DESCRIPTION
TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 10 SEER AC012M102 THRU AC030M1021 (1 THRU 2.5 NOMINAL TONS, 1 PH) AC036X102 THRU 60 (3 THRU 5 NOMINAL TONS, 1 PH) AC036X10(3,4) THRU 60 (3 THRU 5 NOMINAL TONS, 3 PH)
AC012M1021 THRU 030
AC036X1021 THRU 060 AC036X10(31,41) THRU 060 TI
FI
ED
T O ARI
C M
ER
-C
PL
RY
UN I
NI N G
G W IT H
OI
IT
TA
Y
D ON
MA N U F A C T U R
AS
AIR
NI
ER
O
C
R
This product was manufactured in a plant whose quality system is certified/registered as being in conformity with ISO 9001.
RT
IF
RI
F
U I P M EN T
I CA T I ON
O
EQ
E C
A
T IO
NS
S EC 10 S T A NDA R D 2
Certification applies only when the complete system is listed with ARI.
LISTED
Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com for the most up-to-date technical information. Additional rating information can be found at www.ariprimenet.org.
The 10 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custom-matched with one of UPG’s complete line of evaporator sections, each designed to serve a specific function. Matching Air Handlers are available for upflow, downflow or horizontal applications to provide a complete system. Electric Heaters are available if required. Add-On coils are available for use with upflow, downflow or horizontal furnaces and air handlers.
WARRANTY 5-year limited parts warranty. 5-year limited compressor warranty.
FEATURES • QUALITY CONDENSER COILS - The coil is constructed of enhanced copper tube and aluminum fins. • COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard. • PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compressor. • DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted desert sand finish insure less fading when exposed to sunlight. • LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof. • TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. • LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. • LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing. • EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls and the molex plug in the control box connecting the condenser fan, make for easy servicing of the unit. • SECURED SERVICE VALVES - Secured re-usable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging. • U.L. AND C.U.L. LISTED - Approved for outdoor application. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21065-003 Rev. E (0405)
Physical and Electrical Data - 1 Phase MODEL
012M1021 018M1021 024M1021 030M1021 036X1021
Unit Supply Voltage
042X1021
048X1021
060X1022
208/230 – 1 – 60
Normal Voltage Range
187 to 252
Minimum Circuit Ampacity
8.8
10.1
15.3
19.3
21.5
26.1
30.1
37.3
Max. Overcurrent Device Amps
15
15
20
25
35
40
45
60
Rotary
Recip
Recip
Recip
Recip
Recip
Recip
ScrollB
Rated Load
6.7
7.7
11.5
14.7
16.1
19.8
23
28.9
Locked Rotor
33
48
60
73
82
97
110
160
No
No
No
No
No
No
No
No 1.3
Compressor Type Compressor Amps Crankcase Heater Fan Motor Amps
Rated Load
0.5
0.9
0.9
0.9
1.4
1.4
1.3
17-1/2
17-1/2
17-1/2
17-1/2
18
18
22
22
Rated HP
1/12
1/12
1/8
1/8
1/4
1/4
1/4
1/4
Nominal RPM
1,100
1,100
1,075
1,075
1,100
1,100
850
850
Nominal CFM
1,600
1,550
1,750
1,750
2,750
2,750
3,250
3,300
Face Area Sq. Ft.
7.22
7.22
7.22
7.94
9.15
12.58
15.72
15.72
Rows Deep
1
1
1
1
1
1
1
1
Fin / Inches
14
16
20
20
18
18
18
22
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
5/8
5/8
5/8
3/4
3/4
3/4
7/8
7/8
Unit Charge (Lbs. - Oz.)
3-2
3-1
3-4
3-9
3 - 15
5-4
7-5
6-2
Charge Per Foot, Oz.
0.66
0.66
0.66
0.68
0.68
0.68
0.70
0.70
Operating Weight Lbs.
94
114
119
122
137
161
176
188
Fan Diameter Inches Fan Motor
Coil
Physical and Electrical Data - 3 Phase MODEL Unit Supply Voltage Normal Voltage Range 1 Minimum Circuit Ampacity Max. Overcurrent Device Amps 2 Compressor Type3 Compressor Amps
Rated Load Locked Rotor
Crankcase Heater Fan Motor Amps Rated Load Fan Diameter Inches Rated HP Fan Motor Nominal RPM Nominal CFM Face Area Sq. Ft. Coil Rows Deep Fin / Inch Liquid Line OD Vapor Line OD Unit Charge (Lbs. - Oz.) 4 Charge Per Foot, Oz. Operating Weight Lbs. 1. 2. 3. 4.
2
AC036X1031
AC048X1031
15.0 25
208 / 230 - 3 - 60 187 - 252 17.3 30
Recip
Recip
10.9 78 No 1.4 18 1/4 1,100 2,750 9.15 1 18 3/8 3/4 3 - 15 .68 170
11.7 78 No 1.3 22 1/4 850 3,250 15.72 1 18 3/8 7/8 7-5 .70 206
AC060X1031
AC036X1041
AC048X1041
AC060X1041
21.3 35
8.0 15
460 - 3 - 60 432 - 504 8.3 15
10.8 15
ScrollB 16.0 125 No 1.3 22 1/4 850 3,450 23.58 1 18 3/8 7/8 9-7 .70 228
Recip
Recip
5.8 40 No .8 18 1/4 1,100 2,750 9.15 1 18 3/8 3/4 3 - 15 .68 170
6.1 39 No .7 22 1/5 850 3,250 15.72 1 18 3/8 7/8 7-5 .70 206
ScrollB 8.0 67 No .8 22 1/4 850 3,450 23.58 1 18 3/8 7/8 9-7 .70 228
Rated in accordance with ARI Standard 110, utilization range “A”. Dual element fuses or HACR circuit breaker. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
Unitary Products Group
036-21065-003 Rev. E (0405)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 PHASE ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS 012M1021 018M1021 024M1021 030M1021 036X1021 042X1021 47 51 59 63 73 81 Unit Orifice (s) 1 Factory R-22 Charge, lbs-oz 3-2 3-1 3-4 3-9 3 - 15 5-4 Outdoor Unit
Indoor Coil Coil Orifice 2 G2FD024(S,H)14/17 61 G2FD030(S,H)17 65 G2FD035(S,H)14 65 G2FD036(S,H)17 75 G2FD036(S,H)21 75 G2FD042(S,H)21 78 G2FD046(S,H)17 78 G2FD048(S,H)21/24 78 G1HA024H14 61 G1HA036H14 75 G1HA036H17 78 G1HA048H21 84 G1HA060H24 90 G1FA/G1UA024S14/17 59 G1FA/G1UA030S14 65 G1FA/G1UA036S14 73 G1FA/G1UA03617/21 73 G1FA/G1UA048S17 84 G1FA/G1UA048S21 84 G1FA/G1UA060S24 90 G1NA024S17G 51 G1NA030S17H 57 G1NA030S17K 63 G1NA030S21B 57 G1NA030S21M 63 G1NA036S17J 67 G1NA036S21C 67 G1NA048S21D 78 G1NA048S24P 78 G1NA060S24T 87 G1NF024SOF 63 G1NF036SOF 67 G1NF048SOF G1NF060SOF F2RP/F2FP018 F2RP/F2FP024 F2RP/F2FP030 F2RC/F2FC036 F2RP/F2FP036 F2RP/F2FP042 F2FP048N06 F2FP060N06 FOOTNOTES:
78 87 53 61 65 75 75 78 84 90
47 + 8 — — — — — — — 053 + 14 — — — — 47 + 6 — — — — — — 47 + 0 — — — — — — — — — — —
51 + 7 — — — — — — — 059 + 06 59 + 14 — — — 51 + 5 — — — — — — 51 + 0 — — — — — — — — — — —
59 + 2 — — — — — — — — 69 + 09 69 + 14 — — 59 + 0 — 59 + 6 — — — — — 59 + 2 — 59 + 2 — — — — — — 59 + 2 —
— — 47 + 3 — — — — — — —
— — 51 + 1 51 + 7 — — — — — —
— — — 59 + 2 — — — — — —
048X1021 81 7-5
System Orifice - Additional Charge, Oz — — — 63 + 2 — — 63 + 1 71 + 0 — — 71 + 3 — — 71 + 3 — — 71 + 7 75 + 1 — 71 + 7 75 + 1 — — 75 + 9 — — — 71 + 03 — — 71 + 07 75 + 01 — 75 + 11 81 + 07 81 + 13 — — 81 + 20 — — — 63 + 3 — — 63 + 3 73 + 0 — 63 + 1 73 + 0 — — 75 + 11 — — 75 + 11 81 + 7 — — 81 + 14 — — — — — — 63 + 2 — — — — — 63 + 2 — — — 67 + 7 — — 67 + 7 — — — 78 + 0 — — 78 + 0 — — — 63 + 0 — — — — 67 + 73 — — — — 63 + 2 — 63 + 8 — — —
— — — — — 71 + 0 73 + 4 73 + 8 — —
78 + 03 — — — — — — 75 + 1 73 + 8 —
060X1022 96 6-2
— — — — — — 78 + 6 81 + 15 — — — — — — — — — 81 + 13 81 + 13 81 + 20 — — — — — — — 78 + 4 78 + 4 — — —
— — — — — — — — 96 + 6 — — — 96 + 1 — — — — — — 96 + 6 — — — — — — — — — 96 + 0 — —
78 + 43 — — — — — — — 87 + 6 87 + 10
— 96 + 11 — — — — — — — —
1. These orifices are packed in the customer packet of each outdoor unit. 2. These orifices are factory mounted in the flow control device of each indoor coil. 3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line tubing. 2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table. 3. Add charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above. 4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set. 5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Unitary Products Group
3
036-21065-003 Rev. E (0405)
Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 PHASE ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS Outdoor Unit Unit Orifice (s)
AC036X 1
AC048X
AC060X
61
81
90
3 - 15
7-5
9-7
67
61 + 2
—
G1NA036S21C
67
61 + 2
—
—
G1NA048S21D
78
—
78 + 4
—
G1NA048S24P
78
—
78 + 4
—
G1NA060S24T
87
—
—
87 + 0
Factory R-22 Charge, lbs-oz
Indoor Coil G1NA036S17J
Coil Orifice 2
System Orifice = Additional Charge, Oz —
G1FA/G1UA036S17/21
73
61
—
—
G1FA/G1UA048S21
84
63 + 13
81 + 13
—
G1FA/G1UA060S21/24
90
—
—
90 + 5
G2FD036(S,H)17
75
61
—
—
G2FD036(S,H)21
75
61 + 5
—
—
G2FD042(S,H)21
78
—
—
—
G2FD048(S,H)21/24
78
—
81 + 15
—
G2FD060(S,H)24
90
—
—
90 + 5
G1NF036SOF
73
61 + 0
—
—
G1NF048SOF
78
—
78 + 4
—
G1NF060SOF
87
—
—
87 + 0
FOOTNOTES: 1. These orifices are packed in the customer packet of each outdoor unit. 2. These orifices are factory mounted in the flow control device of each indoor coil. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of interconnecting line tubing. 2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table. 3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above. 4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set. 5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
4
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING CAPACITY - With Air Handler Coils COOLING COIL1 NET MBH SEER RATED ELECTRIC2 W MODEL CFM TOTAL SENS. W/O TXV HEAT KW 1 PH 10 SEER AC WITH N1AH / G2FD 10 17 G2FD024(S,H)17 450 14.5 10.4 10.00 10 17 G2FD024(S,H)17 650 18.6 13.4 10.00 10 17 G2FD024(S,H)17 850 23.4 16.8 10.00 10,15,18 17 G2FD030(S,H)17 1050 28.2 20.3 10.00 10,15,18 17 G2FD036(S,H)17 1200 33.8 25.0 10.00 10,15,18 21 G2FD042(S,H)21 1400 39.5 29.2 10.00 10,15,18 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 8,10,15,20,25,30 24 G2FD060(S,H)24 1800 56.0 40.2 10.50 3 PH 10 SEER AC WITH N1AH / G2FD 10,15 21 G2FD036(S,H)17 1200 33.8 25.0 10.00 10,15 21 G2FD042(S,H)21 1400 40.0 30.1 10.00 10,15 21 G2FD048(S,H)21 1600 46.0 34.0 10.10 10,15,29 24 G2FD048(S,H)24 1600 24.6 34.0 10.10 10,15,29 24 G2FD048(S,H)24 1600 46.0 34.0 10.10 10,15,29 24 G2FD060(S,H)24 1750 58.5 39.8 10.00
AIR HANDLER UNIT MODEL
MODEL
AC012M1021 AC018M1021 AC024M1021 AC030M1021 AC036X1021 AC042X1021 AC048X1021 AC060X1022
N1AHB0806 N1AHB0806 N1AHB0806 N1AHB1206 N1AHB1206 N1AHC1606 N1AHC1606 N1AHD2006
AC036X10(31,41) AC036X10(31,41) AC048X10(31,41) AC048X10(31,41) AC048X10(31,41) AC060X10(31,41)
N1AHB1246 N1AHB1246 N1AHC1646 N1AHD2046 N1AHD2046 N1AHD2046
AC012M1021 AC012M1021 AC018M1021 AC018M1021 AC024M1021 AC024M1021 AC030M1021 AC030M1021 AC036X1021 AC036X1021 AC036X1021 AC042X1021 AC042X1021 AC048X1021 AC048X1021 AC060X1022
F2RP018 M1HC012 F2RP/F2FP018 F2RP/F2FP024 F2RP/F2FP024 F2RP/F2FP024 F2RP/F2FP030 F2RP/F2FP036 F2RC/F2FC036 F2RP/F2FP036 F2RP/F2FP042 F2FP048 F2RP/F2FP042 F2FP048 F2FP060 F2FP060
AC036X10(31,41) AC048X10(31,41) AC060X10(31,41)
F2RC/F2FC036 F2FP048 F2FP060
1 PH 10 SEER AC / F2RP / RC / FC 4,5 2,5,8 18 500 450 2,5,8 18 650 5,8,10 18 650 5,8,10 18 850 5,8,10 18 650 5,8,10,15 18 1050 5,8,10,15,19 21 1050 5,8,10,15 21 1200 5,8,10,15,19 21 1200 5,8,10,15 21 1200 5,8,10,15,20,25 24 1400 5,8,10,15 21 1400 5,8,10,15,20,25 24 1600 5,8,10,15,20,25 24 1600 5,8,10,15,20,25 24 1800 3 PH 10 seer AC with F2RP / FP 5,8,10,15 21 1200 5,8,10,15,20,25 24 1600 5,8,10,15,20,25 24 1750
14.5 13.7 17.4 18.6 23.4 18.6 28.4 29.0 33.6 34.4 34.4 40.5 39.5 45.5 46.5 56.0
10.6 9.6 12.6 13.4 16.8 20.3 20.7 21.5 25.2 25.2 28.9 30.0 33.7 34.3 41.0
10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.20 10.15 10.00 10.00 10.00 10.00 10.00
33.6 45.5 58.5
25.2 33.7 39.8
10.00 10.00 10.00
SEER + TXV3
EER
-
10.00 9.50 9.15 9.00 9.20 9.00 9.50 9.35
-
9.20 9.05 9.50 9.50 9.50 10.25
-
9.70 10.00 9.35 9.50 9.15 9.50 9.05 9.15 9.10 9.30 9.20 9.20 9.00 9.15 9.70 9.15
-
9.10 9.15 9.80
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 1. 2. 3. 4. 5.
G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters. TXV = Use 1TV700 Series Kit. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC. models. All ratings remain the same. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard. - = Not applicable.
Unitary Products Group
5
036-21065-003 Rev. E (0405)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils FURNACE** UNIT MODEL
AC012M1021
250 650
AC018M1021
575 725
AC024M1021
750 950
AC030M1021
925 1175
AC036X1021
6
CFM RANGE (MIN.-MAX.)
1050 1350
COOLING
W
COIL MODEL
RATED CFM
14,17 17 14,17 14,17 14,17 14 17 14,17 14,17 14,17 14 14 14 17 21 14,17 14 14,17 14 14 17,21 14 17 17 21 14 14 17,21 17 14 14 17,21 17 21,24 14 17 21 17 21 14 17,21 17 21,24 14 17 21 21 17
G1FA024S14,17 G1HD024 G1NA024S17G G1UA024S14,17 G2FD024(S,H)14,17 G1FA024S14,17 G1HA024H14 G1HD024 G1NA024S17G G1UA024S14,17 G2FD024(S,H)14,17 G1FA024S14,17 G1FA036S14 G1HA024H14 G1HA036H14 G1HD024 G1NA030S17H G1NA030S21B G1UA024S14,17 G1UA036S14 G2FD024(S,H)14,17 G1FA030S14 G1FA036S14 G1FA036S17,21 G1HA036H14 G1HA036H17 G1HD036 G1NA030S17K G1NA030S21M G1UA030S14 G1UA036S14 G1UA036S17,21 G2FD030(S,H)17 G2FD035(S,H)14 G1FA036S14 G1FA036S17,21 G1FA048S17 G1FA048S21 G1HA036H14 G1HA036H17 G1HA048H21 G1HD036 G1HD048 G1NA036S17J G1NA036S21C G1UA036S14 G1UA036S17,21 G1UA048S17 G1UA048S21 G2FD035(S,H)14 G2FD036(S,H)17 G2FD036(S,H)21 G2FD042(S,H)21 G2FD046(S,H)17
450 450 450 450 450 650 650 650 650 650 650 850 850 800 800 850 850 850 850 850 850 1050 1050 1050 1000 1000 1050 1050 1050 1050 1050 1050 1050 1050 1200 1200 1200 1200 1150 1200 1200 1200 1165 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
NET MBH TOTAL
SENS.
SEER W/O TXV
14.4 14.6 14.1 14.4 14.5 18.3 18.6 18.5 17.7 18.3 18.6 23.0 23.8 23.9 25.6 23.6 23.6 23.6 23.0 23.8 23.4 28.2 28.2 28.0 29.5 30.2 28.4 28.4 28.4 28.2 28.2 28.0 28.2 28.0 33.6 33.6 35.0 36.0 33.2 33.8 36.0 34.4 34.8 34.4 34.4 33.6 33.6 35.0 36.0 33.4 33.8 33.8 34.4 34.4
10.3 10.4 10.0 10.3 10.4 13.3 13.2 13.5 12.4 13.3 13.4 16.6 17.2 17.0 18.2 17.0 16.5 16.5 16.6 17.2 16.8 20.2 20.2 20.0 20.9 21.7 20.2 19.9 19.9 20.2 20.2 20.0 20.3 20.0 24.9 24.9 25.9 26.6 23.6 24.3 26.3 25.5 25.8 25.5 25.5 24.9 24.9 25.9 26.6 24.7 25.0 25.0 25.5 25.5
10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.30 10.40 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.30 10.40 10.00 10.00 10.00 10.15 10.15
SEER + TXV1
EER
-
9.95 10.00 9.80 9.95 10.00 9.40 9.70 9.50 9.50 9.40 9.50 9.05 9.25 9.45 9.70 9.25 9.20 9.20 9.05 9.25 9.15 8.95 8.95 8.95 9.65 9.70 9.00 9.00 9.00 8.95 8.95 8.95 9.00 8.95 9.10 9.10 9.40 9.40 9.20 9.30 9.40 8.90 8.95 9.20 9.30 9.10 9.10 9.40 9.40 9.10 9.20 9.20 9.30 9.30
-
-
-
-
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued) FURNACE** UNIT MODEL
AC036X10(31,41)
CFM RANGE (MIN.-MAX.)
1050 1350
COOLING
W
COIL MODEL
RATED CFM
17,21 21,24 17 21 17,21 21,24 17 21
G1FA036S17,21 G1FA048S21 G1NA036S17J G1NA036S21C G1UA036S17,21 G1UA048S21 G2FD036(S,H)17 G2FD036(S,H)21
17 21,24 21,24 17 21 21 21 17 21,24 21,24 21 17 21,24 24 21,24 21,24 21 21 21,24 21,24 21 17 21,24 17 21,24 21,24 21 24 21 17 21,24 21,24 17 21,24 24 21,24 21 21,24 21,24
G1FA048S17 G1FA048S21 G1FA060S21,24 G1HA036H17 G1HA048H21 G1HD048 G1NA036S21C G1NA048S21D G1UA048S17 G1UA048S21 G1UA060S21,24 G2FD042(S,H)21 G2FD046(S,H)17 G2FD048(S,H)21,24 G2FD060(S,H)24 G1FA048S21 G1FA060S21,24 G1NA036S21C G1NA048S21D G1UA048S21 G1UA060S21,24 G2FD042(S,H)21 G2FD046(S,H)17 G2FD048(S,H)21,24 G1FA048S17 G1FA048S21 G1FA060S21,24 G1HA048H21 G1HA060H24 G1HD048 G1HD060 G1NA048S21D G1UA048S17 G1UA048S21 G1UA060S21,24 G2FD046(S,H)17 G2FD048(S,H)21,24 G2FD060(S,H)24 G1FA048S21 G1NA048S21D G1UA048S21 G2FD048(S,H)21,24
NET MBH TOTAL
SENS.
SEER W/O TXV
SEER + TXV1
EER
1200 1200 1200 1200 1200 1200 1200 1200
33.6 36.0 34.4 34.4 33.6 36.0 33.8 33.8
24.9 26.6 25.5 25.5 24.9 26.6 25.0 25.0
10.00 10.40 10.00 10.00 10.00 10.40 10.00 10.00
-
9.10 9.40 9.20 9.30 9.10 9.40 9.20 9.20
1380 1400 1400 1300 1400 1390 1400 1400 1380 1400 1450 1400 1380 1450 1450 1400 1400 1400 1400 1400 1400 1400 1380 1450 1500 1600 1600 1550 1600 1600 1600 1400 1500 1600 1600 1500 1600 1600 1600 1400 1600 1600
40.0 41.0 42.0 38.8 41.0 40.5 40.0 40.5 40.0 41.0 42.0 39.5 40.0 41.0 42.0 41.0 42.0 40.0 40.5 41.0 42.0 39.5 40.0 41.0 44.5 45.5 47.0 45.0 46.0 45.5 46.5 46.5 44.5 45.5 47.0 44.5 46.0 47.0 45.5 46.5 45.5 46.0
30.2 30.3 31.0 27.9 29.9 30.0 28.3 28.6 30.2 30.3 31.1 29.2 29.6 30.3 31.0 30.3 31.0 28.3 28.6 30.3 31.1 29.2 29.6 30.3 33.5 33.7 34.8 32.9 33.1 33.7 34.4 34.4 33.5 33.7 34.8 32.9 34.0 34.0 33.5 34.4 33.5 34.0
10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.10 10.00 10.00 10.10 10.10 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.00 10.10 10.00 10.00 10.40 10.00 10.00 10.00 10.20 10.00 10.00 10.00 10.40 10.00 10.10 10.40 10.00 10.00 10.00 10.10
-
9.05 9.25 9.45 9.00 9.25 9.05 9.15 9.15 9.05 9.25 9.50 9.00 9.05 9.15 9.50 9.25 9.45 9.15 9.15 9.25 9.45 9.00 9.05 9.15 9.15 9.45 9.70 9.45 9.70 9.50 9.65 9.50 9.15 9.45 9.70 9.15 9.50 9.70 9.45 9.50 9.45 9.50
For Notes See Page 5.
AC042X1021
1225 1575
AC042X1031,41
1225 1575
AC048X1021
1400 1800
AC048X10(31,41)
1400 1800
Unitary Products Group
-
-
7
036-21065-003 Rev. E (0405)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued) FURNACE** UNIT MODEL
AC060X1022
1600 2100
AC060X10(31,41)
1525 1975
COOLING
W
COIL MODEL
RATED CFM
21,24 24 21 24 21,24 24 24 21,24 24 21,24 24
G1FA060S21,24 G1HA060H24 G1HD060 G1NA048S21D G1NA060S24T G1UA060S21,24 G2FD060(S,H)24 G2FD061H24 G1FA060S21,24 G1NA060S24T G1UA060S21,24 G2FD060(S,H)24
1800 1800 2000 1500 1800 1800 1800 2000 1750 1750 1750 1750
CFM RANGE (MIN.-MAX.)
NET MBH TOTAL
SENS.
56.0 54.9 55.5 51.0 55.0 56.0 56.0 57.0 58.5 57.5 58.5 58.5
40.2 39.5 40.0 34.8 39.8 40.2 40.2 40.9 39.8 39.1 39.8 39.8
SEER W/O TXV
SEER + TXV1
EER
10.50 10.00 10.50
-
9.35 9.35 9.15
10.50 10.50 10.50 10.50 10.00 10.00 10.00 10.00
-
9.25 9.35 9.35 9.35 10.25 10.00 10.25 10.25
1. TXV = Use 1TV700 Series Kit.
* Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.
COOLING PERFORMANCE MODEL
AC012M1021
AC018M1021
AC024M1021
AC030M1021
AC036X1021 AC036X10(31,41)
AIR TEMP ON CONDENSER 75ºF 95ºF 115ºF TEMP. PSIG MBH KW MBH KW MBH KW SUCT. T/P @ COMPR. 35 40 45 50 35 40 45 50 35 40 45 50 35 40 45 50 35 40 45 50
61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0
13.1 14.5 15.9 17.4 16.2 17.7 19.3 20.8 21.0 22.9 25.0 26.8 25.1 27.4 29.9 32.1 30.5 33.3 36.4 39.1
1.01 1.03 1.04 1.06 1.66 1.67 169 1.70 2.23 2.24 2.27 2.28 2.68 2.70 2.74 2.75 3.28 3.31 3.35 3.36
11.6 12.8 14.1 15.5 13.1 14.9 16.7 18.5 17.0 19.3 21.6 23.9 20.3 23.1 25.8 28.6 24.7 28.1 31.4 34.8
1.20 1.23 1.26 1.28 1.84 1.88 1.92 1.96 2.46 2.52 2.58 2.63 2.97 3.04 3.10 3.17 3.64 3.72 3.80 3.88
10.1 11.2 12.4 13.6 11.0 12.8 14.2 15.9 14.2 16.5 18.3 20.5 17.0 19.7 21.9 24.5 20.6 24.0 26.7 29.9
1.40 1.44 1.47 1.51 1.96 2.04 2.11 2.18 2.63 2.74 2.83 2.92 3.17 3.30 3.41 3.51 3.88 4.04 4.18 4.31
MODEL
AC042X1021
AC048X1021 AC048X10(31,41)
AC060X1022
AC060X10(31,41)
AIR TEMP ON CONDENSER 75ºF 95ºF 115ºF TEMP. PSIG MBH KW MBH KW MBH KW SUCT. T/P @ COMPR. 35 40 45 50 35 40 45 50 35 40 45 50 35 40 45 50
61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0 61.5 68.5 76.0 84.0
35.8 39.1 42.6 45.8 39.9 43.6 47.6 51.1 49.4 54.0 58.4 62.7 54.4 60.1 65.8 71.9
3.83 3.86 3.90 3.93 4.18 4.21 4.26 4.28 4.15 4.19 4.27 4.32 4.46 4.44 4.53 4.62
28.9 32.9 36.8 40.8 32.3 36.7 41.1 45.5 43.8 48.2 52.4 56.9 50.5 56.0 61.6 67.5
4.25 4.34 4.53 4.63 4.63 4.73 4.84 4.94 5.13 5.14 5.25 5.38 4.74 4.83 4.92 5.01
24.2 28.2 31.3 35.0 27.0 31.4 34.9 39.0 38.2 42.3 46.3 50.2 46.3 51.6 56.9 62.6
4.53 4.72 4.87 5.03 4.94 5.14 5.32 5.48 6.34 6.35 6.47 5.61 5.08 5.18 5.26 5.36
NOTES: 1. For condensing unit only. Does not include effect of evaporator motor power or heat. 2. Performance based on 15° superheat and 15° sub-cooling at condensing unit. a. Increase capacity 1% for each 2° increase in sub-cooling. b. Decrease capacity 1% for each 2° decrease in sub-cooling. 3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°F. Maximum recommended condensing temperature is 140°F.
8
Unitary Products Group
036-21065-003 Rev. E (0405)
1. Including Fan guard.
ACCESSORIES*
C
Refer to Price Manual for specific model numbers. Hard Start Kit - Provides increased starting torque for areas with low voltage.
A
Compressor Blanket - Designed to further reduce the normal compressor operating sound. Refer to price pages for specific match-ups. Off Cycle Timer Delay - Provides a 5-minute off cycle to prevent rapid recycling of the compressor.
B
Room Thermostats - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation. 1 Heat Stage only, manual, mechanical thermostat. Add subbase for 1H/1C.
C
1H/1C, manual change-over electronic non-programmable thermostat. 1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
A
1H/1C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the price book or consult factory. B
SOUND POWER RATINGS*
DIMENSIONS - 1 Phase Unit Model A 012
Refrigerant Connection Service Valve Size
Dimensions (Inches) 1
22
B 21-3/4
C
Liquid
Vapor
21-3/4
018
22
21-3/4
21-3/4
024
22
21-3/4
21-3/4
030
24
21-3/4
21-3/4
036
19
35
23
042
25
35
23
048
27
38
27
060
27
37
27
2
3/4”
UNIT MODEL
(dBA)
012
72
018
74
024
75
030
76
036
82
042
82
048
82
060
80
*Rated in accordance with ARI 270-95 Standards.
3/8”
3/4”
7/8”
1. Including Fan guard. 2. Reducer fitting required for 5/8” line set.
DIMENSIONS - 3 Phase Unit Model
036 048 060
Refrigerant Connection Service Valve Size
Dimensions (Inches) A1 19 27 39
Unitary Products Group
B 35 37 37
C 23 27 27
Liquid 3/8” 3/8” 3/8”
Vapor 3/4” 7/8” 7/8”
9
036-21065-003 Rev. E (0405)
TYPICAL INSTALLATION - AC012M1021 THRU 030 AND AC036X1021 THRU 060 60” OVERHEAD CLEARANCE
MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE WEATHERPROOF DISCONNECT SWITCH
THERMOSTAT
TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 1 WIRING
6” CLEARANCE AROUND PERIMETER 1 TO 2.5 TON, 10 SEER (“M” SERIES ONLY)
NEC CLASS 2 WIRING
10” CLEARANCE COIL AREA 3 TO 5 TONS, 10 SEER
TO INDOOR COIL
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
CONTROL ACCESS PANEL
TYPICAL FIELD WIRING - 1 PHASE APPLICATION ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER WIRING POWER WIRING 24 VOLT CONTROL WIRING 208/230-1-60 CONTROL WIRING MINIMUM 18 GA. WIRE 230-1-50 FACTORY WIRING (NEC CLASS 2) FURNACE OR AIR HANDLER TERMINAL BLOCK
* TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
C
Y
R
G
W
Y
R
G
W
CONTACTOR TERMINALS GND. LUG
COIL
*
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TYPICAL FIELD WIRING - 3 PHASE APPLICATION ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER WIRING 208/230-3-60 460-3-60
POWER WIRING CONTROL WIRING FACTORY WIRING
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK C
Y
R
G
W
Y
R
G
W
* TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT. CONTACTOR TERMINALS GND. LUG
COIL CONDENSING UNIT
*
ROOM THERMOSTAT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
10
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC012M1021
INDOOR COIL MODEL NO.
G1NA024S17G
CONDENSER ENTERING AIR TEMPERATURE
ID CFM
400
ID DB (°F)
85
80
450 70
85
80
500 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
15.4
14.6
13.8
15.4
14.7
14.0
15.5
14.8
14.2
75
85
95
105
115
125
S.C.
9.6
9.6
9.2
10.0
9.9
9.7
10.3
10.3
10.2
K.W
1.21
1.21
1.21
1.23
1.22
1.22
1.25
1.24
1.24 13.6
T.C.
15.2
14.2
13.1
15.3
14.4
13.3
15.4
14.6
S.C.
9.8
9.5
9.0
10.1
10.0
9.5
10.5
10.4
10.1
K.W
1.32
1.31
1.31
1.34
1.33
1.33
1.36
1.35
1.35
T.C.
15.1
13.8
12.4
15.2
14.1
12.7
15.3
14.4
13.0
S.C.
9.9
9.5
8.8
10.3
10.0
9.3
10.7
10.5
9.9
K.W
1.43
1.42
1.42
1.45
1.44
1.44
1.47
1.46
1.46
T.C.
14.2
13.0
11.6
14.3
13.2
11.9
14.5
13.4
12.1
S.C.
9.5
9.0
8.3
10.0
9.6
8.8
10.5
10.1
9.4
K.W
1.56
1.55
1.53
1.58
1.57
1.55
1.60
1.59
1.57
T.C.
13.3
12.1
10.9
13.5
12.2
11.1
13.6
12.4
11.2
S.C.
9.2
8.6
7.7
9.8
9.1
8.3
10.4
9.7
8.9
K.W
1.69
1.67
1.65
1.71
1.70
1.67
1.73
1.72
1.69 10.4
T.C.
12.5
11.3
10.2
12.6
11.3
10.3
12.8
11.3
S.C.
8.8
8.1
7.2
9.5
8.7
7.8
10.2
9.2
8.4
K.W
1.82
1.80
1.76
1.84
1.82
1.78
1.86
1.85
1.81
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB0806
G2FD024(S,H)17
1.01
1.03
1.04
F2RP018
1.03
1.06
1.04
M1HC012
0.97
0.96
0.95
G1FA024S14,17
1.02
1.03
1.01
G1HD024
1.04
1.04
1.01
G1UA024S14,17
1.02
1.03
1.01
G2FD024(S,H)14,17
1.03
1.04
1.01
Unitary Products Group
11
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC018M1021
INDOOR COIL MODEL NO.
G1NA024S17G
CONDENSER ENTERING AIR TEMPERATURE
ID CFM
500
ID DB (°F)
85
80
650 70
85
80
800 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
20.6
19.1
17.8
20.7
19.5
18.3
20.9
19.9
18.8
75
85
95
105
115
125
S.C.
11.3
11.1
10.8
12.0
12.0
12.1
12.7
13.0
13.4
K.W
1.59
1.58
1.56
1.66
1.64
1.63
1.72
1.71
1.70
T.C.
19.7
18.2
16.5
19.9
18.6
17.1
20.1
19.0
17.7
S.C.
11.3
10.9
10.4
12.3
12.2
11.8
13.4
13.5
13.2
K.W
1.70
1.68
1.66
1.77
1.75
1.73
1.84
1.82
1.80
T.C.
18.9
17.3
15.2
19.1
17.7
15.9
19.4
18.0
16.5
S.C.
11.3
10.8
9.9
12.6
12.4
11.5
14.0
13.9
13.0
K.W
1.81
1.79
1.76
1.88
1.86
1.83
1.95
1.92
1.90
T.C.
17.4
15.5
13.5
17.7
16.0
14.1
18.1
16.6
14.7
S.C.
10.7
10.0
9.2
12.4
11.7
10.8
14.0
13.4
12.3
K.W
1.92
1.88
1.84
1.99
1.95
1.91
2.06
2.02
1.98
T.C.
15.9
13.7
11.8
16.4
14.4
12.4
16.9
15.1
12.9
S.C.
10.2
9.2
8.5
12.1
11.1
10.1
14.0
12.9
11.6
K.W
2.02
1.96
1.92
2.09
2.04
1.99
2.17
2.12
2.06
T.C.
14.4
11.9
10.1
15.0
12.8
10.6
15.7
13.7
11.1
S.C.
9.7
8.4
7.8
11.8
10.4
9.4
14.0
12.4
10.9
K.W
2.12
2.05
1.99
2.20
2.13
2.07
2.28
2.22
2.15
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB0806
G2FD024(S,H)17
1.05
1.08
1.05
F2RP/F2FP018
0.98
1.02
1.00
F2RP/F2FP024
1.05
1.08
1.05
G1FA024S14,17
1.03
1.07
1.04
G1HD024
1.05
1.09
1.05
G1NA024S17G
1.00
1.00
1.00
G1UA024S14,17
1.03
1.07
1.04
G2FD024(S,H)14,17
1.05
1.08
1.05
12
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC024M1021
INDOOR COIL MODEL NO.
G1NA030S17H
CONDENSER ENTERING AIR TEMPERATURE
ID CFM
650
ID DB (°F)
85
80
850 70
85
80
1050 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
28.0
26.3
23.9
28.3
26.6
24.7
28.5
27.0
25.5
S.C.
15.5
15.3
14.6
16.9
16.9
16.5
18.3
18.4
18.5
K.W
2.25
2.21
2.17
2.34
2.30
2.26
2.42
2.39
2.35
75
85
95
105
115
125
T.C.
26.6
24.5
22.5
26.9
25.1
23.1
27.2
25.7
23.7
S.C.
15.4
14.8
13.9
17.0
16.7
15.9
18.7
18.5
17.8
K.W
2.39
2.33
2.28
2.48
2.43
2.38
2.57
2.53
2.47
T.C.
25.1
22.8
21.0
25.5
23.6
21.5
25.9
24.4
21.9
S.C.
15.2
14.4
13.1
17.1
16.5
15.2
19.0
18.6
17.2
K.W
2.53
2.46
2.39
2.63
2.57
2.50
2.72
2.68
2.60
T.C.
23.1
20.7
18.5
23.5
21.5
19.1
24.0
22.2
19.7
S.C.
14.4
13.6
12.4
16.5
15.7
14.4
18.6
17.8
16.3
K.W
2.73
2.64
2.57
2.84
2.75
2.67
2.94
2.85
2.77
T.C.
21.0
18.6
16.1
21.5
19.3
16.8
22.0
19.9
17.5
S.C.
13.7
12.8
11.7
16.0
14.9
13.5
18.3
16.9
15.4
K.W
2.93
2.81
2.75
3.04
2.92
2.84
3.16
3.03
2.94
T.C.
19.0
16.5
13.6
19.5
17.1
14.5
20.1
17.7
15.3
S.C.
13.0
12.1
11.0
15.5
14.1
12.7
18.0
16.1
14.4
K.W
3.12
2.99
2.92
3.25
3.10
3.02
3.38
3.21
3.11
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB0806
G2FD024(S,H)17
0.99
1.02
1.00
F2RP/F2FP024
0.99
1.02
1.00
F2RP/F2FP024
0.79
0.00
0.76
G1FA024S14,17
0.97
1.01
0.99
G1FA036S14
1.01
1.04
1.00
G1HD024
1.00
1.03
0.99
G1NA030S17H
1.00
1.00
1.00
G1NA030S21B
1.00
1.00
1.00
G1UA024S14,17
0.97
1.01
0.99
G1UA036S14
1.01
1.04
1.00
G2FD024(S,H)14,17
0.99
1.02
1.00
Unitary Products Group
13
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC030M1021
INDOOR COIL MODEL NO.
G1NA030S17K
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
850 85
80
1050 70
85
80
1250 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
32.8
31.3
29.0
33.2
31.8
29.9
33.7
32.3
30.7
S.C.
19.6
19.4
19.2
20.4
20.5
20.5
21.3
21.7
21.9
K.W
2.75
2.72
2.68
2.85
2.81
2.78
2.94
2.90
2.87
75
85
95
105
115
125
T.C.
31.3
29.5
27.1
31.9
30.1
27.9
32.5
30.6
28.7
S.C.
19.2
19.0
18.6
20.4
20.2
20.0
21.6
21.5
21.3
K.W
2.95
2.89
2.83
3.05
2.99
2.93
3.15
3.08
3.03
T.C.
29.9
27.7
25.3
30.6
28.4
26.0
31.2
29.0
26.7
S.C.
18.9
18.5
18.0
20.4
19.9
19.4
21.9
21.3
20.7
K.W
3.14
3.06
2.98
3.24
3.16
3.09
3.35
3.27
3.20
T.C.
27.9
25.6
22.9
28.6
26.2
23.6
29.3
26.9
24.4
S.C.
18.1
17.6
16.9
19.7
19.0
18.4
21.3
20.5
19.8
K.W
3.32
3.22
3.12
3.43
3.33
3.23
3.54
3.44
3.34
T.C.
25.9
23.4
20.5
26.6
24.1
21.3
27.4
24.9
22.1
S.C.
17.4
16.7
15.7
19.0
18.2
17.3
20.6
19.7
19.0
K.W
3.50
3.37
3.27
3.61
3.49
3.38
3.72
3.60
3.49
T.C.
23.8
21.3
18.1
24.6
22.0
19.0
25.5
22.8
19.8
S.C.
16.7
15.7
14.6
18.3
17.3
16.3
20.0
18.9
18.1
K.W
3.67
3.53
3.42
3.79
3.65
3.53
3.91
3.77
3.64
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB1206
G2FD030(S,H)17
0.99
1.02
0.99
F2RP/F2FP030
1.00
1.02
0.99
F2RP/F2FP036
1.02
1.04
1.00
G1FA030S14
0.99
1.02
1.00
G1FA036S14
0.99
1.02
1.00
G1FA036S17,21
0.99
1.01
0.99
G1HD036
1.00
1.02
1.00
G1NA030S21M
1.00
1.00
1.00
G1UA030S14
0.99
1.02
1.00
G1UA036S14
0.99
1.02
1.00
G1UA036S17,21
0.99
1.01
0.99
G2FD030(S,H)17
0.99
1.02
0.99
G2FD035(S,H)14
0.99
1.01
0.99
14
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC036X1021, AC036X10(31,41)
INDOOR COIL MODEL NO.
G1FA036S17,21
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
1150 85
80
1250 70
85
80
1350 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
38.3
36.1
34.4
37.9
36.3
34.6
38.0
36.4
34.9
S.C.
24.0
23.7
24.0
24.1
24.5
24.7
24.7
25.3
25.2
K.W
3.19
3.14
3.09
3.23
3.20
3.14
3.26
3.23
3.18
75
85
95
105
115
125
T.C.
36.9
34.6
32.2
36.9
34.9
32.6
37.0
35.2
33.0
S.C.
24.2
23.7
22.9
24.7
24.6
23.9
25.3
25.5
24.8
K.W
3.45
3.39
3.30
3.50
3.44
3.36
3.53
3.49
3.40
T.C.
35.5
33.2
30.0
35.8
33.6
30.4
36.0
34.0
31.0
S.C.
24.3
23.6
21.9
25.4
24.9
23.6
26.0
25.6
24.4
K.W
3.71
3.63
3.52
3.76
3.69
3.58
3.80
3.75
3.62
T.C.
33.2
30.4
26.7
33.4
30.8
27.2
33.6
31.3
27.7
S.C.
23.7
22.5
20.7
24.5
23.6
21.9
25.4
24.6
23.0
K.W
3.97
3.84
3.71
4.02
3.91
3.77
4.06
3.96
3.81
T.C.
31.0
27.6
23.5
31.1
28.2
24.2
31.3
28.5
24.4
S.C.
23.1
21.3
19.6
23.9
22.6
20.7
24.8
23.7
21.6
K.W
4.22
4.06
3.90
4.29
4.13
3.94
4.33
4.18
4.00
T.C.
28.7
24.8
20.2
28.9
25.6
21.1
29.0
25.7
21.0
S.C.
22.5
20.2
18.4
23.2
21.6
19.6
24.2
22.7
20.2
K.W
4.47
4.28
4.09
4.56
4.35
4.11
4.60
4.40
4.19
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
3 Phase
Air Handler
Coil
T.C.
S.C.
KW
Air Handler
Coil
T.C.
S.C.
KW
N1AHB1206
G2FD036(S,H)17
1.01
1.00
1.00
N1AHB1246
G2FD036(S,H)17
1.00
1.00
0.98
N1AHB1206
G2FD046(S,H)17
G2FD046(S,H)21
1.02
1.02
1.00
1.00
0.86
1.00
1.02
1.02
1.00
N1AHB1246
F2RC/F2FC036
1.00
0.86
1.00
F2RC/F2FC036
F2RP/F2FP036
1.02
1.01
1.00
G1FA048S21
1.07
1.07
1.04
F2RP/F2FP042
1.02
1.01
1.01
G1NA036S17J
1.02
1.02
1.01
G1FA036S14
1.00
1.00
1.00
G1NA036S21C
1.02
1.02
1.00
G1FA048S17
1.04
1.04
1.01
G1UA036S17,21
1.00
1.00
1.00
G1FA048S21
1.07
1.07
1.04
G1UA048S21
1.07
1.07
1.04
G1HD036
1.02
1.02
1.05
G2FD036(S,H)17
1.01
1.00
1.00
G2FD046(S,H)17
1.02
1.02
1.00
G2FD036(S,H)21
1.01
1.00
1.00
G1HD048
1.04
1.04
1.05
G1NA036S17J
1.02
1.02
1.01
G1NA036S21C
1.02
1.02
1.00
G1UA036S14
1.00
1.00
1.00
G1UA036S17,21
1.00
1.00
1.00
G1UA048S17
1.04
1.04
1.01
G1UA048S21
1.07
1.07
1.04
G2FD035(S,H)14
0.99
0.99
0.99
G2FD036(S,H)17
1.01
1.00
1.00
G2FD036(S,H)21
1.01
1.00
1.00
G2FD042(S,H)21
1.02
1.02
1.00
Unitary Products Group
15
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC042X1021, AC042X10(31,41)
INDOOR COIL MODEL NO.
G1FA048S21
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
1200 85
80
1400 70
85
1600
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
47.2
44.1
41.2
47.5
44.6
41.9
47.9
45.1
42.6
S.C.
30.2
29.6
29.4
31.9
31.1
31.0
33.6
32.6
32.6
K.W
3.90
3.85
3.78
4.05
3.99
3.94
4.19
4.14
4.09
75
85
95
105
115
125
T.C.
45.5
42.1
38.5
45.9
42.8
39.3
46.3
43.4
40.2
S.C.
29.8
28.9
28.1
31.4
30.7
30.0
33.0
32.5
31.9
K.W
4.13
4.06
3.96
4.28
4.21
4.13
4.43
4.36
4.29
T.C.
43.9
40.2
35.7
44.3
41.0
36.8
44.8
41.8
37.8
S.C.
29.5
28.2
26.9
30.9
30.3
29.1
32.4
32.4
31.2
K.W
4.36
4.27
4.14
4.52
4.43
4.31
4.67
4.59
4.49
T.C.
40.5
36.3
32.0
41.2
37.1
32.8
42.0
38.0
33.7
S.C.
28.1
26.7
25.1
29.9
28.8
27.2
31.7
30.9
29.3
K.W
4.58
4.44
4.30
4.74
4.60
4.47
4.89
4.77
4.64
T.C.
37.1
32.3
28.3
38.2
33.3
28.9
39.2
34.2
29.6
S.C.
26.8
25.1
23.3
29.0
27.2
25.4
31.1
29.4
27.4
K.W
4.81
4.62
4.45
4.96
4.78
4.62
5.10
4.95
4.79
T.C.
33.7
28.4
24.5
35.1
29.4
25.0
36.4
30.4
25.4
S.C.
25.5
23.5
21.5
28.0
25.7
23.5
30.5
27.9
25.5
K.W
5.04
4.79
4.61
5.18
4.96
4.78
5.32
5.13
4.94
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
3 Phase
Air Handler
Coil
T.C.
S.C.
KW
Air Handler
Coil
T.C.
S.C.
KW
N1AHC1606
G2FD042(S,H)21
0.96
0.96
0.99
N1AHC1646
G2FD042(S,H)21
0.98
0.99
1.00
N1AHC1606
G2FD048(S,H)21
1.00
1.00
1.01
N1AHC1646
G2FD048(S,H)21
0.99
1.01
1.01
F2RP/F2FP042
0.96
0.95
0.99
F2RP/F2FP042
0.95
0.95
0.99
F2FP048
0.99
0.99
0.99
F2FP048
0.99
0.99
0.99
G1FA048S17
0.98
1.00
1.00
G1FA060S21,24
1.02
1.02
1.00
G1FA060S21,24
1.02
1.02
1.00
G1NA036S21C
0.98
0.93
0.99
G1HD048
0.99
0.99
1.01
G1NA048S21D
0.99
0.94
1.00
G1NA036S21C
0.98
0.93
0.99
G1UA048S21
1.00
1.00
1.00
G1NA048S21D
0.99
0.94
1.00
G1UA060S21,24
1.02
1.03
1.00
G1UA048S17
0.98
1.00
1.00
G2FD042(S,H)21
0.96
0.96
0.99
G1UA048S21
1.00
1.00
1.00
G2FD046(S,H)17
0.98
0.98
1.00
G1UA060S21,24
1.02
1.03
1.00
G2FD048(S,H)21,24
1.00
1.00
1.01
G2FD042(S,H)21
0.96
0.96
0.99
G2FD046(S,H)17
0.98
0.98
1.00
G2FD048(S,H)21,24
1.00
1.00
1.01
G2FD060(S,H)24
1.02
1.02
1.00
16
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC048X1021, AC048X10(31,41)
INDOOR COIL MODEL NO.
G1FA048S21
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
1200 85
80
1400 75
70
85
80
1600 75
70
85
80
75
70
ID WB (°F)
72
67
62
57
72
67
62
57
72
67
62
57
T.C.
53.4
48.9
45.1
40.2
54.3
49.8
45.9
41.3
54.9
50.3
46.4
41.8
75
85
95
105
115
125
S.C.
32.2
32.3
31.0
32.5
34.0
34.0
32.7
34.7
35.2
35.3
33.9
35.9
K.W
4.32
4.15
4.00
3.83
4.44
4.26
4.11
3.95
4.53
4.36
4.21
4.04
T.C.
52.0
47.5
43.7
39.2
52.7
48.3
44.5
40.0
53.2
48.7
45.2
40.5
S.C.
32.2
32.3
31.1
32.7
34.1
34.1
32.8
34.7
35.4
35.5
34.5
36.0
K.W
4.62
4.43
4.26
4.07
4.74
4.55
4.38
4.18
4.84
4.65
4.48
4.28
T.C.
49.0
44.9
41.3
36.9
49.6
45.5
42.0
37.6
50.0
45.8
42.4
38.3
S.C.
31.6
31.6
30.4
31.8
33.5
33.7
32.4
33.8
34.9
35.0
33.7
35.6
K.W
4.91
4.70
4.51
4.31
5.02
4.81
4.64
4.43
5.13
4.92
4.74
4.53
T.C.
45.6
41.6
38.4
34.3
46.0
42.2
39.0
35.0
46.2
42.5
39.3
36.2
S.C.
30.5
30.6
29.5
30.9
32.6
32.8
31.5
32.8
34.1
34.2
32.7
34.5
K.W
5.18
4.96
4.76
4.54
5.30
5.07
4.88
4.67
5.39
5.18
4.99
4.83
T.C.
41.8
38.3
35.3
31.7
42.3
38.8
35.8
33.0
42.5
39.0
36.2
33.5
S.C.
29.3
29.5
28.2
29.6
31.6
31.4
30.1
31.5
33.0
32.9
31.5
32.0
K.W
5.42
5.18
4.98
4.76
5.52
5.31
5.10
4.94
5.63
5.41
5.21
5.06
T.C.
38.0
35.0
32.3
29.1
38.6
35.4
32.7
31.0
38.8
35.5
33.2
30.8
S.C.
28.1
28.4
26.9
28.3
30.6
30.0
28.7
30.2
31.9
31.6
30.4
29.5
K.W
5.66
5.40
5.20
4.98
5.74
5.55
5.32
5.21
5.87
5.64
5.43
5.29
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
3 Phase
Air Handler
Coil
T.C.
S.C.
KW
Air Handler
Coil
T.C.
S.C.
KW
N1AHC1606
G2FD048(S,H)21
1.01
1.01
1.01
N1AHC1646
G2FD048(S,H)21
1.01
1.01
1.00
N1AHD2006
G2FD060(S,H)24
1.03
1.03
1.01
N1AHD2046
G2FD048(S,H)24
1.01
1.01
1.00
F2FP048
1.00
1.00
1.03
N1AHD2046
G2FD060(S,H)24
1.03
1.03
1.00
F2FP060
1.02
1.02
1.00
F2FP048
1.00
1.00
1.03
0.98
0.99
1.01
G1FA048S21
1.00
1.00
1.00
G1FA048S17 G1FA060S21,24
1.03
1.03
1.01
G1NA048S21D
1.02
1.02
1.02
G1UA048S21
1.00
1.00
1.00
G1UA048S21
1.00
1.00
1.00
G1HD048
1.00
1.00
0.99
G2FD048(S,H)21,24
1.01
1.01
1.01
G1HD060
1.02
1.02
1.00
Unitary Products Group
17
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC060X1022
INDOOR COIL MODEL NO.
G1FA060S21,24
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
2050 85
80
1800 70
85
1550
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
64.7
61.9
58.2
64.1
61.2
57.2
63.6
60.5
56.2
S.C.
46.3
44.9
42.9
43.3
42.1
40.3
40.3
39.3
37.7
K.W
5.18
5.13
5.03
5.08
5.02
4.92
4.97
4.91
4.81
75
85
95
105
115
125
T.C.
62.8
59.6
55.4
62.3
58.6
54.3
61.8
57.6
53.3
S.C.
45.9
44.3
41.9
42.8
41.2
39.2
39.7
38.2
36.5
K.W
4.94
4.86
4.77
5.58
5.50
5.40
5.48
5.40
5.28
T.C.
60.9
57.3
52.7
60.4
56.0
51.5
59.9
54.7
50.3
S.C.
45.7
43.5
40.8
42.4
40.2
38.0
39.2
37.0
35.2
K.W
6.19
6.10
6.00
6.09
5.99
5.87
5.98
5.88
5.74
T.C.
57.2
53.4
48.4
56.6
52.3
47.4
56.0
51.1
46.4
S.C.
44.6
42.1
39.3
41.3
39.0
36.6
38.0
35.9
33.8
K.W
6.82
6.70
6.56
6.71
6.59
6.44
6.60
6.47
6.31
T.C.
53.5
49.5
44.1
52.8
48.5
43.3
52.1
47.5
42.4
S.C.
43.6
40.5
37.7
40.2
37.6
35.1
36.8
34.7
32.4
K.W
7.47
7.32
7.14
7.35
7.19
7.01
7.22
7.06
6.88
T.C.
49.8
45.6
39.9
49.0
44.8
39.2
48.2
43.9
38.5
S.C.
42.5
39.0
36.1
39.0
36.3
33.6
35.6
33.6
31.0
K.W
8.12
7.94
7.72
7.99
7.79
7.58
7.84
7.65
7.45
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHD2006
G2FD060(S,H)24
1.00
1.00
1.00
1.00
1.02
1.02
G1HD060
0.99
1.00
1.01
G1NA048S21D
0.91
0.87
0.96
G1NA060S24T
0.98
0.99
0.99
G1UA060S21,24
1.00
1.00
1.00
G2FD060(S,H)24
1.00
1.00
1.00
G2FD061H24
1.02
1.02
1.02
F2FP060
18
Unitary Products Group
036-21065-003 Rev. E (0405)
COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO.
AC060X10(31,41)
INDOOR COIL MODEL NO.
G2FD060(S,H)24A
CONDENSER ENTERING AIR TEMPERATURE
ID CFM ID DB (°F)
1450 85
80
1700 70
85
80
1950 70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
T.C.
61.2
58.5
56.3
61.8
59.1
56.9
62.3
59.6
57.5
S.C.
37.6
37.4
37.1
40.1
39.9
39.5
42.5
42.3
41.8
K.W
4.66
4.57
4.51
4.67
4.58
4.53
4.68
4.58
4.55
75
85
95
105
115
125
T.C.
60.6
58.0
55.0
61.2
58.6
55.8
61.9
59.3
56.7
S.C.
37.6
37.3
36.5
40.2
39.9
39.1
42.8
42.5
41.7
K.W
5.26
5.13
5.08
5.27
5.14
5.10
5.28
5.15
5.11
T.C.
60.0
57.4
53.7
60.7
58.5
54.8
61.4
59.0
55.8
S.C.
37.5
37.1
35.9
40.3
39.8
38.8
43.1
42.6
41.6
K.W
5.86
5.70
5.65
5.87
5.71
5.67
5.88
5.72
5.68
T.C.
58.1
54.6
50.0
58.9
55.7
51.3
59.7
56.8
52.7
S.C.
36.9
36.0
34.4
39.8
39.0
37.3
42.7
41.9
40.2
K.W
6.54
6.39
6.29
6.56
6.42
6.30
6.57
6.45
6.32
T.C.
56.2
51.8
46.3
57.1
53.2
47.9
57.9
54.5
49.5
S.C.
36.2
34.9
32.9
39.3
38.1
35.9
42.3
41.2
38.8
K.W
7.23
7.07
6.92
7.25
7.12
6.94
7.26
7.17
6.97
T.C.
54.3
49.0
42.6
55.2
50.6
44.5
56.2
52.3
46.4
S.C.
35.6
33.8
31.4
38.7
37.2
34.4
41.9
40.5
37.4
K.W
7.92
7.76
7.55
7.94
7.83
7.58
7.96
7.90
7.62
Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
T.C.
S.C.
KW
N1AHD2046
G2FD060(S,H)24
1.00
1.00
1.00
1.00
1.00
1.05
G1FA060S21,24
1.00
1.00
1.00
G1NA060S24T
0.98
0.98
1.01
G1UA060S21,24
1.00
1.00
1.00
F2FP060
Unitary Products Group
19
MATCHING INDOOR COMPONENTS
ADD-ON COILS - FOR FURNACE APPLICATIONS
G1UA 1/2 CASED UPFLOW
G1NA UNCASED UPFLOW
G1HD HORIZONTAL DUCT
G2FD* MULTI-POSITION (UPFLOW, HORIZONTAL AND DOWNFLOW)
G1FA FULL CASED UPFLOW * Available with factory installed horizontal drain pan.
AIR HANDLERS - FOR NON-FURNACE APPLICATIONS
N-AH OR N-VS MODULAR BLOWER (UPFLOW, HORIZONTAL AND DOWNFLOW)
G+FD COIL
Subject to change without notice. Printed in U.S.A. Copyright © by York International Corp. 2005. All rights reserved.
Unitary Product Group
F+RC / F+FC OR F+RC / F+FP FAN COIL UNITS (UPFLOW, HORIZONTAL)