960W Three Phase Industrial DIN RAIL with PFC Function
TDR-960 series
■
‧
‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ ‧ SPECIFICATION MODEL
OUTPUT
TDR-960-24
TDR-960-48
DC VOLTAGE RATED CURRENT
24V 40A
48V 20A
CURRENT RANGE
0 ~ 40A
0 ~ 20A
RATED POWER
960W
960W
RIPPLE & NOISE (max.) Note.2 180mVp-p
250mVp-p
VOLTAGE ADJ. RANGE 24 ~ 28V VOLTAGE TOLERANCE Note.3 ±1.0%
48 ~ 55V ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION SETUP, RISE TIME
±1.0% 1000ms, 100ms/400VAC
HOLD UP TIME (Typ.) VOLTAGE RANGE
INPU T
12ms / 400VAC
±1.0% 800ms, 100ms/500VAC at full load
14ms / 500VAC at full load
Note.4 Three-Phase 340 ~ 550VAC (Dual phase operation possible) 480 ~ 780VDC
FREQUENCY RANGE POWER FACTOR (Typ.)
47 ~ 63Hz PF≧ 0.88/400VAC
EFFICIENCY (Typ.)
94%
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
2A/400VAC 1.4A/500VAC COLD START 60A
LEAKAGE CURRENT
PF≧0.86/500VAC at full load 94.5%
<3.5mA / 530VAC 105 ~ 130% rated output power
OVERLOAD
Pro tection type : Constant current limiting, unit will shut down after 3 sec. ,re-p ower on to recover
PROTECTION OVER VOLTAGE OVER TEMPERATURE FUNCTION
±0.5%
29 ~ 33V Protection type : Shut down o/p voltage, re-power on to recover
56 ~ 65V
90℃ ±5℃ (TSW) detect on heatsink of power switch
85℃± 5℃ (TSW) detect on heatsink of power switch
Pro tection type : Shut down o/p voltage, recovers automatically after temperature goes down
DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load Please refer to function manual
CURRENT SHARING
WORKING TEMP. WORKING HUMIDITY
Note.5 -30 ~ +70℃ (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS
-40 ~ +85℃, 10 ~ 95% RH
SAFE TY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION
I/P-O/P:3KVAC
OTHERS
UL508 approved, IEC60950-1 CB approved by SIQ I/P-FG:2KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
MTBF
59.4K hrs min.
DIMENSION
110*125.2*150mm (W*H*D) 2.47Kg ; 6pcs/15.8Kg/1.47CUFT
PACKING NOTE
±0.03%/℃ (0 ~ 50℃) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
MIL-HDBK-217F (25℃)
℃ File Name:TDR-960-SPEC 2013-04-26
TDR-960 series
960W Three Phase Industrial DIN RAIL with PFC Function Mechanical Specification
Case No.214A
Unit:mm
123 4
1 25 .2 CN205 12 34
1 2 3 4 5 6
TB1 1 2 3 4
TB2
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Termina l Pin No. Assignment (TB1) Pin No. 1 2 3 4
Te rminal P in No. Assignment (TB2)
Assignm ent FG AC/L3 AC/L2 AC/L1
Pin No. 1,2 ,3 4,5,6
Assignment DC OUTPUT +V DC OUTPUT -V
Control Pin (CN205 ) : DINK LE ECH250R-04P or equival ent Pin No . Assignment 1 P-( Current Share) 2 P+( Current Share) 3,4 DC OK Relay Cont ac t
Mating Housing
Wi re Diameter
DINKLE ESC250V-04P or equivalent (Including in the single package)
Block Diagram
0.081~0.517mm2 (28~20AWG)
PFC fosc : 65KHz PWM fosc : 60KHz DC OK
I/P
EMI FILTE R & RE CTIFIERS
POWER SWITCHING
PFC CIRCUIT
RECTIFIERS & F ILTER
+V -V O .C.P.
O.L.P. FG
P WM CO NTROL
PFC CO NTROL
DETECTION CIR CUIT CURRENT S HARE
O.T.P.
CURRENT SHARE
O.V.P.
DC OK Relay Contact Contact Close
P SU turns on / DC OK.
Contact Open
P SU turns off / DC Fail.
Contact Ratings ( max .) 30V/1A res istive load.
File Name:TDR-960-SPEC 2013-04-26
TDR-960 series
960W Three Phase Industrial DIN RAIL with PFC Function Derating Curve
Output derating VS input voltage
100
100
Three phase operation 90
80 80 60
Dual phase operation(L1 & L3)
70 60
40
Dual phase operation(L1 & L2 or L2 & L3) 50
20 40 -30
0
10
20
30
40
50
60
70 (VERTICAL)
340
360
AMBIENT TEMPERATURE (℃)
380
400
450
500
550
INPUT VOLTAGE (V) 60Hz
Function Manual 1. Current sharing (1) Parallel operation is available by connecting th e units shown as below (P+,P- are connected m utually in parallel). (2) Difference of output voltages among parallel units should be less than 0.2V. (3) The total output current must not exceed the v alue determined by the following equation (Outp ut current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9. (4) In parallel ope ration 4 units is the maximum, please consult th e manufacture fo r other applications. (5) The power supplies should be paralleled using short and large diameter wiring and then connected to the load. (6) When in parallel operation, the minimum output load should be greater than 5% of total output load. (Min. load >5% rated current per unit x number of unit) (7) In parallel connection, maybe only one unit (m aster) operate if the total output load is less than 5% of rated loa d condition. The other PSUs (slaves) may go into standby mode and their output LEDs & relays will not turn on. (8) Some minor noise may be heard at light load condition under parallel operation. This is a normal phenomenon and the performance of the PSU will not be influenced.
LOAD +V
-V
P+ and P- lines shoul d be tw isted in pairs
P+(pin2) DCO K 4 DCO K 3 P+ 2 P- 1 CN2 05
DCOK 4 DCOK 3 P+ 2 P- 1 CN205
+V -V TB2
+V -V TB2
PSU
P-(pin1)
DC OK 4 DC OK 3 P+ 2 P- 1 C N20 5
+V -V TB2
PSU
DC OK 4 DC OK 3 P+ 2 P- 1 CN 20 5
+V -V TB2
PSU
PSU
File Name:TDR-960-SPEC 2013-04-26