Transcript
5324342-BTG-B-0617
TECHNICAL GUIDE SINGLE PACKAGE AIR CONDITIONER / ELECTRIC HEAT 16 SEER – R-410A – 460V - 3 PHASE 3 THRU 5 NOMINAL TONS
MODELS: PCE6*36 THRU 60
DESCRIPTION These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
FEATURES • Operating Efficiency - The 3-4 ton PCE6 air conditioner models are rated at 16.0 SEER and 12.5 EER for cooling operation. The 5 ton PCE6 air conditioner model is rated at 16.0 SEER and 12.0 EER for cooling operation. All PCE6 models utilize a multi-stage compressor for maximum comfort and efficiency. • On Site Flexibility - All model sizes use a compact design cabinet. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory. • Lower Installation Cost - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof. All units are completely wired, charged with R-410A and tested prior to shipment. Test stations using a state-of-the-art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers during assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. Equal size side supply and return duct connections allow easy connection of ducts to match low crawl spaces without transition pieces.
®
Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at
www.upgnet.com Additional rating information can be found at:
www.ahridirectory.org WARRANTY SUMMARY* Standard 1-Year limited parts warranty. Standard 5-Years limited compressor warranty.
• Utility Connections Made Easy - Electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed. • Convertible Airflow Design - The bottom duct openings are covered when they leave the factory, ready to be used for a side supply/side return application. If a bottom supply/bottom return application is desired, simply remove the two panels from the bottom of the unit and place them in the side supply/ side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory. • Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect and drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality). • Condensate Drain - The 3/4 inch NPT female connection is rigidly mounted to assure proper fit and leak tight seal. Continued on next page.
*See limited warranty certificate in User’s Information Manual for details.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5324342-BTG-B-0617 • Durable Finish - The cabinet is made of G90 galvanized steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder paint finish ensures less fading when exposed to sunlight, and provides superior corrosion resistance (1000 hour salt spray tested). • Full Perimeter Base Rails - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the base rails may be removed by removing 2 screws in each corner. • Attractive Appearance - A single-piece top cover containing a top-discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. • Top Discharge - The top-discharge outdoor fan does not disrupt neighboring areas or dry out vegetation surrounding the unit. The warm air from the top mounted fan is blown up and away from the structure and any landscaping. • Outdoor Coil Grille - All models utilize a stamped slotted design which provides superior impact protection against small objects during transit and after installation. • Low Operating Sound Level - The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates noise. Isolator mounted compressor and the rippled fins of the outdoor coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound attenuation with its structural design. • Fan System - All models operate over a wide range of design conditions with an enhanced ECM indoor fan motor. These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements. The cooling speed is factory-set and can be field-adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input, but can be field adjusted. This allows maximum comfort conditions. • Dehumidification/Humidity Switch Input - This model unit features a built in de-humidification feature for advanced dehumidification during cooling operation. The unit indoor blower control is designed to work with a humidity control that closes when the humidity is below the set-point. The control is open when the humidity is above the set-point. This humidity control may be referred to as a humidistat or dehumidistat.
• Simple Control Circuit - Field thermostat wiring connect to color coded leads using twist on wire connections. Cooling controls use a contactor and a 2nd stage 24 VAC to 24 VDC rectifier for simple application and troubleshooting. Mate-nlock plug connectors are used. Enhanced ECM indoor blower control is managed by a multi-stage indoor blower control board that includes field adjustable speed tap jumpers for maximum flexibility and product application. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded. • Protected Compressor - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of scroll bypass and a temperature sensor which protect the compressor if undesirable operating conditions occur. • Pressure Switches - A high pressure switch is standard in all units. It is an automatic reset switch. When discharge pressure reaches 650 psi, the compressor will de-energize until pressure reaches 450 psi. • Loss of Charge Switch - All models include a loss of charge switch to provide safe shutdown of compressor. • Exclusive Coil Design - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils will use tin-coated copper tubing with aluminum fins for effective heat transfer. • Electric Heat - All PCE models use 6HK electric heat, which are available in 460V/3/60 from 10 kW to 25 kW. Single point field wiring kits are available for all applications. • Low Maintenance - Long life, permanently lubricated indoor and outdoor fan motor bearings need no annual maintenance, adding greater reliability to the unit. Slide-out blower assembly and indoor coil assembly can be easily removed for cleaning. • Easy Service Access - Individual access panels are provided in access to all major components - compressors, indoor coils, blower, controls/electric heat kits, filters, etc. that makes servicing easy. Removing these panels allow easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting. • Replacement Parts - The installer requires no special training to replace any of the components of these units and the number of new components have been reduced to minimize the inventory of unique parts. • Filter Frame Kit - All 3 phase units include a filter frame kit which is shipped inside the unit from production. Field installation is required.
To use this feature, the control HUM STAT jumper must be set to YES and a humidistat is connected from the low voltage R and HUM color coded leads. During cooling operation if the humidity level is above the humidistat set point, the indoor blower speed is reduced by approximately 15%.
2
Johnson Controls Unitary Products
5324342-BTG-B-0617
NOMENCLATURE PCE
4
A
24
50
2
X
1
A
1
2
3
4
5
6
7
8
9
1. Model Family PCG - packaged A/C with gas heat, PHG - packaged heat pump with gas heat, PCE - packaged A/C with electric heat, PHE - packaged heat pump with electric heat,
5. Gas Heating Input BTU/Hr x 1000 050 = 50,000 BTU/Hr. input, blank = electric heat
2. Nominal Cooling Efficiency 4 = 14 SEER, 6 = 16 SEER, etc.
7. NOx Approval X = low-NOx, blank = not low-Nox
3. Cabinet Size A = small 35 x 51, B = large 45 x 51
8. Generation Level 1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000 24 = 24,000 BTU, etc.
9. Revision Level A = original release, B = second release
6. Voltage-Phase-Frequency 2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
Examples: PCE6B4221A is a packaged A/C with electric heat, 16 SEER, 3-1/2 ton, large cabinet, 230 volt, single phase, low-NOx model (first generation, first release).
COMPONENT LOCATION 287'225)$102725
287'225)$1
287'225&2,/ %HKLQG3DQHO
&2,/*8$5'3$1(/
(&0)$102725 &21752/%2$5'
&217$&725 7;9
&$3$&,725
75$16)250(5 &2035(6625
%/2:(502725 237,21$/ (/(&75,&+($7.,7
,1'225&2,/
,1'225%/2:(5
5(029$%/( %$6(5$,/6
$
UNIT LIMITATIONS Unit Limitations Model
Unit Voltage
All Models
Johnson Controls Unitary Products
460-3-60
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
432
504
125
3
5324342-BTG-B-0617
ACCESSORIES • Economizer for Downflow Applications (S1-2EE04710024, S1-2EE04710124) - Modulating integrated economizer provides simultaneous operation between mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single/dual enthalpy kits are also available. • Economizer for Horizontal Applications (S1-2EE04710224, S1-2EE04710324) - Modulating integrated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are available. • Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) Sensor replaces supply air temperature dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature of indoor supply air plus the enthalpy content of the outdoor air. • CO2 Sensor Kit (S1-2AQ04700824) - Sensor kit detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits. • Electric Heat (Optional) - All PCE models use 6HK electric heat kits, which are available in 460V/3/60 from 10 kW to 25 kW. Single point field wiring kits are available for all applications. • Supply Air Temperature Sensor Kit (S1-TE-6361E-2D) - Replacement outdoor air temperature sensor kit used with economizers. • Motorized Fresh Air Damper (S1-2MD04705224, S1-2MD04705124) - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly. • Low Ambient Temperature Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F. • Rectangle to Round (Horizontal) Adapter (S1-1AK0110, S1-1AK0111) - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current horizontal duct openings on the base unit. Transition is from rectangle to 12" round for the 1AK0110 kit and from rectangle to 14" round for the 1AK0111 kit. • Rectangle to Round (Downflow) Adapter (S1-1AK0108, S1-1AK0109) - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit into current downflow duct openings on the roof curb. Transition is from rectangle to 16" round for the 1AK0108 kit and from rectangle to 18" round for the 1AK0109 kit.
4
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure an air tight seal. These are 8 inch high roof curbs. • Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed for assembly through hinge pins in each corner. Kit also provides seal strip to assure air tight seal. These are 14 inch high roof curbs. • Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications and unit mounted down supply/return applications. Includes hood and screen assembly. • Transformer Kit (S1-2EC06700124) - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper). • Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block off openings, i.e. prevent animal entrance. • Single Point Wiring Accessory Kits for 6HK Electric Heat Applications (S1-SPWK*) - Kits provide field option for connecting electrical power supplies to the field installed 6HK heat kits to allow single point connections for single phase electric heat applications with the exception of 25 kW kits. • Transition Curb Kits (S1-1TC01*) - Adapter kits to allow field use of pre-existing installed roof curbs to match PCE6 footprint to Affinity roof curbs, Carrier, Trane, or Goodman curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCE6 price pages for more details. • Thermostat - Compatible thermostat controls are available through accessory sourcing. For optimum performance, these outdoor units are fully compatible with the residential Hx™ Touchscreen Thermostat (S1-THXU280*) available through Source1. For more information, see the thermostat section of the Product Equipment Catalog. • Wall Thermostat - The units are designed to operate with standard, 24-volt electronic non power stealing and electromechanical thermostats. All units require the use of a multistage conventional thermostat.
* For additional kit numbers refer to the price pages.
Johnson Controls Unitary Products
5324342-BTG-B-0617
GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by Unitary Products in an ISO 9001 certified facility. These packaged cooling and heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. Air Conditioning units provide electric cooling and electric heating, with field installed electric heat kits from 10 kW to 25 kW for heating operation. DESCRIPTION Units shall be factory-assembled, single packaged, Air Conditioners with Electric Cooling/Electric Heating units, designed for outdoor installation. They shall have built in, equal size, field convertible duct connections for supply/return or horizontal supply/return. The units shall be factory wired, piped, charged with R-410A Refrigerant and factory tested prior to shipment. All models shall be rated in accordance with DOE and AHRI test procedures for both heating and cooling operation. Units shall be CSA listed to the UL 1995/CAN/CSA No. 236-M90 standards. • Operating Efficiency - All models shall be rated at a minimum of 16.0 SEER and 12.0 EER for cooling and heating operation rated in accordance with DOE requirements. • Low Operating Sound Level - The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates noise. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound attenuation with its structural design. Sound ratings as tested under AHRI test procedures shall be less than 77 dbA for all models. UNIT CABINET Unit cabinet shall be a single piece design, with drip edges and no-seam corners to provide optimum water integrity. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with foil-faced or foam insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be separate, easily removable for servicing and maintenance. Unit shall be built on a formed, design base pan, with embossments at critical points to add strength and rigidity and to aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be easily removable, when required to lower unit height. Filters shall be factory furnished and be accessible through a removable access door, sealed airtight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams without modification to building structure, duct work and base unit. • Durable Finish - The cabinet shall be is made of G90 galvanized steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel shall provide a better paint-to-steel bond, which resists corrosion and rust creep. Powder paint finish shall provide superior corrosion resistance (1000 hour salt spray tested).
Johnson Controls Unitary Products
• On Site Flexibility - All model sizes shall use a compact design cabinet. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory. • Attractive Appearance - A single-piece top cover containing a top-discharge condenser fan arrangement shall be used which requires less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance and prevent water penetration. • Convertible Airflow Design - The bottom duct openings are covered when they leave the factory, ready to be used for a side supply/side return application. If a bottom supply/bottom return application is desired, simply remove the two panels from the bottom of the unit and place them in the side supply/ side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory. • Utility Connections Made Easy - Electric utility access shall be provided through the bottom or the side of the unit. Utility connections should be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed. • Easy Service Access - Individual access panels are provided in access to all major components - compressors, indoor coils, blower, controls/electric heat kits, filters, etc. that makes servicing easy. Removing these panels allow easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting. • Top Discharge - The top-discharge outdoor fan does not disrupt neighboring areas or dry out vegetation surrounding the unit. The warm air from the top mounted fan is blown up and away from the structure and any landscaping. • Outdoor Coil Grille - All models utilize a stamped slotted design which provides superior impact protection against small objects during transit and after installation. Indoor Blower Assembly - Fan shall be direct drive design. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be a slide-out design for easy removal and cleaning. Indoor blower motors shall be equipped with a high efficiency brushless DC motor (constant torque) also known as an enhanced ECM motor. Outdoor Fan Assembly - The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings and internally protected against overload conditions.
5
5324342-BTG-B-0617 REFRIGERANT COMPONENTS
CONTROLS
• Protected Compressor - The compressor shall be a fully hermetic type, direct drive compressor, that is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of scroll bypass and a temperature thermal overload sensor which protect the compressor if undesirable operating conditions occur. The hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate voltage. Compressors shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
• Simple Control Circuit - Field thermostat wiring connects to color coded leads using twist on wire connections. Cooling controls use contactor and relays for simple application and troubleshooting. Mate-n-lock plug connectors are used. Enhanced ECM indoor blower control is managed by a multistage indoor blower control board that includes field adjustable speed tap jumpers for maximum flexibility and product application. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/ number coded.
• Indoor Coils - Indoor coils shall be of the direct expansion, draw through design and have aluminum plate fins mechanically bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed. • Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality). • Condensate Drain - The 3/4 inch NPT female connection is rigidly mounted to assure proper fit and leak tight seal. • Outdoor Coils - Outdoor coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed, and be a draw through design. Refrigerant Circuit and Refrigerant Safety Components shall include: Thermal expansion devices (TXV's) shall be factory mounted and provided, Filter/strainer to eliminate any foreign matter, reversing valves to control refrigerant flow.
6
• Pressure Switches - A high pressure switch is standard in all units. It is an automatic reset switch. When discharge pressure reaches 650 psi, the compressor will de-energize until pressure reaches 450 psi. • Factory Testing - Installation time and costs are reduced by easy power and control wiring connections. All units are completely wired, charged with R-410A and tested prior to shipment. Test stations using a state-of-the-art computerized process system shall be used to insure product quality. Refrigerant charge and component part numbers are verified via computer bar code scans during assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. This data could be provided by serial number tracking if requested. • Electric Heat - All electric heat models use 6HK electric heat, which are available in 4 60V/3/60 from 10 kW to 25 kW. Single point field wiring kits are available for all applications. Electric heat kits must be certified to UL 1995 standard requirements.
Johnson Controls Unitary Products
5324342-BTG-B-0617
PHYSICAL DATA MODELS:
PCE6B36
PCE6B48
PCE6B60
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBH)
36.5
49.1
60.0
AHRI net capacity (MBH)
36.0
48.0
58.0
EER
12.5
12.5
12.0
NOMINAL TONNAGE: COMPONENT AHRI Cooling Performance
SEER
16.0
16.0
16.0
Nominal CFM
1200
1600
2000
System power (KW) Refrigerant type Refrigerant charge (lb-oz)
3.0
3.6
4.6
R410A
R410A
R410A
11-8
13-8
14-00
Dimensions (inches) Length
51-1/4
51-1/4
51-1/4
Width
45-3/4
45-3/4
45-3/4
Height
49
53
55
Operating WT. (lbs.)
460
483
500
Scroll
Scroll
Scroll
2
2
2 25.9
Compressors Type Stages Outdoor Coil Data Face area (Sq. Ft.)
19.5
23.8
Rows
2
2
2
Fins per inch
22
22
22
Tube diameter
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced 6.3
Indoor Coil Data Face area (Sq. Ft.)
6.3
6.3
Rows
3
3
4
Fins per inch
16
16
16
Tube diameter
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
TXV
TXV
TXV
Refrigerant control Outdoor Fan Data Fan diameter (Inch)
26
26
26
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
No. speeds
1
1
1
Motor HP each
1/3
1/3
1/3
RPM
850
850
850
Nominal total CFM
3200
3200
3200
Direct Drive Indoor Fan Data Fan Size (Inch) Type Motor HP each RPM Frame size
11 x 10
11 x 10
11 x 10
Centrifugal
Centrifugal
Centrifugal
1/2
1
1
1400 Max
1400 Max
1400 Max
48
48
48
B
B
B
Filters Filter Size Quantity - Size
Johnson Controls Unitary Products
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for replacement filter sizes. A=20 x 10 (2 each), B=20 x 10 (3 each)
7
5324342-BTG-B-0617
COOLING PERFORMANCE DATA - 3 TON (LOW SPEED) PACKAGED UNIT MODEL NO. PCE6B36 INDOOR MODEL NO. CONDENSER ID CFM IDDB 80 80 ENTERING AIR IDWB 57 62 TEMPERATURE 55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
34.8 34.1 2.35 33.2 32.4 2.56 31.5 30.7 2.77 30.2 29.1 3.03 28.8 27.4 3.29 25.6 23.7 3.61 22.5 20.1 3.92 19.4 16.5 4.23
41.4 28.8 2.20 39.0 27.6 2.40 36.6 26.4 2.61 34.7 25.1 2.90 32.7 23.9 3.20 28.5 21.5 3.55 24.4 19.1 3.88 20.4 16.8 4.22
600 75 62
80 67
80 72
80 57
80 62
800 75 62
80 67
80 72
80 57
80 62
1000 75 62
80 67
80 72
41.7 25.1 2.19 39.2 23.7 2.39 36.7 22.2 2.59 34.1 21.0 2.86 31.5 19.8 3.13 27.8 17.5 3.49 24.2 15.2 3.84 20.6 13.0 4.19
46.0 25.4 2.16 43.6 24.2 2.36 41.2 22.9 2.57 38.9 21.6 2.84 36.6 20.4 3.11 32.8 18.5 3.48 29.1 16.6 3.83 25.5 14.7 4.19
49.1 20.5 2.13 47.3 19.5 2.33 45.5 18.4 2.52 42.3 17.0 2.78 39.2 15.7 3.05 35.3 13.9 3.41 31.6 12.1 3.77 27.9 10.4 4.13
37.3 36.8 2.30 35.4 34.8 2.51 33.5 32.9 2.71 31.6 30.9 2.98 29.6 28.8 3.24 26.1 25.0 3.56 22.6 21.3 3.87 19.2 17.6 4.17
41.2 32.1 2.16 38.8 30.7 2.37 36.3 29.4 2.57 34.0 28.3 2.85 31.7 27.1 3.13 27.7 24.1 3.49 23.8 21.1 3.83 20.0 18.1 4.18
41.5 27.8 2.16 38.8 26.3 2.36 36.1 24.8 2.56 33.4 23.5 2.83 30.6 22.2 3.09 26.8 19.8 3.46 23.0 17.6 3.82 19.3 15.4 4.18
44.6 26.7 2.13 42.6 25.9 2.34 40.7 25.0 2.54 38.3 24.0 2.80 36.0 23.0 3.07 31.7 20.8 3.44 27.5 18.7 3.79 23.2 16.6 4.15
47.3 21.0 2.11 45.7 20.3 2.31 44.2 19.6 2.50 41.2 18.2 2.76 38.1 16.8 3.02 33.9 14.8 3.39 29.8 12.9 3.74 25.7 11.0 4.10
39.7 39.4 2.25 37.6 37.3 2.46 35.4 35.1 2.66 33.0 32.7 2.92 30.5 30.2 3.19 26.5 26.3 3.50 22.7 22.5 3.81 18.9 18.7 4.11
41.0 35.4 2.13 38.5 33.9 2.33 36.0 32.4 2.53 33.3 31.4 2.80 30.7 30.4 3.06 26.9 26.7 3.43 23.2 23.0 3.78 19.6 19.4 4.14
41.2 30.6 2.13 38.4 28.9 2.33 35.6 27.3 2.54 32.7 25.9 2.80 29.8 24.5 3.06 25.7 22.2 3.44 21.8 20.0 3.80 17.9 17.7 4.17
43.1 28.0 2.11 41.7 27.6 2.31 40.2 27.2 2.51 37.8 26.4 2.77 35.4 25.6 3.03 30.5 23.2 3.40 25.8 20.9 3.76 21.0 18.5 4.12
45.4 21.5 2.09 44.2 21.2 2.29 42.9 20.8 2.48 40.0 19.4 2.74 37.1 17.9 2.99 32.4 15.8 3.36 27.9 13.7 3.72 23.4 11.7 4.07
COOLING PERFORMANCE DATA - 3 TON (HIGH SPEED) PACKAGED UNIT MODEL NO. PCE6B36 CONDENSER ID CFM 1000 IDDB 80 80 75 ENTERING AIR IDWB 57 62 62 TEMPERATURE
80 67
80 72
80 57
80 62
1200 75 62
80 67
80 72
80 57
80 62
1400 75 62
80 67
80 72
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
43.2 27.7 2.07 41.6 26.7 2.27 40.1 25.7 2.47 37.4 24.6 2.73 34.8 23.4 2.99 31.6 22.0 3.38 28.4 20.5 3.76 25.3 19.1 4.14
46.6 0.6 2.09 44.3 11.6 2.29 41.9 22.5 2.48 40.3 20.5 2.74 38.7 18.5 3.00 35.7 17.1 3.40 32.8 15.8 3.78 29.9 14.4 4.16
41.2 38.3 2.11 39.6 36.8 2.31 38.0 35.3 2.51 36.1 33.4 2.77 34.2 31.5 3.03 31.0 29.2 3.43 28.0 27.0 3.82 25.0 24.7 4.21
42.8 35.5 2.12 40.4 34.7 2.32 38.1 33.9 2.52 35.6 32.5 2.78 33.1 31.2 3.04 30.1 28.7 3.43 27.1 26.4 3.82 24.1 24.0 4.20
41.7 30.0 2.12 36.6 28.6 2.74 31.5 27.3 3.36 32.1 26.5 3.20 32.7 25.7 3.03 29.5 24.0 3.43 26.4 22.4 3.81 23.3 20.9 4.19
45.6 29.9 2.15 43.6 29.1 2.35 41.5 28.2 2.55 38.8 27.0 2.81 36.0 25.8 3.07 32.5 24.3 3.46 29.1 22.8 3.84 25.7 21.4 4.21
48.4 12.8 2.17 46.6 17.9 2.37 44.7 22.9 2.57 42.6 21.3 2.83 40.4 19.8 3.09 37.0 18.3 3.48 33.7 16.9 3.86 30.4 15.5 4.24
43.8 40.6 2.20 42.1 39.0 2.40 40.4 37.4 2.61 38.3 35.3 2.87 36.2 33.2 3.13 32.7 30.7 3.52 29.3 28.2 3.90 25.9 25.7 4.29
44.6 38.7 2.20 42.2 38.0 2.40 39.8 37.3 2.61 37.1 35.7 2.87 34.3 34.1 3.13 31.2 30.9 3.52 28.1 27.9 3.90 25.0 24.8 4.29
43.5 32.5 2.20 41.2 31.7 2.40 38.9 30.9 2.59 36.3 29.5 2.85 33.7 28.1 3.11 30.2 26.3 3.51 26.8 24.5 3.88 23.4 22.8 4.26
48.0 32.0 2.24 45.5 31.4 2.44 43.0 30.8 2.64 40.1 29.5 2.90 37.2 28.2 3.15 33.5 26.6 3.54 29.8 25.2 3.91 26.1 23.7 4.29
50.2 25.0 2.25 48.9 24.1 2.46 47.5 23.3 2.67 44.8 22.2 2.92 42.1 21.1 3.17 38.3 19.6 3.56 34.6 18.1 3.94 30.9 16.6 4.31
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
8
38.5 36.0 2.02 37.1 34.6 2.21 35.6 33.3 2.41 33.9 31.6 2.68 32.2 29.8 2.94 29.4 27.8 3.34 26.7 25.7 3.74 24.1 23.7 4.13
41.0 32.3 2.04 38.7 31.4 2.24 36.3 30.5 2.43 34.1 29.4 2.69 31.9 28.2 2.95 29.0 26.5 3.35 26.1 24.8 3.73 23.3 23.1 4.11
40.0 27.5 2.03 32.0 25.6 3.08 24.1 23.7 4.13 27.9 23.5 3.54 31.7 23.2 2.95 28.8 21.8 3.35 25.9 20.4 3.73 23.1 18.9 4.11
Johnson Controls Unitary Products
5324342-BTG-B-0617
COOLING PERFORMANCE DATA - 4 TON (LOW SPEED) PACKAGED UNIT MODEL NO. PCE6B48 CONDENSER ID CFM IDDB 80 80 ENTERING AIR IDWB 57 62 TEMPERATURE 55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
34.3 32.3 1.67 32.4 30.4 1.86 30.4 28.6 2.05 27.3 26.2 2.39 24.2 23.8 2.72 21.9 21.5 3.15 19.6 19.3 3.56 17.3 17.0 3.98
37.4 28.7 1.64 34.5 27.4 1.83 31.6 26.0 2.03 29.1 23.9 2.36 26.7 21.8 2.68 23.6 20.3 3.16 20.6 18.8 3.63 17.6 17.4 4.10
900 75 62
80 67
80 72
80 57
80 62
1100 75 62
80 67
80 72
80 57
80 62
1300 75 62
80 67
80 72
36.3 24.7 1.65 34.1 21.0 1.85 32.0 17.4 2.04 28.2 18.1 2.43 24.5 18.8 2.82 20.8 17.0 3.22 17.1 15.1 3.60 13.5 13.3 3.98
41.1 24.9 1.63 38.7 23.5 1.79 36.3 22.1 1.96 34.0 20.8 2.37 31.6 19.4 2.78 27.3 19.1 3.16 23.2 18.8 3.53 19.1 18.6 3.91
45.6 20.0 1.49 43.8 18.9 1.73 42.0 17.8 1.97 39.1 16.5 2.30 36.1 15.1 2.63 32.6 13.6 3.06 29.2 12.2 3.47 25.7 10.7 3.89
37.5 34.8 1.63 35.2 32.8 1.85 33.0 30.7 2.07 29.4 28.0 2.41 25.8 25.4 2.74 23.1 22.7 3.17 20.4 20.1 3.58 17.7 17.4 3.99
39.7 32.1 1.61 36.8 30.2 1.83 33.9 28.2 2.05 31.1 26.6 2.38 28.2 25.0 2.72 24.7 22.5 3.17 21.2 20.0 3.61 17.8 17.5 4.05
38.7 27.2 1.62 36.6 23.2 1.84 34.5 19.1 2.06 29.9 19.9 2.42 25.3 20.8 2.78 21.1 18.0 3.20 16.9 15.3 3.60 12.7 12.5 4.00
43.6 27.2 1.59 41.0 25.8 1.82 38.4 24.4 2.05 35.7 22.9 2.39 33.1 21.5 2.74 29.0 21.1 3.14 25.0 20.8 3.53 21.0 20.4 3.92
48.0 21.8 1.52 46.2 20.7 1.76 44.5 19.6 2.01 41.2 18.0 2.33 37.9 16.4 2.65 33.9 14.7 3.09 30.1 13.0 3.51 26.3 11.4 3.93
40.6 37.4 1.58 38.1 35.1 1.84 35.5 32.9 2.10 31.4 29.9 2.43 27.4 26.9 2.76 24.2 23.9 3.18 21.2 20.9 3.59 18.2 17.9 4.00
42.1 35.5 1.58 39.1 33.0 1.82 36.2 30.5 2.06 33.0 29.3 2.41 29.7 28.2 2.75 25.7 24.6 3.18 21.8 21.1 3.60 17.9 17.6 4.01
41.1 29.8 1.58 39.1 25.3 1.83 37.1 20.8 2.08 31.6 21.8 2.41 26.2 22.8 2.74 21.3 19.0 3.18 16.6 15.4 3.60 11.9 11.8 4.02
46.2 29.6 1.56 43.3 28.1 1.84 40.4 26.6 2.13 37.5 25.1 2.42 34.6 23.6 2.70 30.6 23.2 3.12 26.8 22.7 3.53 22.9 22.3 3.93
50.3 23.6 1.55 48.7 22.5 1.79 47.0 21.5 2.04 43.4 19.5 2.36 39.7 17.6 2.68 35.3 15.7 3.12 31.1 13.9 3.54 26.8 12.1 3.97
COOLING PERFORMANCE DATA - 4 TON (HIGH SPEED) PACKAGED UNIT MODEL NO. PCE6B48 CONDENSER ID CFM 1400 IDDB 80 80 75 ENTERING AIR IDWB 57 62 62 TEMPERATURE
80 67
80 72
80 57
80 62
1600 75 62
80 67
80 72
80 57
80 62
1800 75 62
80 67
80 72
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
56.6 35.0 2.93 54.8 33.8 3.11 52.9 32.6 3.29 49.4 31.2 3.72 45.9 29.7 4.15 41.7 27.8 4.65 37.7 26.0 5.14 33.6 24.2 5.62
59.6 27.8 2.75 58.3 27.0 3.13 56.9 26.1 3.51 53.8 24.6 3.77 50.7 23.1 4.03 46.5 21.2 4.58 42.4 19.3 5.12 38.2 17.5 5.66
47.9 47.2 2.76 44.9 44.3 3.03 42.0 41.5 3.29 40.1 39.4 3.64 38.1 37.4 4.00 34.0 33.4 4.51 30.0 29.6 5.00 26.0 25.8 5.50
54.3 43.3 2.80 51.7 35.9 3.06 49.1 28.6 3.32 45.6 33.1 3.67 42.2 37.6 4.01 37.9 34.8 4.54 33.8 32.1 5.06 29.6 29.4 5.58
55.6 36.8 2.80 52.7 37.0 3.06 49.9 37.3 3.33 46.8 34.1 3.66 43.6 30.9 4.00 39.0 26.2 4.47 34.5 21.7 4.94 30.1 17.1 5.40
56.8 35.0 2.92 54.8 34.7 3.15 52.9 34.3 3.38 49.2 32.8 3.77 45.5 31.2 4.15 41.3 29.3 4.65 37.2 27.6 5.13 33.2 25.8 5.62
59.9 28.0 2.82 58.7 31.7 3.16 57.5 35.5 3.51 54.0 29.8 3.81 50.5 24.1 4.11 46.1 22.0 4.63 41.8 20.1 5.14 37.5 18.1 5.66
49.2 48.7 2.86 46.1 45.3 3.13 43.0 41.9 3.39 39.9 39.1 3.74 36.8 36.2 4.09 33.4 32.9 4.59 30.1 29.8 5.09 26.8 26.6 5.58
54.3 45.2 2.88 52.1 31.7 3.06 49.9 18.2 3.25 46.1 28.9 3.67 42.3 39.7 4.09 38.3 36.5 4.60 34.5 33.5 5.09 30.7 30.4 5.58
55.6 38.2 2.87 53.3 40.0 3.14 51.0 41.8 3.41 47.2 37.2 3.75 43.4 32.6 4.08 38.9 25.1 4.52 34.5 17.9 4.95 30.1 10.6 5.39
56.9 35.0 2.90 54.9 35.5 3.19 52.8 36.0 3.47 48.9 34.4 3.81 45.1 32.7 4.15 40.9 30.9 4.65 36.8 29.1 5.13 32.7 27.3 5.62
60.1 28.1 2.89 59.1 36.5 3.20 58.1 44.9 3.50 54.2 34.9 3.85 50.3 25.0 4.19 45.7 22.9 4.68 41.2 20.8 5.17 36.7 18.8 5.65
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
46.5 45.7 2.66 43.8 43.3 2.93 41.1 41.0 3.19 40.3 39.8 3.55 39.4 38.6 3.91 34.6 34.0 4.42 29.9 29.5 4.91 25.2 25.0 5.41
Johnson Controls Unitary Products
54.3 41.3 2.72 51.2 40.2 3.06 48.2 39.1 3.39 45.2 37.3 3.66 42.2 35.5 3.93 37.5 33.1 4.49 33.0 30.7 5.03 28.4 28.4 5.58
55.5 35.4 2.72 52.2 34.1 2.98 48.8 32.9 3.24 46.3 31.1 3.58 43.8 29.3 3.92 39.1 27.4 4.43 34.6 25.5 4.92 30.1 23.6 5.41
9
5324342-BTG-B-0617
COOLING PERFORMANCE DATA - 5 TON (LOW SPEED) PACKAGED UNIT MODEL NO. PCE6B60 CONDENSER ID CFM 1100 IDDB 80 80 75 ENTERING AIR IDWB 57 62 62 TEMPERATURE
80 67
80 72
80 57
80 62
1300 75 62
80 67
80 72
80 57
80 62
1500 75 62
80 67
80 72
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
55.7 36.5 1.74 52.1 34.9 2.11 48.5 33.3 2.48 44.8 31.4 2.74 41.0 29.5 3.00 36.5 27.4 3.46 32.1 25.4 3.91 27.7 23.4 4.35
59.9 30.0 1.90 57.3 28.5 2.08 54.8 26.9 2.26 50.8 25.1 2.61 46.9 23.2 2.96 42.1 21.2 3.43 37.4 19.2 3.87 32.7 17.2 4.32
47.1 47.1 1.87 44.3 44.3 2.15 41.6 41.6 2.43 38.3 38.3 2.78 35.0 35.0 3.13 31.3 31.3 3.62 27.8 27.8 4.10 24.3 24.3 4.58
53.0 47.5 1.87 49.4 45.6 2.15 45.8 43.8 2.42 41.8 40.9 2.77 37.8 37.8 3.13 34.3 34.3 3.59 30.9 30.9 4.03 27.5 27.5 4.47
51.7 40.0 1.88 48.4 38.1 2.20 45.1 36.2 2.51 41.5 34.2 2.87 37.8 32.2 3.23 33.6 29.6 3.66 29.4 27.1 4.07 25.3 24.6 4.49
57.4 39.4 1.84 53.9 37.8 2.16 50.3 36.2 2.48 46.3 34.3 2.79 42.3 32.3 3.10 37.3 30.1 3.56 32.5 28.0 4.01 27.6 25.9 4.46
61.8 31.6 1.92 59.6 30.2 2.14 57.4 28.7 2.36 53.0 26.8 2.71 48.5 25.0 3.07 43.3 22.7 3.53 38.3 20.6 3.98 33.2 18.4 4.43
49.5 49.5 1.98 46.6 46.6 2.25 43.7 43.7 2.52 40.1 40.1 2.87 36.5 36.5 3.22 32.7 32.7 3.69 28.9 28.9 4.13 25.1 25.1 4.58
54.9 51.8 1.98 51.2 49.9 2.24 47.4 47.4 2.51 43.0 43.0 2.88 38.6 38.6 3.25 34.6 34.6 3.70 30.6 30.6 4.13 26.7 26.7 4.57
53.0 43.3 1.99 50.1 41.2 2.25 47.1 39.1 2.52 43.2 37.0 2.88 39.3 34.9 3.24 34.5 32.0 3.70 29.9 29.2 4.14 25.2 25.2 4.59
59.2 42.4 1.94 55.7 40.8 2.22 52.1 39.2 2.49 47.9 37.2 2.84 43.6 35.1 3.20 38.1 32.9 3.66 32.8 30.7 4.11 27.5 27.5 4.56
63.8 33.3 1.94 61.9 31.9 2.20 60.1 30.4 2.45 55.1 28.6 2.81 50.2 26.7 3.17 44.6 24.3 3.63 39.1 21.9 4.09 33.7 19.6 4.54
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
44.6 44.6 1.77 42.1 42.1 2.05 39.6 39.6 2.34 36.5 36.5 2.69 33.4 33.4 3.04 30.0 30.0 3.56 26.7 26.7 4.07 23.4 23.4 4.57
51.1 43.1 1.77 47.6 41.4 2.05 44.2 39.6 2.33 40.6 37.6 2.67 37.0 35.5 3.02 34.0 32.8 3.48 31.1 30.3 3.93 28.3 27.7 4.38
50.5 36.8 1.77 46.8 35.0 2.14 43.1 33.3 2.51 39.8 31.4 2.87 36.4 29.5 3.23 32.7 27.2 3.62 29.0 25.0 4.00 25.3 22.8 4.39
COOLING PERFORMANCE DATA - 5 TON (HIGH SPEED) PACKAGED UNIT MODEL NO. PCE6B60 CONDENSER ID CFM 1600 IDDB 80 80 75 ENTERING AIR IDWB 57 62 62 TEMPERATURE
80 67
80 72
80 57
80 62
1800 75 62
80 67
80 72
80 57
80 62
2000 75 62
80 67
80 72
T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W. T.C. S.C. K.W.
71.8 46.7 3.21 68.4 44.9 3.34 65.1 43.0 3.47 60.5 41.0 3.95 55.9 39.1 4.44 50.9 36.9 4.96 46.0 34.7 5.46 41.1 32.6 5.96
77.1 37.2 2.93 74.2 35.7 3.37 71.3 34.2 3.81 67.1 32.2 4.02 62.8 30.3 4.23 57.9 28.2 4.84 53.1 26.2 5.43 48.2 24.2 6.01
61.3 61.3 3.03 55.7 55.7 3.30 50.1 50.1 3.57 47.8 47.8 3.94 45.4 45.4 4.30 40.7 40.7 4.82 36.1 36.1 5.32 31.5 31.5 5.82
70.6 59.6 3.08 66.1 42.9 3.34 61.6 26.2 3.60 57.3 38.2 3.96 53.0 50.1 4.31 48.1 46.3 4.87 43.4 42.6 5.42 38.6 38.6 5.96
67.6 49.6 3.08 63.2 51.1 3.35 58.8 52.5 3.61 55.3 47.0 3.96 51.8 41.5 4.30 47.1 33.0 4.77 42.5 24.7 5.23 37.9 16.4 5.68
73.5 49.1 3.28 69.9 47.3 3.48 66.3 45.5 3.68 61.5 43.3 4.10 56.7 41.2 4.52 51.6 39.0 5.04 46.7 36.9 5.54 41.8 34.7 6.04
77.7 38.2 3.14 75.5 46.7 3.51 73.4 55.3 3.89 68.6 43.3 4.17 63.9 31.4 4.44 58.7 29.3 5.00 53.8 27.2 5.54 48.8 25.1 6.09
63.5 63.5 3.26 57.2 57.2 3.53 50.9 50.9 3.80 46.8 46.8 4.16 42.8 42.8 4.52 38.9 38.9 5.03 35.1 35.1 5.54 31.4 31.4 6.04
72.3 63.4 3.30 68.1 31.9 3.42 64.0 0.3 3.55 59.2 26.7 4.04 54.3 53.0 4.53 49.5 48.7 5.04 44.9 44.5 5.54 40.2 40.2 6.04
68.8 52.2 3.30 64.7 56.8 3.56 60.6 60.6 3.83 56.8 52.7 4.17 53.0 43.9 4.51 48.3 29.1 4.92 43.8 14.7 5.33 39.3 0.3 5.74
75.1 51.5 3.34 71.3 49.8 3.62 67.4 48.0 3.90 62.4 45.7 4.25 57.4 43.3 4.60 52.3 41.1 5.11 47.4 39.0 5.61 42.5 36.8 6.11
78.3 39.1 3.35 76.9 57.8 3.66 75.4 75.4 3.97 70.2 54.5 4.32 64.9 32.6 4.66 59.6 30.4 5.17 54.4 28.2 5.66 49.3 26.1 6.16
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
10
59.2 59.2 2.80 54.3 54.3 3.07 49.3 49.3 3.33 48.7 48.7 3.71 48.0 48.0 4.09 42.5 42.5 4.60 37.0 37.0 5.10 31.6 31.6 5.60
68.9 55.8 2.86 64.1 53.9 3.25 59.2 52.0 3.65 55.4 49.6 3.87 51.6 47.2 4.10 46.6 43.9 4.71 41.8 40.7 5.29 37.0 37.0 5.88
66.5 47.0 2.87 61.7 45.4 3.13 57.0 43.7 3.39 53.9 41.4 3.74 50.7 39.1 4.09 45.9 36.8 4.61 41.3 34.7 5.12 36.6 32.5 5.63
Johnson Controls Unitary Products
5324342-BTG-B-0617
COIL GUARD
HIGH VOLTAGE CONNECTION 7/8”
C
HIGH VOLTAGE CONNECTION 1-3/32” HEAT EXCHANGER ACCESS PANEL
COMPRESSOR ACCESS PANEL
CONDENSATE DRAIN BLOWER ACCESS PANEL
B
A
LOW VOLTAGE CONNECTION
CONTROL ACCESS PANEL
A0379-001
UNIT DIMENSIONS & ACCESS LOCATIONS Dimensions
Model
A
B
C
PCE6B36
51-1/4
45-3/4
49
PCE6B48
51-1/4
45-3/4
53
PCE6B60
51-1/4
45-3/4
55
UNIT CLEARANCES Direction
Distance (in.)
Direction
Distance (in.)
Top1
36
Power Entry (Right Side)
36
Side Opposite Ducts
36
Left Side
24
Duct Panel
0
Bottom2,3
1
NOTES: 1. Minimum Clearance of 1inch all sides of supply air duct for the first 3 feet of duct for 20 & 25 kW., zero inches thereafter. For all other heaters, zero inch clearance all sides for entire length of duct. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obscure outdoor air discharge outlet. 3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials. Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct.
INDOOR BLOWER SPECIFICATIONS Motor
Model
HP
RPM
EFF.
SF
Frame
PCE6B36
1/2
Variable
0.8
1.0
48
PCE6B48
1
Variable
0.8
1.0
48
PCE6B60
1
Variable
0.8
1.0
48
SOUND PERFORMANCE Model (Tons)
Sound Rating1 dB (A)
125
250
500
1000
2000
4000
PCE6B36
74
58.5
61.8
65.4
66.5
60.7
54.8
49.8
PCE6B48
74
63.5
63.9
62.3
65
64
54.1
46.6
PCE6B60
76
72.3
65.0
63.9
64
60
55.5
49.0
Octave Band Centerline Frequency (Hz) 8000
NOTES: 1. Rated in accordance with AHRI Standard 270.
Johnson Controls Unitary Products
11
5324342-BTG-B-0617
ELECTRICAL DATA - 460-3-60 - SINGLE SOURCE POWER
Compressor Model
RLA LRA MCC
PCE6B36 5.7
PCE6B48 6.4
PCE6B60 7.6
38.0
8.9
41.0 10.0
52.0 11.9
OD ID Fan Blower Motor Motor FLA
FLA
0.87
1.9
0.87
0.87
3.3
3.3
Max Max Max Fuse2 or Fuse2 or Fuse2 or Breaker MCA1 Breaker MCA1 Breaker Electric Heat Option MCA1 (Unit Unit Size3 Size3 Size3 Heater Heater (Total (Total Less (Unit Less (Heater (Heater Heater Kit4 Unit) Only) kW Stages Amps Unit) Heater) Heater) Only) none
--
--
--
9.9
15
9.9
15
--
--
6HK06501046
8.8
1
11
13.4
15
9.9
15
13.8
15
6HK06501546
13.2
1
16.6
18.9
20
9.9
15
20.7
25
none
--
--
--
12.2
15
12.2
15
--
--
6HK06501046
8.8
1
11
15.2
20
12.2
15
13.8
15
6HK06501546
13.2
1
16.6
20.7
25
12.2
15
20.7
25
6HK06501846
15.9
1
20
24.1
25
12.2
15
24.9
25
6HK06502046
17.6
1
22.1
26.2
30
12.2
15
27.6
30
none
--
--
--
13.7
20
13.7
20
--
--
6HK06501046
8.8
1
11
15
20
13.7
20
13.8
15
6HK06501546
13.2
1
16.6
20.5
25
13.7
20
20.7
25
6HK06501846
15.9
1
20
23.9
25
13.7
20
24.9
25
6HK06502046
17.6
1
22.1
26
30
13.7
20
27.6
30
6HK06502546
22
1
27.6
31.5
35
13.7
20
34.5
35
NOTES: Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification. 1. 2. 3. 4.
MCA = Minimum Circuit Ampacity. Maximum Over Current Protection per standard UL 1995. Fuse or HACR circuit breaker to be field installed. Single Point Connection Required.
ELECTRICAL DATA FOR - 460-3-60 MULTI SOURCE POWER Compressor Model RLA LRA MCC
OD Blower Fan Motor Motor FLA
FLA
PCE6A36
5.7
38.0
8.9
0.87
1.9
PCE6B48
6.4
41.0 10.0
0.87
3.3
PCE6B60
7.6
52.0 11.9
0.87
3.3
12
MCA Amps
Electric Heat Option Heater Kit none 6HK06501046 6HK06501546 none 6HK06501046 6HK06501546 6HK06501846 6HK06502046 none 6HK06501046 6HK06501546 6HK06501846 6HK06502046 6HK06502546
Heater Stages kW --8.8 1 13.2 1 --8.8 1 13.2 1 15.9 1 17.6 1 --8.8 1 13.2 1 15.9 1 17.6 1 22.0 1
Heater Amps -11.0 16.6 -11.0 16.6 20.0 22.1 -11.0 16.6 20.0 22.1 27.6
Max Fuse or Breaker Size
CIRCUIT #1 Unit Minus Heaters 9.9 15 9.9 15 9.9 15 12.2 15 12.2 15 12.2 15 12.2 15 12.2 15 13.7 20 13.7 20 13.7 20 13.7 20 13.7 20 13.7 20
MCA Amps
Max Fuse or Breaker Size
CIRCUIT #2 Heaters --13.8 15 20.7 25 --13.8 15 20.7 25 24.9 25 27.6 30 --13.8 15 20.7 25 24.9 25 27.6 30 34.5 35
Johnson Controls Unitary Products
5324342-BTG-B-0617
SINGLE POINT WIRING KIT PART NUMBERS Unit Model Number
Voltage
PCE6B3641
460-3-60
PCE6B4841
460-3-60
PCE6B6041
460-3-60
Heater Kit 6HK06501046 6HK06501546 6HK06501046 6HK06501546 6HK06501846 6HK06502046 6HK06501046 6HK06501546 6HK06501846 6HK06502046 6HK06502546
Single-Point Wiring Kit S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK036 S1-2SPWK037
Unit Fuse Size (Amps) 15 15 15 15 15 15 20 20 20 20 20
Heater Fuse Size (Amps) 15 25 15 25 25 30 15 25 25 30 35
"D"
CENTER OF GRAVITY COMPRESSOR
"C"
"A"
FRONT OF UNIT Y
"B"
X
A0295-001-TG
WEIGHTS AND DIMENSIONS Model
Weight (lbs.) Shipping
Operating
Center of Gravity
4 Point Load Location (lbs.)
X
Y
A
B
C
D 38
PCE6B36
466
461
32
13
167
131
130
PCE6B48
488
483
30
19
158
125
130
75
PCE6B60
505
500
30
20
157
134
140
74
Johnson Controls Unitary Products
13
5324342-BTG-B-0617
RECOMMENDED BLOWER SPEED FOR ELECTRIC HEAT Heater kW
Model
10
15
18
20
25
PCE6B36
C (ML)
A (HI)
--
--
--
PCE6B48
D (LO)
C (ML)
B (MH)
A (HI)
--
PCE6B60
D (LO)
D (LO)
C (ML)
B (MH)
A (HI)
NOTE: The recommended HEAT speed selections above will give approximately a 45 degree temperature rise at 0.3" static with 460V power supply. If lower or higher heating airflow is desired, or if duct static or voltage are different than specified, other speed taps may be used.
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION Model
Jumper Position
High Cool
36
Low Cool
Heat
High Cool
48
Low Cool
Heat
High Cool
60
Low Cool
Heat
A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D
0.1 SCFM 1621 1507 1410 1224 1060 1017 974 813 1264 1147 1003 902 1893 1785 1703 1654 1304 1265 1200 1304 1423 1304 1125 1000 2305 2186 2007 1935 1675 1523 1369 1413 1762 1479 1369 1209
0.2 SCFM 1531 1418 1288 1137 964 919 875 721 1179 1056 904 802 1845 1737 1649 1596 1225 1183 1116 1225 1351 1225 1039 912 2255 2144 1963 1887 1627 1463 1307 1352 1724 1418 1307 1147
0.3 SCFM 1454 1339 1209 1052 879 830 780 617 1092 972 813 700 1804 1694 1595 1535 1152 1109 1039 1152 1281 1152 957 820 2215 2101 1919 1840 1566 1405 1251 1295 1661 1361 1251 1084
External Static Pressure (Inches WC) 0.4 0.5 0.6 0.7 SCFM SCFM SCFM SCFM 1223 1138 1371 1299 1268 1200 1130 1059 1132 1054 982 904 978 902 824 748 795 706 623 538 570 487 742 650 688 595 517 436 509 404 323 237 865 787 1017 942 895 815 735 657 724 632 552 470 602 504 429 348 1672 1625 1764 1717 1650 1597 1547 1501 1546 1491 1436 1385 1483 1427 1370 1315 893 842 1072 998 1026 950 839 789 952 874 757 707 893 842 1072 998 1056 1002 1211 1143 1072 998 893 842 870 791 672 623 733 652 529 481 2164 2103 2074 2024 2059 2003 1956 1930 1781 1731 1873 1828 1788 1754 1702 1645 1423 1374 1512 1473 1350 1302 1248 1196 1196 1141 1082 1024 1240 1187 1130 1073 1608 1574 1526 1478 1201 1147 1306 1256 1196 1141 1082 1024 1022 957 897 835
0.8 SCFM 1039 981 831 682 459 415 371 171 735 578 400 292 1576 1452 1327 1252 785 733 652 785 941 785 564 418 1965 1886 1693 1609 1324 1143 964 1015 1429 1092 964 777
0.9 SCFM 966 911 755 611 397 344 291 81 662 511 327 201 1528 1392 1264 1187 731 681 599 731 883 731 507 354 1910 1837 1646 1560 1278 1089 907 959 1390 1037 907 722
1.0 SCFM 869 837 691 549 331 276 222 81 598 450 258 201 1473 1335 1200 1118 648 596 512 648 804 648 416 255 1867 1796 1606 1519 1234 1044 849 905 1341 989 849 669
NOTES: 1. Airflow tested with dry coil conditions, without air filters, at 460 volts 2. Applications above 0.8" w.c. external static pressure are not recommended. 3. Brushless DC high efficiency enhanced ECM blower motor used for all indoor blower assemblies. 4. Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases. 5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
14
Johnson Controls Unitary Products
5324342-BTG-B-0617
ADDITIONAL STATIC RESISTANCE Size (Tons)
36 (3.0)
48 (4.0)
60 (5.0)
CFM
700 800 900 1000 1100 1200 1300 1400 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
Wet Indoor Coil Economizer
0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.09 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.09
0.00 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.02 0.02 0.02 0.03 0.04 0.04 0.04 0.04 0.05 0.05 0.02 0.02 0.02 0.03 0.04 0.04 0.04 0.04 0.05 0.05
BOTTOM DUCT DIMENSIONS (Inches) 1
Filter/Frame Kit
0.04 0.06 0.08 0.10 0.13 0.16 0.17 0.18 0.04 0.04 0.05 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.04 0.04 0.05 0.05 0.06 0.07 0.08 0.09 0.10 0.11
D
VIEW LOOKING UP AT BOTTOM OF UNIT
16
1.75
C
RETURN AIR DUCT
A
E
B
SUPPLY AIR DUCT
A
F
A0343-001
Model
A
B
C
D
E
F
36, 48, 60
14
13.5
5
3.5
47.5
42
REAR DUCT DIMENSIONS (Inches)
NOTES: 1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. Filter pressure drop based on standard filter media tested at velocities not to exceed 300 ft/min.
SUPPLY AIR DUCT
15.6
RETURN AIR DUCT
6.75
A0344-001
Johnson Controls Unitary Products
A
B
A
4.3
Model
A
B
36, 48, 60
13.6
14
15
5324342-BTG-B-0617
UNIT TYPICAL DUCT APPLICATIONS ROOF CURB INSTALLATION REAR DUCT
ROOF CURB INSTALLATION BOTTOM DUCT
SLAB ON GROUND INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN AIR DUCT
SUPPLY AIR DUCT
FIELD-SUPPLIED DISCONNECT SWITCH CONDENSATE DRAIN CONTROL WIRING TO INDOOR THERMOSTAT
16
A0390-001
Johnson Controls Unitary Products
5324342-BTG-B-0617
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF CONDENSATE DRAIN ROOF CURB FIELD-SUPPLIED DISCONNECT SWITCH
TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT RETURN AIR DUCT
Johnson Controls Unitary Products
SUPPLY AIR DUCT
A0389-001
17
NOTES
Subject to change without notice. Published in U.S.A. Copyright © 2017 by Johnson Controls, Inc. All rights reserved.
York International Corp. 5005 York Drive Norman, OK 73069
5324342-BTG-B-0617 Supersedes: 5324342-BTG-A-0317