
158,090 156,750
214,370 210,210
251,670 249,135
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 66,170 77,300
84,965
130,655
148,870
HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 300 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc)
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
4-15 5.1 Kw
173,115 138,650 5.0 13.8 --------
164,410 194,160 142 157 --------------------
(Standard)
4-15 5.1 Kw
Cycling Cycling Modulating (0-10 Vdc)
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890
2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760
3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815
5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020
5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800
7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880
3/ 14.6 394
3/ 19.8 442
3/ 24.3 422
3/ 24.3 506
Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm
4-6
3/ 9.7 386
3/ 14.6 343
Glycol Cooled ( )-072-DG
( )-096-DG
( )-120-DG
( )-180-DG
( )-240-DG
( )-312-DG
Scroll, (2) 5,278
Scroll, (2) 8,187
Scroll, (2) 11,011
Scroll, (2) 13,568
Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,960
Scroll, (2) 4,138
Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution Total Heat of Rej.
92,447 Btu/h
130,382 Btu/h
162,550 Btu/h
249,027 Btu/h
326,144 Btu/h
391,777 Btu/h
GPM @ 110°F EGT Unit Press. Drop (Ft. of H2O) Condenser Type
20.4 GPM 26.6 Ft. Coaxial
28.8 GPM 22.4 Ft. Coaxial
35.9 GPM 34.4 Ft. Coaxial
54.9 GPM 27.2 Ft. Plate-Finned
71.9 GPM 36.2 Ft. Plate-Finned
86.5 GPM 41.9 Ft. Plate-Finned
Head Pressure Control Standard Control
2-way, 150 psig Glycol Regulating Valves, (factory installed)
Optional Control
Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options !
Connection Sizes - Copper 7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet Condenser In/Out
1/4" OD 1-1/8" OD
1/4" OD 1-3/8" OD
1/4" OD 1-3/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
FSS-204A
FSS-205A
FSS-208A
FSS-211A
FSS-301A
Remote Drycooler/Pump Data Selection @ 95°F
FSS-107A
GPM @ 120°F EGT No. of Feeds Expansion Tank Pipe Connection (In/Out) 105°F Amb. Selections
20.4 GPM 18 15 Gal 1-1/2" MPT
28.8 GPM 35.9 GPM 18 18 15 Gal 15 Gal 2" MPT 2" MPT Optional - Please refer to Glycol Pump /
54.9 GPM 71.9 GPM 27 36 15 Gal 15 Gal 2-1/2" MPT 2-1/2" MPT Drycooler Engineering Manual
86.5 GPM 54 15 Gal 3.0" MPT
Standard Pump Quantity Horsepower Total Hd Press. (ft. w.g.) Dual Pump Packages
GPS-015-S 1(one) 1.5 Hp 78.0 Ft.
GPS-015-S GPS-015-S 1(one) 1(one) 1.5 Hp 1.5 Hp 75.0 Ft. 72.0 Ft. Optional - Please refer to Glycol Pump /
GPS-020-S GPS-030-S 1(one) 1(one) 2.0 Hp 3.0 Hp 72.0 Ft. 82.0 Ft. Drycooler Engineering Manual
GPS-030-S 1(one) 3.0 Hp 75.0 Ft.
F( )S-( )
Evaporator Air Inlet
Outdoor Propeller Air Cooled Drycoolers
F( )S-( ) Outdoor Propeller Air Cooled Drycoolers
ON OFF
EVAPORATOR AIR OUTLET
GPS-( )-( )
EVAPORATOR AIR OUTLET
GPS-( )-( )
Single & Dual Glycol Pump Packages
Single & Dual Glycol Pump Packages
Evaporator Air Outlet
VFS-072 thru VFS-312-DG-D Self-Contained, DX - Glycol Cooled (Standard Down-Flow Air Pattern)
- Glycol Cooled (6 to 26 Ton Systems)
Condensate Drain, (w/ pump)
Performance Data
"VFS" Model
Condenser Data (6 to 26 Ton "VFS")
EVAPORATOR AIR INLET
VFS-072 thru VFS-312-DG-U Self-Contained, DX - Glycol Cooled (Optional Up-Flow Air Pattern)
DX - Glycol Cooled with "Free Cooling" Option Performance Data <<< Please see page 4-8 for DX - Glycol Cooled with "Free Cooling" Option Performance Data. >>>
4-7
DX Glycol Cooled w/ Free-Cooling - 6 to 26 Ton "VFS"
Performance Data - DX Glycol Cooled w/ FC (6 to 26 Ton Systems)
4-8
"VFS" Model
072-DG-FC
096-DG-FC
120-DG-FC
180-DG-FC
240-DG-FC
312-DG-FC
NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
69,610 65,460
95,490 91,030
119,725 109,440
174,540 159,760
237,750 208,890
280,370 246,790
66,390 63,120
91,100 87,675
114,150 105,850
166,350 154,340
226,750 202,950
267,365 240,020
64,320 61,340
88,280 85,175
110,560 103,125
161,050 150,275
219,760 198,300
259,155 234,880
68,265 67,535
94,310 93,415
117,220 114,340
171,060 166,575
231,520 221,275
272,120 262,990
65,245 64,955
90,150 89,720
111,940 110,315
163,275 160,500
221,000 214,500
259,580 254,970
63,225 63,225
87,445 87,445
108,420 107,810
158,090 156,750
214,370 210,210
251,670 249,135
FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
65,765 65,765
89,570 89,570
107,005 106,880
163,070 161,740
199,955 192,725
225,230 222,750
59,135 59,135
80,650 80,650
96,295 96,295
147,305 147,305
179,220 179,220
205,095 205,095
54,800 54,800
74,815 74,815
89,340 89,340
136,685 136,685
166,485 166,485
190,460 190,460
65,675 65,675
89,430 89,430
106,640 106,640
163,100 163,100
198,480 198,480
227,075 227,075
59,190 59,190
80,730 80,730
96,350 96,350
147,390 147,390
179,465 179,465
205,310 205,310
54,850 54,850
74,885 74,885
89,430 89,430
136,825 136,825
166,660 166,660
190,660 190,660
28.8 GPM
35.9 GPM
54.9 GPM
71.9 GPM
86.5 GPM
Flow Rates, Free-Cooling Coil Flow Rate
20.4 GPM
Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975
3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870
5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940
7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200
7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975
10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080
Evaporator Coil, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2)
3/ 9.7
3/ 14.6
3/ 14.6
3/ 19.8
3/ 24.3
3/ 24.3
FC Coil: Rows/Face Area (ft2)
4/ 9.0
4/ 9.0
4/ 9.0
4/ 12.2
4/ 14.2
4/ 14.2
DX Glycol Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" 072-DG-FC
096-DG-FC
120-DG-FC
180-DG-FC
240-DG-FC
312-DG-FC
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control
4-15 5.1 Kw
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
(Standard)
4-15 5.1 Kw
Cycling Cycling Modulating (0-10 Vdc)
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,960
Scroll, (2) 4,138
Scroll, (2) 5,278
Scroll, (2) 8,187
Scroll, (2) 11,011
Scroll, (2) 13,568
Total Heat of Rej.
92,447 Btu/h
130,382 Btu/h
162,550 Btu/h
249,027 Btu/h
326,144 Btu/h
391,777 Btu/h
GPM @ 110°F EGT Unit PD (Ft. of H2O)
20.4 GPM 37.9 Ft.
28.8 GPM 27.5 Ft.
35.9 GPM 45.3 Ft.
54.9 GPM 34.7 Ft.
71.9 GPM 45.6 Ft.
86.5 GPM 52.8 Ft.
Type
Coaxial
Coaxial
Coaxial
Plate-Finned
Plate-Finned
Plate-Finned
DX- Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Regulating Valve: DX Hd Pr. Valve Type
3-way, 150 psig DX Condenser Source Regulating Valve - factory installed
Free-Cooling Valve:
FC Valve Size Cv
3/4" 7.5 Cv
Standard Valve Type Optional Valve Combos
1.0" 14.0 Cv --------
1.0" 14.0 Cv
1-1/4" 20.0 Cv
1-1/2" 28.0 Cv
3-way, 400 psig, Modulating (0-10 Vdc) - factory installed
1-1/2" 28.0 Cv --------
Please refer to page 3-9 for Higher Pressure Rated Valve Combination Options!
Connection Sizes - Copper Condensate Drain, (w/ pump)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet Source Glycol In/Out
1/4" OD 1-1/8" OD
1/4" OD 1-3/8" OD
1/4" OD 1-3/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
- DX Glycol Cooled w/ FC (6 to 26 Ton Systems)
Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution
Performance Data
"VFS" Model
4-9
DX Water Cooled w/ Free-Cooling - 6 to 26 Ton "VFS"
Performance Data - DX Water Cooled w/ FC (6 to 26 Ton Systems)
4-10
"VFS" Model
072-DW-FC
096-DW-FC
120-DW-FC
180-DW-FC
240-DW-FC
312-DW-FC
NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
78,245 70,325
107,525 97,990
134,380 117,420
194,200 170,840
266,500 223,315
313,200 262,975
74,645 68,105
102,660 94,835
128,280 114,105
185,100 165,600
254,175 217,746
298,440 256,460
72,315 66,275
99,565 92,355
124,420 111,475
179,270 161,650
246,560 213,170
289,410 251,145
76,190 73,500
105,540 101,910
131,100 124,110
189,535 180,125
258,940 238,330
303,540 281,450
72,770 71,060
100,900 98,430
125,260 120,390
180,820 174,215
247,070 232,000
289,225 273,950
70,500 69,550
97,860 96,205
121,475 118,100
175,045 170,685
239,655 227,695
280,410 268,110
FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Water Temperature, 0% Glycol Solution 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
88,135 78,640
111,680 101,105
125,865 114,380
189,920 172,425
222,920 201,895
246,390 231,135
77,160 74,290
98,100 95,710
110,785 108,390
167,565 163,550
196,500 191,420
221,265 221,085
70,670 70,670
90,080 90,080
101,900 101,900
154,380 154,380
180,985 180,985
206,050 206,050
84,515 83,810
107,605 107,605
121,660 121,660
184,230 184,230
215,965 215,965
245,270 245,270
75,170 75,170
96,195 96,195
109,150 109,150
165,705 165,705
194,260 194,260
222,015 222,015
69,690 69,690
89,370 89,370
101,410 101,410
153,965 153,965
185,510 185,510
206,280 206,280
27.0 GPM
33.5 GPM
51.6 GPM
67.4 GPM
80.5 GPM
Flow Rates, Free-Cooling Coil Flow Rate
19.1 GPM
Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975
3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870
5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940
7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200
7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975
10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080
Evaporator Coil, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2)
3/ 9.7
3/ 14.6
3/ 14.6
3/ 19.8
3/ 24.3
3/ 24.3
FC Coil: Rows/Face Area (ft2)
4/ 9.0
4/ 9.0
4/ 9.0
4/ 12.2
4/ 14.2
4/ 14.2
DX Water Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" 072-DW-FC
096-DW-FC
120-DW-FC
180-DW-FC
240-DW-FC
312-DW-FC
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control
4-15 5.1 Kw
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
(Standard)
4-15 5.1 Kw
Cycling Cycling Modulating (0-10 Vdc)
4-15 5.1 Kw
4-15 5.1 Kw
Cycling Cycling -----------------------
Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,174
Scroll, (2) 3,042
Scroll, (2) 3,865
Scroll, (2) 6,315
Scroll, (2) 8,523
Scroll, (2) 10,289
Total Heat of Rej.
95,482 Btu/h
135,100 Btu/h
167,617 Btu/h
258,040 Btu/h
337,181 Btu/h
402,707 Btu/h
GPM @ 85°F EWT/95°F LWT Unit PD (Ft. of H2O)
19.1 GPM 24.2 Ft.
27.0 GPM 20.6 Ft.
33.5 GPM 31.3 Ft.
51.6 GPM 24.4 Ft.
67.4 GPM 32.7 Ft.
80.5 GPM 37.5 Ft.
Type
Coaxial
Coaxial
Coaxial
Plate-Finned
Plate-Finned
Plate-Finned
DX- Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Regulating Valve: DX Hd Pr. Valve Type
3-way, 150 psig DX Condenser Source Regulating Valve - factory installed
Free-Cooling Valve:
FC Valve Size Cv
3/4" 7.5 Cv
Standard Valve Type Optional Valve Combos
1.0" 14.0 Cv --------
1.0" 14.0 Cv
1-1/4" 20.0 Cv
1-1/2" 28.0 Cv
3-way, 400 psig, Modulating (0-10 Vdc) - factory installed
1-1/2" 28.0 Cv --------
Please refer to page 3-9 for Higher Pressure Rated Valve Combination Options!
Connection Sizes - Copper Condensate Drain, (w/ pump)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet Source Glycol In/Out
1/4" OD 1-1/8" OD
1/4" OD 1-3/8" OD
1/4" OD 1-3/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
1/4" OD 2-1/8" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
- DX Water Cooled w/ FC (6 to 26 Ton Systems)
Water Cooled Condenser Data - Based on 0% Glycol Solution
Performance Data
"VFS" Model
4-11
DX Air Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS"
Performance Data
"VFS" Model
- DX Air Cooled w/ AWS (6 to 26 Ton Systems)
4-12
072-DAR-AWS
096-DAR-AWS
120-DAR-AWS
180-DAR-AWS
240-DAR-AWS
312-DAR-AWS
AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
84,570 77,200 17.0 / (0.9)
102,530 97,445 20.5 / (1.2)
114,540 109,855 23.0 / (1.7)
172,100 165,305 34.6 / (2.3)
198,605 192,190 40.0 / (3.4)
219,810 219,810 44.2 / (4.1)
72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
69,310 69,310 13.9 / (0.6)
86,055 86,055 17.3 / (1.0)
97,070 97,070 19.5 / (1.3)
147,725 147,725 29.7 / (1.8)
171,585 171,585 34.5 / (2.6)
193,290 193,290 38.8 / (3.2)
70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,925 60,925 12.2 / (0.5)
76,095 76,095 15.2 / (0.7)
86,330 86,330 17.2 / (1.0)
132,105 132,105 26.5 / (1.4)
154,950 154,950 31.1 / (2.2)
174,705 174,705 35.1 / (2.7)
75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
80,115 80,115 16.0 / (0.8)
99,540 99,540 20.0 / (1.2)
111,795 111,795 22.4 / (1.6)
169,345 169,345 34.0 / (2.2)
195,820 195,820 39.3 / (3.3)
221,045 221,045 44.4 / (4.1)
72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
68,335 68,335 13.7 / (0.6)
85,350 85,350 17.0 / (0.9)
96,975 96,975 19.5 / (1.3)
147,720 147,720 29.7 / (1.8)
171,580 171,580 34.5 / (2.6)
193,610 193,610 38.9 / (3.2)
70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,860 60,860 12.2 / (0.5)
76,165 76,165 15.2 / (0.7)
86,755 86,755 17.4 / (1.1)
132,400 132,400 26.6 / (1.4)
155,630 155,630 31.5 / (2.2)
174,895 174,895 35.1 / (2.7)
NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
70,915 67,020
97,935 92,500
122,825 111,200
185,450 173,650
241,420 215,410
287,260 250,390
67,570 64,745
93,435 89,185
117,130 107,670
176,580 169,340
230,230 211,055
273,826 243,640
65,470 63,135
90,560 86,685
113,495 104,975
171,340 165,145
223,785 206,330
265,460 238,480
69,585 69,585
96,590 95,245
120,150 116,560
181,075 179,590
235,105 228,900
278,670 267,170
66,470 66,470
92,325 91,585
114,730 112,590
173,265 172,460
224,735 222,675
265,720 259,240
64,510 64,510
89,530 89,160
111,165 110,155
168,305 167,655
218,155 217,430
257,640 253,415
7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975
10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080
Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975
3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870
5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940
7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200
Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2)
3/ 9.7
3/ 14.6
3/ 14.6
3/ 19.8
3/ 24.3
3/ 24.3
AWS Coil: Rows/Face Area (ft2)
4/ 9.0
4/ 9.0
4/ 9.0
4/ 12.2
4/ 14.2
4/ 14.2
DX Air Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DAR-AWS
096-DAR-AWS
120-DAR-AWS
180-DAR-AWS
240-DAR-AWS
312-DAR-AWS
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control
(Standard)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
Cycling
Cycling
Cycling
Cycling
Cycling
Cycling
Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD
3/4"/(7.5 Cv) 24.2 Ft.
Standard Valve Type
1"/(14.0 Cv) 20.6 Ft.
--------
Optional Valve
1"/(14.0 Cv) 31.3 Ft.
1-1/4"/(14.0 Cv) 24.4 Ft.
1-1/2"/(14.0 Cv) 32.7 Ft.
3-way, 400 psig, Modulating (0-10 Vdc) - factory installed
1-1/2"/(14.0 Cv) 37.5 Ft.
--------
Please refer to page 3-9 for 2-way and higher pressure valve options.
Compressors - Heat pump duty rated Scroll - HCFC R-22 Scroll, (2) 2,785
Scroll, (2) 3,890
Scroll, (2) 4,950
Scroll, (2) 7,759
Scroll, (2) 10,448
Scroll, (2) 12,812
Total Heat of Rej.
92,991 Btu/h
131,494 Btu/h
163,488 Btu/h
250,800 Btu/h
328,337 Btu/h
394,083 Btu/h
Connection Sizes - Copper,
(Please refer to CyberTWO "VFS" IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant: Liquid Line, (Qty.) Hot Gas Line, (Qty.)
1/2" OD, (2) 5/8" OD, (2)
1/2" OD, (2) 5/8" OD, (2)
1/2" OD, (2) 5/8" OD, (2)
5/8" OD, (2) 7/8" OD, (2)
5/8" OD, (2) 1-1/8 OD, (2)
5/8" OD, (2) 1-1/8 OD, (2)
AWS Coil Source In/Out
1-1/8" OD
1-3/8" OD
1-3/8" OD
2-1/8" OD
2-1/8" OD
2-1/8" OD
Condensate Drain, (w/ pump) Humidifier Inlet
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.)
16x20x4, (2) 20x20x4, (2)
Remote Air Cooled Condenser Data: WCS-( ) - (Remote Outdoor Propeller Fan, Air Cooled Condenser for Model VFS-( )-DAR Evaporator Section) Model @ 95°F Amb.
WCS-008
WCS-010
WCS-012
WCS-020
WCS-025
WCS-028
Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.)
8,640 1/2 Hp, (1)
7,780 1/2 Hp, (1)
7,080 1/2 Hp, (1)
15,400 1.0 Hp, (2)
23,300 1.5 Hp, (2)
22,450 1.5 Hp, (2)
1/3 Hp, (1)
1/3 Hp, (1)
1/3 Hp, (1)
____
____
____
164
179
195
536
580
630
1 1/8" OD, (2) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-1/8" OD, (2) 7/8" OD, (2)
1-3/8" OD, (2) 1-1/8" OD, (2)
1-3/8" OD, (2) 1-1/8" OD, (2)
-20°F
-20°F
+
Motor Hp, (Qty.) Net Weight (lbs)
Refrigerant Connections - Copper Hot Gas Line, (Qty.) 7/8" OD, (2) Liquid Line, (Qty.) 5/8" OD, (2) Low Ambient Control Std Min. Oper. Amb. Optional Min. Oper. Amb
-20°F
-20°F
-30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) Compressors are located with the model VFS-( )-DAR Evaporator Section
-20°F
-20°F
-30°F(Flooded)
-30°F(Flooded)
- DX Air Cooled w/ AWS (6 to 26 Ton Systems)
Type, (Qty.) Watts Input (ea.)
Performance Data
"VFS" Model
4-13
DX Water Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS"
Performance Data
"VFS" Model
- DX Water Cooled w/ AWS (6 to 26 Ton Systems)
4-14
072-DW-AWS
096-DW-AWS
120-DW-AWS
180-DW-AWS
240-DW-AWS
312-DW-AWS
AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
84,570 77,200 17.0 / (0.9)
102,530 97,445 20.5 / (1.2)
114,540 109,855 23.0 / (1.7)
172,100 165,305 34.6 / (2.3)
198,605 192,190 40.0 / (3.4)
219,810 219,810 44.2 / (4.1)
72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
69,310 69,310 13.9 / (0.6)
86,055 86,055 17.3 / (1.0)
97,070 97,070 19.5 / (1.3)
147,725 147,725 29.7 / (1.8)
171,585 171,585 34.5 / (2.6)
193,290 193,290 38.8 / (3.2)
70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,925 60,925 12.2 / (0.5)
76,095 76,095 15.2 / (0.7)
86,330 86,330 17.2 / (1.0)
132,105 132,105 26.5 / (1.4)
154,950 154,950 31.1 / (2.2)
174,705 174,705 35.1 / (2.7)
75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
80,115 80,115 16.0 / (0.8)
99,540 99,540 20.0 / (1.2)
111,795 111,795 22.4 / (1.6)
169,345 169,345 34.0 / (2.2)
195,820 195,820 39.3 / (3.3)
221,045 221,045 44.4 / (4.1)
72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
68,335 68,335 13.7 / (0.6)
85,350 85,350 17.0 / (0.9)
96,975 96,975 19.5 / (1.3)
147,720 147,720 29.7 / (1.8)
171,580 171,580 34.5 / (2.6)
193,610 193,610 38.9 / (3.2)
70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,860 60,860 12.2 / (0.5)
76,165 76,165 15.2 / (0.7)
86,755 86,755 17.4 / (1.1)
132,400 132,400 26.6 / (1.4)
155,630 155,630 31.5 / (2.2)
174,895 174,895 35.1 / (2.7)
NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
78,245 70,325
107,525 97,990
134,380 117,420
194,200 170,840
266,500 223,315
313,200 262,975
74,645 68,105
102,660 94,835
128,280 114,105
185,100 165,600
254,175 217,746
298,440 256,460
72,315 66,275
99,565 92,355
124,420 111,475
179,270 161,650
246,560 213,170
289,410 251,145
76,190 73,500
105,540 101,910
131,100 124,110
189,535 180,125
258,940 238,330
303,540 281,450
72,770 71,060
100,900 98,430
125,260 120,390
180,820 174,215
247,070 232,000
289,225 273,950
70,500 69,550
97,860 96,205
121,475 118,100
175,045 170,685
239,655 227,695
280,410 268,110
7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975
10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080
Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975
3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870
5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940
7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200
Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2)
3/ 9.7
3/ 14.6
3/ 14.6
3/ 19.8
3/ 24.3
3/ 24.3
AWS Coil: Rows/Face Area (ft2)
4/ 9.0
4/ 9.0
4/ 9.0
4/ 12.2
4/ 14.2
4/ 14.2
DX Water Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DW-AWS
096-DW-AWS
120-DW-AWS
180-DW-AWS
240-DW-AWS
312-DW-AWS
15.03 Kw 66,900 (19.6 Kw) 2-Stages
20.04 Kw 84,000 (24.6 Kw) 2-Stages
25.05 Kw 108,000 (31.6 Kw) 2-Stages
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 2-Stages 2-Stages 2-Stages
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control
(Standard)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
Cycling
Cycling
Cycling
Cycling
Cycling
Cycling
Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD
3/4" / (7.5 Cv) 24.2 Ft.
Standard Valve Type
1" / (14.0 Cv) 20.6 Ft.
--------
Optional Valve
1" / (14.0 Cv) 31.3 Ft.
1-1/4" / (14.0 Cv) 24.4 Ft.
1-1/2" / (14.0 Cv) 32.7 Ft.
3-way, 400 psig, Modulating (0-10 Vdc) - factory installed
1-1/2" / (14.0 Cv) 37.5 Ft.
--------
Please refer to page 3-10 for 2-way and higher pressure valve options.
Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,174
Scroll, (2) 3,042
Scroll, (2) 3,865
Scroll, (2) 6,315
Scroll, (2) 8,523
Scroll, (2) 10,289
DX Water Cooled Condenser Data - Based on 0% Glycol Solution Total Heat of Rej.
95,482 Btu/h
135,100 Btu/h
167,617 Btu/h
258,040 Btu/h
337,181 Btu/h
402,707 Btu/h
GPM @ 85°F EWT / 95°F LWT Unit Press. Drop (Ft. of H2O)
19.1 GPM 24.2 Ft.
27.0 GPM 20.6 Ft.
33.5 GPM 31.3 Ft.
51.6 GPM 24.4 Ft.
67.4 GPM 32.7 Ft.
80.5 GPM 37.5 Ft.
Condenser Type
Coaxial
Coaxial
Coaxial
Plate-Finned
Plate-Finned
Plate-Finned
Head Pressure Control Standard Control Optional Control
2-way, 150 psig Water Regulating Valves, (factory installed) Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options !
Connection Sizes - Copper DX Source Water In/Out
1-1/8" OD
1-3/8" OD
1-3/8" OD
2-1/8" OD
2-1/8" OD
2-1/8" OD
AWS Coil Source In/Out
1-1/8" OD
1-3/8" OD
1-3/8" OD
2-1/8" OD
2-1/8" OD
2-1/8" OD
Condensate Drain, (w/ pump)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
- DX Water Cooled w/ AWS (6 to 26 Ton Systems)
Compressors - Heat pump duty rated Scroll - HCFC R-22
Performance Data
"VFS" Model
4-15
DX Glycol Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS"
Performance Data
"VFS" Model
- DX Glycol Cooled w/ AWS (6 to 26 Ton Systems)
4-16
072-DG-AWS
096-DG-AWS
120-DG-AWS
180-DG-AWS
240-DG-AWS
312-DG-AWS
AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
84,570 77,200 17.0 / (0.9)
102,530 97,445 20.5 / (1.2)
114,540 109,855 23.0 / (1.7)
172,100 165,305 34.6 / (2.3)
198,605 192,190 40.0 / (3.4)
219,810 219,810 44.2 / (4.1)
72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
69,310 69,310 13.9 / (0.6)
86,055 86,055 17.3 / (1.0)
97,070 97,070 19.5 / (1.3)
147,725 147,725 29.7 / (1.8)
171,585 171,585 34.5 / (2.6)
193,290 193,290 38.8 / (3.2)
70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,925 60,925 12.2 / (0.5)
76,095 76,095 15.2 / (0.7)
86,330 86,330 17.2 / (1.0)
132,105 132,105 26.5 / (1.4)
154,950 154,950 31.1 / (2.2)
174,705 174,705 35.1 / (2.7)
75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
80,115 80,115 16.0 / (0.8)
99,540 99,540 20.0 / (1.2)
111,795 111,795 22.4 / (1.6)
169,345 169,345 34.0 / (2.2)
195,820 195,820 39.3 / (3.3)
221,045 221,045 44.4 / (4.1)
72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
68,335 68,335 13.7 / (0.6)
85,350 85,350 17.0 / (0.9)
96,975 96,975 19.5 / (1.3)
147,720 147,720 29.7 / (1.8)
171,580 171,580 34.5 / (2.6)
193,610 193,610 38.9 / (3.2)
70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi)
60,860 60,860 12.2 / (0.5)
76,165 76,165 15.2 / (0.7)
86,755 86,755 17.4 / (1.1)
132,400 132,400 26.6 / (1.4)
155,630 155,630 31.5 / (2.2)
174,895 174,895 35.1 / (2.7)
NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible
69,610 65,460
95,490 91,030
119,725 109,440
174,540 159,760
237,750 208,890
280,370 246,790
66,390 63,120
91,100 87,675
114,150 105,850
166,350 154,340
226,750 202,950
267,365 240,020
64,320 61,340
88,280 85,175
110,560 103,125
161,050 150,275
219,760 198,300
259,155 234,880
68,265 67,535
94,310 93,415
117,220 114,340
171,060 166,575
231,520 221,275
272,120 262,990
65,245 64,955
90,150 89,720
111,940 110,315
163,275 160,500
221,000 214,500
259,580 254,970
63,225 63,225
87,445 87,445
108,420 107,810
158,090 156,750
214,370 210,210
251,670 249,135
7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975
10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080
Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM
2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975
3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870
5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940
7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200
Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2)
3/ 9.7
3/ 14.6
3/ 14.6
3/ 19.8
3/ 24.3
3/ 24.3
AWS Coil: Rows/Face Area (ft2)
4/ 9.0
4/ 9.0
4/ 9.0
4/ 12.2
4/ 14.2
4/ 14.2
DX Glycol Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DG-AWS
096-DG-AWS
120-DG-AWS
180-DG-AWS
240-DG-AWS
312-DG-AWS
Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages
Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control
(Standard)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
4-15, (5.1)
Cycling
Cycling
Cycling
Cycling
Cycling
Cycling
Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD
3/4" / (7.5 Cv) 24.2 Ft.
Standard Valve Type
1" / (14.0 Cv) 20.6 Ft.
--------
Optional Valve
1" / (14.0 Cv) 31.3 Ft.
1-1/4" / (14.0 Cv) 24.4 Ft.
1-1/2" / (14.0 Cv) 32.7 Ft.
3-way, 400 psig, Modulating (0-10 Vdc) - factory installed
1-1/2" / (14.0 Cv) 37.5 Ft.
--------
Please refer to page 3-10 for 2-way and higher pressure valve options.
Type, (Qty.) Watts Input (ea.)
Scroll, (2) 2,960
Scroll, (2) 4,138
Scroll, (2) 5,278
Scroll, (2) 8,187
Scroll, (2) 11,011
Scroll, (2) 13,568
DX Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution Total Heat of Rej.
92,447 Btu/h
130,382 Btu/h
162,550 Btu/h
249,027 Btu/h
326,144 Btu/h
391,777 Btu/h
GPM @ 110°F EGT Unit Press. Drop (Ft. of H2O) Condenser Type
20.4 GPM 26.6 Ft. Coaxial
28.8 GPM 22.4 Ft. Coaxial
35.9 GPM 34.4 Ft. Coaxial
54.9 GPM 27.2 Ft. Plate-Finned
71.9 GPM 36.2 Ft. Plate-Finned
86.5 GPM 41.9 Ft. Plate-Finned
Head Pressure Control Standard Control Optional Control
2-way, 150 psig Water Regulating Valves, (factory installed) Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options !
Connection Sizes - Copper DX Source Water In/Out
1-1/8" OD
1-3/8" OD
1-3/8" OD
2-1/8" OD
2-1/8" OD
2-1/8" OD
AWS Coil Source In/Out
1-1/8" OD
1-3/8" OD
1-3/8" OD
2-1/8" OD
2-1/8" OD
2-1/8" OD
Condensate Drain, (w/ pump)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
7/8" OD, (1/2"OD)
Humidifier Inlet
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
1/4" OD
Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.)
20x25x4, (3)
20x25x4, (3)
20x25x4, (3)
20x25x4, (4)
20x25x4, (5)
20x25x4, (5)
Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
16x20x4, (2) 20x20x4, (2)
29x18x4, (4) ____
18x18x4, (6) 29x18x4, (1)
18x18x4, (6) 29x18x4, (1)
- DX Water Cooled w/ AWS (6 to 26 Ton Systems)
Compressors - Heat pump duty rated Scroll - HCFC R-22
Performance Data
"VFS" Model
4-17
Electrical Data - Index Electrical Data
CyberTWO Floor AC's FLA / MCA / MFS INDEX MODEL TYPE ......................................... page
DX - Compressorized Systems Single Compressor Systems:
- Index
• VFS-072/312-DAR, DW, & DG ........................................ 5-2
Free-Cooling & Alternate Water Source Alternate Water Source Systems: • VFS-072/312-D( )-AWS ................................................... 5-3 Free-Cooling Systems: • VFS-072/312-D( )-FC ...................................................... 5-3
Electrical Data Calculation Examples Example 1: • VFS-120-DAR-D .............................................................. 5-4 Example 2: • VFS-312-DW-U ............................................................... 5-4
<< Electrical Data Notes >> 1) Electrical Data is based on standard performance and component selection per Section 4 of this brochure. Please consult your local Sales Representative for "special" equipment electrical data. 2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's and External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data for this Option.
5-1
Electrical Data FLA (OEM rated) DAR
DW
DG
M CA
VFS-096-DAR, DW & DG
M FS
FLA (OEM rated) DAR
DW
DG
M CA
VFS-120-DAR, DW & DG
M FS
FLA (OEM rated) DAR
DW
DG
M CA
M FS
COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60
44.6
44.6
44.6
55.7
60
58.5
58.5
58.5
73.2
80
61.3
60.9
62.1
80.3
90
460/3/60
22.1
22.1
22.1
27.6
30
29.1
29.1
29.1
37.6
40
31.2
30.3
31.6
41.1
45
575/3/60
18.0
18.0
18.0
22.5
25
23.5
23.5
23.5
30.1
35
25.1
24.5
25.5
32.9
35
80.3
90
}
Standard Unit Data
COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 37.9
39.5
50.9
60
55.5
53.7
56.1
72.5
75
61.3
58.9
62.1
20.0
19.4
20.2
25.9
30
28.3
27.4
28.6
37.6
40
31.2
30.0
31.6
41.1
45
16.2
15.8
16.4
21.2
25
22.8
22.1
23.0
30.1
35
25.1
24.2
25.5
32.9
35
208/3/60
39.1
460/3/60 575/3/60
COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60
36.8
34.4
37.6
45.1
50
43.2
39.6
44.4
54.6
60
52.4
47.6
54.0
66.6
80
460/3/60
18.2
17.0
18.6
22.3
25
21.4
19.6
22.0
28.7
35
26.0
23.6
26.8
33.9
40
575/3/60
14.9
13.9
15.2
18.5
20
17.4
15.9
17.8
22.8
25
21.1
19.2
21.7
27.2
35
46.7
46.7
46.7
58.4
70 35
COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60
30.4
460/3/60
15.7
575/3/60
12.8
30.4
37.9
40
15.7
15.7
19.6
20
22.7
12.8
12.8
16.0
20
18.3
30.4
44.3
44.3
55.4
60
22.7
22.7
28.3
30
23.9
23.9
23.9
29.8
18.3
18.3
22.9
25
19.3
19.3
19.3
24.1
25
44.3
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60
22.6
20.2
23.4
30.9
40
29.0
25.4
30.2
40.4
50
38.2
33.4
39.8
52.4
70
460/3/60
11.8
10.6
12.2
15.9
20
15.0
13.2
15.6
22.3
30
19.6
17.2
20.4
27.5
35
575/3/60
9.7
8.7
10.0
13.3
15
12.2
10.7
12.6
17.6
20
15.9
14.0
16.5
22.0
25
VFS-180-DAR, DW & DG MODEL
FLA (OEM rated) DAR
DW
DG
M CA
VFS-240-DAR, DW & DG
M FS
FLA (OEM rated) DAR
DW
DG
M CA
VFS-312-DAR, DW & DG
M FS
FLA (OEM rated) DAR
DW
DG
M CA
M FS
COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60
77.4
73.0
79.6 101.5
125
95.6
91.3
97.0 129.6
150
118.3 113.7 119.7 160.1 175
460/3/60
38.6
36.9
39.2
51.7
60
48.4
46.3
49.1
63.0
70
59.6
57.3
60.3
82.4
90
575/3/60
31.2
29.7
32.0
40.2
50
38.6
36.7
39.2
48.7
50
47.5
45.6
48.0
65.5
70
118.3 113.7 119.7 160.1 175
COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60
76.4
73.0
77.5 101.5
125
95.6
91.3
97.0 129.6
150
460/3/60
38.6
36.9
39.1
51.7
60
48.4
46.3
49.1
63.0
70
59.6
57.3
60.3
82.4
90
575/3/60
31.2
29.7
31.6
40.2
45
38.6
36.7
39.2
48.7
50
47.5
45.6
48.0
65.5
70
COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60
77.4
70.6
79.6 100.6
125
90.6
82.0
93.4 122.9
150
102.4 93.2 105.2 142.8
175
460/3/60
38.2
34.8
39.2
50.9
60
45.2
41.0
46.6
57.2
70
51.0
46.4
52.4
74.5
90
575/3/60
31.1
28.1
32.0
38.5
50
35.9
32.1
37.1
42.6
50
40.6
37.0
41.8
59.2
70
COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60
63.2
56.4
65.4
86.4
100
460/3/60
31.8
28.4
32.8
44.5
60
575/3/60
25.9
22.9
26.8
33.3
45
67.8
79.2 108.7
150
88.2
85.5
91.0 128.6
175
38.8
34.6
40.2
50.8
70
44.6
43.2
46.0
68.1
90
30.7
26.9
31.9
37.4
50
35.4
34.4
36.6
54.0
70
76.4
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60
63.2
56.4
65.4
86.4
100
76.4
67.8
79.2 108.7
150
88.2
79.0
91.0 128.6
175
460/3/60
31.8
28.4
32.8
44.5
60
38.8
34.6
40.2
50.8
70
44.6
40.0
46.0
68.1
90
26.8
33.3
45
31.9
37.4
50
36.6
54.0
70
575/3/60
25.9
22.9
30.7
26.9
35.4
31.8
- DX Compressorized Systems
}
Standard Unit Data
Electrical Data
VFS-072-DAR, DW & DG MODEL
- DX Compressorized Systems
Table Legend: FLA
M C A M FS
FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size
Consult the Factory for electrical data for 50Hz power supply requirements.
5-2
Electrical Data Electrical Data
VFS-072-DAR/DW/DG-AWS/FC MODEL
FLA (OEM rated) DAR
DW
DG
M CA
M FS
- Free-Cooling / Alternate Water Source VFS-096-DAR/DW/DG-AWS/FC FLA (OEM rated) DAR
DW
DG
M CA
M FS
VFS-120--DAR/DW/DG-AWS/FC FLA (OEM rated) DAR
DW
DG
M CA
M FS
COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60
46.0
46.0
46.0
57.4
60
60.9
60.9
60.9
76.2
80
66.5
66.1
67.3
85.5
90
460/3/60
22.8
22.8
22.8
28.5
30
30.3
30.3
30.3
38.8
40
33.8
32.9
34.2
43.7
45
575/3/60
18.5
18.5
18.5
23.1
25
24.5
24.5
24.5
31.1
35
27.2
26.6
27.6
35.0
40
66.5
64.1
67.3
85.5
90 45 40
}
Standard Unit Data
}
Standard Unit Data
COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60
40.5
39.3
40.9
52.3
60 30
29.5
25
23.8
460/3/60
20.7
20.1
20.9
26.6
575/3/60
16.7
16.3
16.9
21.7
57.9
58.5
74.9
80
28.6
29.8
38.8
40
33.8
32.6
34.2
43.7
23.1
24.0
31.1
35
27.2
26.3
27.6
35.0
56.1
COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT )
- Free-Cooling / Alternate Water Source Systems
5-3
208/3/60
38.2
35.8
39.0
46.5
50
45.6
42.0
46.8
57.0
70
57.6
52.8
59.2
71.8
90
460/3/60
18.9
17.7
19.3
23.0
25
22.6
20.8
23.2
29.9
35
28.6
26.2
29.4
36.5
45
575/3/60
15.4
14.4
15.7
19.0
20
18.4
16.9
18.8
23.8
30
23.2
21.3
23.8
29.3
35
COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60
31.8
31.8
31.8
39.7
40
46.7
46.7
46.7
58.4
60
51.9
51.9
51.9
64.9
70
460/3/60
16.4
16.4
16.4
20.5
25
23.9
23.9
23.9
29.8
30
26.5
26.5
26.5
33.1
40
575/3/60
13.3
13.3
13.3
16.6
20
19.3
19.3
19.3
24.1
25
21.4
21.4
21.4
26.7
30
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60
24.0
21.6
24.8
32.3
40
31.4
27.8
32.6
42.8
50
43.4
38.6
45.0
57.6
70
460/3/60
12.5
11.3
12.9
16.6
20
16.2
14.4
16.8
23.5
30
22.2
19.8
23.0
30.1
40
575/3/60
10.2
9.2
10.5
13.8
15
13.2
11.7
13.6
18.6
25
18.0
16.1
18.6
24.1
30
VFS-180-DAR-AWS,DW/DG-FC MODEL
FLA (OEM rated) DAR
DW
DG
M CA
M FS
VFS-240-DAR-AWS,DW/DG-FC FLA (OEM rated) DAR
DW
DG
M CA
M FS
VFS-312-DAR-AWS,DW/DG-FC FLA (OEM rated) DAR
DW
DG
M CA
M FS
COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60
85.8
81.4
88.0 109.9
125
104.0 99.7 105.4 138.0
175
124.7 120.1 126.1 166.5
175
460/3/60
42.8
41.1
43.4
55.9
70
52.6
50.5
53.3
67.2
80
62.8
60.5
63.5
85.6
100
575/3/60
34.1
32.6
34.9
43.1
50
41.5
39.6
42.1
51.6
60
50.3
48.4
50.8
68.3
80
COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60
84.8
81.4
85.9 109.9
125
104.0 99.7 105.4 138.0
150
124.7 120.1 126.1 166.5
175
460/3/60
42.8
41.1
43.3
55.9
60
52.6
50.5
53.3
67.2
80
62.8
60.5
63.5
85.6
100
575/3/60
34.1
32.6
34.5
43.1
50
41.5
39.6
42.1
51.6
60
50.3
48.4
50.8
68.3
80
COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60
85.8
79.0
88.0 109.0
125
99.0
90.4 101.8 131.3
175
108.8 99.6 111.6 149.2
175
70
49.4
45.2
50.8
61.4
80
54.2
49.6
55.6
77.7
100
50
38.8
35.0
40.0
45.5
50
43.4
39.8
44.6
62.0
80
460/3/60
42.4
39.0
43.4
55.1
575/3/60
34.0
31.0
34.9
41.4
COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60
71.6
64.8
73.8
94.8
125
84.8
76.2
87.6 117.1 150
94.6
91.9
97.4 135.0
175
460/3/60
36.0
32.6
37.0
48.7
60
43.0
38.8
44.4
55.0
70
47.8
46.4
49.2
71.3
90
575/3/60
28.8
25.8
29.7
36.2
45
33.6
29.8
34.8
40.3
50
38.2
37.2
39.4
56.8
70
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60
71.6
64.8
73.8
94.8
125
84.8
76.2
87.6 117.1 150
94.6
85.4
97.4 135.0
175
460/3/60
36.0
32.6
37.0
48.7
60
43.0
38.8
44.4
55.0
70
47.8
43.2
49.2
71.3
90
575/3/60
28.8
25.8
29.7
36.2
45
33.6
29.8
34.8
40.3
50
38.2
34.6
39.4
56.8
70
Table Legend: FLA
M C A M FS
FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size
Consult the Factory for electrical data for 50Hz power supply requirements.
Electrical Data
- Calculation Examples Electrical Data Calculation
Example 1:
Example 2:
Suppose an application calls for a nominal 10 Ton CyberAiR model VFS-120-DAR-D with the following standard features:
Suppose an application calls for a nominal 26 Ton CyberAiR model VFS-312-DW-U system with the following features:
VFS-120-DAR-D
VFS-312-DW-U
-
-
460/3/60 Main Power Supply (both evap and cond) 15 kW Electric Reheat/Heat (2-stages), (Standard) 15 lb/hr Steam Humidifier, (Standard)
208/3/60 Main Power Supply Hot Gas Reheat in lieu of standard Electric Reheat No Humidifier
Solution:
Solution:
From DX Compressorized Electrical Data table page 5-2 for model VFS-120-DAR-( ) incorporating COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER:
From DX Compressorized Electrical Data table page 5-2 for model VFS-312-DW-( ) incorporating COOLING Only with or without Hot Gas Reheat (No Electric Reheat or Humidifier):
FLA (OEM Rated) MCA MFS
= = =
31.2 41.1 45
VFS-312-DW @ 208/3/60 w/ above options: FLA (OEM Rated) MCA MFS
Table Legends: FLA
M C A M FS
FLA = MCA = MFS =
Full Load Amps (OEM Rated Load Amps) Minimum Circuit Amps (wire size amps) Maximum Fuse Size
Consult the Factory for electrical data for 50 Hz power supply requirements.
= = =
79.0 128.6 175
- Calculation Examples
VFS-120-DAR-D @ 460/3/60 w/ above options:
Electrical Data
EXAMPLES -
5-4
Physical Data -
Standard "VFS" Configurations
Physical Data
"Index" (Drwg. #)
D
W
MODEL TYPE ............. page
H4
EVAPORATOR AIR OUTLET H2
Physical Data- Unit Weights H1
Unit Net Weights (lbs) Table ............................................. 6-2
- Index
Unit Weight Calculation Examples .................................. 6-2
Vertical Floor System Dimensions 6-10 Ton:
VFS-072/120-DAR, DW, DG-( )
(VF-01) "Down-Flow" Air Pattern Configuration ............... 6-3 (VF-02) "Up-Flow" Air Pattern Configuration .................... 6-4
EVAPORATOR AIR INLET
15-26 Ton: VFS-180/312-DAR, DW, DG & 180/312-( )
Up-Flow Air Patterns
(VF-03) "Down-Flow" Air Pattern Configuration ............... 6-5 (VF-04) "Up-Flow" Air Pattern Configuration .................... 6-6 6-10 Ton:
VFS-072/120-( )-FC/AWS-( )
(VF-07) "Down-Flow" Air Pattern Configuration ............... 6-7 (VF-08) "Up-Flow" Air Pattern Configuration .................... 6-8
EVAPORATOR AIR INLET D
15-26 Ton: VFS-180/312-( )-FC/AWS-( ):
W
(VF-09) "Down-Flow" Air Pattern Configuration ............... 6-9 (VF-10) "Up-Flow" Air Pattern Configuration .................... 6-10
Adjustable Floor Stand Dimensions
H1
(VF-11) VFS-072/120-DAR, DW & DG .............................. 6-11 (VF-12) VFS-072/120-( )-AWS/FC .................................... 6-11 (VF-13) VFS-180/312-( ) All Models ................................. 6-12
EVAPORATOR AIR OUTLET
Down-Flow Air Patterns
6-1
Physical Data -
Unit Weights (lbs.)
Physical Data
"VFS" EVAPORATORS
Approximate U nit Physical Weight (Standard Features Only Units, please see notes, Given in lbs.) Model
072-( )
096-( )
120-( )
180-( )
240-( )
312-( )
VFS-( )-DAR-D
1,025
1,125
1,170
1,455
1,615
1,740
VFS-( )-DW-D
1,060
1,195
1,240
1,545
1,720
1,840
VFS-( )-DG-D
1,060
1,195
1,240
1,545
1,720
1,840
890
950
980
1,125
1,245
1,265
VFS-( )-( )-FC-D
1,245
1,410
1,470
1,815
2,055
2,180
VFS-( )-( )-AWS-D
1,185
1,315
1,375
1,700
1,885
2,01 0
VFS-( )-C-D
Features/Options
Model Sizes 072/120 180/312
Deleting Features: Steam Humidifier Electric Reheat
Net Deduction - 25 lbs - 25 lbs - 20 lbs - 25 lbs
Adding Features: Hot Gas Reheat Hot Water Reheat Steam Reheat -30 Flooded Control Condensate Pump
+ + + + +
Net Addition 25 lbs + 35 lbs 25 lbs + 35 lbs 25 lbs + 35 lbs 100 lbs + 150 lbs 15 lbs + 15 lbs
Features/Options
Model Sizes 072/120 180/312
Adding Features: Upflow Air Pattern 2-way Plenum Box 3-way Plenum Box Floor Stand (12 " H)
+ + + +
Net Addition 35 lbs + 40 lbs 85 lbs + 200 lbs 85 lbs + 200 lbs 30 lbs + 100 lbs
Note 2: When substituting Hot Gas, Hot Water or Steam Reheat for standard Electric Reheat, DO NOT deduct the negative (-) weights shown above for Electric Reheat/Heat to the weights shown in the "VFS" EVAPORATOR weight table. The positive (+) weights shown above for Hot Gas, Hot Water or Steam Reheat should be added directly to the weights shown in the "VFS" EVAPORATOR weight table for these cases. (Please refer to Example-2 page 6-3.)
- Unit Weights (lbs.)
Note-1: Weights shown are for standard Evaporator units with standard Electric Reheat/ Heat and Steam Humidifier included. If these Standard features are deleted or Options are included, please add or delete the following approximate weights to the standard configuration weights shown in the adjacent table:
EXAMPLES - VFS Physical Weight (lbs.) Calculations Example-1:
Example-2:
Suppose an application calls for a nominal 10 Ton CyberAiR model VFS-120-DAR-D with the following features:
Suppose an application calls for a nominal 8 Ton CyberAiR model VFS-096-DW-U systems with the following features:
VFS-120-DAR-D
VFS-096-DW-U
-
-
15 kW Electric Reheat/Heat (2-stages), (Standard) 15 lb/hr Steam Humidifier, (Standard) Optional Condensate Pump (factory mounted) Optional 12" Floor Stand
Hot Gas Reheat in lieu of Standard Electric Reheat No Humidifier Optional Condensate Pump (factory mounted) Optional 3-way Plenum Discharge Box
Solution:
Solution:
From "VFS" EVAPORATORS Physical Weight Table page 62 for VFS-120-DAR-D:
From "VFS" EVAPORATORS Physical Weight Table page 62 for VFS-096-DW-D (std base unit):
VFS-120-DAR-D Steam Humidifier Electric Reheat Condensate Pump Floor Stand
= = = = =
1,170 lbs (base unit) Incl. in base unit wt. incl. in base unit wt. + 15 lbs + 30 lbs
VFS-120-DAR-D
=
1,215 lbs (approx.)
VFS-096-DW-D Up-Flow Air Pattern Hot Gas Reheat Delete Humidifier Condensate Pump 3-way Plenum Box
= = = = = =
1,195 lbs (base unit) + 35 lbs + 25 lbs - 25 lbs + 15 lbs + 85 lbs
VFS-096-DW-U
=
1,330 lbs (approx.)
6-2
6 to 10 Ton -
"Down-Flow" Air Pattern Systems
Dimensional Data
(VF-01) VFS-072 thru 120-DAR, DW, DG-D
DIMENSIONAL DATA Std CFM @ 0.5" esp
"Down-Flow" Vertical A/C ("Free-Return" or Optional "Ducted-Return")
MODEL “M” VFS-072-( )-D
15.62"
VFS-096 & 120-( )-D
18.62"
Note:
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes.
OPTIONAL 1.0" DUCT FLANGE CONNECTION
EVAPORATOR AIR INLET
68.0
- 6 to 10 Tons ("Down-Flow" Air Pattern Systems)
6-3
1.0 1.0
76.0
30.0
77.0 W/ OPTIONAL DUCT CONNECTION
4.0
20.5
17.0
M
70.0 (BASE)
72.0 (OVERALL)
32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR
FRONT / LEFT
Optional Floor Stand: See Page 6-11 (VF-11)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR PIPING / UTILITY CONNECTION SEE NOTE 1
REAR / RIGHT
6 to 10 Ton -
"Up-Flow" Air Pattern Systems
Note:
"Up-Flow" Vertical A/C ("Front Free-Return" or Opt. "Rear Ducted-Return")
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes.
70.0
(OPTIONAL) 2 OR 3 WAY PLENUM DISCHARGE BOX - FIELD INSTALLED
18.5
EVAPORATOR AIR OUTLET
STANDARD 1.0" DUCT FLANGE CONNECTION
68.0
EVAPORATOR AIR OUTLET
1.0 77.0 W/ STANDARD DUCT CONNECTION
1.0 30.0
6.0
76.0
36.3
72.0 (OVERALL)
33.0 (OVERALL)
OPTIONAL FILTER ACCESS
39.0 3.5 3.0
FRONT / LEFT
Optional Floor Stand: See Page 6-11 (VF-11)
REAR / RIGHT
("Up-Flow" Air Pattern Systems)
70.0 (BASE) 32.0 (BASE)
OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION)
EVAPORATOR AIR INLET
- 6 to 10 Tons
PIPING / UTILITY CONNECTIONS SEE NOTE 1
Dimensional Data
(VF-02) VFS-072 thru 120-DAR, DW, DG-U
6-4
15 to 26 Ton -
"Down-Flow" Air Pattern Systems
Dimensional Data
(VF-03) VFS-180 thru 312-DAR, DW, DG-D
DIMENSIONAL DATA
"Down-Flow" Vertical A/C ("Free-Return" or Optional "Ducted-Return")
St d CFM @ 0.5" es p MODEL
“ A”
“B”
“ C” “J”
“K”
“ M”
VFS-180-( )-D
90.0"
88.0"
86.0"
17.5"
44.63"
15.62"
VFS-240 & 312-( )-D
102.0"
100.0"
98.0"
19.0"
51.5"
18.62"
Note:
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes.
OPTIONAL 1.0" DUCT FLANGE CONNECTION
EVAPORATOR AIR INLET
C
- 15 to 26 Tons ("Down-Flow" Air Pattern Systems)
6-5
1.0
76.0
77.0 W/ OPTIONAL DUCT CONNECTION
1.0
4.0
30.0
20.5 J K M
M
B (BASE)
A (OVERALL)
32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR
FRONT / LEFT
Optional Floor Stand: See Page 6-12 (VF-13)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR
PIPING / UTILITY CONNECTIONS SEE NOTE 1
REAR / RIGHT
15 to 26 Ton -
"Up-Flow" Air Pattern Systems
"Up-Flow" Vertical A/C ("Front Free-Return" or Opt. "Rear Ducted-Return")
DIMENSIONAL DATA MODEL
“ A”
“B ”
“ C”
“ H”
VFS-180-( )-U
90.0"
88.0"
86.0"
58.5"
VFS-240 & 312-( )-U
102.0"
100.0"
98.0"
73.5"
Note:
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes.
B
OPTIONAL 2 OR 3 WAY PLENUM DISCHARGE BOX - FIELD INSTALLED
18.5
STANDARD 1.0" DUCT FLANGE CONNECTION
EVAPORATOR AIR OUTLET
PIPING / UTILITY CONNECTIONS SEE NOTE 1
Dimensional Data
(VF-04) VFS-180 thru 312-DAR, DW, DG-U
EVAPORATOR AIR OUTLET
C
1.0
6.0
1.0 30.0 36.3
EVAPORATOR AIR INLET
A (OVERALL)
32.0 (BASE)
33.0 (OVERALL)
OPTIONAL FILTER ACCESS
3.5
3.0
FRONT / LEFT
Optional Floor Stand: See Page 6-12 (VF-13)
REAR / RIGHT
OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION)
("Up-Flow" Air Pattern Systems)
H
(BASE)
- 15 to 26 Tons
77.0 W/ STANDARD DUCT CONNECTION 76.0
6-6
Free-Cooling / Alternate Water Source -
6 to 10 Ton, "Down-Flow"
Dimensional Data
DIMENSIONAL DATA
(VF-07) VFS-072 thru 120-( )-FC/AWS-D
Std CFM @ 0.5" esp
"Down-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Free-Return" or Opt. "Ducted-Return")
MODEL “M” VFS-072-( )-FC/AWS-D
15.62"
VFS-096 & 120-( )-FC/AWS-D
18.62"
Note:
STANDARD FILTER BOX FIELD INSTALLED
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes.
OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET
80.0
12.0
1.0
89.0 W/ OPTIONAL DUCT CONNECTION
1.0
30.0 88.0 76.0
- 6 to 10 Tons (FC/AWS "Down-Flow" Air Pattern Systems)
6-7
P
N
17.0
M
82.0 (BASE)
84.0 (OVERALL)
32.0 (BASE)
33.0 (OVERALL)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR
FRONT / LEFT
Optional Floor Stand: See Page 6-11 (VF-12)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR PIPING / UTILITY CONNECTION SEE NOTE 1
REAR / RIGHT
Free-Cooling / Alternate Water Source -
6 to 10 Ton, "Up-Flow"
(1) Please refer to Section 4 for piping connection sizes.
"Up-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Front Free-Return" or Opt. "Rear Ducted-Return")
(2) 3.5" high shipping guards, 79.5" Total unit rigging height (76.0" unit + 3.5" shipping guard).
STANDARD HEATER ACCESS SKIRT - FIELD INSTALLED STANDARD 1.0" DUCT FLANGE CONNECTION
11.0
80.0
SEE NOTE 2 1.0 SEE NOTE 2
1.0
30.0
PIPING / UTILITY CONNECTIONS SEE NOTE 1
EVAPORATOR AIR OUTLET
Dimensional Data
Notes: (Connection Sizes)
(VF-08) VFS-072 thru 120-( )-FC/AWS-U
SEE NOTE 2 EVAPORATOR AIR OUTLET
SEE NOTE 2
SEE NOTE 2
76.0
SEE NOTE 2 6.0
SEE NOTE 2
36.3
84.0 (OVERALL)
OPTIONAL FILTER ACCESS
39.0
32.0 (BASE)
33.0 (OVERALL)
3.5 3.0
REAR / RIGHT
FRONT / LEFT
2 or 3-Way, Top Discharge Plenum Box: (Optional) (VFS-072/120-( )-FC/AWS-U Upflow Models) 82.0"
Optional Floor Stand: See Page 6-11 (VF-12) 29.0 54.2 79.0
SEE NOTE 1
18.5" 20.0
24.0
30.6
Note: Top Discharge Plenum Box shall be field installed. Heater Access Skirt shall not be provided with Plenum Box option.
45.0
1.38
SEE NOTE 1
(FC/AWS "Up-Flow" Air Pattern Systems)
OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION)
EVAPORATOR AIR INLET 82.0 (BASE)
- 6 to 10 Tons
77.0 W/ STANDARD DUCT CONNECTION
SEE NOTE 2
6-8
Free-Cooling / Alternate Water Source -
Dimensional Data
(VF-09) VFS-180 thru 312-( )-FC/AWS-D
15 to 26 Ton, "Down-Flow"
DIMENSIONAL DATA Std CFM @ 0.5" esp
"Down-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Free-Return" or Opt. "Ducted-Return")
MODEL
“A”
“B ”
“C ” “J ”
“K ”
“M”
VFS-180-( )-FC/AWS-D
102.0"
100.0"
98.0"
17.5"
44.63"
15.62"
VFS-240 & 312-( )-FC/AWS-D
114.0"
112.0"
110.0"
19.0"
51.5"
18.62"
Note:
(Connection Sizes)
(1) Please refer to Section 4 for piping connection sizes. STANDARD FILTER BOX FIELD INSTALLED OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET
12.0
C
89.0 W/ OPTIONAL DUCT CONNECTION 1.0
88.0
- 15 to 26 Tons
1.0
(FC/AWS "Down-Flow" Air Pattern Systems)
6-9
4.0
76.0 30.0
20.5 J K M
M
B (BASE)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR
A (OVERALL)
32.0 (BASE) 33.0 (OVERALL)
EVAPORATOR AIR OUTLET INTO RAISED FLOOR
FRONT / LEFT
Optional Floor Stand: See Page 6-12 (VF-13)
PIPING / UTILITY CONNECTIONS SEE NOTE 1
REAR / RIGHT
Free-Cooling / Alternate Water Source -
15 to 26 Ton, "Up-Flow"
DIM ENSIONAL DATA MODEL
"Up-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Front Free-Return" or Opt. "Rear Ducted-Return")
“A”
“B ”
“ C”
“ H”
VFS-180-( )-FC/AWS-U
102.0"
100.0"
98.0"
58.5"
VFS-240 & 312-( )-FC/AWS-U
114.0"
112.0"
110.0"
73.5"
Notes: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. (2) 3.5" high shipping guards, 79.5" total unit rigging height (76.0" unit + 3.5" shipping guard).
STANDARD HEATER ACCESS SKIRT - FIELD INSTALLED STANDARD 1.0" DUCT FLANGE CONNECTION
11.0
B C
SEE NOTE 2
Dimensional Data
(VF-10) VFS-180 thru 312-( )-FC/AWS-U
SEE NOTE 2
1.0 1.0
EVAPORATOR AIR OUTLET
EVAPORATOR AIR OUTLET
30.0
SEE NOTE 2
SEE NOTE 2
77.0 W/ STANDARD DUCT CONNECTION 76.0
SEE NOTE 2
6.0
SEE NOTE 2 SEE NOTE 2
36.25
EVAPORATOR AIR INLET B (BASE)
32.0 (BASE) 33.0 (OVERALL)
H OPTIONAL FILTER ACCESS
3.5
OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION)
3.0
FRONT / LEFT
2 or 3-Way, Top Discharge Plenum Box: (Optional) (VFS-180/312-( )-FC/AWS-U Upflow Models) B
18.5"
Note: Top Discharge Plenum Box shall be field installed. Heater Access Skirt shall not be provided with Plenum Box option.
REAR / RIGHT
Optional Floor Stand: See Page 6-12 (VF-13)
(FC/AWS "Up-Flow" Air Pattern Systems)
A (OVERALL)
- 15 to 26 Tons
SEE NOTE 2 PIPING / UTILITY CONNECTIONS SEE NOTE 1
6-10
Floor Stand Options Dimensional Data
(VF-11)
Models VFS-072/120-( )
VFS-072/120-DAR, DW & DG: (72.0" Wide Cabinet)
(VF-11a) w/o Turning Vanes:
(VF-11b) with Optional Turning Vanes: 29.0
29.0
42.2 67.0
67.0 SEE NOTE 1
SEE NOTE 1
20.0
A
A
1.38
SEE NOTE 1
SEE NOTE 1
- Floor Stand Options (6 to 10 Ton Systems)
Front/Right
(VF-12)
Front/Right
VFS-072/120-( )-AWS/FC: (84.0" Wide Cabinet)
(VF-12a) w/o Turning Vanes:
(VF-12b) with Optional Turning Vanes:
29.0
29.0
6-11
54.2
79.0
SEE NOTE 1
79.0 SEE NOTE 1
20.0 A
24.0
30.6
30.6 45.0
SEE NOTE 1
Front/Right
45.0
Front/Right
Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height
Adjustable Height
Turning Vane Availability
Minimum Maximum
4.0" (Upflow Units Only)
3.5"
4.5"
Not Available
6.0"
5.0"
7.0"
Not Available
12.0"
11.0"
15.0"
Optional
15.0"
14.0"
18.0"
Optional
18.0"
17.0"
21.0"
Optional
24.0"
23.0"
26.0"
Optional
Note-1: Only required for Nominal 24" High Floor Stands.
1.38
SEE NOTE 1
Floor Stand Options -
VFS-180/312-( ) All Models: (All Cabinets - see tables below)
(VF-13a) w/o Turning Vanes:
(VF-13b) with Optional Turning Vanes:
C
C
SEE NOTE 1
D
B
F B SEE NOTE 1 20.0
20.0
A I
Dimensional Data
(VF-13)
Models VFS-180/312-( )
I
SEE NOTE 1
1.38 J
Front/Right
Front/Right
Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height
Adjustable Height
Turning Vane Availability
Minimum Maximum
4.0" (Upflow Units Only)
3.5"
4.5"
Not Available
6.0"
5.0"
7.0"
Not Available
12.0"
11.0"
15.0"
Optional
15.0"
14.0"
18.0"
Optional
18.0"
17.0"
21.0"
Optional
24.0"
23.0"
26.0"
Optional
Note-1: Only required for Nominal 24" High Floor Stands.
DIMENSIONAL DATA- Floor Stands (15 to 26 Ton Systems) U N IT MOD EL
“ A”
“ B”
" C"
" D"
“ F”
VFS-180-D AR , D W, D G, C -( )
se e above
85.0"
29.0"
34.00"
61.13"
44.63"
37.00"
se e above
97.0"
29.0"
37.65"
73.13"
56.63"
37.0"0
se e above
97.0"
29.0"
37.65"
70.15"
52.50"
41.13"
se e above
109.0"
29.0"
39.81"
82.15"
64.50"
41.13"
(90" Wi d e C ab i n et )
VFS-180-( )-FC /AWS-( ) (102" Wi d e C ab i n et )
VFS-240/312-( )-D AR , D W, D G, C -( ) (102" Wi d e C ab i n et )
VFS-240/312-( )-FC /AWS-( ) (114" Wi d e C ab i n et )
“ I”
“ J”
SEE NOTE 1
- Floor Stand Options (15 to 26 Ton Systems)
J
6-12
Globally close to you. Stulz-ATS, located in Frederick, MD USA, is part of The STULZ Group with headquarters in Hamburg, Germany and production facilities world wide. Our network of manufacturer’s representatives and sales partners span the globe, providing innovative solutions to your unique environmental control needs.
North American Headquarters: 1572 Tilco Drive, Frederick, Maryland 21704, USA
www.stulz-ats.com
Phone: (301) 620-2033, Facsimile: (301) 662-5487, Email:
[email protected]
Worldwide: World Headquarters: STULZ GmbH Holsteiner Chaussee 283, D-22457 Hamburg Tel: +49(40)55 85 269; Fax: +49(40)55 85 308, email:
[email protected] www.stulz.com
Copyright 02/06 - Form L-03-C-104 Specifications are subject to change without notice