Systems - Stulz Usa

   EMBED


Share

Transcript

SATS The Natural Alternative Engineering Manual From 6 to 26 Tons (60 Hz Data) Vertical Floor Mounted Precision Air Conditioners Dual Compressor DX & Chilled Water Systems! Stulz Air Technology Systems, Inc. (SATS) Founded in 1947, STULZ acquired Air Technology Systems (ATS) in March 2001, naming the new company Stulz Air Technology Systems, Inc. (SATS). SATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class "island" manufacturing processes in a modern, 150,000 ft2 facility. The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the precision air conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service. ISO-9001:2001 Quality Registered Stulz-ATS is committed to satisfying customer expectations by meeting and exceeding customer requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We continually measure our performance to improve the effectiveness of our quality management system. Precision A/C Applications SATS is dedicated to the manufacturing of supplemental and precision air conditioning products. With an extensive installation base, SATS has earned a solid reputation as a quality supplier and leader in its field. 1-1 CyberTWO™ vertical, floor mounted air conditioning units provide precision temperature and/or humidity control for computer rooms and other critical areas where continuous 24 hrs/day, 365 days/yr operation is required. Designed for front only access, CyberTWO systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications. Typical applications include: INDUSTRIES:          Telecommunications Internet / Web Hosting Financial / Banking Insurance Legal Services Airlines / Mass Transit Entertainment Government Colleges / Universities APPLICATIONS:          Computer / LAN Rooms Telecommunications Rooms Co-location Centers ISP (Internet Service Providers) ASP (Applications Service Providers) Copier / Fax Rooms ATM Bank Centers Hospital Operating & Isolation Rooms Laboratories Table of Contents SECTION - 1 Introduction to SATS .........................................................1-1 Table of Contents .............................................................. 1-2 SECTION - 2 CyberTWO SYSTEMS: Outstanding Advantages ................................................... 2-1 User Oriented Features & Options ................................... 2-2 Available Configurations ................................................ 2-3/4 MODEL NOMENCLATURE: Nomenclature Chart ......................................................... 2-5 Model Nomenclature Specifications .............................. 2-6/7 SECTION - 3 GUIDE SPECIFICATIONS: Standard Features Index ................................................... 3-1 Standard Guide Specifications ......................................3-2/4 SECTION - 6 DIMENSIONAL / INSTALLATION DRAWINGS: Dimensional Drawing Index ............................................. 6-1 Physical Data - Unit Weights (lbs) .................................... 6-2 CyberTWO "VFS" Systems: 6 to 10 Ton, Down-Flow Systems ..................................... 6-3 6 to 10 Ton, Up-Flow Systems .......................................... 6-4 15 to 26 Ton, Down-Flow Systems ................................... 6-5 15 to 26 Ton, Up-Flow Systems ........................................ 6-6 Free-Cool/Alternate Water Source Systems: 6 to 10 Ton, Down-Flow Systems ..................................... 6-7 6 to 10 Ton, Up-Flow Systems .......................................... 6-8 15 to 26 Ton, Down-Flow Systems ................................... 6-9 15 to 26 Ton, Up-Flow Systems ..................................... 6-10 Floor Stand Options: ................................................ 6-11-12 Optional Features Index ................................................... 3-5 Microprocessor Controls Specifications ....................... 3-6/7 Optional Features Guide Specifications ..................... 3-8/12 SECTION - 4 PERFORMANCE / CAPACITY SPECIFICATIONS: Performance Specifications Index .................................... 4-1 DX - Air Cooled Systems ................................................ 4-2/3 DX - Water Cooled Systems .......................................... 4-4/5 DX - Glycol Cooled Systems .......................................... 4-6/7 Free-Cooling & Alternate Water Source Systems ...... 4-8/17 SECTION - 5 ELECTRICAL DATA: (FLA / MCA / MFS) Electrical Data Index ......................................................... 5-1 DX - Compressorized Systems: Air Cooled, Split Systems ................................................. 5-2 Water Cooled Systems ..................................................... 5-2 Glycol Cooled Systems .................................................... 5-2 CyberTWO™ VFS Free-Cooling & Alternate Water Source: DX with Free-Cooling ........................................................ 5-3 DX with Alternate Water Source ........................................ 5-3 1-2 CyberTWO Systems SUPPLY AIR OUTLET CyberTWO systems are designed to provide precision temperature and humidity control 24 hrs/day, 365 days/yr. A wide variety of cabinet configurations and options make SATS products the most flexible precision air conditioning line available in the industry. CyberTWO systems require only front service access and are easily installed sideby-side, tucked into a corner or between cabinets. The CyberTWO Series units are especially adaptable to raised floors and are available in both down-flow and up-flow air pattern configurations. RETURN AIR INLET Down-Flow Air Patterns Up-Flow Air Patterns CyberTWO Systems Offer Outstanding Advantages Flexibility Microprocessor Controls A wide variety of cooling methods are available to meet your unique requirements. Precision temperature and/or humidity control with unrivaled, user-friendly C-6000 series controls, offer a wide range of functions and alarms. • DX - Air Cooled • DX - Water Cooled • DX - Glycol Cooled (w/ Remote Drycoolers & Pump Packages • Free-Cooling Systems • Alternate Water Source Systems • • ... and more! • Chilled Water Air Handling Units Versatility • Plenum Box Spot Cooling & Ducted systems • Self-Contained & Split systems 100% Front Service Access Designed for 100% Front Only Access, CyberTWO systems require minimal floor space and can be installed side-by-side, tucked into a corner or between cabinets. Wide Size Range DX systems from 6 to 26 ton capacity in six incremental sizes and Chilled Water systems from 6 to 40 ton capacity in seven incremental sizes. Non-Proprietary Parts CyberTWO systems incorporate nonproprietary components where possible. Most major HVAC, refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components. 2-1 Featuring: BMS Connection Unit Sequencing Complete Temperature & Humidity Control • Electrode Canister Steam Humidification • Dehumidification Mode with - Electric Reheat/Heat - Optional Hot Gas Reheat (Energy $aver) - Optional Hot Water & Steam Reheat/Heat Capacity Modulation Options • • • • Dual / 2-Stage Scroll Compressor Systems Hot Gas Bypass Systems Multi-stage Reheat/Heat Modulating Chilled Water Valves Code (UL / CSA) Conformance L LISTED NRT UL 1995 C R - NYC MEA Approved (MEA-163-88-E) - CSA Compliance - MET-C Recognized by Standards Council of Canada User Oriented Features & Options Scroll Compressors CyberTWO DX A/C's incorporate Dual Scroll Compressor Technology. Scroll Compressors provide higher efficiency, higher reliability and lower sound power than other compressor technologies. Year Round Operation Option offerings available with CyberTWO air conditioners allow for year-round, 24 hours-a-day system operation in any environment in the world: Low Ambient Control (DX - Air Cooled) • -20°F Variable Fan Speed • -30°F Flooded Head Pressure Modular Motor Controllers CyberTWO systems incorporate modular motor controllers with motor circuit breakers in lieu of inconvenient replaceable fuses. Quiet Operation Low sound power Scroll compressors coupled with low RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation. Warranty - 2 Year Parts Standard - Optional 5 Year Compressor Selected Standard Features: 100% Front Access (Saves Up-To 18 ft2 Floor Space) • • • • • • • • • • • Main Power Circuit Breaker Modular Motor Controllers (w/ motor circuit breakers) Acoustical / Thermal Insulation Aluminum Fin / Copper Tube Coils Thermal Expansion Valves Refrigerant Sight Glasses Refrigerant Filter / Drier Strainers Liquid Refrigerant Reclaim Valves Insulated Stainless Steel Condensate Drain Pan High / Low Refrigerant Pressure Switches Rotolock Compressor Service Valves Other Available Options: CyberTWO (Model VFS-240-DAR-D Shown) - 2 & 3-way Grilled Plenum Boxes Floor Stands (with & without turning vanes, seismic) Condensate Pumps Smoke Detectors Firestats Water Leak Detectors Special High Efficiency Filtration (4" Filters up-to 60% Dust Spot) High Pressure DX - Water/Glycol Cooled Condenser Regulating Valves Free-Cooling & Alternate Water Source Units Drycoolers & Pump Packages Many more options available (see page 3-5) ! 2-2 Application Dependent Configuration Choices AIR COOLED SYSTEMS WATER COOLED SYSTEMS SELF-CONTAINED WATER COOLED SYSTEMS SPLIT AIR COOLED Evaporator Air Inlet OFF Evaporator Air Inlet ON OFF ON WCS-( ) (Remote Outdoor Propeller Condenser) Evaporator Air Outlet VFS-072 thru 312-DW-( ) VFS-072 thru 312-DAR-( ) Remote Water Source (supplied by others) Evaporator Air Outlet (Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern) (Dual Compressors - Split Evaporator) (Up-Flow or Down-Flow Air Pattern) GLYCOL COOLED SYSTEMS FREE-COOLING SYSTEMS SELF-CONTAINED GLYCOL COOLED SYSTEMS Evaporator Air Inlet Evaporator Air Inlet ON OFF ON OFF F( )S-( ) / GPS-( ) (Outdoor Propeller Drycooler & Pump Package) Evaporator Air Outlet Evaporator Air Outlet VFS-072 thru 312-DW/DG-FC-( ) VFS-072 thru 312-DG-( ) (Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern) (Dual Compressors, Self-Contained) (Up-Flow or Down-Flow Air Pattern) ALTERNATE WATER SOURCE SYSTEMS Evaporator Air Inlet WCS-( ) "At Night" (Remote DX Heat Rejection Source) Evaporator Air Outlet Remote Liquid Chiller "By Day" VFS-072 thru 312-DW/DG/DAR-AWS-( ) (supplied by others) (Dual Compressors - Evaporator) (Up-Flow or Down-Flow Air Pattern) 2-3 F( )S-( ) / GPS-( ) (Outdoor Propeller Drycooler & Pump Package) Flexible Air Pattern Configuration Choices Down-Flow Systems: Top "Ducted" Return with: Top "Free" Return with: RETURN AIR INLET 1 2 SUPPLY AIR OUTLET Bottom Discharge Into Raised Floor Floor Stand (Optional) Bottom Discharge Into Raised Floor Up-Flow Systems: Top Discharge Through 2 or 3-way Grilled Plenum Box with: SUPPLY AIR OUTLET 4 3 EVAPORATOR AIR OUTLET EVAPORATOR AIR INLET RETURN AIR INLET Front "Free" Return Rear "Ducted" Return Top "Ducted" Discharge with: SUPPLY AIR OUTLET SUPPLY AIR OUTLET 5 6 RETURN AIR INLET Front "Free" Return RETURN AIR INLET Rear "Ducted" Return 2-4 Model Nomenclature - "VFS" Systems Nomenclature VFS-240-DG-FC-U COS MCS OHS VFS FCS GPS WCS F( )S D U = CyberONE System = Modular Cyber System = OverHead System = Vertical Floor System = Floor Console System = Glycol Pump System = Air Cooled Condenser = Air Cooled Fluid Cooler AWS FC = Down-Flow Air Pattern = Up-Flow Air Pattern = "Alternate Water Source" = "Free-Cooling" Nominal Capacity in 1,000's of BTU/H - Model Nomenclature Chart AHU AR AS CAA D( ) G GRC P V F LGA RCU-I S W = = = = = = = = = = = = Air Handling Unit Remote (Split) Air Cooled Self-Contained Air Cooled Indoor Centrifugal Condenser Dual (Two) Circuit or Pump System Glycol Cooled Glycol Cooled Remote Condensing Unit Outdoor Propeller Condenser for 0°F Outdoor Propeller Condenser for -20°F Outdoor Propeller Condenser for -30°F Outdoor Propeller Glycol Drycooler Indoor Centrifugal Remote Condensing Unit = Single Pump = Water Cooled EVAPORATOR AIR OUTLET EVAPORATOR AIR INLET VFS-( )-( )-D VFS-( )-( )-U Down-Flow Air Patterns Up-Flow Air Patterns CyberTWO - Dual Circuit & Chilled Water Floor A/C's 2-5 Model Nomenclature Specifications DX - EVAPORATOR SECTIONS Air Cooled Remote Evaporator (Models VFS-( )-DAR) The system shall be a remote (split) air cooled, floor mounted precision air conditioner evaporator. The evaporator section shall house, as a minimum, the evaporator coil, expansion valve, compressor, evaporator blower/ motor and associated electrical and refrigeration components. The evaporator system shall require only a single point main power supply connection; and the system shall ship from the SATS factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging. Remote Outdoor Propeller (Models WCS-( )-( )) The system shall be a remote outdoor air cooled condenser with direct-driven propeller fan(s). The condenser cabinet shall house the condenser coil, fan(s) and fan motor(s) and Nema 3R condenser motor control/enabling box. The compressor(s) shall be located with the VFS-( )-AR evaporator section. The condenser shall be sized to provide the total heat of rejection of the system at a 95°F DB ambient temperature for the corresponding CyberTWO model VFS-( )-AR evaporator. WCS-( )-V: Low Ambient Head Pressure Control down to a minimum ambient temperature of -20°F via Variable Fan Speed Head Pressure Control. WCS-( )-F: Low Ambient Head Pressure Control down to a minimum ambient temperature of -30°F via Flooded Head Pressure Control. DX - WATER COOLED SYSTEMS Integral Self-Contained (Models VFS-( )-DW) The system shall be a dual compressor, self-contained, floor mounted precision air conditioner to include integral water cooled condensers with factory installed head pressure water regulating control valves. Condenser (source) water shall be provided by a cooling tower or some other remote water source. The system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Water Regulating Valves: Head pressure shall be automatically controlled by factory installed 2-way water regulating valves rated for 150 psig w.w.p. (Note: 3-way and high pressure valves are optionally available, page 3-9.) DX - GLYCOL COOLED SYSTEMS Integral Self-Contained (Models VFS-( )-DG) The system shall be a dual compressor, self-contained, floor mounted precision air conditioner to include integral glycol cooled condensers with factory installed head pressure glycol regulating control valves. Condenser (source) glycol solution shall be provided via a CyberAiR model GPS-( )-( ) / F( )S-( ) remote glycol pump package and drycooler system. The evaporator system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. Glycol Regulating Valves: Head pressure shall be automatically controlled by factory installed 2-way glycol regulating valves rated for 150 psig w.w.p. (Note: 3-way and high pressure valves are optionally available, page 3-9.) GLYCOL PUMP PACKAGE & REMOTE DRYCOOLERS (Single Pump Packages) (Models GPS-( )-S) The system shall be a single pump package designed to provide the total required glycol condenser coolant flow rate at the total rated system pressure drop. The pump packaged shall include, as a minimum; pump, starter/ contactor, main power non-fused disconnect switch, 24 Volt control transformer, A/C unit and drycooler interconnect contacts. - CyberTWO Systems The VFS-( )-DAR evaporator section shall be located at some distance from its corresponding SATS model WCS-( ) outdoor air cooled condenser. Note: The outdoor propeller condensers are model designated as follows: Nomenclature "CyberTWO" Model Nomenclature Guide Specifications (Dual Pump Packages) (Models GPS-( )-D) The system shall be a dual (two), redundant, pump package designed to provide the total required glycol condenser coolant flow rate at the total rated system pressure drop. A coolant sensing flow switch shall be provided for automatic switchover from primary to backup pump operation in the event of a loss of coolant flow. The dual pump package shall include, as a minimum; quantity two (2) equal horsepower pumps, pump starters/contactors, main power nonfused disconnect switch, 24 Volt control transformer, A/C unit and drycooler interconnect contacts. 2-6 Model Nomenclature Specifications Nomenclature Remote Drycooler (Models WCS-( )-( )) The system shall be a remote outdoor air cooled glycol drycooler (fluid-cooler) sized to provide the total heat of rejection of the system glycol condenser source solution at a ___°F DB ambient temperature. The drycooler shall include, as a minimum; glycol coil, direct-driven propeller fan(s), fan motor starters/ contactors, main power non-fused disconnect switch, drycooler fan cycling control aquastat(s) and field installed 15 gallon expansion tank and airtrol fitting. - CyberTWO Systems DX COOLING with "Assist-Mode" FREE-COOLING SYTEMS (Water/Glycol Economizer Coil) The evaporator system shall require only single point main power supply connection, and the system shall ship from the SATS factory with a full operating refrigerant (R-22) charge. ALTERNATE WATER SOURCE (Chilled Water by "Day" and DX-Backup by "Night"!) (Models VFS-( )-DAR, DW, DG-AWS) The system shall be a dual compressor floor mounted precision air conditioner to include a combination DX refrigeration cycle and Alternate Water Source cooling cycle. The Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply, when available, as the primary cooling cycle with DX refrigerant cooling as a backup. (Models VFS-( )-DW/DG-FC) The system shall be a self-contained, floor mounted precision air conditioner to include a combination integral, dual compressor, DX Water/ Glycol Cooled refrigeration cycle and Free-Cooling economizer cycle. The Free-Cooling cycle shall be provided to take advantage of low ambient air temperature conditions to provide compressor-less cooling. Condenser (source) and free-cooling coil glycol solution shall be provided via a CyberAiR model GPS-( )-( ) / WCS-( )-( ) remote glycol pump package and drycooler system. During free-cooling mode, the drycooler capacity shall be increased by reversing the typical drycooler fan(s) cycling sequence of operation to provide maximum cooling effect for the glycol coolant solution. CyberTWO (Model VFS-120-DAR-D Shown) 2-7 "VFS" Series "VFS" Model VFS-072/312-( ) SELECTED STANDARD FEATURES: TEMPERATURE CONTROL • • • • 2-Stage Cooling Mode 2-Stage Electric Reheating / Heating Cooling &/or Heating Only (No Humidity Control) 3-Stage Electric Reheating / Heating Standard Standard Optional Optional HUMIDITY CONTROL • Electrode Canister Steam Humidifier • Dehumidification Mode with 2-Stage Electric Reheat Standard Standard CONTROLS • C-6000 Graphic Microprocessor w/ Alarms • MIB Gateway BMS/LAN Connection Standard Optional CABINET • • • • Powder Coat Painted Galvanneal Steel Insulated Stainless Steel Condensate Drain Pan 2 lb Density Thermal & Sound Insulation Floor Stand (Varying heights available - see page 3-10 for details.) Standard Standard Standard Optional • 4", 30% Dust Spot Efficient Pleated Filters • 4", 60% Dust Spot Efficient Pleated Filters • 2 or 3-way Plenum Box (Up-Flow Units) Standard Optional Optional DX-REFRIGERATION CIRCUIT • • • • • • • HCFC R22 Refrigerant Dual Scroll Compressors w/ Rotolock Service Valves High Efficiency, Aluminum Fin / Copper Tube Coils Thermal Expansion Valves Refrigerant Sight Glasses & Filter/Drier Strainers Refrigerant Service Valves HFC R407C Refrigerant Standard Standard Standard Standard Standard Standard Optional BLOWERS/MOTORS • Belt-Drive Evaporator Blower(s) / Motor • Low RPM DWDI Centrifugal Blower(s) Standard Standard ELECTRICAL • 3-Phase Power Supply • Multi-Voltage Control Transformer (24V Class 2) • Modular Motor Controllers with Integral Circuit Breakers ----------- See Electrical Tables Section 5 ----------Standard Standard SAFETY FEATURES • • • • C-6000 Audible/Visual Local & Remote Alarms Main Power Circuit Breaker, unit mounted High / Low Refrigerant Pressure Switches (DX units) Motor Overload Protection Standard Standard Standard Standard SPECIFIC MODEL STANDARD FEATURES: AIR COOLED • Remote Outdoor, Air Cooled Condenser rated for -20°F to 95°F Amb. Oper. • Low Ambient Control to -30°F & High Ambient to 105°F Standard Optional WATER/GLYCOL COOLED • 2-way, 150 psig Water / Glycol Regulating Valves • High Pressure &/or 3-way Valves • Coaxial or Brazed-Plate Heat Exchangers Standard Optional Standard ALL SPLIT DX SYSTEMS • Liquid Line Solenoid Valves to Prevent Liquid Slugging Standard DUAL CIRCUIT DX SYSTEMS • Two (2) Independent Refrigerant Circuits - Standard Features "Quick-Reference" Table FILTERS / PLENUMS Guide Specifications Selected Standard Features - Standard CODE CONFORMANCE • NRTL Conformance Compliance to UL 1995 Standard • CSA / NYC MEA-163-88-E Standard Standard 3-1 Guide Specifications - Standard Equipment Guide Specifications QUALITY ASSURANCE Cabinet Construction (ISO-9001:2001 Registered) The cabinet and access panels shall be fabricated from heavy gauge galvannealed steel and powder-coat paint processed for decor matching and corrosion protection. The panels shall be lined with 2 lb/ft2 high density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B. SATS operates in an ISO-9001 registered quality control environment. Each SATS employee is committed to satisfying his or her customer expectations with the highest level of consistent, measurable and continuous quality improvement. GENERAL GUIDE SPECIFICATION Electrical System General Description The indoor evaporator shall be provided with a unit mounted main power circuit breaker with lockable handle. The circuit breaker shall provide main power lockout during routine maintenance and service. The circuit breaker shall be a thermal magnetic type selected to protect the fast-bus power distribution system, providing short circuit and ground fault system protection. - Standard Equipment Remote Stop / Start Included in the system's electrical control circuit shall be a 2-pin terminal connection for remote stop / start of the CyberTWO air conditioner by a remote source. Modular Motor Controllers The system shall be a floor mounted air conditioner designed and built to provide precision temperature and humidity control. The system shall be complete and factory run-tested before shipment. The system shall be MET Laboratory (an NRTL) listed and labeled in compliance with UL 1995 and CSA C22.2 No. 236. The system shall be MEA NYC approved (MEA-163-88-E). The system shall be manufactured by Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA. 100% Front Access The air conditioner shall require front only access for all routinely maintenanced components. No allowance for side service access shall be required, however, removable side access shall be provided for additional access. 3-2 Main Power - Circuit Breaker The system shall incorporate modular motor controllers utilizing motor start protectors and circuit breakers eliminating the need for fusing, as well as providing: Evaporator Coils • Motor branch circuit short circuit protection • Motor load switching controllers (contactors) • Motor overload protection The system shall incorporate overcurrent and overload protection in accordance with UL 1995 requirements. Each blower motor, compressor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter / contactor. The control circuit shall be a 24 VAC Class 2 low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and grounding wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC). The DX-evaporator coil shall be an AFrame design to provide maximum coil surface area and minimum depth to provide a high sensible cooling capacity. The coil shall be seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a dual interlaced circuiting design for maximum heat transfer. Coil end plates shall be hot dipped galvanized. The evaporator coil shall be mounted in an insulated stainless steel condensate drain pan. Guide Specifications - Thermal Expansion Valves Filter Drier/ Strainers overloads, internal pressure relief valve, internal discharge gas vibration eliminator and external vibration mounting isolation. Blowers/Motors Sight Glasses Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge. Scroll Compressors DX systems shall be provided with two independently circuited high efficiency, high reliability and low sound Scroll compressors. Each compressor shall be complete with rotolock service valves, charging and service schraeder ports, internal vibration isolation, internal thermal The standard CyberTWO floor A/C includes the C-6000 Advanced Microprocessor Controller, Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/Heat providing precision temperature and humidity control. C-6000 Microprocessor The blower(s) shall be belt driven with double width, double inlet housing, forward curved blades and permanently lubricated ball bearings sized for an average 150,000 hours of service life. The blower(s) shall be dynamically and statically balanced to minimize vibration and operate in the Class I range. The blower(s) shall be belt driven with dual belts (3 Hp and higher) sized for 200% of the fan motor horsepower. The blower shall have an adjustable base for belt tensioning and a locking system to prevent the motors from moving. The motor's drive sheaves shall have an adjustable pitch to change the speed of the blowers. The motor shall be 1725 RPM and shall have overload protection and a minimum NEMA service factor of 1.15. (Microprocessor Controller w/ Alarms) Control shall be provided by SATS' Advanced C-6000 Microprocessor temperature and humidity controller with alarms. The user friendly C-6000 shall provide both local & remote alarm indication, if applicable, for:        High Temperature Low Temperature High Humidity Low Humidity High Head Press. Low Suction Press. Comm. Failure       Dirty Filter Loss of Air Flow Firestat Smoke Detection Leak Detection Sensor Failure Electrode Canister Steam Humidifier - Standard Equipment All refrigeration piping shall be refrigerant grade tubing. Each refrigerant circuit shall include, as a minimum, refrigerant drier/strainer, sight glass with moisture detector, thermal expansion valve with rapid bleed port feature and external equalizer, evaporator coil, compressor, high pressure switch with manual reset and a low pressure switch with automatic reset. Split / Remote systems shall have a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be brazed, and the entire system shall be pressure tested at the factory with dry nitrogen, evacuated to at least 50 microns and fully charged with refrigerant. Temp & Humid Control Guide Specifications DX-Refrigeration System Standard Equipment The humidifier shall be an electrode steam canister type. Manually adjustable ON/OFF steam output shall be standard. Dehumidification Mode A Dehumidification mode with Electric Reheat/ Heat shall be incorporated as standard. (Note: Please refer to pages 3-5 thru 3-12 of this brochure for more specification details on all CyberTWO Temperature and Humidity Control Options.) 3-3 Guide Specifications Guide Specifications Evaporator Air Patterns DOWN-FLOW: (standard) (VFS-( )-( )-D) The air conditioner shall be configured for a down-flow air pattern with free evaporator return air from the top and conditioned supply air discharge through the bottom of the unit into the raised floor. (Floor Stands are available as option, page 3-10.) Down-Flow Air Pattern Standard Equipment Air Filtration The A/C shall have slide out, 4" deep, class 2 (per U.L. Standard 900) filters. The filters shall be easily accessed through a front access door. The filters shall have an efficiency rating of at least, 30% average as measured by ASHRAE Standard 52-76 test method. DX - Heat Rejection AIR COOLED Remote Outdoor Air Cooled Condenser WATER / GLYCOL COOLED Water/Glycol Cooled Condensers Coaxial Tube-In-Tube: (Models VFS-072/120-DW/DG) Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured, tube-in-tube coaxial condenser; designed and tested for a 450 psig. w.w.p. - Standard Equipment (For model WCS-( )-( )) SS Brazed-Plated: A remote outdoor air cooled condenser with direct driven propeller fan(s) shall be provided. The condenser shall be suitable for outdoor installation. Each fan shall be provided with a low RPM, nonoverloading direct driven motor. Each evaporator refrigerant circuit shall be directly connected to an independent condenser coil circuit rated for the full heat of rejection of the air conditioner at a 95°F DB ambient air temperature. Each evaporator refrigerant circuit shall be provided with a factory installed single pass, counterflow configured brazed plate heat exchanger, with integral sub-cooler, constructed of type 316 stainless steel; designed and tested for a 450 psig. w.w.p. (Models VFS-180/312-DW/DG) (Please refer to page 2-4 for available "down-flow" air pattern configurations.) (A top 1" flanged return air duct connection is optionally available.) UP-FLOW: (optional) (VFS-( )-( )-U) The air conditioner shall be configured for an up-flow air pattern with free evaporator return air through front filtered grille and conditioned supply air through the top of the unit. SUPPLY AIR OUTLET Up-Flow Air Pattern 2-Way, 150 psig Regulating Valve (Standard on all VFS-( )-DW/DG) (Note: Condensers rated for 105°F DB ambient are optionally available, pg 42.) RETURN AIR INLET (Please refer to page 2-4 for available "up-flow" air pattern configurations.) (A 1" flanged duct connection shall be provided as a standard. 2 & 3-way top discharge plenum boxes are available as options, page 3-10.) 3-4 -20°F, Variable Speed Control WCS-( )-V: Low Ambient Head Pressure Control down to a minimum ambient temperature of -20°F via Variable Fan Speed Head Pressure Control. (Note: Low ambient head pressure control down to -30°F DB minimum ambient air temperature via flooded head pressure control is optionally available, page 3-9.) Each refrigerant circuit's head pressure shall be automatically controlled by a factory installed 2-way water / glycol regulating valve rated for 150 psig. w.w.p. (Note: 3-way and high pressure water/ glycol regulating valves are optionally available, page 3-9.) Optional Features - Guide Specifications OPTION.................................................... page Microprocessor Controls • C-6000 Microprocessor (standard) ....................... 3-6/7 - User Interface ....................................................... 3-6 - Alarms .................................................................. 3-6 - Control Inputs/Outputs .......................................... 3-7 - Security ................................................................ 3-7 - Diagnostics & Services ......................................... 3-7 - Multi Unit Sequencing ........................................... 3-7 • Remote BMS communications ............................. 3-7 Humidity Control Options • 350 psig Rated System: (optional) ...................... 3-9 - 3-way, 350 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve • 400 psig Rated System: (optional) ...................... 3-9 - 3-way, 400 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve DX - Capacity Modulation • Snap-Acting, Hot Gas Bypass ............................... 3-9 • Steam Humidifier (standard) .................................. 3-8 High Static Pressure Blowers • Floor Stands - Seismic Floor Stand ........................................... 3-10 - Turning Vanes ..................................................... 3-10 • 2 or 3-Way Plenum Discharge Box .................... 3-10 Index 3-8 3-8 3-8 3-8 3-8 ACCESSORIES - • Dehumidification Cycle - Electric Reheat / Heat (standard) .......................... - Hot Gas Reheat .................................................... - Hot Water Reheat / Heat ...................................... - Steam Reheat / Heat ............................................ - Electric SCR-Fired Reheat / Heat ......................... Free Cooling - Valve Combinations • 150 psig Rated System: (standard) ..................... 3-9 - 3-way, 150 psig, DX Condenser Valves - 3-way, 400 psig, FC Coil Valve Optional Features Optional Features Index • Condensate Pump ............................................... 3-10 • Smoke Detector ................................................... 3-10 • High Static Belt-Drive Blower Upgrade ................... 3-8/9 (Up to 2.0" ext. static pressure) High Efficiency Filtration (IAQ) • IAQ High Efficiency Filters ....................................... 3-9 Head Pressure Control Options Air Cooled - Low Ambient Control • 0°F Ambient .......................................................... 3-9 • -20°F Ambient ....................................................... 3-9 • -30°F Ambient ....................................................... 3-9 • Firestat ................................................................. 3-10 • Remote Water Detector: - Qty. One, Spot Type ............................................ 3-11 - Qty. Two, Spot Type ............................................. 3-11 - 25 Ft. - Strip/Cable Type ...................................... 3-11 - Water Detector Auxiliary Contact ......................... 3-11 • Acoustical Compressor Sound Jackets ............... 3-11 Energy $aving Cooling Options • Free-Cooling Cycle .............................................. 3-12 • Alternate Water Source Cycle ............................ 3-12 Water/Glycol Cooled - Regulating Valves • 2-way, 150 psig (standard) .................................... 3-9 • 2-way, 350 psig ..................................................... 3-9 • 2-way, 400 psig ..................................................... 3-9 • 3-way, 150 psig ..................................................... 3-9 • 3-way, 350 psig ..................................................... 3-9 • 3-way, 400 psig ..................................................... 3-9 3-5 Microprocessor Controls - C-6000 Guide Specifications C-6000 Series Controls Advanced Microprocessor Temperature & Humidity Controller with Alarms windows type structure, in three different modes; Information, Operation, and Service. FIELD CONFIGURABLE: The C-6000 controller is field program configurable and capable of matching the unique needs of any data center, telecommunication or other critical area. - Microprocessor Control Options The CyberTWO floor mounted A/C shall be provided with SATS’ C-6000 Microprocessor based Temperature and Humidity controller with Alarms. The controller shall incorporate a “user-friendly” operating environment, to allow easy system setup and operation. The C-6000 is a complete microprocessor based control system designed for operating, controlling and monitoring the air conditioning unit. The C-6000 controller shall include a full-featured LCD, Graphical display for visual indication of the units operating conditions. USER INTERFACE Compressor Evaporator Blower Motor Humidifier Heater Pump ALARM CONDITIONS As a standard, the C-6000 temperature and humidity sensor shall be factory unit mounted in the return air stream of the Precision A/C unit, after the filter(s). Alarm conditions activate an audible and visual indicator. An alarm shall be acknowledged through a button located on the user interface. The C-6000 alerts to the following alarm conditions (if applicable): (Note: Remote Sensor installation is available as an option.) SYSTEM SETUP & ADJUSTMENTS The C-6000 shall be completely factory pre-programmed, and therefore, most applications will require no field setup. However, the “default” set points and their ranges are easily adjusted from the C-6000 interface. UNIT STATUS DISPLAY • Current Dry Bulb Temp Set Point • Current Relative Humidity Set Point • Actual Time Current Unit Status: The C-6000 LCD Graphic Display shall indicate current unit functions: 3-6 • • • • • SENSOR LOCATION OPTIONS: The C-6000 LCD Graphic Display shall indicate current room status: The User Interface shall feature an easy to read, liquid-crystal, graphical display. The attractive unit mounted interface, allows the operator to visually monitor and customize unit functions and settings. The controller is operated via a 4-key menu-driven Run Times The historical run-time in hours of the following major components shall be available directly from the C-6000 interface: (if applicable) • System ON/OFF • Standby Mode • Cooling • Manual Mode • Heating • Day/Night Operation • Humidifying • Service Required • Dehumidifying • Graphical display of room temperature and humidity for the last 24 hours.        High Temperature Low Temperature High Humidity Low Humidity High Head Press. Low Suction Press. Comm. Failure       Dirty Filter Loss of Air Flow Firestat Smoke Detection Leak Detection Sensor Failure Summary Alarm Contact: A summary alarm dry-contact (n/o or n/c) connection shall be available for remote annunciation of an alarm condition. An additional user-defined custom alarm drycontact shall also be available on most system configurations. Alarm History: The C-6000 controller provides users with a recorded history of the previous 80 alarms, including the time and date of the alarm. CONTROL INPUTS/OUTPUTS The C-6000 is capable of both digital (on/off) and analog input and output device control. Prior to shipment, each Precision A/C unit’s C-6000 is factory program configured to match the unit’s system operational requirements. Microprocessor Controls - C-6000 An expansion board shall increase the capability by providing and additional 8 digital inputs and 8 digital outputs. Power Loss Restart In the event of a loss of power to the system, the C-6000 can be configured for Automatic or Manual Restart. The C-6000’s non-volatile memory enables the system to restart when power is restored, without the loss of the “last” stored set points and other system configuration settings. Sequential Load Activation To minimize the total in rush current loads during system startup/restart, the C-6000 controller shall be configured for time-delay sequence startup. The user can designate specific unit restart time-delays, as well as, each unit’s respective electric heater and/or humidifier. Unit restart delay can be adjusted from 0 to 10 minutes. Electric heater and/or humidifier restart delay can be adjusted from 0 to 60 seconds. Start Delay: After a power loss, the C-6000’s Start Delay feature allows the Precision A/C to operate with a delayed start period (adjustable up to 42 minutes). SECURITY Keypad Lockout The C-6000 includes a 2-level password protection feature that prevents unauthorized users from making changes to system setpoints and settings available directly from the multi-function interface. DIAGNOSTICS AND SERVICE MODE The C-6000 shall incorporate a unique self-diagnostics algorithm that continually tests systems functions and hardware operation. In the event of such a failure, the user will be alerted to the condition via a visual and audible alarm. Control Board The Control Board shall initiate a self-test of the control system. number of “standby” units can be designated as any number. Automatic timed change over is designated between 1 and 255 hours. Automatic change-on-failure can be user customized by selecting which normally displayed alarms will result in a switchover to the “standby” unit. As well, standby units can be sequenced to maintain temperature and or humidity as needed. It is necessary that the remote sensor option be utilized for this function. The Multi-Unit Sequencing function shall exist inherently within the standard C-6000 controller. Interconnect wiring between the RS-485 data bus ports as well as field configuration from the C-6000 user interface shall be all that is required to incorporate this feature. When BMS communication is required (MIB Gateway), the RS-485 serial port shall be utilized for the MIB interface. The Multi-Unit Sequencing function shall then be accomplished in the same manner as described above but via the MIB Gateway. Remote BMS Connection MIB GATEWAY Input Diagnostics All system inputs and output devices shall be continuously monitored for proper operation. MULTI UNIT SEQUENCING Multi-Unit Sequencing (Up to 6 Units) The C-6000 shall enable a unit sequencing function with automatic time-based switch over as well as change-on-failure switch over for up to 6 units via the standard RS-485 serial port. One unit shall be designated as the “master” with all others being designated as “standby”. The C-6000 Inputs & Outputs shall be remotely monitored (address readable) and remotely controlled (address writable) via any building management system (BMS)/local area network (LAN) control system that can communicate via a ModBus protocol. Each C-6000 configured for BMS communication shall incorporate an RS-485 Serial Communication Port that is field connected to a factory provided wall mounted ModBus Gateway. - Microprocessor Control Options Temperature Anticipation The C-6000 shall incorporate a selfcalibrating and self-adjusting control logic that adjusts the response of the SATS air conditioner to changes in temperature and humidity. The system shall provide premium setpoint accuracy while controlling the room conditions rate of change, minimizing the equipment energy consumption and maximizing the system’s operating life and reliability. Recovery Delay After a power loss, the C-6000’s Recovery Delay feature allows the Precision AC A/C to operate without initiating any high or low temperature or humidity alarms for a delayed period. This feature allows the A/C time (adjustable up to 42 minutes) to “pull-down” the conditioned space’s load without nuisance alarms during initial startup or power loss restart. Guide Specifications Digital (on/off) and Analog (0-10 VDC) Inputs & Outputs The C-6000 I/O Board provides as a standard 10 digital outputs, 8 digital inputs, 7 analog inputs, and 4 analog outputs. 3-7 Optional Features - Humidity Control CyberTWO floor systems include the C-6000 Microprocessor Controller, Electrode Canister Steam Humidifier and Dehumidification Mode with Electric Reheat/Heat for total temperature and humidity control, as a standard. Canister Steam Humidification: (standard) The humidifier shall be an electrode steam canister type and shall have an adjustable humidity output setting A factory mounted and wired electric resistance heater shall be included to provide automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Electric heaters shall be provided with thermal/magnetic circuit breakers which shall protect each conductor. Included shall be one automatic resetting and one manual resettable over-temperature safety device (pilot duty). The floor A/C shall be provided with a refrigeration based dehumidification mode. Moisture is condensed on the (Note: Hot Gas Reheat is not available on systems incorporating Free-Cooling or Alternate Water Source, because no method of reheat would be available during non-compressorized FC or AWS operation.) Hot Gas Reheat: (Models VFS-()-DAR, DW & DG only) Remote Air Cooled Condenser Scroll Compressor Hot Gas Reheat Valve Flooded Head Pressure Control Valve Relief Valve Refrigerant Reclaim Port Liquid Refrigerant Receiver LP HP Sight Glass Hot Gas Evaporator Cooling Coil Reheat Coil Feeler Bulb A factory installed copper tube, aluminum fin heat/reheat coil and 2way control valve shall be provided to control the flow of hot water for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. Steam Reheat/Heat A factory installed copper tube, aluminum fin heat/reheat coil and 2-way control valve shall be provided to control the flow of steam for automatic sensible reheating mode during the dehumidification cycle and automatic heating mode as required. (Note: Steam trap and steam piping specialties shall be provided by others, not by SATS.) SCR Fired Reheat/Heat Reheat Options Dehumidification Cycle: (standard) reheat coil providing energy free sensible reheating. Hot Water Reheat/Heat Heater elements shall be of a safe low-watt density, plated fin-tubular design. Two (2) stages of electric reheat/heat shall be provided as standard. from 25 to 100% of the full rated humidifier capacity. The humidifier shall incorporate an automatic flush cycle that senses the current consumption of the humidifier and controls mineral concentration of the water. A “Change Cylinder” light shall notify service personnel when the humidification output is below rated requirements and when maintenance is due. 3-8 Electric Heat/Reheat: (standard) Equalizer Line - Guide Specifications However, these standard features can be deleted and/or substituted with alternate features to allow you the flexibility to select the configuration best suited for your unique application. cooling coil and discharged through the condensate drain. Reheat (electric, hot gas, steam or hot water) shall be provided to offset sensible cooling during the dehumidification cycle. Equalizer Line Optional Features SELECTED OPTIONS Guide Specifications Air Flow Solenoid Valve Refrigerant Drier / Strainer Thermal Expansion Valve A factory installed copper tube, aluminum fin hot gas reheat coil and valve shall be provided for automatic sensible reheating mode during dehumidification cycle. Hot compressor discharge gas shall be diverted from the condenser to the hot gas The electric heat/reheat shall be controlled through a “Zero Firing” Silicon Controlled Rectifier (SCR) with an extruded aluminum heat sink and solid state logic system to provide close dry bulb temperature control of the leaving conditioned air temperature. C-6000 proportional (0-10 Vdc) microprocessor controls shall be provided with the SCR Fired Electric Reheat option. High Static Pressure Belt-Drive Blowers The CyberTWO vertical floor air conditioner shall be provided with a high static pressure belt-driven evaporator blower to provide standard unit CFM @ ____ " e.s.p. Optional Features - Blower Motor Horsepower Net Cooling Capacity Electrical Data Discharge Blower Data Unit Air Flow Rate (CFM) will match the standard data as shown in Section 4 of this manual for each respective unit model. Filtration FREE-COOLING SYSTEMS AIR COOLED - Low Ambient -30°F, Flooded Control Remote Air Cooled Condenser Scroll Compressor High Pressure Switch Flooded Head Pressure Control Valve Relief Valve Liquid Refrigerant Receiver HP Evaporator Cooling Coil LP Sight Glass Refrigerant Reclaim Port Low Pressure Switch Liquid Line Solenoid Valve Refrigerant Drier / Strainer Equalizer Line • • • • Head Pressure Control Feeler Bulb Thermal Expansion Valve The air cooled system shall incorporate a low ambient flooded head pressure control for year-round system operation down to -30°F DB minimum ambient air temperature. 150 psig Rated System: (standard) • DX Valves = 3-way, 150 psig • FC Valve = 3-way, 400 psig 350 psig Rated System: (optional) • DX Valves = 3-way, 350 psig • FC Valve = 3-way, 400 psig 400 psig Rated System: (optional) • DX Valves = 3-way, 400 psig • FC Valve = 3-way, 400 psig WATER / GLYCOL COOLED DX - Capacity Modulation/ Freeze Protecion CyberTWO vertical floor A/C's are available with the following standard and optional high efficiency IAQ conscious filtration: Air Pattern Type Filters Avail. Up-Flow Units: w/ free-front return: F1, F2 w/ ducted rear return: F1, F2 Down-Flow Units: w/ top return: F1, F2, F3 Filter ratings are based on dust spot efficiency ratings per ASHRAE Test Standard 52-76. (Note: F2 & F3 optional filters create additional static pressure and may require the High Static Pressure BeltDrive Option. Please consult your local SATS sales representative for details.) DX Water Cooled and Glycol Cooled systems are available with following standard (V1) and optional (V2-V6) head pressure regulating control valves: V1: 2-way, 150 psig (standard) V2: 2-way, 350 psig V3: 2-way, 400 psig V4: 3-way, 150 psig V5: 3-way, 350 psig V6: 3-way, 400 psig } 3-way valves require front & left side access Each refrigerant circuit's head pressure shall be controlled by a factory installed ____-way water / glycol regulating valve rated for ____ psig. w.w.p. The CyberTWO floor A/C shall incorporate a snap acting hot gas bypass system to provide modulation of the unit’s cooling capacity and evaporator coil freeze protection under low load conditions. Remote Air Cooled Condenser Scroll Compressor High Pressure Switch Evaporator Cooling Coil HP LP Low Pressure Switch Feeler Bulb Equalizer Line F1: 4", 30% Eff. Filters (standard) F2: 4", 60% Eff. Filters F3: 2", 30% Pre / 4", 60% Eff. Final Filters SNAP-ACTING, Hot Gas Bypass (Models VFS-()-DAR, DW & DG only) - Guide Specifications Each circuit shall include factory installed crankcase heaters, cold-start relays, liquid refrigerant receivers with receiver liquid level sight glass and head pressure regulating valves for flooded condenser operation. DX Water/Glycol Cooled systems with Free-Cooling are available with the following standard and optional DX head pressure and Free-Cooling valve combinations: Optional Features (Note: Due to the probable change in standard unit blower motor horsepower for the High Static Belt-Drive Blower option, please consult your local SATS sales representative for the following unit specification changes: Guide Specifications Flooded Head Pressure Control Valve Hot Gas Regulator Valve (Optional) Relief Valve Refrigerant Liquid Refrigerant Reclaim Port Receiver Sight Glass Liquid Line Solenoid Valve Refrigerant Drier / Strainer Thermal Expansion Valve 3-9 Optional Features Optional Features AWS Control Valves Guide Specifications Note: For additional floor stand heights, please contact your local SATS sales representative. Additional Floor Stand Options: Seismic Zone-4 Rate: The adjustable floor stand shall be certified rated for seismic zone-4 installation. Alternate Water Source cooling shall be controlled by the following standard and optional control valves: V1: 3-way, 400 psig (standard) V2: 2-way, 400 psig (optional) - Guide Specifications Standard Valve Control: A ____-way modulating AWS cooling control valve rated for a maximum ____ psig w.w.p. shall be factory installed. Precision cooling control shall be accomplished via an analog control signal to the proportionally actuating control valve. Turning Vanes: Turning vanes shall be factory provided for field installation to each unit's floor stand. Adjustable Floor Stand The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers. The condensate pump shall be rated for 145 GPH at 40 ft. of head with a shut-off at 50 ft. of head. Smoke Detector Top Discharge Plenum Box (Up-Flow units only) Evaporator Air Outlet ACCESSORIES stop/start terminals, shall open the A/ C's control circuit, thereby shutting the A/C down in the event of a condensate overflow. A 2 or 3-way (please specify) plenum discharge box shall be provided. The plenum box shall include doubledeflecting, adjustable grilles. The plenum box shall ship separately for rigging purposes. Condensate Pump (Factory Mounting Available) A photo-electric smoke detector shall be factory installed in the CyberTWO evaporator section on the suction side of the evaporator blower. The smoke detector shall be rated for high air velocity applications, and shall shut down the air conditioner upon sensing smoke in the return air stream. Optional Auxiliary Contact: An auxiliary dry-contact (n/o) terminal connection shall be provided for remote notification of a smoke detection alarm. Firestat A _____ " high adjustable floor stand shall be provided to allow for ease of installation of the CyberTWO A/C onto a raised floor. The floor stand shall be field installed. Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height 3-10 Adjustable Height Turning Vane Availability Minimum Maximum 4.0" (Upflow Units Only) 3.5" 4.5" Not Available 6.0" 5.0" 7.0" Not Available 12.0" 11.0" 15.0" Optional 15.0" 14.0" 18.0" Optional 18.0" 17.0" 21.0" Optional 24.0" 23.0" 26.0" Optional A condensate pump shall be factory installed within the CyberTWO system for automatic removal of condensate and humidifier flush water (if applicable). The condensate pump shall include an internal overflow safety float switch which, when wired to the A/C's remote The air conditioner shall be provided with a factory wired and mounted firestat. The firestat shall shut down the air conditioner upon sensing a high return air temperature. Optional Features Single (one) - Spot Type Detector: Optional Auxiliary Contact: An auxiliary dry-contact (n/o) terminal connection shall be provided for remote notification of a water detection alarm. Compressor Sound Jackets (VFS-( )-DW/DG-() Only!) Quantity 1-(one) remote spot type water/leak detector per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. Quantity 2-(two) remote spot type water/leak detectors per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. 25 Ft. - Strip/Cable Type Detector: Low Entering Condenser Water Kit For Water/Glycol systems that require entering condenser water temperatures from 65°F to 45°F, the system shall be provided with a factory installed in-line liquid refrigerant receiver to help reduce the negative effect the low condenser source can have on the evaporator. A compressor crankcase heater shall also be provided standard with this option. (Compressor Sound Jackets are not available with this option due to the crankcase heater). - Guide Specifications Dual (two) - Spot Type Detectors: Each compressor shall be provided with a factory installed acoustical sound jacket. Each sound jacket shall have a snap closure system for ease of removing and reinstallation during maintenance. Each sound jacket shall have a Noise Reduction Coefficient NRC of 85 per ASTM C-423 and a Sound Transmission Loss STC of 11 per ASTM E-90. Optional Features Remote Water Detectors Guide Specifications A 25 Ft. in length remote strip/cable type water/leak detector shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the air conditioner's water producing operations. 3-11 Optional Features (Water/Glycol Economizer Coil) A Free-Cooling economizer cycle shall be provided to take advantage of low ambient air temperature conditions to provide compressor-less cooling. The air conditioner shall have three modes of operation: Remote Drycooler (Optional) Primary Mode: The free-cooling coil shall be closely sized to match the DX mode sensible cooling capacity to increase the number of hours that the system can operate in the free-cooling mode, thereby increasing the operating savings of the installation. Secondary / Backup Mode: 100%, 2-Stage DX Cooling Mode: Pump (Optional) 3-Way Mixing Modulating Valve Free-Cooling Coil T DX1 - Cooling Coil DX1 3-Way Head Pressure Control Valve HP Water / Glycol Cooled Condenser Coil LP Equalizer Line - Free-Cooling & Alternate Water Source Free-Cooling Aqua-Stat Scroll Compressor Feeler Bulb Expansion Valve Refrigerant Reclaim Port Sight Glass Refrigerant Drier / Strainer "Assist" FC + 1-Stage DX Mode: When outdoor air temperatures are between approximately 35°F to 65°F and cooling is required, the C-6000 microprocessor controller's "assistmode" free-cooling program algorithm shall analyze input data from factory provided and installed ambient temperature sensors, aquastat and return room air temperature and relative humidity sensors. Based on this data, the C--6000 shall automatically activate partial precooling mode in conjunction with one stage of DX cooling. This "precooling" effect decreases the hours of compressor operation, thereby increasing the operating savings of the installation. 100% Free-Cooling Mode: When outdoor air temperatures are below approximately 35°F and space cooling is required, all source coolant shall be diverted from the DX - Water / Glycol Cooled refrigerant condenser to a chilled water/glycol coil (free- 3-12 cooling coil & control valve). To maximize the cooling effect for the coolant solution during the freecooling mode, the drycooler capacity shall be increased by reversing the typical drycooler fan(s) cycling sequence of operation. When outdoor air temperatures are above 65°F, or at any time when the free-cooling mode cannot handle the space cooling or dehumidification load, the C-6000 shall automatically switch to 100%, 2-stage DX - water / glycol cooled compressorized cooling mode. Alternate Water Source (Chilled Water by "Day" and DX-Backup by "Night" !) An Alternate Water Source cooling cycle shall be provided to utilize building chilled water supply when available as the primary cooling cycle, with dual compressor, DX refrigerant cooling as a backup. The air conditioner shall have two cooling systems: Remote Liquid Chiller (by others) Alternate Water Source Cooling Coil Pump (by others) Flow Switch AWS Control Valve FS Alternate Water Source Aqua-Stat T Remote Air Cooled Condenser Scroll Compressor Flooded Head Pressure Control Valve Relief Valve Refrigerant Reclaim Port Receiver LP HP Sight Glass DX - Cooling Coil Equalizer Line Guide Specifications Free-Cooling "Assist-Mode" Option - Free-Cooling/Alternate Water Source Feeler Bulb Solenoid Valve Refrigerant Drier / Strainer Expansion Valve The primary mode of cooling shall be a chilled water / glycol circuit with alternate water source cooling coil and 3-way modulating (0-10 Vdc) control valve rated for 400 psig. w.w.p. The secondary/backup mode of cooling shall be a dual compressor, DX refrigerant circuit. The C-6000 microprocessor's Alternate Water Source program algorithm shall analyze input data from factory provided and installed water flow switch, aquastat and return room air temperature, and relative humidity sensors. Based on this data, the C6000 microprocessor shall automatically control the sequencing of the primary AWS chilled water to and from the secondary/backup dual compressor DX modes of operation. If chilled water is available, the system shall operate like a chilled water unit, without the compressors operating. When the water temperature is too high, or the water flow rate is not sufficient, the air conditioner shall automatically switch to the dual compressor, DX refrigerant cycle. (Note: DX Air Cooled with AWS cooling is shown for illustration purposes only. DX Water and Glycol Cooled with AWS cooling are also available.) Performance/Capacity Specifications - Index MODEL TYPE .......................................... page Air Cooled • Air Cooled Systems - VFS-072/312-DAR ................................................ 4-2 - Remote Air Cooled Condenser Data ...................... 4-3 Water Cooled • Water Cooled Sytems - VFS-072/312-DW ................................................. 4-4 - Water Cooled Condenser Data .............................. 4-5 Glycol Cooled • Glycol Cooled Sytems - VFS-072/312-DG .................................................. 4-6 - Glycol Cooled Condenser Data ............................. 4-7 - Remote Drycooler/Pump Data .............................. 4-7 DX Free Cooling • DX Glycol Cooled w/ Free Cooling - VFS-072/312-DG-FC ............................................. 4-8 - Glycol Cooled Condenser Data ............................. 4-9 • DX Air Cooled w/ Alternate Water Source - VFS-072/312-DAR-DWS ..................................... 4-12 - Remote Air Cooled Condenser Data .................... 4-13 Index DX Alternate Water Source Cooling - • DX Water Cooled w/ Free Cooling - VFS-072/312-DW-FC .......................................... 4-10 - Water Cooled Condenser Data ............................. 4-11 Performance/Capacity Specifications Index • DX Water Cooled w/ Alternate Water Source - VFS-072/312-DW-AWS ...................................... 4-14 - Water Cooled Condenser Data ............................ 4-15 • DX Glycol Cooled w/ Alternate Water Source - VFS-072/312-DG-AWS ....................................... 4-16 - Glycol Cooled Condenser Data ........................... 4-17 4-1 Air Cooled Performance Data "VFS" Model 6 to 26 Ton "VFS" ( )-072-DAR ( )-096-DAR ( )-120-DAR ( )-180-DAR ( )-240-DAR ( )-312-DAR NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible - Air Cooled (6 to 26 Ton Systems) 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 70,915 67,020 97,935 92,500 122,825 111,200 185,450 173,650 241,420 215,410 287,260 250,390 67,570 64,745 93,435 89,185 117,130 107,670 176,580 169,340 230,230 211,055 273,826 243,640 65,470 63,135 90,560 86,685 113,495 104,975 171,340 165,145 223,785 206,330 265,460 238,480 69,585 69,585 96,590 95,245 120,150 116,560 181,075 179,590 235,105 228,900 278,670 267,170 66,470 66,470 92,325 91,585 114,730 112,590 173,265 172,460 224,735 222,675 265,720 259,240 64,510 64,510 89,530 89,160 111,165 110,155 168,305 167,655 218,155 217,430 257,640 253,415 Reheat/Heat - Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 61,795 107,785 79,700 122,675 139,530 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 300 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- 4-15 5.1 Kw 163,130 138,650 5.0 13.8 -------- 164,410 194,160 142 157 -------------------- (Standard) 4-15 5.1 Kw Cycling Cycling Modulating (0-10 Vdc) 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890 2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760 3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815 5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020 5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800 7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880 3/ 14.6 394 3/ 19.8 442 3/ 24.3 422 3/ 24.3 506 Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm 4-2 3/ 9.7 386 3/ 14.6 343 Air Cooled - ( )-072-DAR ( )-096-DAR ( )-120-DAR ( )-180-DAR ( )-240-DAR ( )-312-DAR Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,785 Scroll, (2) 3,890 Scroll, (2) 4,950 Scroll, (2) 7,759 Scroll, (2) 10,448 Scroll, (2) 12,812 Total Heat of Rej. 92,991 Btu/h 131,494 Btu/h 163,488 Btu/h 250,800 Btu/h 328,337 Btu/h 394,083 Btu/h Connection Sizes - Copper, Refrigerant: Liquid Line, (Qty.) Hot Gas Line, (Qty.) (Please refer to CyberTWO "VFS" IOM Manual for proper interconnecting refrigerant line sizing.) 1/2" OD, (2) 5/8" OD, (2) 1/2" OD, (2) 5/8" OD, (2) 1/2" OD, (2) 5/8" OD, (2) 5/8" OD, (2) 7/8" OD, (2) 5/8" OD, (2) 1-1/8 OD, (2) 5/8" OD, (2) 1-1/8 OD, (2) Condensate Drain, (w/ pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) Remote Air Cooled Condenser Data: WCS-( ) - (Remote Outdoor Propeller Fan(s), Air Cooled Condenser for Model VFS-( )-DAR Evaporator Section) Model @ 95°F Amb. WCS-008 WCS-010 WCS-012 WCS-020 WCS-025 WCS-028 Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) 8,640 1/2 Hp, (1) 7,780 1/2 Hp, (1) 7,080 1/2 Hp, (1) 15,400 1.0 Hp, (2) 23,000 1.5 Hp, (2) 22,450 1.5 Hp, (2) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (1) ____ ____ ____ 164 + Motor Hp, (Qty.) Net Weight (lbs) 179 195 536 580 630 Refrigerant Connections - Copper Hot Gas Line, (Qty.) 7/8" OD, (2) Liquid Line, (Qty.) 5/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-3/8" OD, (2) 1-1/8" OD, (2) 1-3/8" OD, (2) 1-1/8" OD, (2) Model @ 105°F Amb. WCS-010 WCS-015 WCS-016 WCS-028 WCS-036 WCS-041 7,780 1/2 Hp, (1) 15,700 1.0 Hp, (2) 15,600 1.0 Hp, (2) 22,450 1.5 Hp, (2) 20,700 1.5 Hp, (2) 33,675 1.5 Hp, (3) 1/3 Hp, (1) ____ ____ ____ ____ ____ 174 Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) + Motor Hp, (Qty.) Net Weight (lbs) 510 518 630 730 900 Refrigerant Connections Hot Gas Line, (Qty.) 1-1/8" OD, (2) Liquid Line, (Qty.) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-3/8" OD, (2) 1-1/8" OD, (2) 1-5/8" OD, (2) 1-3/8" OD, (2) 1-5/8" OD, (2) 1-3/8" OD, (2) Low Ambient Control Std Minimum Op. Amb. Head Press. Method -20°F Variable Speed -20°F Variable Speed -20°F Variable Speed -20°F Variable Speed -20°F Variable Speed -20°F Variable Speed -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) Optional Min. Op. Amb - Air Cooled (6 to 26 Ton Systems) 20x25x4, (3) Performance Data "VFS" Model Remote Condenser Data (6 to 26 Ton "VFS") Compressors are located with the model VFS-( )-DAR Evaporator Section 4-3 Water Cooled Performance Data "VFS" Model ( )-072-DW 6 to 26 Ton "VFS" ( )-096-DW ( )-120-DW ( )-180-DW ( )-240-DW ( )-312-DW NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible - Water Cooled (6 to 26 Ton Systems) 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 78,245 70,325 107,525 97,990 134,380 117,420 194,200 170,840 266,500 223,315 313,200 262,975 74,645 68,105 102,660 94,835 128,280 114,105 185,100 165,600 254,175 217,746 298,440 256,460 72,315 66,275 99,565 92,355 124,420 111,475 179,270 161,650 246,560 213,170 289,410 251,145 76,190 73,500 105,540 101,910 131,100 124,110 189,535 180,125 258,940 238,330 303,540 281,450 72,770 71,060 100,900 98,430 125,260 120,390 180,820 174,215 247,070 232,000 289,225 273,950 70,500 69,550 97,860 96,205 121,475 118,100 175,045 170,685 239,655 227,695 280,410 268,110 Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 44,305 52,440 58,655 90,750 102,170 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 250 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- 4-15 5.1 Kw 123,200 138,650 5.0 13.8 -------- 164,410 194,160 142 157 -------------------- (Standard) 4-15 5.1 Kw Cycling Cycling Modulating (0-10 Vdc) 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890 2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760 3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815 5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020 5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800 7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880 3/ 14.6 394 3/ 19.8 442 3/ 24.3 422 3/ 24.3 506 Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm 4-4 3/ 9.7 386 3/ 14.6 343 Water Cooled ( )-072-DW ( )-096-DW ( )-120-DW ( )-180-DW ( )-240-DW ( )-312-DW Scroll, (2) 3,865 Scroll, (2) 6,315 Scroll, (2) 8,523 Scroll, (2) 10,289 Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,174 Scroll, (2) 3,042 Water Cooled Condenser Data - Based on 0% Glycol Solution Total Heat of Rej. 95,482 Btu/h 135,100 Btu/h 167,617 Btu/h 258,040 Btu/h 337,181 Btu/h 402,707 Btu/h GPM @ 85°F EWT / 95°F LWT Unit Press. Drop (Ft. of H2O) 19.1 GPM 24.2 Ft. 27.0 GPM 20.6 Ft. 33.5 GPM 31.3 Ft. 51.6 GPM 24.4 Ft. 67.4 GPM 32.7 Ft. 80.5 GPM 37.5 Ft. Condenser Type Coaxial Coaxial Coaxial Plate-Finned Plate-Finned Plate-Finned Head Pressure Control Standard Control 2-way, 150 psig Water Regulating Valves, (factory installed) Optional Control Refer to page 3-11 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options! Performance Data "VFS" Model Condenser Data (6 to 26 Ton "VFS") Connection Sizes - Copper 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet Condenser In/Out 1/4" OD 1-1/8" OD 1/4" OD 1-3/8" OD 1/4" OD 1-3/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) Remote Water Source Remote Water Source (supplied by others) Evaporator Air Inlet OFF (supplied by others) EVAPORATOR AIR OUTLET ON EVAPORATOR AIR OUTLET - Water Cooled (6 to 26 Ton Systems) Condensate Drain, (w/ pump) EVAPORATOR AIR INLET Evaporator Air Outlet EVAPORATOR AIR INLET VFS-072 thru VFS-312-DW-D Self-Contained, DX - Water Cooled (Down-Flow Air Pattern) VFS-072 thru VFS-312-DW-U Self-Contained, DX - Water Cooled (Up-Flow Air Pattern) DX - Water Cooled with "Free Cooling" Option Performance Data <<< Please see page 4-10 for DX - Water Cooled with "Free Cooling" Option Performance Data. >>> 4-5 Glycol Cooled Performance Data "VFS" Model ( )-072-DG 6 to 26 Ton "VFS" ( )-096-DG ( )-120-DG ( )-180-DG ( )-240-DG ( )-312-DG NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible - Glycol Cooled (6 to 26 Ton Systems) 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 69,610 65,460 95,490 91,030 119,725 109,440 174,540 159,760 237,750 208,890 280,370 246,790 66,390 63,120 91,100 87,675 114,150 105,850 166,350 154,340 226,750 202,950 267,365 240,020 64,320 61,340 88,280 85,175 110,560 103,125 161,050 150,275 219,760 198,300 259,155 234,880 68,265 67,535 94,310 93,415 117,220 114,340 171,060 166,575 231,520 221,275 272,120 262,990 65,245 64,955 90,150 89,720 111,940 110,315 163,275 160,500 221,000 214,500 259,580 254,970 63,225 63,225 87,445 87,445 108,420 107,810 158,090 156,750 214,370 210,210 251,670 249,135 Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages HOT GAS REHEAT - with 3-way Heat Reclaim Valve, (Optional) BTU/H 66,170 77,300 84,965 130,655 148,870 HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, (Optional) BTU/H 82,070 94,580 103,050 110,300 115,100 GPM 5.0 5.0 5.0 5.0 5.0 Pressure Drop, ft. wg 15.4 15.4 15.4 15.7 13.8 Control Valve -------------------2-way, 300 psig, Modulating (0-10 Vdc) -----------STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72°F DB, (Optional) BTU/H (nominal) 120,030 139,230 151,160 156,860 Condensate (lb/hr) 115 132 140 135 Control Valve -------------------2-way Modulating (0-10 Vdc) Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- 4-15 5.1 Kw 173,115 138,650 5.0 13.8 -------- 164,410 194,160 142 157 -------------------- (Standard) 4-15 5.1 Kw Cycling Cycling Modulating (0-10 Vdc) 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 1.5 Hp, (1) 3,750 @ 0.5" Belt Driven one 890 2.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 760 3.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 815 5.0 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,020 5.0 Hp, (1) 10,250 @ 0.5" Belt Driven two 800 7.5 Hp, (1) 12,300 @ 0.5" Belt Driven two 880 3/ 14.6 394 3/ 19.8 442 3/ 24.3 422 3/ 24.3 506 Evaporator Coil - Aluminum Fin, Copper Tube Rows/Face Area (ft2) Face Velocity, fpm 4-6 3/ 9.7 386 3/ 14.6 343 Glycol Cooled ( )-072-DG ( )-096-DG ( )-120-DG ( )-180-DG ( )-240-DG ( )-312-DG Scroll, (2) 5,278 Scroll, (2) 8,187 Scroll, (2) 11,011 Scroll, (2) 13,568 Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,960 Scroll, (2) 4,138 Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution Total Heat of Rej. 92,447 Btu/h 130,382 Btu/h 162,550 Btu/h 249,027 Btu/h 326,144 Btu/h 391,777 Btu/h GPM @ 110°F EGT Unit Press. Drop (Ft. of H2O) Condenser Type 20.4 GPM 26.6 Ft. Coaxial 28.8 GPM 22.4 Ft. Coaxial 35.9 GPM 34.4 Ft. Coaxial 54.9 GPM 27.2 Ft. Plate-Finned 71.9 GPM 36.2 Ft. Plate-Finned 86.5 GPM 41.9 Ft. Plate-Finned Head Pressure Control Standard Control 2-way, 150 psig Glycol Regulating Valves, (factory installed) Optional Control Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options ! Connection Sizes - Copper 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet Condenser In/Out 1/4" OD 1-1/8" OD 1/4" OD 1-3/8" OD 1/4" OD 1-3/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) FSS-204A FSS-205A FSS-208A FSS-211A FSS-301A Remote Drycooler/Pump Data Selection @ 95°F FSS-107A GPM @ 120°F EGT No. of Feeds Expansion Tank Pipe Connection (In/Out) 105°F Amb. Selections 20.4 GPM 18 15 Gal 1-1/2" MPT 28.8 GPM 35.9 GPM 18 18 15 Gal 15 Gal 2" MPT 2" MPT Optional - Please refer to Glycol Pump / 54.9 GPM 71.9 GPM 27 36 15 Gal 15 Gal 2-1/2" MPT 2-1/2" MPT Drycooler Engineering Manual 86.5 GPM 54 15 Gal 3.0" MPT Standard Pump Quantity Horsepower Total Hd Press. (ft. w.g.) Dual Pump Packages GPS-015-S 1(one) 1.5 Hp 78.0 Ft. GPS-015-S GPS-015-S 1(one) 1(one) 1.5 Hp 1.5 Hp 75.0 Ft. 72.0 Ft. Optional - Please refer to Glycol Pump / GPS-020-S GPS-030-S 1(one) 1(one) 2.0 Hp 3.0 Hp 72.0 Ft. 82.0 Ft. Drycooler Engineering Manual GPS-030-S 1(one) 3.0 Hp 75.0 Ft. F( )S-( ) Evaporator Air Inlet Outdoor Propeller Air Cooled Drycoolers F( )S-( ) Outdoor Propeller Air Cooled Drycoolers ON OFF EVAPORATOR AIR OUTLET GPS-( )-( ) EVAPORATOR AIR OUTLET GPS-( )-( ) Single & Dual Glycol Pump Packages Single & Dual Glycol Pump Packages Evaporator Air Outlet VFS-072 thru VFS-312-DG-D Self-Contained, DX - Glycol Cooled (Standard Down-Flow Air Pattern) - Glycol Cooled (6 to 26 Ton Systems) Condensate Drain, (w/ pump) Performance Data "VFS" Model Condenser Data (6 to 26 Ton "VFS") EVAPORATOR AIR INLET VFS-072 thru VFS-312-DG-U Self-Contained, DX - Glycol Cooled (Optional Up-Flow Air Pattern) DX - Glycol Cooled with "Free Cooling" Option Performance Data <<< Please see page 4-8 for DX - Glycol Cooled with "Free Cooling" Option Performance Data. >>> 4-7 DX Glycol Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" Performance Data - DX Glycol Cooled w/ FC (6 to 26 Ton Systems) 4-8 "VFS" Model 072-DG-FC 096-DG-FC 120-DG-FC 180-DG-FC 240-DG-FC 312-DG-FC NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 69,610 65,460 95,490 91,030 119,725 109,440 174,540 159,760 237,750 208,890 280,370 246,790 66,390 63,120 91,100 87,675 114,150 105,850 166,350 154,340 226,750 202,950 267,365 240,020 64,320 61,340 88,280 85,175 110,560 103,125 161,050 150,275 219,760 198,300 259,155 234,880 68,265 67,535 94,310 93,415 117,220 114,340 171,060 166,575 231,520 221,275 272,120 262,990 65,245 64,955 90,150 89,720 111,940 110,315 163,275 160,500 221,000 214,500 259,580 254,970 63,225 63,225 87,445 87,445 108,420 107,810 158,090 156,750 214,370 210,210 251,670 249,135 FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 65,765 65,765 89,570 89,570 107,005 106,880 163,070 161,740 199,955 192,725 225,230 222,750 59,135 59,135 80,650 80,650 96,295 96,295 147,305 147,305 179,220 179,220 205,095 205,095 54,800 54,800 74,815 74,815 89,340 89,340 136,685 136,685 166,485 166,485 190,460 190,460 65,675 65,675 89,430 89,430 106,640 106,640 163,100 163,100 198,480 198,480 227,075 227,075 59,190 59,190 80,730 80,730 96,350 96,350 147,390 147,390 179,465 179,465 205,310 205,310 54,850 54,850 74,885 74,885 89,430 89,430 136,825 136,825 166,660 166,660 190,660 190,660 28.8 GPM 35.9 GPM 54.9 GPM 71.9 GPM 86.5 GPM Flow Rates, Free-Cooling Coil Flow Rate 20.4 GPM Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975 3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870 5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940 7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200 7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975 10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080 Evaporator Coil, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2) 3/ 9.7 3/ 14.6 3/ 14.6 3/ 19.8 3/ 24.3 3/ 24.3 FC Coil: Rows/Face Area (ft2) 4/ 9.0 4/ 9.0 4/ 9.0 4/ 12.2 4/ 14.2 4/ 14.2 DX Glycol Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" 072-DG-FC 096-DG-FC 120-DG-FC 180-DG-FC 240-DG-FC 312-DG-FC Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control 4-15 5.1 Kw 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- (Standard) 4-15 5.1 Kw Cycling Cycling Modulating (0-10 Vdc) 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,960 Scroll, (2) 4,138 Scroll, (2) 5,278 Scroll, (2) 8,187 Scroll, (2) 11,011 Scroll, (2) 13,568 Total Heat of Rej. 92,447 Btu/h 130,382 Btu/h 162,550 Btu/h 249,027 Btu/h 326,144 Btu/h 391,777 Btu/h GPM @ 110°F EGT Unit PD (Ft. of H2O) 20.4 GPM 37.9 Ft. 28.8 GPM 27.5 Ft. 35.9 GPM 45.3 Ft. 54.9 GPM 34.7 Ft. 71.9 GPM 45.6 Ft. 86.5 GPM 52.8 Ft. Type Coaxial Coaxial Coaxial Plate-Finned Plate-Finned Plate-Finned DX- Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Regulating Valve: DX Hd Pr. Valve Type 3-way, 150 psig DX Condenser Source Regulating Valve - factory installed Free-Cooling Valve: FC Valve Size Cv 3/4" 7.5 Cv Standard Valve Type Optional Valve Combos 1.0" 14.0 Cv -------- 1.0" 14.0 Cv 1-1/4" 20.0 Cv 1-1/2" 28.0 Cv 3-way, 400 psig, Modulating (0-10 Vdc) - factory installed 1-1/2" 28.0 Cv -------- Please refer to page 3-9 for Higher Pressure Rated Valve Combination Options! Connection Sizes - Copper Condensate Drain, (w/ pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet Source Glycol In/Out 1/4" OD 1-1/8" OD 1/4" OD 1-3/8" OD 1/4" OD 1-3/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) - DX Glycol Cooled w/ FC (6 to 26 Ton Systems) Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution Performance Data "VFS" Model 4-9 DX Water Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" Performance Data - DX Water Cooled w/ FC (6 to 26 Ton Systems) 4-10 "VFS" Model 072-DW-FC 096-DW-FC 120-DW-FC 180-DW-FC 240-DW-FC 312-DW-FC NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 78,245 70,325 107,525 97,990 134,380 117,420 194,200 170,840 266,500 223,315 313,200 262,975 74,645 68,105 102,660 94,835 128,280 114,105 185,100 165,600 254,175 217,746 298,440 256,460 72,315 66,275 99,565 92,355 124,420 111,475 179,270 161,650 246,560 213,170 289,410 251,145 76,190 73,500 105,540 101,910 131,100 124,110 189,535 180,125 258,940 238,330 303,540 281,450 72,770 71,060 100,900 98,430 125,260 120,390 180,820 174,215 247,070 232,000 289,225 273,950 70,500 69,550 97,860 96,205 121,475 118,100 175,045 170,685 239,655 227,695 280,410 268,110 FREE-COOLING CAPACITY - BTU/H @ 45°F Entering Water Temperature, 0% Glycol Solution 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 88,135 78,640 111,680 101,105 125,865 114,380 189,920 172,425 222,920 201,895 246,390 231,135 77,160 74,290 98,100 95,710 110,785 108,390 167,565 163,550 196,500 191,420 221,265 221,085 70,670 70,670 90,080 90,080 101,900 101,900 154,380 154,380 180,985 180,985 206,050 206,050 84,515 83,810 107,605 107,605 121,660 121,660 184,230 184,230 215,965 215,965 245,270 245,270 75,170 75,170 96,195 96,195 109,150 109,150 165,705 165,705 194,260 194,260 222,015 222,015 69,690 69,690 89,370 89,370 101,410 101,410 153,965 153,965 185,510 185,510 206,280 206,280 27.0 GPM 33.5 GPM 51.6 GPM 67.4 GPM 80.5 GPM Flow Rates, Free-Cooling Coil Flow Rate 19.1 GPM Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975 3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870 5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940 7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200 7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975 10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080 Evaporator Coil, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2) 3/ 9.7 3/ 14.6 3/ 14.6 3/ 19.8 3/ 24.3 3/ 24.3 FC Coil: Rows/Face Area (ft2) 4/ 9.0 4/ 9.0 4/ 9.0 4/ 12.2 4/ 14.2 4/ 14.2 DX Water Cooled w/ Free-Cooling - 6 to 26 Ton "VFS" 072-DW-FC 096-DW-FC 120-DW-FC 180-DW-FC 240-DW-FC 312-DW-FC Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Steam Output, Lbs/Hour Power Input Std Control Optional Control 4-15 5.1 Kw 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- (Standard) 4-15 5.1 Kw Cycling Cycling Modulating (0-10 Vdc) 4-15 5.1 Kw 4-15 5.1 Kw Cycling Cycling ----------------------- Compressors - Heat pump duty rated Scroll - HCFC R-22 Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,174 Scroll, (2) 3,042 Scroll, (2) 3,865 Scroll, (2) 6,315 Scroll, (2) 8,523 Scroll, (2) 10,289 Total Heat of Rej. 95,482 Btu/h 135,100 Btu/h 167,617 Btu/h 258,040 Btu/h 337,181 Btu/h 402,707 Btu/h GPM @ 85°F EWT/95°F LWT Unit PD (Ft. of H2O) 19.1 GPM 24.2 Ft. 27.0 GPM 20.6 Ft. 33.5 GPM 31.3 Ft. 51.6 GPM 24.4 Ft. 67.4 GPM 32.7 Ft. 80.5 GPM 37.5 Ft. Type Coaxial Coaxial Coaxial Plate-Finned Plate-Finned Plate-Finned DX- Head Pressure & Free-Cooling Coil Control Valve Combinations DX Head Pressure Regulating Valve: DX Hd Pr. Valve Type 3-way, 150 psig DX Condenser Source Regulating Valve - factory installed Free-Cooling Valve: FC Valve Size Cv 3/4" 7.5 Cv Standard Valve Type Optional Valve Combos 1.0" 14.0 Cv -------- 1.0" 14.0 Cv 1-1/4" 20.0 Cv 1-1/2" 28.0 Cv 3-way, 400 psig, Modulating (0-10 Vdc) - factory installed 1-1/2" 28.0 Cv -------- Please refer to page 3-9 for Higher Pressure Rated Valve Combination Options! Connection Sizes - Copper Condensate Drain, (w/ pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet Source Glycol In/Out 1/4" OD 1-1/8" OD 1/4" OD 1-3/8" OD 1/4" OD 1-3/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD 1/4" OD 2-1/8" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) - DX Water Cooled w/ FC (6 to 26 Ton Systems) Water Cooled Condenser Data - Based on 0% Glycol Solution Performance Data "VFS" Model 4-11 DX Air Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" Performance Data "VFS" Model - DX Air Cooled w/ AWS (6 to 26 Ton Systems) 4-12 072-DAR-AWS 096-DAR-AWS 120-DAR-AWS 180-DAR-AWS 240-DAR-AWS 312-DAR-AWS AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 84,570 77,200 17.0 / (0.9) 102,530 97,445 20.5 / (1.2) 114,540 109,855 23.0 / (1.7) 172,100 165,305 34.6 / (2.3) 198,605 192,190 40.0 / (3.4) 219,810 219,810 44.2 / (4.1) 72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 69,310 69,310 13.9 / (0.6) 86,055 86,055 17.3 / (1.0) 97,070 97,070 19.5 / (1.3) 147,725 147,725 29.7 / (1.8) 171,585 171,585 34.5 / (2.6) 193,290 193,290 38.8 / (3.2) 70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,925 60,925 12.2 / (0.5) 76,095 76,095 15.2 / (0.7) 86,330 86,330 17.2 / (1.0) 132,105 132,105 26.5 / (1.4) 154,950 154,950 31.1 / (2.2) 174,705 174,705 35.1 / (2.7) 75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 80,115 80,115 16.0 / (0.8) 99,540 99,540 20.0 / (1.2) 111,795 111,795 22.4 / (1.6) 169,345 169,345 34.0 / (2.2) 195,820 195,820 39.3 / (3.3) 221,045 221,045 44.4 / (4.1) 72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 68,335 68,335 13.7 / (0.6) 85,350 85,350 17.0 / (0.9) 96,975 96,975 19.5 / (1.3) 147,720 147,720 29.7 / (1.8) 171,580 171,580 34.5 / (2.6) 193,610 193,610 38.9 / (3.2) 70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,860 60,860 12.2 / (0.5) 76,165 76,165 15.2 / (0.7) 86,755 86,755 17.4 / (1.1) 132,400 132,400 26.6 / (1.4) 155,630 155,630 31.5 / (2.2) 174,895 174,895 35.1 / (2.7) NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 70,915 67,020 97,935 92,500 122,825 111,200 185,450 173,650 241,420 215,410 287,260 250,390 67,570 64,745 93,435 89,185 117,130 107,670 176,580 169,340 230,230 211,055 273,826 243,640 65,470 63,135 90,560 86,685 113,495 104,975 171,340 165,145 223,785 206,330 265,460 238,480 69,585 69,585 96,590 95,245 120,150 116,560 181,075 179,590 235,105 228,900 278,670 267,170 66,470 66,470 92,325 91,585 114,730 112,590 173,265 172,460 224,735 222,675 265,720 259,240 64,510 64,510 89,530 89,160 111,165 110,155 168,305 167,655 218,155 217,430 257,640 253,415 7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975 10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080 Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975 3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870 5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940 7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200 Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2) 3/ 9.7 3/ 14.6 3/ 14.6 3/ 19.8 3/ 24.3 3/ 24.3 AWS Coil: Rows/Face Area (ft2) 4/ 9.0 4/ 9.0 4/ 9.0 4/ 12.2 4/ 14.2 4/ 14.2 DX Air Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DAR-AWS 096-DAR-AWS 120-DAR-AWS 180-DAR-AWS 240-DAR-AWS 312-DAR-AWS Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control (Standard) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Cycling Cycling Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD 3/4"/(7.5 Cv) 24.2 Ft. Standard Valve Type 1"/(14.0 Cv) 20.6 Ft. -------- Optional Valve 1"/(14.0 Cv) 31.3 Ft. 1-1/4"/(14.0 Cv) 24.4 Ft. 1-1/2"/(14.0 Cv) 32.7 Ft. 3-way, 400 psig, Modulating (0-10 Vdc) - factory installed 1-1/2"/(14.0 Cv) 37.5 Ft. -------- Please refer to page 3-9 for 2-way and higher pressure valve options. Compressors - Heat pump duty rated Scroll - HCFC R-22 Scroll, (2) 2,785 Scroll, (2) 3,890 Scroll, (2) 4,950 Scroll, (2) 7,759 Scroll, (2) 10,448 Scroll, (2) 12,812 Total Heat of Rej. 92,991 Btu/h 131,494 Btu/h 163,488 Btu/h 250,800 Btu/h 328,337 Btu/h 394,083 Btu/h Connection Sizes - Copper, (Please refer to CyberTWO "VFS" IOM Manual for proper interconnecting refrigerant line sizing.) Refrigerant: Liquid Line, (Qty.) Hot Gas Line, (Qty.) 1/2" OD, (2) 5/8" OD, (2) 1/2" OD, (2) 5/8" OD, (2) 1/2" OD, (2) 5/8" OD, (2) 5/8" OD, (2) 7/8" OD, (2) 5/8" OD, (2) 1-1/8 OD, (2) 5/8" OD, (2) 1-1/8 OD, (2) AWS Coil Source In/Out 1-1/8" OD 1-3/8" OD 1-3/8" OD 2-1/8" OD 2-1/8" OD 2-1/8" OD Condensate Drain, (w/ pump) Humidifier Inlet 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) Remote Air Cooled Condenser Data: WCS-( ) - (Remote Outdoor Propeller Fan, Air Cooled Condenser for Model VFS-( )-DAR Evaporator Section) Model @ 95°F Amb. WCS-008 WCS-010 WCS-012 WCS-020 WCS-025 WCS-028 Condenser Fan Data CFM @ free discharge Motor Hp, (Qty.) 8,640 1/2 Hp, (1) 7,780 1/2 Hp, (1) 7,080 1/2 Hp, (1) 15,400 1.0 Hp, (2) 23,300 1.5 Hp, (2) 22,450 1.5 Hp, (2) 1/3 Hp, (1) 1/3 Hp, (1) 1/3 Hp, (1) ____ ____ ____ 164 179 195 536 580 630 1 1/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-1/8" OD, (2) 7/8" OD, (2) 1-3/8" OD, (2) 1-1/8" OD, (2) 1-3/8" OD, (2) 1-1/8" OD, (2) -20°F -20°F + Motor Hp, (Qty.) Net Weight (lbs) Refrigerant Connections - Copper Hot Gas Line, (Qty.) 7/8" OD, (2) Liquid Line, (Qty.) 5/8" OD, (2) Low Ambient Control Std Min. Oper. Amb. Optional Min. Oper. Amb -20°F -20°F -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) -30°F(Flooded) Compressors are located with the model VFS-( )-DAR Evaporator Section -20°F -20°F -30°F(Flooded) -30°F(Flooded) - DX Air Cooled w/ AWS (6 to 26 Ton Systems) Type, (Qty.) Watts Input (ea.) Performance Data "VFS" Model 4-13 DX Water Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" Performance Data "VFS" Model - DX Water Cooled w/ AWS (6 to 26 Ton Systems) 4-14 072-DW-AWS 096-DW-AWS 120-DW-AWS 180-DW-AWS 240-DW-AWS 312-DW-AWS AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 84,570 77,200 17.0 / (0.9) 102,530 97,445 20.5 / (1.2) 114,540 109,855 23.0 / (1.7) 172,100 165,305 34.6 / (2.3) 198,605 192,190 40.0 / (3.4) 219,810 219,810 44.2 / (4.1) 72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 69,310 69,310 13.9 / (0.6) 86,055 86,055 17.3 / (1.0) 97,070 97,070 19.5 / (1.3) 147,725 147,725 29.7 / (1.8) 171,585 171,585 34.5 / (2.6) 193,290 193,290 38.8 / (3.2) 70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,925 60,925 12.2 / (0.5) 76,095 76,095 15.2 / (0.7) 86,330 86,330 17.2 / (1.0) 132,105 132,105 26.5 / (1.4) 154,950 154,950 31.1 / (2.2) 174,705 174,705 35.1 / (2.7) 75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 80,115 80,115 16.0 / (0.8) 99,540 99,540 20.0 / (1.2) 111,795 111,795 22.4 / (1.6) 169,345 169,345 34.0 / (2.2) 195,820 195,820 39.3 / (3.3) 221,045 221,045 44.4 / (4.1) 72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 68,335 68,335 13.7 / (0.6) 85,350 85,350 17.0 / (0.9) 96,975 96,975 19.5 / (1.3) 147,720 147,720 29.7 / (1.8) 171,580 171,580 34.5 / (2.6) 193,610 193,610 38.9 / (3.2) 70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,860 60,860 12.2 / (0.5) 76,165 76,165 15.2 / (0.7) 86,755 86,755 17.4 / (1.1) 132,400 132,400 26.6 / (1.4) 155,630 155,630 31.5 / (2.2) 174,895 174,895 35.1 / (2.7) NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 78,245 70,325 107,525 97,990 134,380 117,420 194,200 170,840 266,500 223,315 313,200 262,975 74,645 68,105 102,660 94,835 128,280 114,105 185,100 165,600 254,175 217,746 298,440 256,460 72,315 66,275 99,565 92,355 124,420 111,475 179,270 161,650 246,560 213,170 289,410 251,145 76,190 73,500 105,540 101,910 131,100 124,110 189,535 180,125 258,940 238,330 303,540 281,450 72,770 71,060 100,900 98,430 125,260 120,390 180,820 174,215 247,070 232,000 289,225 273,950 70,500 69,550 97,860 96,205 121,475 118,100 175,045 170,685 239,655 227,695 280,410 268,110 7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975 10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080 Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975 3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870 5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940 7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200 Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2) 3/ 9.7 3/ 14.6 3/ 14.6 3/ 19.8 3/ 24.3 3/ 24.3 AWS Coil: Rows/Face Area (ft2) 4/ 9.0 4/ 9.0 4/ 9.0 4/ 12.2 4/ 14.2 4/ 14.2 DX Water Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DW-AWS 096-DW-AWS 120-DW-AWS 180-DW-AWS 240-DW-AWS 312-DW-AWS 15.03 Kw 66,900 (19.6 Kw) 2-Stages 20.04 Kw 84,000 (24.6 Kw) 2-Stages 25.05 Kw 108,000 (31.6 Kw) 2-Stages Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 2-Stages 2-Stages 2-Stages Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control (Standard) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Cycling Cycling Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD 3/4" / (7.5 Cv) 24.2 Ft. Standard Valve Type 1" / (14.0 Cv) 20.6 Ft. -------- Optional Valve 1" / (14.0 Cv) 31.3 Ft. 1-1/4" / (14.0 Cv) 24.4 Ft. 1-1/2" / (14.0 Cv) 32.7 Ft. 3-way, 400 psig, Modulating (0-10 Vdc) - factory installed 1-1/2" / (14.0 Cv) 37.5 Ft. -------- Please refer to page 3-10 for 2-way and higher pressure valve options. Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,174 Scroll, (2) 3,042 Scroll, (2) 3,865 Scroll, (2) 6,315 Scroll, (2) 8,523 Scroll, (2) 10,289 DX Water Cooled Condenser Data - Based on 0% Glycol Solution Total Heat of Rej. 95,482 Btu/h 135,100 Btu/h 167,617 Btu/h 258,040 Btu/h 337,181 Btu/h 402,707 Btu/h GPM @ 85°F EWT / 95°F LWT Unit Press. Drop (Ft. of H2O) 19.1 GPM 24.2 Ft. 27.0 GPM 20.6 Ft. 33.5 GPM 31.3 Ft. 51.6 GPM 24.4 Ft. 67.4 GPM 32.7 Ft. 80.5 GPM 37.5 Ft. Condenser Type Coaxial Coaxial Coaxial Plate-Finned Plate-Finned Plate-Finned Head Pressure Control Standard Control Optional Control 2-way, 150 psig Water Regulating Valves, (factory installed) Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options ! Connection Sizes - Copper DX Source Water In/Out 1-1/8" OD 1-3/8" OD 1-3/8" OD 2-1/8" OD 2-1/8" OD 2-1/8" OD AWS Coil Source In/Out 1-1/8" OD 1-3/8" OD 1-3/8" OD 2-1/8" OD 2-1/8" OD 2-1/8" OD Condensate Drain, (w/ pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) - DX Water Cooled w/ AWS (6 to 26 Ton Systems) Compressors - Heat pump duty rated Scroll - HCFC R-22 Performance Data "VFS" Model 4-15 DX Glycol Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" Performance Data "VFS" Model - DX Glycol Cooled w/ AWS (6 to 26 Ton Systems) 4-16 072-DG-AWS 096-DG-AWS 120-DG-AWS 180-DG-AWS 240-DG-AWS 312-DG-AWS AWS COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (includes motor heat @ std 0.5" e.s.p.) 75°FDB/62.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 84,570 77,200 17.0 / (0.9) 102,530 97,445 20.5 / (1.2) 114,540 109,855 23.0 / (1.7) 172,100 165,305 34.6 / (2.3) 198,605 192,190 40.0 / (3.4) 219,810 219,810 44.2 / (4.1) 72°FDB/60°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 69,310 69,310 13.9 / (0.6) 86,055 86,055 17.3 / (1.0) 97,070 97,070 19.5 / (1.3) 147,725 147,725 29.7 / (1.8) 171,585 171,585 34.5 / (2.6) 193,290 193,290 38.8 / (3.2) 70°FDB/58.5°FWB, 50% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,925 60,925 12.2 / (0.5) 76,095 76,095 15.2 / (0.7) 86,330 86,330 17.2 / (1.0) 132,105 132,105 26.5 / (1.4) 154,950 154,950 31.1 / (2.2) 174,705 174,705 35.1 / (2.7) 75°FDB/61°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 80,115 80,115 16.0 / (0.8) 99,540 99,540 20.0 / (1.2) 111,795 111,795 22.4 / (1.6) 169,345 169,345 34.0 / (2.2) 195,820 195,820 39.3 / (3.3) 221,045 221,045 44.4 / (4.1) 72°FDB/58.5°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 68,335 68,335 13.7 / (0.6) 85,350 85,350 17.0 / (0.9) 96,975 96,975 19.5 / (1.3) 147,720 147,720 29.7 / (1.8) 171,580 171,580 34.5 / (2.6) 193,610 193,610 38.9 / (3.2) 70°FDB/57°FWB, 45% RH Med. Flow Total (10°F ΔTw) Sens. GPM / (pd. psi) 60,860 60,860 12.2 / (0.5) 76,165 76,165 15.2 / (0.7) 86,755 86,755 17.4 / (1.1) 132,400 132,400 26.6 / (1.4) 155,630 155,630 31.5 / (2.2) 174,895 174,895 35.1 / (2.7) NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ AWS evaporator motor heat @ std CFM & e.s.p. ratings) 75°FDB/62.5°FWB, 50% RH Total Sensible 72°FDB/60°FWB, 50% RH Total Sensible 70°FDB/58.5°FWB, 50% RH Total Sensible 75°FDB/61°FWB, 45% RH Total Sensible 72°FDB/58.5°FWB, 45% RH Total Sensible 70°FDB/57°FWB, 45% RH Total Sensible 69,610 65,460 95,490 91,030 119,725 109,440 174,540 159,760 237,750 208,890 280,370 246,790 66,390 63,120 91,100 87,675 114,150 105,850 166,350 154,340 226,750 202,950 267,365 240,020 64,320 61,340 88,280 85,175 110,560 103,125 161,050 150,275 219,760 198,300 259,155 234,880 68,265 67,535 94,310 93,415 117,220 114,340 171,060 166,575 231,520 221,275 272,120 262,990 65,245 64,955 90,150 89,720 111,940 110,315 163,275 160,500 221,000 214,500 259,580 254,970 63,225 63,225 87,445 87,445 108,420 107,810 158,090 156,750 214,370 210,210 251,670 249,135 7.5 Hp, (1) 10,250 @ 0.5" Belt Driven two 975 10.0 Hp, (1) 12,300 @ 0.5" Belt Driven two 1,080 Evaporator Blower / Motor, DX w/ AWS - DWDI Centrifugal, Variable Pitch Pulleys Horsepower, (Qty.) CFM @ ext. st. press. Drive Method Qty. of Blowers Blower RPM 2.0 Hp, (1) 3,750 @ 0.5" Belt Driven one 975 3.0 Hp, (1) 5,000 @ 0.5" Belt Driven one 870 5.0 Hp, (1) 5,750 @ 0.5" Belt Driven one 940 7.5 Hp, (1) 8,750 @ 0.5" Belt Driven two 1,200 Evaporator Coil, (Both DX & AWS Respectively) - Aluminum Fin, Copper Tube DX Coil: Rows/Face Area (ft2) 3/ 9.7 3/ 14.6 3/ 14.6 3/ 19.8 3/ 24.3 3/ 24.3 AWS Coil: Rows/Face Area (ft2) 4/ 9.0 4/ 9.0 4/ 9.0 4/ 12.2 4/ 14.2 4/ 14.2 DX Glycol Cooled w/ Alternate Water Source - 6 to 26 Ton "VFS" 072-DG-AWS 096-DG-AWS 120-DG-AWS 180-DG-AWS 240-DG-AWS 312-DG-AWS Reheat/Heat - BTU/H Performance Capacities Include Motor Heat ELECTRIC REHEAT / HEAT Heater Kw Rating Tot. BTU/H w/ Motor Heat (Kw) No. of Stages Finned Tubular Heaters, (Standard) 10.02 Kw 15.03 Kw 15.03 Kw 15.03 Kw 20.04 Kw 25.05 Kw 38,970 (11.4 Kw) 57,680 (16.9 Kw) 60,750 (17.8 Kw) 66,900 (19.6 Kw) 84,000 (24.6 Kw) 108,000 (31.6 Kw) 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages 2-Stages Humidification - Electrode Steam Canister Humidifier with Adjustable Output, Lbs/Hour, (Kw Input) Std Control (Standard) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1) Cycling Cycling Cycling Cycling Cycling Cycling Alternate Water Source Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions AWS Valve Size / (Cv) Total AWS Unit PD 3/4" / (7.5 Cv) 24.2 Ft. Standard Valve Type 1" / (14.0 Cv) 20.6 Ft. -------- Optional Valve 1" / (14.0 Cv) 31.3 Ft. 1-1/4" / (14.0 Cv) 24.4 Ft. 1-1/2" / (14.0 Cv) 32.7 Ft. 3-way, 400 psig, Modulating (0-10 Vdc) - factory installed 1-1/2" / (14.0 Cv) 37.5 Ft. -------- Please refer to page 3-10 for 2-way and higher pressure valve options. Type, (Qty.) Watts Input (ea.) Scroll, (2) 2,960 Scroll, (2) 4,138 Scroll, (2) 5,278 Scroll, (2) 8,187 Scroll, (2) 11,011 Scroll, (2) 13,568 DX Glycol Cooled Condenser Data - Based on 40% Ethylene Glycol Solution Total Heat of Rej. 92,447 Btu/h 130,382 Btu/h 162,550 Btu/h 249,027 Btu/h 326,144 Btu/h 391,777 Btu/h GPM @ 110°F EGT Unit Press. Drop (Ft. of H2O) Condenser Type 20.4 GPM 26.6 Ft. Coaxial 28.8 GPM 22.4 Ft. Coaxial 35.9 GPM 34.4 Ft. Coaxial 54.9 GPM 27.2 Ft. Plate-Finned 71.9 GPM 36.2 Ft. Plate-Finned 86.5 GPM 41.9 Ft. Plate-Finned Head Pressure Control Standard Control Optional Control 2-way, 150 psig Water Regulating Valves, (factory installed) Refer to page 3-9 of the Optional Guide Specifications Section for High Pressure and 3-way Valve Options ! Connection Sizes - Copper DX Source Water In/Out 1-1/8" OD 1-3/8" OD 1-3/8" OD 2-1/8" OD 2-1/8" OD 2-1/8" OD AWS Coil Source In/Out 1-1/8" OD 1-3/8" OD 1-3/8" OD 2-1/8" OD 2-1/8" OD 2-1/8" OD Condensate Drain, (w/ pump) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) 7/8" OD, (1/2"OD) Humidifier Inlet 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD 1/4" OD Filters - 4" deep, 30% "Dust-Spot" Efficient Pleated Throwaway Down-Flow: Nom. Size (in.), (Qty.) 20x25x4, (3) 20x25x4, (3) 20x25x4, (3) 20x25x4, (4) 20x25x4, (5) 20x25x4, (5) Up-Flow (Front-Free Return): Nom. Size (in.), (Qty.) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 16x20x4, (2) 20x20x4, (2) 29x18x4, (4) ____ 18x18x4, (6) 29x18x4, (1) 18x18x4, (6) 29x18x4, (1) - DX Water Cooled w/ AWS (6 to 26 Ton Systems) Compressors - Heat pump duty rated Scroll - HCFC R-22 Performance Data "VFS" Model 4-17 Electrical Data - Index Electrical Data CyberTWO Floor AC's FLA / MCA / MFS INDEX MODEL TYPE ......................................... page DX - Compressorized Systems Single Compressor Systems: - Index • VFS-072/312-DAR, DW, & DG ........................................ 5-2 Free-Cooling & Alternate Water Source Alternate Water Source Systems: • VFS-072/312-D( )-AWS ................................................... 5-3 Free-Cooling Systems: • VFS-072/312-D( )-FC ...................................................... 5-3 Electrical Data Calculation Examples Example 1: • VFS-120-DAR-D .............................................................. 5-4 Example 2: • VFS-312-DW-U ............................................................... 5-4 << Electrical Data Notes >> 1) Electrical Data is based on standard performance and component selection per Section 4 of this brochure. Please consult your local Sales Representative for "special" equipment electrical data. 2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's and External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data for this Option. 5-1 Electrical Data FLA (OEM rated) DAR DW DG M CA VFS-096-DAR, DW & DG M FS FLA (OEM rated) DAR DW DG M CA VFS-120-DAR, DW & DG M FS FLA (OEM rated) DAR DW DG M CA M FS COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60 44.6 44.6 44.6 55.7 60 58.5 58.5 58.5 73.2 80 61.3 60.9 62.1 80.3 90 460/3/60 22.1 22.1 22.1 27.6 30 29.1 29.1 29.1 37.6 40 31.2 30.3 31.6 41.1 45 575/3/60 18.0 18.0 18.0 22.5 25 23.5 23.5 23.5 30.1 35 25.1 24.5 25.5 32.9 35 80.3 90 } Standard Unit Data COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 37.9 39.5 50.9 60 55.5 53.7 56.1 72.5 75 61.3 58.9 62.1 20.0 19.4 20.2 25.9 30 28.3 27.4 28.6 37.6 40 31.2 30.0 31.6 41.1 45 16.2 15.8 16.4 21.2 25 22.8 22.1 23.0 30.1 35 25.1 24.2 25.5 32.9 35 208/3/60 39.1 460/3/60 575/3/60 COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60 36.8 34.4 37.6 45.1 50 43.2 39.6 44.4 54.6 60 52.4 47.6 54.0 66.6 80 460/3/60 18.2 17.0 18.6 22.3 25 21.4 19.6 22.0 28.7 35 26.0 23.6 26.8 33.9 40 575/3/60 14.9 13.9 15.2 18.5 20 17.4 15.9 17.8 22.8 25 21.1 19.2 21.7 27.2 35 46.7 46.7 46.7 58.4 70 35 COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60 30.4 460/3/60 15.7 575/3/60 12.8 30.4 37.9 40 15.7 15.7 19.6 20 22.7 12.8 12.8 16.0 20 18.3 30.4 44.3 44.3 55.4 60 22.7 22.7 28.3 30 23.9 23.9 23.9 29.8 18.3 18.3 22.9 25 19.3 19.3 19.3 24.1 25 44.3 COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60 22.6 20.2 23.4 30.9 40 29.0 25.4 30.2 40.4 50 38.2 33.4 39.8 52.4 70 460/3/60 11.8 10.6 12.2 15.9 20 15.0 13.2 15.6 22.3 30 19.6 17.2 20.4 27.5 35 575/3/60 9.7 8.7 10.0 13.3 15 12.2 10.7 12.6 17.6 20 15.9 14.0 16.5 22.0 25 VFS-180-DAR, DW & DG MODEL FLA (OEM rated) DAR DW DG M CA VFS-240-DAR, DW & DG M FS FLA (OEM rated) DAR DW DG M CA VFS-312-DAR, DW & DG M FS FLA (OEM rated) DAR DW DG M CA M FS COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60 77.4 73.0 79.6 101.5 125 95.6 91.3 97.0 129.6 150 118.3 113.7 119.7 160.1 175 460/3/60 38.6 36.9 39.2 51.7 60 48.4 46.3 49.1 63.0 70 59.6 57.3 60.3 82.4 90 575/3/60 31.2 29.7 32.0 40.2 50 38.6 36.7 39.2 48.7 50 47.5 45.6 48.0 65.5 70 118.3 113.7 119.7 160.1 175 COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60 76.4 73.0 77.5 101.5 125 95.6 91.3 97.0 129.6 150 460/3/60 38.6 36.9 39.1 51.7 60 48.4 46.3 49.1 63.0 70 59.6 57.3 60.3 82.4 90 575/3/60 31.2 29.7 31.6 40.2 45 38.6 36.7 39.2 48.7 50 47.5 45.6 48.0 65.5 70 COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60 77.4 70.6 79.6 100.6 125 90.6 82.0 93.4 122.9 150 102.4 93.2 105.2 142.8 175 460/3/60 38.2 34.8 39.2 50.9 60 45.2 41.0 46.6 57.2 70 51.0 46.4 52.4 74.5 90 575/3/60 31.1 28.1 32.0 38.5 50 35.9 32.1 37.1 42.6 50 40.6 37.0 41.8 59.2 70 COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60 63.2 56.4 65.4 86.4 100 460/3/60 31.8 28.4 32.8 44.5 60 575/3/60 25.9 22.9 26.8 33.3 45 67.8 79.2 108.7 150 88.2 85.5 91.0 128.6 175 38.8 34.6 40.2 50.8 70 44.6 43.2 46.0 68.1 90 30.7 26.9 31.9 37.4 50 35.4 34.4 36.6 54.0 70 76.4 COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60 63.2 56.4 65.4 86.4 100 76.4 67.8 79.2 108.7 150 88.2 79.0 91.0 128.6 175 460/3/60 31.8 28.4 32.8 44.5 60 38.8 34.6 40.2 50.8 70 44.6 40.0 46.0 68.1 90 26.8 33.3 45 31.9 37.4 50 36.6 54.0 70 575/3/60 25.9 22.9 30.7 26.9 35.4 31.8 - DX Compressorized Systems } Standard Unit Data Electrical Data VFS-072-DAR, DW & DG MODEL - DX Compressorized Systems Table Legend: FLA M C A M FS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Consult the Factory for electrical data for 50Hz power supply requirements. 5-2 Electrical Data Electrical Data VFS-072-DAR/DW/DG-AWS/FC MODEL FLA (OEM rated) DAR DW DG M CA M FS - Free-Cooling / Alternate Water Source VFS-096-DAR/DW/DG-AWS/FC FLA (OEM rated) DAR DW DG M CA M FS VFS-120--DAR/DW/DG-AWS/FC FLA (OEM rated) DAR DW DG M CA M FS COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60 46.0 46.0 46.0 57.4 60 60.9 60.9 60.9 76.2 80 66.5 66.1 67.3 85.5 90 460/3/60 22.8 22.8 22.8 28.5 30 30.3 30.3 30.3 38.8 40 33.8 32.9 34.2 43.7 45 575/3/60 18.5 18.5 18.5 23.1 25 24.5 24.5 24.5 31.1 35 27.2 26.6 27.6 35.0 40 66.5 64.1 67.3 85.5 90 45 40 } Standard Unit Data } Standard Unit Data COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60 40.5 39.3 40.9 52.3 60 30 29.5 25 23.8 460/3/60 20.7 20.1 20.9 26.6 575/3/60 16.7 16.3 16.9 21.7 57.9 58.5 74.9 80 28.6 29.8 38.8 40 33.8 32.6 34.2 43.7 23.1 24.0 31.1 35 27.2 26.3 27.6 35.0 56.1 COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) - Free-Cooling / Alternate Water Source Systems 5-3 208/3/60 38.2 35.8 39.0 46.5 50 45.6 42.0 46.8 57.0 70 57.6 52.8 59.2 71.8 90 460/3/60 18.9 17.7 19.3 23.0 25 22.6 20.8 23.2 29.9 35 28.6 26.2 29.4 36.5 45 575/3/60 15.4 14.4 15.7 19.0 20 18.4 16.9 18.8 23.8 30 23.2 21.3 23.8 29.3 35 COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60 31.8 31.8 31.8 39.7 40 46.7 46.7 46.7 58.4 60 51.9 51.9 51.9 64.9 70 460/3/60 16.4 16.4 16.4 20.5 25 23.9 23.9 23.9 29.8 30 26.5 26.5 26.5 33.1 40 575/3/60 13.3 13.3 13.3 16.6 20 19.3 19.3 19.3 24.1 25 21.4 21.4 21.4 26.7 30 COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60 24.0 21.6 24.8 32.3 40 31.4 27.8 32.6 42.8 50 43.4 38.6 45.0 57.6 70 460/3/60 12.5 11.3 12.9 16.6 20 16.2 14.4 16.8 23.5 30 22.2 19.8 23.0 30.1 40 575/3/60 10.2 9.2 10.5 13.8 15 13.2 11.7 13.6 18.6 25 18.0 16.1 18.6 24.1 30 VFS-180-DAR-AWS,DW/DG-FC MODEL FLA (OEM rated) DAR DW DG M CA M FS VFS-240-DAR-AWS,DW/DG-FC FLA (OEM rated) DAR DW DG M CA M FS VFS-312-DAR-AWS,DW/DG-FC FLA (OEM rated) DAR DW DG M CA M FS COOLING with ELECT RIC REHEAT /HEAT and HUMIDIFIER 208/3/60 85.8 81.4 88.0 109.9 125 104.0 99.7 105.4 138.0 175 124.7 120.1 126.1 166.5 175 460/3/60 42.8 41.1 43.4 55.9 70 52.6 50.5 53.3 67.2 80 62.8 60.5 63.5 85.6 100 575/3/60 34.1 32.6 34.9 43.1 50 41.5 39.6 42.1 51.6 60 50.3 48.4 50.8 68.3 80 COOLING and ELECT RIC REHEAT /HEAT ONLY, (No Humidifier) 208/3/60 84.8 81.4 85.9 109.9 125 104.0 99.7 105.4 138.0 150 124.7 120.1 126.1 166.5 175 460/3/60 42.8 41.1 43.3 55.9 60 52.6 50.5 53.3 67.2 80 62.8 60.5 63.5 85.6 100 575/3/60 34.1 32.6 34.5 43.1 50 41.5 39.6 42.1 51.6 60 50.3 48.4 50.8 68.3 80 COOLING and HUMIDIFIER ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Electric RH/HT ) 208/3/60 85.8 79.0 88.0 109.0 125 99.0 90.4 101.8 131.3 175 108.8 99.6 111.6 149.2 175 70 49.4 45.2 50.8 61.4 80 54.2 49.6 55.6 77.7 100 50 38.8 35.0 40.0 45.5 50 43.4 39.8 44.6 62.0 80 460/3/60 42.4 39.0 43.4 55.1 575/3/60 34.0 31.0 34.9 41.4 COOLING and ELECT RIC HEAT ONLY, (No Electric Reheat or Humidifier) 208/3/60 71.6 64.8 73.8 94.8 125 84.8 76.2 87.6 117.1 150 94.6 91.9 97.4 135.0 175 460/3/60 36.0 32.6 37.0 48.7 60 43.0 38.8 44.4 55.0 70 47.8 46.4 49.2 71.3 90 575/3/60 28.8 25.8 29.7 36.2 45 33.6 29.8 34.8 40.3 50 38.2 37.2 39.4 56.8 70 COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat 208/3/60 71.6 64.8 73.8 94.8 125 84.8 76.2 87.6 117.1 150 94.6 85.4 97.4 135.0 175 460/3/60 36.0 32.6 37.0 48.7 60 43.0 38.8 44.4 55.0 70 47.8 43.2 49.2 71.3 90 575/3/60 28.8 25.8 29.7 36.2 45 33.6 29.8 34.8 40.3 50 38.2 34.6 39.4 56.8 70 Table Legend: FLA M C A M FS FLA = Full Load Amps MCA = Minimum Circuit Amps (wire size amps) MFS = Maximum Fuse Size Consult the Factory for electrical data for 50Hz power supply requirements. Electrical Data - Calculation Examples Electrical Data Calculation Example 1: Example 2: Suppose an application calls for a nominal 10 Ton CyberAiR model VFS-120-DAR-D with the following standard features: Suppose an application calls for a nominal 26 Ton CyberAiR model VFS-312-DW-U system with the following features: VFS-120-DAR-D VFS-312-DW-U - - 460/3/60 Main Power Supply (both evap and cond) 15 kW Electric Reheat/Heat (2-stages), (Standard) 15 lb/hr Steam Humidifier, (Standard) 208/3/60 Main Power Supply Hot Gas Reheat in lieu of standard Electric Reheat No Humidifier Solution: Solution: From DX Compressorized Electrical Data table page 5-2 for model VFS-120-DAR-( ) incorporating COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER: From DX Compressorized Electrical Data table page 5-2 for model VFS-312-DW-( ) incorporating COOLING Only with or without Hot Gas Reheat (No Electric Reheat or Humidifier): FLA (OEM Rated) MCA MFS = = = 31.2 41.1 45 VFS-312-DW @ 208/3/60 w/ above options: FLA (OEM Rated) MCA MFS Table Legends: FLA M C A M FS FLA = MCA = MFS = Full Load Amps (OEM Rated Load Amps) Minimum Circuit Amps (wire size amps) Maximum Fuse Size Consult the Factory for electrical data for 50 Hz power supply requirements. = = = 79.0 128.6 175 - Calculation Examples VFS-120-DAR-D @ 460/3/60 w/ above options: Electrical Data EXAMPLES - 5-4 Physical Data - Standard "VFS" Configurations Physical Data "Index" (Drwg. #) D W MODEL TYPE ............. page H4 EVAPORATOR AIR OUTLET H2 Physical Data- Unit Weights H1 Unit Net Weights (lbs) Table ............................................. 6-2 - Index Unit Weight Calculation Examples .................................. 6-2 Vertical Floor System Dimensions 6-10 Ton: VFS-072/120-DAR, DW, DG-( ) (VF-01) "Down-Flow" Air Pattern Configuration ............... 6-3 (VF-02) "Up-Flow" Air Pattern Configuration .................... 6-4 EVAPORATOR AIR INLET 15-26 Ton: VFS-180/312-DAR, DW, DG & 180/312-( ) Up-Flow Air Patterns (VF-03) "Down-Flow" Air Pattern Configuration ............... 6-5 (VF-04) "Up-Flow" Air Pattern Configuration .................... 6-6 6-10 Ton: VFS-072/120-( )-FC/AWS-( ) (VF-07) "Down-Flow" Air Pattern Configuration ............... 6-7 (VF-08) "Up-Flow" Air Pattern Configuration .................... 6-8 EVAPORATOR AIR INLET D 15-26 Ton: VFS-180/312-( )-FC/AWS-( ): W (VF-09) "Down-Flow" Air Pattern Configuration ............... 6-9 (VF-10) "Up-Flow" Air Pattern Configuration .................... 6-10 Adjustable Floor Stand Dimensions H1 (VF-11) VFS-072/120-DAR, DW & DG .............................. 6-11 (VF-12) VFS-072/120-( )-AWS/FC .................................... 6-11 (VF-13) VFS-180/312-( ) All Models ................................. 6-12 EVAPORATOR AIR OUTLET Down-Flow Air Patterns 6-1 Physical Data - Unit Weights (lbs.) Physical Data "VFS" EVAPORATORS Approximate U nit Physical Weight (Standard Features Only Units, please see notes, Given in lbs.) Model 072-( ) 096-( ) 120-( ) 180-( ) 240-( ) 312-( ) VFS-( )-DAR-D 1,025 1,125 1,170 1,455 1,615 1,740 VFS-( )-DW-D 1,060 1,195 1,240 1,545 1,720 1,840 VFS-( )-DG-D 1,060 1,195 1,240 1,545 1,720 1,840 890 950 980 1,125 1,245 1,265 VFS-( )-( )-FC-D 1,245 1,410 1,470 1,815 2,055 2,180 VFS-( )-( )-AWS-D 1,185 1,315 1,375 1,700 1,885 2,01 0 VFS-( )-C-D Features/Options Model Sizes 072/120 180/312 Deleting Features: Steam Humidifier Electric Reheat Net Deduction - 25 lbs - 25 lbs - 20 lbs - 25 lbs Adding Features: Hot Gas Reheat Hot Water Reheat Steam Reheat -30 Flooded Control Condensate Pump + + + + + Net Addition 25 lbs + 35 lbs 25 lbs + 35 lbs 25 lbs + 35 lbs 100 lbs + 150 lbs 15 lbs + 15 lbs Features/Options Model Sizes 072/120 180/312 Adding Features: Upflow Air Pattern 2-way Plenum Box 3-way Plenum Box Floor Stand (12 " H) + + + + Net Addition 35 lbs + 40 lbs 85 lbs + 200 lbs 85 lbs + 200 lbs 30 lbs + 100 lbs Note 2: When substituting Hot Gas, Hot Water or Steam Reheat for standard Electric Reheat, DO NOT deduct the negative (-) weights shown above for Electric Reheat/Heat to the weights shown in the "VFS" EVAPORATOR weight table. The positive (+) weights shown above for Hot Gas, Hot Water or Steam Reheat should be added directly to the weights shown in the "VFS" EVAPORATOR weight table for these cases. (Please refer to Example-2 page 6-3.) - Unit Weights (lbs.) Note-1: Weights shown are for standard Evaporator units with standard Electric Reheat/ Heat and Steam Humidifier included. If these Standard features are deleted or Options are included, please add or delete the following approximate weights to the standard configuration weights shown in the adjacent table: EXAMPLES - VFS Physical Weight (lbs.) Calculations Example-1: Example-2: Suppose an application calls for a nominal 10 Ton CyberAiR model VFS-120-DAR-D with the following features: Suppose an application calls for a nominal 8 Ton CyberAiR model VFS-096-DW-U systems with the following features: VFS-120-DAR-D VFS-096-DW-U - - 15 kW Electric Reheat/Heat (2-stages), (Standard) 15 lb/hr Steam Humidifier, (Standard) Optional Condensate Pump (factory mounted) Optional 12" Floor Stand Hot Gas Reheat in lieu of Standard Electric Reheat No Humidifier Optional Condensate Pump (factory mounted) Optional 3-way Plenum Discharge Box Solution: Solution: From "VFS" EVAPORATORS Physical Weight Table page 62 for VFS-120-DAR-D: From "VFS" EVAPORATORS Physical Weight Table page 62 for VFS-096-DW-D (std base unit): VFS-120-DAR-D Steam Humidifier Electric Reheat Condensate Pump Floor Stand = = = = = 1,170 lbs (base unit) Incl. in base unit wt. incl. in base unit wt. + 15 lbs + 30 lbs VFS-120-DAR-D = 1,215 lbs (approx.) VFS-096-DW-D Up-Flow Air Pattern Hot Gas Reheat Delete Humidifier Condensate Pump 3-way Plenum Box = = = = = = 1,195 lbs (base unit) + 35 lbs + 25 lbs - 25 lbs + 15 lbs + 85 lbs VFS-096-DW-U = 1,330 lbs (approx.) 6-2 6 to 10 Ton - "Down-Flow" Air Pattern Systems Dimensional Data (VF-01) VFS-072 thru 120-DAR, DW, DG-D DIMENSIONAL DATA Std CFM @ 0.5" esp "Down-Flow" Vertical A/C ("Free-Return" or Optional "Ducted-Return") MODEL “M” VFS-072-( )-D 15.62" VFS-096 & 120-( )-D 18.62" Note: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET 68.0 - 6 to 10 Tons ("Down-Flow" Air Pattern Systems) 6-3 1.0 1.0 76.0 30.0 77.0 W/ OPTIONAL DUCT CONNECTION 4.0 20.5 17.0 M 70.0 (BASE) 72.0 (OVERALL) 32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR FRONT / LEFT Optional Floor Stand: See Page 6-11 (VF-11) EVAPORATOR AIR OUTLET INTO RAISED FLOOR PIPING / UTILITY CONNECTION SEE NOTE 1 REAR / RIGHT 6 to 10 Ton - "Up-Flow" Air Pattern Systems Note: "Up-Flow" Vertical A/C ("Front Free-Return" or Opt. "Rear Ducted-Return") (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. 70.0 (OPTIONAL) 2 OR 3 WAY PLENUM DISCHARGE BOX - FIELD INSTALLED 18.5 EVAPORATOR AIR OUTLET STANDARD 1.0" DUCT FLANGE CONNECTION 68.0 EVAPORATOR AIR OUTLET 1.0 77.0 W/ STANDARD DUCT CONNECTION 1.0 30.0 6.0 76.0 36.3 72.0 (OVERALL) 33.0 (OVERALL) OPTIONAL FILTER ACCESS 39.0 3.5 3.0 FRONT / LEFT Optional Floor Stand: See Page 6-11 (VF-11) REAR / RIGHT ("Up-Flow" Air Pattern Systems) 70.0 (BASE) 32.0 (BASE) OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION) EVAPORATOR AIR INLET - 6 to 10 Tons PIPING / UTILITY CONNECTIONS SEE NOTE 1 Dimensional Data (VF-02) VFS-072 thru 120-DAR, DW, DG-U 6-4 15 to 26 Ton - "Down-Flow" Air Pattern Systems Dimensional Data (VF-03) VFS-180 thru 312-DAR, DW, DG-D DIMENSIONAL DATA "Down-Flow" Vertical A/C ("Free-Return" or Optional "Ducted-Return") St d CFM @ 0.5" es p MODEL “ A” “B” “ C” “J” “K” “ M” VFS-180-( )-D 90.0" 88.0" 86.0" 17.5" 44.63" 15.62" VFS-240 & 312-( )-D 102.0" 100.0" 98.0" 19.0" 51.5" 18.62" Note: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET C - 15 to 26 Tons ("Down-Flow" Air Pattern Systems) 6-5 1.0 76.0 77.0 W/ OPTIONAL DUCT CONNECTION 1.0 4.0 30.0 20.5 J K M M B (BASE) A (OVERALL) 32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR FRONT / LEFT Optional Floor Stand: See Page 6-12 (VF-13) EVAPORATOR AIR OUTLET INTO RAISED FLOOR PIPING / UTILITY CONNECTIONS SEE NOTE 1 REAR / RIGHT 15 to 26 Ton - "Up-Flow" Air Pattern Systems "Up-Flow" Vertical A/C ("Front Free-Return" or Opt. "Rear Ducted-Return") DIMENSIONAL DATA MODEL “ A” “B ” “ C” “ H” VFS-180-( )-U 90.0" 88.0" 86.0" 58.5" VFS-240 & 312-( )-U 102.0" 100.0" 98.0" 73.5" Note: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. B OPTIONAL 2 OR 3 WAY PLENUM DISCHARGE BOX - FIELD INSTALLED 18.5 STANDARD 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR OUTLET PIPING / UTILITY CONNECTIONS SEE NOTE 1 Dimensional Data (VF-04) VFS-180 thru 312-DAR, DW, DG-U EVAPORATOR AIR OUTLET C 1.0 6.0 1.0 30.0 36.3 EVAPORATOR AIR INLET A (OVERALL) 32.0 (BASE) 33.0 (OVERALL) OPTIONAL FILTER ACCESS 3.5 3.0 FRONT / LEFT Optional Floor Stand: See Page 6-12 (VF-13) REAR / RIGHT OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION) ("Up-Flow" Air Pattern Systems) H (BASE) - 15 to 26 Tons 77.0 W/ STANDARD DUCT CONNECTION 76.0 6-6 Free-Cooling / Alternate Water Source - 6 to 10 Ton, "Down-Flow" Dimensional Data DIMENSIONAL DATA (VF-07) VFS-072 thru 120-( )-FC/AWS-D Std CFM @ 0.5" esp "Down-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Free-Return" or Opt. "Ducted-Return") MODEL “M” VFS-072-( )-FC/AWS-D 15.62" VFS-096 & 120-( )-FC/AWS-D 18.62" Note: STANDARD FILTER BOX FIELD INSTALLED (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET 80.0 12.0 1.0 89.0 W/ OPTIONAL DUCT CONNECTION 1.0 30.0 88.0 76.0 - 6 to 10 Tons (FC/AWS "Down-Flow" Air Pattern Systems) 6-7 P N 17.0 M 82.0 (BASE) 84.0 (OVERALL) 32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR FRONT / LEFT Optional Floor Stand: See Page 6-11 (VF-12) EVAPORATOR AIR OUTLET INTO RAISED FLOOR PIPING / UTILITY CONNECTION SEE NOTE 1 REAR / RIGHT Free-Cooling / Alternate Water Source - 6 to 10 Ton, "Up-Flow" (1) Please refer to Section 4 for piping connection sizes. "Up-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Front Free-Return" or Opt. "Rear Ducted-Return") (2) 3.5" high shipping guards, 79.5" Total unit rigging height (76.0" unit + 3.5" shipping guard). STANDARD HEATER ACCESS SKIRT - FIELD INSTALLED STANDARD 1.0" DUCT FLANGE CONNECTION 11.0 80.0 SEE NOTE 2 1.0 SEE NOTE 2 1.0 30.0 PIPING / UTILITY CONNECTIONS SEE NOTE 1 EVAPORATOR AIR OUTLET Dimensional Data Notes: (Connection Sizes) (VF-08) VFS-072 thru 120-( )-FC/AWS-U SEE NOTE 2 EVAPORATOR AIR OUTLET SEE NOTE 2 SEE NOTE 2 76.0 SEE NOTE 2 6.0 SEE NOTE 2 36.3 84.0 (OVERALL) OPTIONAL FILTER ACCESS 39.0 32.0 (BASE) 33.0 (OVERALL) 3.5 3.0 REAR / RIGHT FRONT / LEFT 2 or 3-Way, Top Discharge Plenum Box: (Optional) (VFS-072/120-( )-FC/AWS-U Upflow Models) 82.0" Optional Floor Stand: See Page 6-11 (VF-12) 29.0 54.2 79.0 SEE NOTE 1 18.5" 20.0 24.0 30.6 Note: Top Discharge Plenum Box shall be field installed. Heater Access Skirt shall not be provided with Plenum Box option. 45.0 1.38 SEE NOTE 1 (FC/AWS "Up-Flow" Air Pattern Systems) OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION) EVAPORATOR AIR INLET 82.0 (BASE) - 6 to 10 Tons 77.0 W/ STANDARD DUCT CONNECTION SEE NOTE 2 6-8 Free-Cooling / Alternate Water Source - Dimensional Data (VF-09) VFS-180 thru 312-( )-FC/AWS-D 15 to 26 Ton, "Down-Flow" DIMENSIONAL DATA Std CFM @ 0.5" esp "Down-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Free-Return" or Opt. "Ducted-Return") MODEL “A” “B ” “C ” “J ” “K ” “M” VFS-180-( )-FC/AWS-D 102.0" 100.0" 98.0" 17.5" 44.63" 15.62" VFS-240 & 312-( )-FC/AWS-D 114.0" 112.0" 110.0" 19.0" 51.5" 18.62" Note: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. STANDARD FILTER BOX FIELD INSTALLED OPTIONAL 1.0" DUCT FLANGE CONNECTION EVAPORATOR AIR INLET 12.0 C 89.0 W/ OPTIONAL DUCT CONNECTION 1.0 88.0 - 15 to 26 Tons 1.0 (FC/AWS "Down-Flow" Air Pattern Systems) 6-9 4.0 76.0 30.0 20.5 J K M M B (BASE) EVAPORATOR AIR OUTLET INTO RAISED FLOOR A (OVERALL) 32.0 (BASE) 33.0 (OVERALL) EVAPORATOR AIR OUTLET INTO RAISED FLOOR FRONT / LEFT Optional Floor Stand: See Page 6-12 (VF-13) PIPING / UTILITY CONNECTIONS SEE NOTE 1 REAR / RIGHT Free-Cooling / Alternate Water Source - 15 to 26 Ton, "Up-Flow" DIM ENSIONAL DATA MODEL "Up-Flow" Vertical A/C with Free-Cooling or Alternate Water Source Option ("Front Free-Return" or Opt. "Rear Ducted-Return") “A” “B ” “ C” “ H” VFS-180-( )-FC/AWS-U 102.0" 100.0" 98.0" 58.5" VFS-240 & 312-( )-FC/AWS-U 114.0" 112.0" 110.0" 73.5" Notes: (Connection Sizes) (1) Please refer to Section 4 for piping connection sizes. (2) 3.5" high shipping guards, 79.5" total unit rigging height (76.0" unit + 3.5" shipping guard). STANDARD HEATER ACCESS SKIRT - FIELD INSTALLED STANDARD 1.0" DUCT FLANGE CONNECTION 11.0 B C SEE NOTE 2 Dimensional Data (VF-10) VFS-180 thru 312-( )-FC/AWS-U SEE NOTE 2 1.0 1.0 EVAPORATOR AIR OUTLET EVAPORATOR AIR OUTLET 30.0 SEE NOTE 2 SEE NOTE 2 77.0 W/ STANDARD DUCT CONNECTION 76.0 SEE NOTE 2 6.0 SEE NOTE 2 SEE NOTE 2 36.25 EVAPORATOR AIR INLET B (BASE) 32.0 (BASE) 33.0 (OVERALL) H OPTIONAL FILTER ACCESS 3.5 OPTIONAL EVAPORATOR AIR INLET (W/ 1.0" DUCT FLANGE CONNECTION) 3.0 FRONT / LEFT 2 or 3-Way, Top Discharge Plenum Box: (Optional) (VFS-180/312-( )-FC/AWS-U Upflow Models) B 18.5" Note: Top Discharge Plenum Box shall be field installed. Heater Access Skirt shall not be provided with Plenum Box option. REAR / RIGHT Optional Floor Stand: See Page 6-12 (VF-13) (FC/AWS "Up-Flow" Air Pattern Systems) A (OVERALL) - 15 to 26 Tons SEE NOTE 2 PIPING / UTILITY CONNECTIONS SEE NOTE 1 6-10 Floor Stand Options Dimensional Data (VF-11) Models VFS-072/120-( ) VFS-072/120-DAR, DW & DG: (72.0" Wide Cabinet) (VF-11a) w/o Turning Vanes: (VF-11b) with Optional Turning Vanes: 29.0 29.0 42.2 67.0 67.0 SEE NOTE 1 SEE NOTE 1 20.0 A A 1.38 SEE NOTE 1 SEE NOTE 1 - Floor Stand Options (6 to 10 Ton Systems) Front/Right (VF-12) Front/Right VFS-072/120-( )-AWS/FC: (84.0" Wide Cabinet) (VF-12a) w/o Turning Vanes: (VF-12b) with Optional Turning Vanes: 29.0 29.0 6-11 54.2 79.0 SEE NOTE 1 79.0 SEE NOTE 1 20.0 A 24.0 30.6 30.6 45.0 SEE NOTE 1 Front/Right 45.0 Front/Right Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height Adjustable Height Turning Vane Availability Minimum Maximum 4.0" (Upflow Units Only) 3.5" 4.5" Not Available 6.0" 5.0" 7.0" Not Available 12.0" 11.0" 15.0" Optional 15.0" 14.0" 18.0" Optional 18.0" 17.0" 21.0" Optional 24.0" 23.0" 26.0" Optional Note-1: Only required for Nominal 24" High Floor Stands. 1.38 SEE NOTE 1 Floor Stand Options - VFS-180/312-( ) All Models: (All Cabinets - see tables below) (VF-13a) w/o Turning Vanes: (VF-13b) with Optional Turning Vanes: C C SEE NOTE 1 D B F B SEE NOTE 1 20.0 20.0 A I Dimensional Data (VF-13) Models VFS-180/312-( ) I SEE NOTE 1 1.38 J Front/Right Front/Right Dimensional Data - Floor Stand Heights “A” Dimension Floor Stand Nominal Height Adjustable Height Turning Vane Availability Minimum Maximum 4.0" (Upflow Units Only) 3.5" 4.5" Not Available 6.0" 5.0" 7.0" Not Available 12.0" 11.0" 15.0" Optional 15.0" 14.0" 18.0" Optional 18.0" 17.0" 21.0" Optional 24.0" 23.0" 26.0" Optional Note-1: Only required for Nominal 24" High Floor Stands. DIMENSIONAL DATA- Floor Stands (15 to 26 Ton Systems) U N IT MOD EL “ A” “ B” " C" " D" “ F” VFS-180-D AR , D W, D G, C -( ) se e above 85.0" 29.0" 34.00" 61.13" 44.63" 37.00" se e above 97.0" 29.0" 37.65" 73.13" 56.63" 37.0"0 se e above 97.0" 29.0" 37.65" 70.15" 52.50" 41.13" se e above 109.0" 29.0" 39.81" 82.15" 64.50" 41.13" (90" Wi d e C ab i n et ) VFS-180-( )-FC /AWS-( ) (102" Wi d e C ab i n et ) VFS-240/312-( )-D AR , D W, D G, C -( ) (102" Wi d e C ab i n et ) VFS-240/312-( )-FC /AWS-( ) (114" Wi d e C ab i n et ) “ I” “ J” SEE NOTE 1 - Floor Stand Options (15 to 26 Ton Systems) J 6-12 Globally close to you. Stulz-ATS, located in Frederick, MD USA, is part of The STULZ Group with headquarters in Hamburg, Germany and production facilities world wide. Our network of manufacturer’s representatives and sales partners span the globe, providing innovative solutions to your unique environmental control needs. North American Headquarters: 1572 Tilco Drive, Frederick, Maryland 21704, USA www.stulz-ats.com Phone: (301) 620-2033, Facsimile: (301) 662-5487, Email: [email protected] Worldwide: World Headquarters: STULZ GmbH Holsteiner Chaussee 283, D-22457 Hamburg Tel: +49(40)55 85 269; Fax: +49(40)55 85 308, email: [email protected] www.stulz.com Copyright 02/06 - Form L-03-C-104 Specifications are subject to change without notice