Transcript
GB.TBLZ2425.130915
Instructions for Installation Temperature sensor, TBLZ-1-25-2/MIRUVENT
1. General The sensor is intended for wall mounting and is equipped with a screw terminal connection for a cable.
2. Range of Application The outdoor sensor is designed for measuring the outdoor air temperature or the room temperature.. It is used for offsetting the pressure or airflow setpoint.
3. Installation Secure the sensor to an exterior wall by means of two screws. Note that the sensor should be mounted with the cable gland facing downward. Position the sensor at a representative point of measurement. Avoid sources of interference such as direct solar radiation, exhaust air discharge and the like.
TBLZ-1-25-2
4. Technical data Dimensions (W x H x D) Enclosure class Range of measurement
Swegon reserves the right to alter specifications.
52x55x27 mm IP 43 -50 °C – +70 °C
www.swegon.com
1
GB.TBLZ2425.130915
5. Electrical connections The electrical connections should be wired by a qualified electrician in accordance with local electrical safety regulations.
Temperature sensor TBLZ-1-25-2 20
21
MIRU Control
Max. permissible length of cable: 100 m Min. permissible cross-sectional cable area: 0.5 mm²
2
www.swegon.com
Swegon reserves the right to alter specifications.