T6590 Series
FAN-COIL CONTROLLER PRODUCT DATA
FEATURES • • • • •
APPLICATIONS The T6590 range of digital thermostats is designed to control the valves, fan and auxiliary electric heater within fan-coil systems. Modern, attractive styling and comprehensive feature set makes the T6590 suitable for a wide range of applications. There are a total of 8 application configurations supported, and these are: Application
Description
0
2 pipe system, heating only
1
2 pipe system, cooling only
2
2 pipe system, 1 stage heat or 1 stage cool
3
2 pipe system, 1 stage heat or 1 stage cool, auto changeover
4
4 pipe system 1 stage heat and 1 stage cool
5
4 pipe system 1 stage heat and 1 stage cool auto changeover
6
2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heater
7
4 pipe system, mixed manual and auto
The different applications can be selected from the installer setup mode and by altering the external wiring connections
• • • • • • • • • • • • • • • • • • • • • •
EN0H8579 R0 2009
Large, easy to read LCD display with backlight Heat / Cool or standby mode displayed on LCD Lockable keypad Room setpoint adjustable via simple-to-use up/down buttons Fan speed ON/Off, low/med/high or auto
•
Auto mode, fan speed is proportional to distance of room temperature from setpoint
Manual or automatic heat / cool changeover Control of auxiliary electric heater Inbuilt or remote sensor (NTC20K) options available Simultaneous display of room temperature and user setpoint Push button adjustment of setpoint Switches allow manual control of system operation and fan speed Special energy savings mode activated by external input from Energy Management System (EMS) – a window contact or hotel card-key - overrides the temperature setting to installer defined heating and cooling temperatures Energy savings input (remote setback) can be configured to be normally open (NO) circuit or normally closed (NC) circuit All models have a proportional plus integral (P+I) T6590 meets all relevant requirements for CE approval Installer setup mode allowing operating parameters to be changed Installer set up settings retained in the event of a power loss Central remote setback for both cooling and heating operation Freeze protection Automatic setback to unoccupied mode with no key operation °C display 0°C to 2°C Temperature display offset available Easy to use installer setup mode allows for simple thermostat setup Adjustable deadband for heat & cool sequence control Setpoint range 10°C to 32°C Installer test mode for on-site wiring checks Line voltage (230V~) models available
T6590 FAN-COIL THERMOSTAT
SPECIFICATIONS Setpoint range
10...32oC
Supply voltage
230 V~ (+10%, -15%), 50/60 Hz P+I algorithm applied to ON/OFF control gives typical control to ±1.0°C at 22°C at 50% duty cycle, nominal control to ±1.0°C
Control Performance Electrical ratings Operational life Mounting
Fan Motor: 230V~, 50…60Hz, 3.0A run, with inrush 6A Valve Actuators: 230V~, 50…60Hz, 1.0A run, with inrush 3.5A Greater than 100,000 cycles (all loads) for thermostat contacts at 230 V~ Mounts directly onto wall or wall-box - a standard 65x65mm junction box (hole pitch 60mm). Mounting screws supplied.
Wiring
11 screw-in terminals per unit, capable of accepting either 2 wires up to 1.5 mm2 , or 1 x 2.5mm2
Energy Savings Input
Voltage-free contact (rating 24Vdc), maximum contact resistance of 1000ohms
Enclosure
Plastic 3-piece housing
Dimensions
97 x 148 x 29 mm (h x w x d)
Environmental requirements
Operating temperature range 5 to 45ºC Shipping and storage temperature range -20 to 55ºC Humidity range 5 to 95% rh, non-condensing
Approvals
CE mark, complying with standards EN60730-1 (2001), EN55014-1 (2007), EN55014-2 (1997). Product must be wired as shown for CE compliance.
T6590 APPLICATIONS T6590A1000 – 2 Pipe Model Application
Description
Changeover
0
2 pipe system, heating only
No
1
2 pipe system, cooling only
No
2 3 6
2 pipe system, 1 stage heat or 1 stage cool 2 pipe system, 1 stage heat or 1 stage cool, auto changeover 2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heater
Manual Seasonal Changeover
Fan speed On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto
Remote sensor
Pipe sensor
Remote setback
Auxiliary Heater
Output type
Y
Y
On Off
Y
Y
On Off
Y
Y
On Off On Off
Y
Y
Y
Manual with seasonal changeover
On/Off, 3 speed or Auto
Y
Y
Y
Y
On Off
Fan speed
Remote sensor
Pipe sensor
Remote setback
Auxiliary Heater
Output type
T6590B1000 – 4 Pipe Model Application
Description
Changeover
0
2 pipe system, heating only
No
2 pipe system, cooling only
No
1
4
2 pipe system, 1 stage heat or 1 stage cool 2 pipe system, 1 stage heat or 1 stage cool, auto changeover 4 pipe system 1 stage heat and 1 stage cool
5
2 3
Manual Seasonal Changeover
On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto
Y
Y
On Off
Y
Y
On Off
Y
Y
On Off
Y
On Off
Y
Y
Manual
On/Off, 3 speed or Auto
Y
Y
On Off
4 pipe system 1 stage heat and 1 stage cool auto changeover
Auto changeover
On/Off, 3 speed or Auto
Y
Y
On Off
6
2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heater
Manual with seasonal changeover
On/Off, 3 speed or Auto
Y
7
4 pipe system, mixed manual and auto
Manual / Auto changeover
On/Off, 3 speed or Auto
Y
EN0H8579 R0 2009
2
Y
Y
Y
Y
On Off
On Off
T6590 FAN-COIL THERMOSTAT
INSTALLATION 1. 2. 3. 4. 5. 6.
Locate the wall-plate in the mounting position, insert the mounting screws through the appropriate holes, and screw into position. Complete the wiring. Attach the thermostat to the wall-plate as follows: Locate the 4 side slots on the wall plate into the appropriate slots on the back of the thermostat. Press down firmly and snap the thermostat into place. Tighten retaining screw in lower edge of thermostat.
Wiring the thermostat
The standard wiring access is via a hole in the centre of the thermostat wall-plate.
Removing the thermostat from the wall
If it becomes necessary to remove the thermostat from the wall-plate:
Location
1. 2.
The T6590 Series thermostat is the temperature control element in the fan-coil or air-conditioning system, and must be located about 1.2 to 1.5m above the floor (according to local building regulations) in a position with good air circulation at room temperature. Do not mount it where it could be affected by :-
3. 4.
draughts or dead spots behind doors or in corners hot or cold air from ducts radiant heat from the sun or appliances unheated (uncooled) areas such as an outside wall behind the thermostat concealed pipes or chimneys
5.
Mounting the thermostat
Any T6590 Series thermostat can be directly mounted on the wall or horizontally on either a 65x65mm standard junction box or a 2x4inch US junction box. Mounting screws are supplied for both alternatives. IMPORTANT The installer must be a trained service engineer Isolate the power supply before beginning installation
3 EN0H8579 R0 2009
Isolate the power supply before removing the thermostat. Loosen the retaining screw in the lower edge of the thermostat. Pry the lower edge of the thermostat away from the wallplate. Use both hands to pull the thermostat straight away from the wall-plate. NOTE - Incorrect removal of the thermostat from the wall-plate may damage the device.
T6590 FAN-COIL THERMOSTAT
INSTALLER SETUP MODE (ISU) – T6590A1000 & T6590B1000 ISU Number and description
Units
Range
-
0 = 2 Pipe system Heat Only
-
1 = 2 Pipe system Cool Only
-
2 = 2 Pipe system 1H1C manual changeover
-
3 = 2 Pipe system 1H1C auto changeover (default on T6590A1000)
-
4 - 4 pipe system with manual changeover (not available on T6590A1000)
-
5 = 4 Pipe system auto changeover (default on T6590B1000) (Not available on T6590A1000)
-
6 = 2 pipe system 1H1C with Auxiliary Heater. Manual changeover
-
7 = 4 pipe system, mixed manual and automatic changeover (not available on T6590A1000)
-
0 NO ON/OFF (Default)
-
1 NC ON/OFF
-
0 Onboard Sensor (Default)
-
1 remote sensor (NTC20K)
-
0 NO input (default mode is Heat)
-
1 NO input (default mode is Cool)
-
2 NC input (default mode is Heat)
-
3 NC input (default mode is Cool)
-
4 Analog input (Default)(NTC20K, T7414C1012)
5 Threshold for pipe sensor cooling
ºC
Range: 10-18 ºC (Default 15 ºC)
6 Threshold for pipe sensor heating
ºC
Range: 24-32 ºC (Default 27 ºC)
7 Fan control type
-
0 User can choose Cycle or Constant (Default) (3 speed: Low->Med->High->Auto-> Low)
-
1 CONSTANT ONLY (3 speed: Low->Med->High-> Low)
-
2 CYCLE ONLY Auto has fan ramping algorithm
8 Dead band for four pipes
ºC
1ºC, 2ºC (Default), 3ºC, 4ºC, 5ºC (not available on T6590A1000)
9 Cycles Per Hour (CPH) value for heating
-
1 – 12CPH (Default 4)
10 Cycles Per Hour (CPH) value for cooling
-
1 – 6CPH (Default 3)
11 Cycles Per Hour (CPH) value for Auxiliary Heater
-
1-12 (Default 6)
1 System Type
2 Valve output type
3 Sensor Type
4 Pipe sensor (Note: This item will be automatically populated based on ISU #2 selection).
N0H8579 R0 2009
T6590 FAN-COIL THERMOSTAT
ISU Number and description
Units
Range
ºC
-2ºC - +2ºC (Default 0ºC)
-
0 display Room Temperature
-
1 display Setpoint
-
2 display both (Default)
14 Heating setpoint Range Stops
ºC
10-32ºC (default 32ºC)
15 Cooling setpoint Range Stops
ºC
10-32ºC (default 10ºC)
16 Keypad Lockout
-
0 All keys available(default)
-
1 System button Locked out
-
2 Fan and System button Locked out
-
3 All buttons locked out
-
1: Hotel card NO, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc.
-
2: Hotel Card NC, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc.
-
3: Hotel Card enabled, NO, with 1 second software delay going from UnOcc to Occupied; 30 minute delay going from Occupied to UnOcc
-
4: Hotel Card enabled, NC, with 1 second software delay going from UnOcc to Occupied; 30 minute delay going from Occupied to UnOcc.
18 Remote setback heating setpoint
ºC
Range 10-21ºC (Default 18ºC)
19 Remote setback cooling setpoint
ºC
Range 22-32ºC (Default 26ºC)
-
0 Disabled (Default)
-
1 4 Hour Sensing
-
2 12 Hour Sensing
-
3 24 Hour Sensing Comment: Anytime the thermostat is not touched (no single key pressed), the thermostat will automatically fall back into unoccupied setpoints. When any key is pressed, thermostat controls to occupied mode.
-
0 Disabled (Default)
-
1 Enabled – Stat Cycles On Heat when room temperature reaches 4ºC and disables Heat when room temperature reaches below 8ºC. This feature can not activate if the application is cool only
-
0 Inactive (Default)
-
1 Reset back to Auto after 2 hours (Not when constant fan is selected in ISU #7). The start time is calculated after the initial call for heat/cool.
-
2 Reset back to Auto after 4 hours (Not allowed when constant fan is selected in ISU #7). The start time is calculated after the initial call for heat/cool.
S
0 – 600Sec (Default 60Sec)
12 Display Temperature adjustment 13 Temperature Display mode
17 Remote setback
20 Activity Sensing (No single key pressed after certain period which is configured in this parameter, the system will enter unoccupied mode)
21 Freeze Protection
22 Auto Fan Reset
23 Fan run-on time after auxiliary heater is switched off
5 EN0H8579 R0 2009
T6590 FAN-COIL THERMOSTAT
DIMENSIONS
Remote sensor Remote setback
Application 2: Two pipes heating or Cooling, manual changeover wiring diagram
WIRING DIAGRAMS
Remote sensor Remote setback Pipe sensor
Application 3: Two pipes, one stage heating or cooling – Auto changeover wiring diagram
Remote sensor Remote setback
Application 0: Two Pipes, Heating-Only wiring Diagram
Remote sensor Remote setback
Application 4, 5 & 7: Four pipes (Heat + Cool) Manual / Auto changeover wiring diagram
N Remote sensor Remote setback
Application 1: Two Pipes, Cooling-Only wiring diagram
N0H8579 R0 2009
T6590 FAN-COIL THERMOSTAT
WIRING DIAGRAMS (CONT)
N Remote sensor Remote setback Pipe sensor
Application 6: Two pipe heating or cooling with Auxiliary electric heater wiring diagram
ORDERING SPECIFICATIONS OS Number
Description
T6590A1000
FCU Controller two pipe, 230VAC
T6590B1000
FCU Controller two or four pipe, 230VAC
Honeywell Control Systems Limited Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom EN0H8579 R0 2009