Transcript
Table of Contents T8 Programmed Start Ballasts
Ballasts
gelighting.com
T8 Instant Start
UltraStart® T8 120–277V Programmed Start For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps.......................... 11-2 Wiring Diagrams.............................................................11-13
T8 Programmed Start
Case Dimensions............................................................11-14
Programmed Start Dimming T5 Electronic Programmed Start T12 Electronic & High Output T12 Magnetic Sign Compact Fluorescent 11-1
HID Electronic & Electromagnetic
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 75952 – GE132-MVPS-L
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency). • Anti-Striation Control for better light quality, with no striations. • Extends lamp life in frequently switched applications (>100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Starting time visually the same as instant start
UltraStart® T8 Programmed Start 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Enclosure Type Additional Info
Dimensions Wiring diagram – LFL PS1 – see example on page 11-13 Case dimensions- Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Black White Blue Yellow
Electronic - Program/ Rapid Start Programmed start Parallel 10 % 70 °C (158 °F) Low-PS (.71) Active A (20-24 decibels) Metal Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency (MIN)
50Hz/60 Hz
Order information 10 Pack 75952
Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs 18 ft 18 AWG Length (± 1 in.) 25.0 in (635 mm) 25.0 in (635 mm) 33.0 in (838 mm) 47.0 in (1194 mm)
Specifications by lamp and wattage Lamp F32T8 F32T8/WM F28T8 F32T8/25W F25T8 F25T8/WM F17T8 F17T8/WM FE15T8 F40T8 F25T12
# of Lamps 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Line Volts 120 277 120 277 120 277 120 277 277 120 120 277 120 277 120 277 120 277 120 277 120 277
Safety and performance
11-2
System Watts 25 25 23 23 22 22 20 21 20 19 17 18 14 15 13 13 12 13 29 29 20 21
Nom. Line Current 0.22 A 0.10 A 0.20 A 0.09 A 0.19 A 0.09 A 0.18 A 0.08 A 0.08 A 0.17 A 0.15 A 0.07 A 0.12 A 0.06 A 0.11 A 0.06 A 0.10 A 0.10 A 0.25 A 0.11 A 0.18 A 0.08 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.72 0.72 0.71 0.71 0.71 0.71 0.71 0.71 0.73 0.73 0.71 0.71 0.75 0.75 0.74 0.74 0.66 0.66 0.71 0.71 0.72 0.72
Ballast Efficacy Factor 2.88 2.88 3.09 3.09 3.23 3.23 3.55 3.38 3.65 3.84 4.18 3.94 5.36 5.00 5.69 5.69 5.50 5.08 2.45 2.45 3.60 3.43
FCC – CLASS A Non-Consumer
UL Class P
Power Factor% (>=) 99 96 99 95 99 94 99 94 93 99 99 92 99 89 99 87 99 86 99 97 99 94 ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
RoHS Compliant
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0.0/-18 0.0/-18 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18
UL Listed
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps • < 10% THD, > 99% power factor • A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency). • Anti-Striation Control for better light quality, with no striations. • Extends lamp life in frequently switched applications (>100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Starting time visually the same as instant start
UltraStart® T8 Programmed Start 1 F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
Dimensions
General characteristics
70 °C (158 °F) Normal Active A (20-24 decibels) Metal Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency Supply Current Frequency (MIN)
50Hz 50Hz/60 Hz
Order information 10 Pack 75953
Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in.) 47.0 in (1194 mm) 25.0 in (635 mm) 33.0 in (838 mm) 33.0 in (838 mm) 25.0 in (635 mm)
Programmed Start Dimming
Wiring diagram – LFL PS1 – see example on page 11-13 Case dimensions- Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Yellow White Red Blue Black
Electronic - Program/ Rapid Start Programmed start Parallel 10 %
T8 Programmed Start
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Enclosure Type Additional Info
T8 Instant Start
75953 – GE132-MVPS-N
Specifications by lamp and wattage Lamp
F32T8/WM F28T8 F32T8/25W F25T8 F25T8/WM
FE15T8 F40T8 F25T12
Line Volts 120 277 120 277 120 277 120 277 277 120 12 120 277 120 277 120 277 120 277 120 277 120 277
Nom. Line Current 0.26 A 0.12 A 0.24 A 0.11 A 0.22 A 0.10 A 0.21 A 0.10 A 0.09 A 0.20 A 0.18 A 0.18 A 0.08 A 0.15 A 0.07 A 0.13 A 0.07 A 0.12 A 0.06 A 0.31 A 0.01 A 0.21 A 0.10 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.89 0.89 0.87 0.87 0.87 0.87 0.86 0.86 0.89 0.89 0.88 0.88 0.88 0.91 0.91 0.90 0.90 0.80 0.80 0.88 0.88 0.89 0.89
Ballast Efficacy Factor 2.97 2.97 3.11 3.11 3.35 3.35 3.58 3.58 3.71 3.71 4.40 4.40 4.19 5.35 5.06 6.00 6.00 5.71 5.33 2.51 2.51 3.56 3.56
FCC – CLASS A Non-Consumer
UL Class P
Power Factor% (>=) 99 95 99 94 99 93 99 93 92 99 99 99 90 99 87 99 85 99 83 99 96 99 93 ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
RoHS Compliant
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0.0/-18 0.0/-18 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18
UL Listed
T12 Magnetic
Safety and performance
System Watts 30 30 28 28 26 26 24 24 24 24 20 20 21 17 18 15 15 14 15 35 35 25 25
T12 Electronic & High Output
F17T8 F17T8/WM
# of Lamps 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
T5 Electronic Programmed Start
F32T8
Ballasts
gelighting.com
Sign Compact Fluorescent 11-3
HID Electronic & Electromagnetic
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 75954 – GE132-MVPS-H
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency). • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V • Anti-Striation Control for better light quality, with no striations.
UltraStart® T8 Programmed Start 1 F32T8 120V-277V High Light 1.18 BF <10% THD UltraStart®
Dimensions
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Wiring diagram – LFL PS1 – see example on page 11-13 Case dimensions- Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Yellow White Black Blue
Electronic - Program/ Rapid Start Programmed start Parallel 10 % 70 °C (158 °F) High (1.18) Active A (20-24 decibels) Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency (MIN)
60 Hz
Order information 10 Pack 75954
Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.40 lbs Side 18 ft 18 AWG Length (± 1 in.) 47.0 in (1194 mm) 25.0 in (635mm) 25.0 in (635 mm) 33.0 in (838 mm)
Specifications by lamp and wattage Lamp F32T8 F32T8/WM F28T8 F32T8/25W F25T8 F25T8/WM F17T8 F17T8/WM FE15T8 F40T8 F25T12
# of Lamps 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Line Volts 120 277 120 277 120 277 120 277 277 120 120 277 120 277 120 277 120 277 120 277 120 277
Safety and performance
System Watts 39 39 36 36 33 33 31 31 30 30 26 27 21 22 19 19 17 18 48 47 33 33
Nom. Line Current 0.35 A 0.15 A 0.32 A 0.14 A 0.29 A 0.13 A 0.27 A 0.12 A 0.12 A 0.27 A 0.23 A 0.10 A 0.19 A 0.09 A 0.17 A 0.08 A 0.15 A 0.08 A 0.42 A 0.18 A 0.29 A 0.13 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 1.18 1.18 1.16 1.16 1.16 1.16 1.15 1.15 1.17 1.17 1.16 1.16 1.19 1.19 1.18 1.18 1.05 1.05 1.18 1.18 1.25 1.25
FCC – CLASS A Non-Consumer
High Temperature Rated: Suitable for high temperature applications
11-4
Ballast Efficacy Factor 3.03 3.03 3.22 3.22 3.52 3.52 3.71 3.71 3.90 3.90 4.46 4.30 5.67 5.41 6.21 6.21 6.18 5.83 2.46 2.51 3.79 3.79 UL Class P
Power Factor% (>=) 98 97 99 96 99 96 99 95 95 99 99 94 99 91 99 89 99 88 99 98 99 96 ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
RoHS Compliant
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 UL Listed
Min. Starting Temp (°F/°C) 0.0/-18 0.0/-18 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 50.0/10 50.0/10 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 NRCan
70C max case temp 5 yr warranty or 90C max case temp 3 yr warranty
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 96714 – GE232-MVPS-N UltraStart® T8 Programmed Start 2 or 1 – F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
General characteristics
Dimensions Electronic – Programmed/ Rapid Start Programmed start Parallel 10% 104°F (40°C) 70°C (158°F) Normal Active A (20-24 decibels) Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics Supply Current Frequency Supply Current Frequency (MIN)
50 Hz/Supply Current Frequency (MIN)/ 50 Hz/ 60 (MIN) 50 Hz/60 Hz
Order information Pallet Pack 96717
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 25 in (635 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
Safety and performance
Nom. Line Current 0.48 A 0.21 A 0.30 A 0.14 A 0.45 A 0.20 A 0.28 A 0.13 A 0.42 A 0.18 A 0.26 A 0.12 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.89 0.89 1.05 1.05 0.88 0.88 1.02 1.02 0.86 0.86 1.00 1.00
Ballast Efficacy Factor 1.50 1.53 2.83 2.83 1.60 1.62 3.00 3.00 1.68 1.72 3.12 3.12
FCC – CLASS A Non-Consumer
RoHS Compliant
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 50 / 10 50 / 10 50 / 10 50 / 10 50 / 10 50 / 10 50 / 10 50 / 10
UL Listed
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 2 or 1 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
Dimensions Electronic – Programmed / Rapid Start Programmed start Parallel 10% 104°F (40°C) 70°C (158°F) Low Active A (20-24 decibels) Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics Supply Current Frequency (MIN)
50 Hz/60 Hz
Order information Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 25 in (635 mm) 47 in (1194 mm)
Sign
Wiring diagram – LFL PS2 – see example on page 11-13 Case dimensions- Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Black Blue and Red White Yellow
T12 Magnetic
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 96720
ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
T12 Electronic & High Output
96720 – GE232-MVPS-L
UL Class P
Power Factor% (>=) 99 96 98 93 99 96 98 93 99 95 98 92
T5 Electronic Programmed Start
# of Lamps Line Volts System Watts 2 120 59 2 277 58 1 120 37 F32T8 1 277 37 2 120 55 2 277 54 1 120 34 F32T8/WM 1 277 34 2 120 51 2 277 50 1 120 32 F28T8 1 277 32 Other compatible lamps: F17T8, F25T8, F32T8/25W
Programmed Start Dimming
Wiring diagram – LFL 4a – see example on page 11-13 Case dimensions- Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Black Blue and Red White Yellow
T8 Programmed Start
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 96714
T8 Instant Start
• < 10% THD, > 99% power factor • A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V
Ballasts
gelighting.com
Specifications by lamp and wattage Lamp
Nom. Line Current 0.39 A 0.17 A 0.28 A 0.11 A 0.36 A 0.16 A 0.26 A 0.11 A 0.34 A 0.15 A 0.24 A 0.10 A 0.14 A 0.31 A 0.09 A 0.23 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.71 0.71 0.81 0.81 0.67 0.67 0.79 0.79 0.65 0.65 0.77 0.77 0.73 0.73 0.86 0.86
Ballast Efficacy Factor 1.51 1.51 2.70 2.70 1.52 1.52 2.82 2.82 1.58 1.58 2.96 2.96 1.92 1.97 3.44 3.58
FCC – CLASS A Non-Consumer
ANSI – C62.41
Power Factor% (>=) 99 95 98 90 99 95 98 90 99 94 98 90 94 99 85 97
RoHS Compliant
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 16 10 16 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18
UL Listed
11-5
HID Electronic & Electromagnetic
Safety and performance See page E-1 for warranty information.
System Watts 47 47 30 30 44 44 28 28 41 41 26 26 38 37 25 24
Compact Fluorescent
# of Lamps Line Volts 2 120 2 277 1 120 F32T8 1 277 2 120 2 277 1 120 F32T8/WM 1 277 2 120 2 277 1 120 F28T8 1 277 2 277 2 120 1 277 F25T8 1 120 Other compatible lamps: F17T8, F32T8/25W
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 29675 – GE-232-MVPS-H
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 2 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
Dimensions
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) High Active A (20-24 decibels) Auto-restart, Thermally protected
Wiring diagram – LFL PS2 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Blue and Red Black White Yellow Blue
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information 10 Pack 29675
Pallet Pack 29651
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 2.40 lbs Side 18 ft 18 AWG Length (± 1 in) 33 in (838 mm) 25 in (635 mm) 25 in (635 mm) 47 in (1194 mm) 33 in (838 mm)
Specifications by lamp and wattage Lamp
# of Lamps Line Volts 2 120 2 277 1 277 F32T8 1 120 2 120 2 277 1 120 F32T8/WM 1 277 2 120 2 277 1 277 F28T8 1 120 2 120 2 277 1 120 F25T8 1 277 Other compatible lamps: F17T8, F32T8/25W
Safety and performance
System Watts 75 74 47 46 69 69 43 43 63 62 39 38 59 59 37 37
Nom. Line Current 0.64 A 0.28 A 0.19 A 0.40 A 0.60 A 0.27 A 0.36 A 0.18 A 0.54 A 0.25 A 0.16 A 0.32 A 0.50 A 0.24 A 0.32 A 0.15 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 1.15 1.15 1.37 1.37 1.14 1.14
Ballast Efficacy Factor 1.53 1.55 2.91 2.97 1.65 1.65
1.34 1.10 1.11 1.29
3.11 1.74 1.79 3.30
1.14 1.14 1.34 1.34
1.93 1.93 3.62 3.62
RoHS Compliant
FCC – CLASS A Non-Consumer
Power Factor% (>=) 98 94 90 98 98 95 98 90 94 98 89 98 98 93 98 87 ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 16 10 21
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18
UL Listed
High Temperature Rated: Suitable for high temperature applications 70°C max case temp 5 yr warranty or 90°C max case temp 3 yr warranty.
11-6
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 29671 – GE-232-MVPS-XL UltraStart® T8 Programmed Start 2 – F32T8 120V-277V Ultra Low Watt .60 BF <10% THD
Dimensions
General characteristics Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) Ultra low Active A (20-24 decibels) Auto-restart, Thermally protected
Electrical characteristics Supply Current Frequency
50 Hz/ 60 Hz
Order information Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 33 in (838 mm) 25 in (635 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
Nom. Line Current 0.39 A 0.19 A 0.12 A 0.24 A 0.15 A 0.24 A 0.22 A 0.20 A 0.12 A 0.15 A 0.12 A 0.20 A 0.31 A 0.15 A 0.10 A 0.10 A 0.20 A
RoHS Compliant
UL Type 1 Outdoor
System Ballast Factor 0.60 0.60 0.70 0.70 0.59 0.59
Ballast Efficacy Factor 1.33 1.36 2.50 2.59 1.40 1.40
0.68 0.59 0.59 0.67
2.51 1.51 1.51 2.68
0.61 0.61
1.69 1.69
0.68 0.68
2.95 3.09
ANSI – C62.41
UL Type HL
29623 – GE-332-120-PS-N
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
FCC Part 18 Class B at 120 Volts
UL Class P
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 15 16 10 cUL Listed
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18 0 / -18 UL Listed
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 3 – F32T8 120V Normal Light .87 BF <10% THD UltraStart®
Dimensions Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) Normal Active A (20-24 decibels) Auto-restart, Thermally protected
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information Pallet Pack 29633
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Sign
Wiring diagram – LFL PS3 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Red/White Yellow
T12 Magnetic
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 29623
NRCan
Power Factor% (>=) 98.0 90.0 83.0 98.0 99.0 87.0 0.9 81.0 99.0 86.0 79.0 98.0 98.0 87.0 79.0 79.0 98.0
T12 Electronic & High Output
Safety and performance
System Watts 45 44 28 27 42 42 27 27 39 39 25 24 36 36 23 23 22
T5 Electronic Programmed Start
# of Lamps Line Volts 2 120 2 277 1 277 F32T8 1 120 2 120 2 277 1 120 F32T8/WM 1 277 2 120 2 277 1 277 F28T8 1 120 2 120 2 277 1 277 1 277 F25T8 1 120 Other compatible lamps: F17T8, F32T8/25W
Programmed Start Dimming
Wiring diagram – LFL PS2 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths Blue and Red White and Black Yellow
T8 Programmed Start
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 29671
T8 Instant Start
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
Ballasts
gelighting.com
Specifications by lamp and wattage Lamp
System Watts 84 64 80 60 72 54 66 51 45 35 RoHS Compliant
See page E-1 for warranty information.
UL Type 1 Outdoor
System Ballast Factor 0.89 1.00 0.87 0.98 0.85 0.95 0.89 0.99 0.88 0.98 ANSI – C62.41
Ballast Efficacy Factor 1.05 1.56 1.08 1.63 1.18 1.75 1.34 1.94 1.95 2.80
UL Type HL
NRCan
Power Factor% (>=) 99.00 99.00 0.99 99.00 99.00 99.00 99.00 99.00 99.00 99.00
FCC – CLASS A Non-Consumer
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 UL Class P
THD% (<=) 10 10 10 10 10 10 10 10 10 10 cUL Listed
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18 UL Listed
11-7
HID Electronic & Electromagnetic
Safety and performance
Nom. Line Current 0.71 A 0.56 A 0.69 A 0.52 A 0.62 A 0.47 A 0.57 A 0.43 A 0.39 A 0.31 A
Compact Fluorescent
# of Lamps Line Volts 3 120 2 120 3 120 F32T8/WM 2 120 3 120 F28T8 2 120 3 120 F25T8 2 120 3 120 F17T8 2 120 Other compatible lamps: F32T8/25W F32T8
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 29676 – GE-332-MVPS-H
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 3 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
General characteristics
Dimensions
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) High Active A (20-24 decibels) Auto-restart, Thermally protected
Wiring diagram – LFL PS3 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Red/White Yellow
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information 10 Pack 29676
Pallet Pack 29656
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 2.40 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
# of Lamps Line Volts 3 120 3 277 2 120 F32T8 2 277 3 120 3 277 2 120 F32T8/WM 2 277 3 120 3 277 2 277 F28T8 2 120 3 120 3 277 2 120 F25T8 2 277 Other compatible lamps: F17T8, F32T8/25W
Safety and performance
System Watts 110 108 82 82 102 100 77 76 92 91 69 58 86 85 65 64
Nom. Line Current 0.95 A 0.41 A 0.70 A 0.32 A 0.88 A 0.39 A 0.64 A 0.30 A 0.79 A 0.35 A 0.27 A 0.58 A 0.74 A 0.33 A 0.56 A 0.26 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 1.15 1.15 1.28
Ballast Efficacy Factor 1.04 1.06 1.56
1.13 1.14
1.10 1.14
1.26 1.09 1.10 1.23
1.65 1.18 1.20 1.78
1.14 1.14 1.25
1.32 1.34 1.92
RoHS Compliant
FCC – CLASS A Non-Consumer
Power Factor% (>=) 98 96 98 94 99 96 98 95 99 96 94 98 98 96 98 93
ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 14 10 16
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18
UL Listed
High Temperature Rated: Suitable for high temperature applications 70°C max case temp 5 yr warranty or 90°C max case temp 3 yr warranty.
11-8
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 96715 – GE332-MVPS-N UltraStart® T8 Programmed Start 3 – F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
General characteristics
Dimensions Electronic – Programmed / Rapid Start Programmed start Parallel 10% 104°F (40°C) 70°C (158°F) Normal Active A (20-24 decibels) Anti-striation control, TCLP compliant, Thermally protected, Universal voltage
Additional Info
Electrical characteristics Supply Current Frequency (MIN)
50 Hz/60 Hz
Order information Pallet Pack 96718
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
Safety and performance
Nom. Line Current 0.72 A 0.30 A 0.54 A 0.24 A 0.66 A 0.28 A 0.51 A 0.22 A 0.61 A 0.26 A 0.47 A 0.21 A
RoHS Compliant
UL Type 1 Outdoor
System Ballast Factor 0.89 0.89 0.98 0.98 0.86 0.86 0.96 0.96 0.84 0.84 0.93 0.93
ANSI – C62.41
UL Type HL
Power Factor% (>=) 99 97 98 95 99 97 98 95 99 97 98 95
FCC – CLASS A Non-Consumer
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16
UL Listed
T12 Electronic & High Output
96721 – GE332-MVPS-L
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations. • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 3 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
Dimensions Electronic – Programmed / Rapid Start Programmed start Parallel 10% 104°F (40°C) 70°C (158°F) Low Active A (20-24 decibels) Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics Supply Current Frequency (MIN)
50 Hz/60 Hz
Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Sign
Order information
Wiring diagram – LFL PS3 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Red/White Yellow
T12 Magnetic
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 96721
Ballast Efficacy Factor 1.03 1.05 1.48 1.50 1.07 1.08 1.57 1.57 1.15 1.16 1.63 1.63
T5 Electronic Programmed Start
# of Lamps Line Volts System Watts 3 120 86 3 277 84 2 120 66 F32T8 2 277 65 3 120 80 3 277 79 2 120 61 F32T8/WM 2 277 61 3 120 73 3 277 72 2 120 57 F28T8 2 277 57 Other compatible lamps: F17T8, F25T8, F32T8/25W
Programmed Start Dimming
Wiring diagram – LFL PS3 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Red/White Yellow
T8 Programmed Start
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating
10 Pack 96715
T8 Instant Start
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Parallel lamp operation means system maintenance is easier to manage • Starting time visually the same as instant start
Ballasts
gelighting.com
Specifications by lamp and wattage Lamp
Nom. Line Current 0.60 A 0.26 A 0.45 A 0.19 A 0.54 A 0.24 A 0.40 A 0.18 A 0.49 A 0.22 A 0.38 A 0.17 A 0.22 A 0.45 A 0.35 A 90.0 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.71 0.71 0.77 0.77 0.67 0.67 0.75 0.75 0.66 0.66 0.74 0.74 0.66 0.74 0.82
RoHS Compliant
Ballast Efficacy Factor 1.02 1.04 1.48 1.48 1.06 1.08 1.56 1.56 1.13 1.13 1.64 1.64 1.13 1.37 2.00
FCC – CLASS A Non-Consumer
Power Factor% (>=) 99 96 98 92 99 95 98 92 99 95 98 92 95 99 98 0.82
UL Class P
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
ANSI – C62.41
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 15 10 10 15
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18
UL Listed
11-9
HID Electronic & Electromagnetic
Safety and performance See page E-1 for warranty information.
System Watts 69 68 52 52 63 62 48 48 58 58 45 45 58 54 41 0.158
Compact Fluorescent
# of Lamps Line Volts 3 120 3 277 2 120 F32T8 2 277 3 120 3 277 2 120 F32T8/WM 2 277 3 120 3 277 2 120 F28T8 2 277 3 277 3 120 2 120 F25T8 2 277 Other compatible lamps: F17T8, F32T8/25W
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 29672 – GE-332-MVPS-XL
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 3 – F32T8 120V-277V Ultra Low Watt .60 BF <10% THD
General characteristics
Dimensions
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) Ultra low Active A (20-24 decibels) Auto-restart, Thermally protected
Wiring diagram – LFL PS3 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Red/White Yellow
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information 10 Pack 29672
Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
# of Lamps Line Volts 3 120 3 277 2 277 F32T8 2 120 3 120 3 277 2 120 F32T8/WM 2 277 3 120 3 277 2 120 F28T8 2 277 3 120 3 277 2 120 F25T8 2 277 Other compatible lamps: F17T8, F32T8/25W
System Watts 67 66 50 49 61 60 45 45 57 56 42 42 53 53 40 40
Safety and performance
Nom. Line Current 0.58 A 0.26 A 0.21 A 0.42 A 0.53 A 0.24 A 0.04 A 0.18 A 0.49 A 0.22 A 0.35 A 0.17 A 0.45 A 0.21 A 0.35 A 0.16 A
UL Type 1 Outdoor
UL Type HL
System Ballast Factor 0.60 0.60 0.64 0.64 0.59 0.59
Ballast Efficacy Factor 0.89 0.90 1.28 1.30 0.96 0.98
0.64 0.58 0.58
1.42 1.01 1.03
0.63 0.60 0.60 0.64 0.64
1.50 1.13 1.13 1.60 1.60
RoHS Compliant
FCC – CLASS A Non-Consumer
29625 – GE-432-120-PS-N
ANSI – C62.41
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 13 10 14
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 0 / -18 0 / -18
UL Listed
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V (H and XL series) • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 4 – F32T8 120V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Dimensions
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) Normal Active A (20-24 decibels) Auto-restart, Thermally protected
Wiring diagram – LFL PS4 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Blue/White Red/White Yellow
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information 10 Pack 29625
Power Factor% (>=) 98 93 92 98 99 94 98 92 99 94 98 91 98 92 98 89
Pallet Pack 29635
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
# of Lamps Line Volts 4 120 3 120 4 120 F32T8/WM 3 120 4 120 F28T8 3 120 4 120 F25T8 3 120 4 120 F17T8 3 120 Other compatible lamps: F32T8/25W F32T8
Safety and performance
11-10
System Watts 112 92 106 87 96 79 87 73 61 51 RoHS Compliant
Nom. Line Current 0.95 A 0.79 A 0.92 A 0.75 A 0.83 A 0.68 A 0.75 A 0.63 A 0.53 A 0.44 A UL Type 1 Outdoor
System Ballast Factor 0.89 0.96 0.87 0.94 0.84 0.91 0.88 0.95 0.89 0.96 UL Type HL
Ballast Efficacy Factor 0.79 1.04 0.82 1.08 0.87 1.15 1.01 1.30 1.45 1.88
ANSI – C62.41
Power Factor% (>=) 99 99 99 99 99 99 99 99 99 99
FCC – CLASS A Non-Consumer
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 0 / -18 0 / -18 50 / 10 0 / -18
UL Listed
See page E-1 for warranty information.
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 96716 – GE432-MVPS-N UltraStart® T8 Programmed Start 4 F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
Dimensions
General characteristics Electronic – Programmed / Rapid Start Rapid start Parallel 10% 104°F (40°C) 70°C (158°F) Normal Active A (20-24 decibels) Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics Supply Current Frequency (MIN)
50 Hz/ 60 Hz
Order information Pallet Pack 96719
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
Safety and performance
RoHS Compliant
Nom. Line Current 0.97 A 0.41 A 0.78 A 0.34 A 0.88 A 0.37 A 0.72 A 0.31 A 0.81 A 0.35 A 0.66 A 0.29 A UL Type 1 Outdoor
System Ballast Factor 0.89 0.89 0.96 0.96 0.86 0.86 0.94 0.94 0.83 0.83 0.92 0.92 UL Type HL
Ballast Efficacy Factor 0.78 0.79 1.03 1.04 0.81 0.83 1.09 1.10 0.86 0.87 1.16 1.17
ANSI – C62.41
FCC – CLASS A Non-Consumer
UL Class P
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16
UL Listed
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start 4 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
Dimensions Electronic – Programmed / Rapid Start Programmed start Parallel 10% 104°F (40°C) 70°C (158°F) Low – PS Active A (20-24 decibels) Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics Supply Current Frequency Supply Current Frequency (MIN)
50 Hz 50 Hz/60 Hz
Order information Pallet Pack
DIY Pack
IP Pack
9.5 in (241 mm) 1.7 in (43 mm) 1.18 in (30 mm) 8.9 in (226 mm) 1.18 in (30 mm) 0.3 in (8 mm) 1.65 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Sign
Wiring diagram – LFL PS4 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Blue/White Red/White Yellow
T12 Magnetic
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 71832
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
T12 Electronic & High Output
71832 – GE432-MVPS-L
Power Factor% (>=) 99 97 98 95 99 97 98 95 99 97 98 95
T5 Electronic Programmed Start
# of Lamps Line Volts System Watts 4 120 114 4 277 112 3 120 93 F32T8 3 277 92 4 120 105 4 277 103 3 120 86 F32T8/WM 3 277 85 4 120 96 4 277 95 3 120 79 F28T8 3 277 78 Other compatible lamps: F17T8, F25T8, F32T8/25W
Programmed Start Dimming
Wiring diagram – LFL PS4 – see example on page 11-13 Case dimensions – Ref Drawing -A – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White and Black Blue and Red Blue/White Red/White Yellow
T8 Programmed Start
Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
10 Pack 96716
T8 Instant Start
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Anti-striation control for better light quality, with no striations • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Multi-voltage technology handles voltage from 120 to 277V • Parallel lamp operation means system maintenance is easier to manage
Ballasts
gelighting.com
Specifications by lamp and wattage Lamp
RoHS Compliant
See page E-1 for warranty information.
UL Type 1 Outdoor
System Ballast Factor 0.71 0.71 0.58 0.58 0.69 0.69 0.57 0.57 0.68 0.68 0.55 0.55 ANSI – C62.41
Ballast Efficacy Factor 0.78 0.80 0.81 0.82 0.81 0.83 0.84 0.85 0.88 0.89 0.88 0.88
UL Type HL
Power Factor% (>=) 1 1 1 1 1 1 1 1 1 1 1 1
FCC – CLASS A Non-Consumer
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 0 / -18 0 / -18 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16 60 / 16
UL Listed
11-11
HID Electronic & Electromagnetic
Safety and performance
Nom. Line Current 0.39 A 0.32 A 0.68 A 0.78 A 0.71 A 0.30 A 0.58 A 0.26 A 0.64 A 0.28 A 0.53 A 0.23 A
Compact Fluorescent
# of Lamps Line Volts System Watts 4 120 90 4 277 88 3 120 72 F32T8 3 277 71 4 120 85 4 277 83 3 120 68 F32T8/WM 3 277 67 4 120 77 4 277 76 3 120 63 F28T8 3 277 63 Other compatible lamps: F17T8, F25T8, F32T8/25W
UltraStart® T8 120–277V Programmed Start T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps 74476 – GE-432-MVPS-H (replaces 29678)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency) • Extends lamp life in frequently switched applications (> 100,000 on/off cycles) • Starting time visually the same as instant start • Multi-voltage technology handles voltage from 120 to 277V • Parallel lamp operation means system maintenance is easier to manage • Anti-Striation Control for better light quality, with no striations.
UltraStart® T8 Programmed Start 4 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
General characteristics Ballast Type Starting Method Lamp Wiring Line Voltage Regulation (+/-) Ambient Temperature (MAX) Case Temperature (MAX) Ballast Factor Power Factor Correction Sound Rating Additional Info
Dimensions
Electronic – Programmed / Rapid Start Programmed start Parallel 10% 105°F (41°C) 70°C (158°F) High Active A (20-24 decibels) Auto-restart, Thermally protected
Wiring diagram – LFL PS4 – see example on page 11-13 Case dimensions – Ref Drawing LG – see Page 11-14 Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp (F32T8) Remote Mounting Wire Gauge Lead lengths White Black Red Red/White Blue Blue/White Yellow
Electrical characteristics Supply Current Frequency
50 Hz/60 Hz
Order information 10 Pack 74476
Pallet Pack 74477 (replaces 29657)
DIY Pack
IP Pack
9.5 in (241 mm) 2.4 in (61 mm) 1.6 in (40 mm) 8.9 in (226 mm) 1.7 in (43 mm) 0.3 in (8 mm) 3.10 lbs Side 18 ft 18 AWG Length (± 1 in) 25 in (635 mm) 25 in (635 mm) 33 in (838 mm) 33 in (838 mm) 33 in (838 mm) 33 in (838 mm) 47 in (1194 mm)
Specifications by lamp and wattage Lamp
F32T8
F32T8/WM
F28T8
F32T8/25W
F25T8
F17T8
# of Lamps 4 4 3 3 4 4 3 3 4 4 3 3 4 4 3 3 4 4 3 3 4 4 3 3
Line Volts 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277
Safety and performance
System Watts 147 144 120 120 139 136 114 112 125 123 103 101 112 111 92 91 117 115 97 96 81 80 67 67 RoHS Compliant
Nom. Line Current 1.27 A 0.55 A 1.03 A 0.45 A 1.20 A 0.52 A 0.95 A 0.43 A 1.08 A 0.47 A 0.86 A 0.39 A
1.00 A 0.44 A 0.83 A 0.37 A 0.69 A 0.31 A 0.58 A 0.26 A
ANSI – C62.41
System Ballast Factor 1.16 1.16 1.26 1.26 1.15 1.15
Ballast Efficacy Factor 0.79 0.81 1.05 1.05 0.83 0.85
1.24 1.12 1.12
1.11 0.90 0.91
1.21 1.12 1.12 1.21 1.21 1.15 1.15 1.23 1.23 1.15 1.15 1.23 1.23
1.20 1.00 1.01 1.32 1.33 0.98 1.00 1.27 1.28 1.42 1.44 1.84 1.84
UL Type 1 Outdoor
UL Type HL
Power Factor% (>=) 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 99 98 99 99
FCC – CLASS A Non-Consumer
Crest Factor (<=) 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
UL Class P
cUL Listed
THD% (<=) 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Min. Starting Temp (°F/°C) -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 0.0/-18 60.0/16 60.0/16 60.0/16 60.0/16 -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30 -22.0/-30
UL Listed
High Temperature Rated: Suitable for high temperature applications 70°C max case temp 5 yr warranty or 90°C max case temp 3 yr warranty.
11-12
See page E-1 for warranty information.
Wiring Diagrams T8 Programmed Start Ballasts
T8 Instant Start
BALLAST Line
T8 Programmed Start
White
Blue
Black
Programmed Start Dimming
T5 Electronic Programmed Start T12 Electronic & High Output T12 Magnetic
Sign
Compact Fluorescent
Yellow
LAMP
LFL PS4
HID Electronic & Electromagnetic
11-13
See page E-1 for warranty information.
LFL PS3 LFL PS2
LFL PS1 LFL 4a
Ballasts
gelighting.com
Case Dimensions T8 Programmed Start Ballasts -A
LG
11-14
See page E-1 for warranty information.