R410A50Hz Universal Outdoor Series Technical Manual
Outdoor Unit
R410A 50Hz Universal Outdoor Series Inverter type
Technical Manual 2014 Version
LCAC/1.0/201401
I
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Content PART 1.General Information ..................................................................................... 1 1. Nomenclature ....................................................................................................... 2 2. Model Names of Indoor/Outdoor Units ................................................................ 3 3. External Appearance............................................................................................ 4 4. Features ............................................................................................................... 6
Part 2 Indoor Unit....................................................................................................... 7 4-Way Cassette Type ...................................................................................................... 7 1. Features ............................................................................................................... 8 2. Specification ....................................................................................................... 11 3. Dimension .......................................................................................................... 13 4. Service Space .................................................................................................... 15 5. Wiring Diagrams ................................................................................................ 16 6. Capacity Table.................................................................................................... 17 7. Electric Characteristics ...................................................................................... 20 8. Exploded View ................................................................................................... 21 9. Accessories ........................................................................................................ 25 10. The Specification of Wiring .............................................................................. 26 11. Field Wiring ...................................................................................................... 27 12. Trouble shooting .............................................................................................. 29 Duct Type .................................................................................................................... 30 1. Features ............................................................................................................. 31 2.Specification ........................................................................................................ 35 3. Dimensions ........................................................................................................ 37 4. Service Space .................................................................................................... 38 5. Wiring Diagrams ................................................................................................ 39 6. Capacity Tables .................................................................................................. 42 7. Static Pressure................................................................................................... 44 8.Electric Characteristics ....................................................................................... 46 9. Accessories ........................................................................................................ 47 10.The Specification of Wiring ............................................................................... 48 11.Field Wiring ....................................................................................................... 49 12. Exploded View ................................................................................................. 50 13. Trouble shooting .............................................................................................. 53 Floor & Ceiling ............................................................................................................ 54 1.Features .............................................................................................................. 55 2. Specifications ..................................................................................................... 57 3.Dimensions ......................................................................................................... 59 4.Service Space ..................................................................................................... 60 5.Wiring Diagrams ................................................................................................. 61 6.Capacity Table..................................................................................................... 62 7.Electric Characteristics ....................................................................................... 64 8. Exploded View ................................................................................................... 65 II
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual 9.Accessories ......................................................................................................... 67 10.The Specification of Power ............................................................................... 68 11.Field Wiring ....................................................................................................... 69 12.Troubleshooting ................................................................................................ 70
Part 3 Outdoor Units................................................................................................ 71 1.Specification ........................................................................................................ 72 2.Dimensions ......................................................................................................... 74 3.Service Space ..................................................................................................... 76 4.Wiring Diagrams ................................................................................................. 77 5.Electric Characteristics ....................................................................................... 79 6.Operation Limits .................................................................................................. 80 7.Sound Levels ...................................................................................................... 81 8.Exploded View .................................................................................................... 82 9.Troubleshooting .................................................................................................. 89
Part 4 Installation ..................................................................................................... 91 1. Precaution on Installation .................................................................................. 92 2.Vacuum Dry and Leakage Checking .................................................................. 93 3.Additional Refrigerant Charge ............................................................................ 95 4.Water Drainage ................................................................................................... 96 5.Insulation Work ................................................................................................... 99 6. Test Operation .................................................................................................. 101
Part 5 Controller..................................................................................................... 102 1.Wireless Remote Controller .............................................................................. 103 2.Wire Controller .................................................................................................. 106
III
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
R410A 50Hz Universal Outdoor series
PART 1.General Information 1.Nomenclature ..................................................................................... 2 2.Model Names of Indoor/Outdoor Units ............................................... 3 3.External Appearance .......................................................................... 4 4.Features ............................................................................................. 6
1
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1. Nomenclature 1.1 Indoor unit
C CA T i - 2 E C V R1 - B Design No Refrigerant -:R22; R1:R410A V:DC Inv. -:Fixed speed. Function code E:Electrical auxiliary heater. Capacity,unit:kBtu/h -:Match universal outdoor unit; i:match individual outdoor Working Condition -:T1 condition; T:T3 condition. Product series CA:4-way cassette; CB:Compact 4-way Casssette TA;Low ESP Duct; TB:Mid ESP Duct; TH:High ESP Duct;UA:Floor & C:Chigo HVAC
1.2 Outdoor unit
C 3 O T - 2 C S V R1 - B Design No Refrigerant
V:DC Inv. Power Code
Function code Capacity,unit:kBtu/h
Working Condition
Product series Match Code C:Chigo HVAC
2
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2. Model Names of Indoor/Outdoor Units 2.1 Indoor Units Model name
Dimension (W×H×D) (mm)
Net/Gross weight(kg)
Power supply
CCA-18HVR1 CCA-24HVR1 CCA-36HVR1
840×230×840 840×230×840 840×285×840
25/30 24/30 30.5/36
220~240V-1Ph-50Hz 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz
CTA-18HVR1 CTA-24HVR1 CTB-36HVR1
1100×467×210 1100×467×210 1425×663×260
22.5/25.5 25/28 46/50
220~240V-1Ph-50Hz 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz
CUA-18HVR1 CUA-24HVR1 CUA-36HVR1
1245×680×244 1245×680×244
34/40 34/40 35/41
220~240V-1Ph-50Hz 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz
1245×680×244
2.2 Outdoor Units Model name COU-18HDR1 COU-24HDR1 COU-36HDR1
3
Dimension (W×H×D) (mm) 930×370×700 960×390×835 911×400×1335
Net/Gross weight(kg) 45/49 59/69 96/101
Power supply 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz 220~240V-1Ph-50Hz
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3. External Appearance 3.1 Indoor unit 4-way Cassette
Low ESP Duct
Middle ESP Duct
Floor & Ceiling
4
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3.2 Outdoor unit COU-18HDR1
COU-24HDR1
COU-36HDR1
5
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4. Features 4.1 Wide operation range, -5 for cooling and -15 for heating. 4.2 Excellent in efficiency, SCOP higher than 3.8, meet the EU’s new energy efficiency standards. 4.3 High quality coils The coil is constructed of advanced inner grooved copper tube and aluminum fins. 4.4 Low operation sound level: Well-known stable and quiet running DC fan motor. 4.5 Well-known compressor, GMCC and Mitsubishi. 4.6 Universal design: convenient for market stock and spare parts stock. 4.8 R410A environment friendly refrigerant. 4.9 CE certification, ROHS certification.
6
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Part 2 Indoor Unit
4-Way Cassette Type 1. Features ............................................................................................. 8 2. Specification ...................................................................................... 11 3. Dimension ....................................................................................... 13 4. Service Space .................................................................................. 15 5. Wiring Diagrams .............................................................................. 16 6. Capacity Table ................................................................................. 17 7. Electric Characteristics .................................................................... 20 8. Exploded View ................................................................................. 21 9. Accessories ..................................................................................... 25 10. The Specification of Wiring ............................................................ 26 11. Field Wiring .................................................................................... 27 12. Trouble shooting ............................................................................ 29
7
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Features (1) Brand-new panel design. Indoor unit use uniform panel, simple and convenient.
(2) Simple, featly and voguish appearance suit for different requirements, it’s mostly used for office, shopping center, restaurant, meeting room and etc. 18kBtu/h~60kBtu/h, standard type, 950mm*950mm
(3) Ultra-thin body design, the min. height is only 230mm, save installation space.
(4) 4-way air flow, cold air can reach each corner of the room, providing a stable and comfortable environment.
(5) Intelligent auto-swing function, three modes for choice. Standard mode
8
Anti-point blow mode
Ceiling against mode
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
(6) 3 fan speed,meet for different requirement.
(7) New streamlined fan design.
(8) Occupied a small installation space, saving interior space
(9) Easy and convenient installation and maintenance, washable filter design.
(10)
Built-in water pump, water head up to 1200mm.
9
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
(11) Integrated electric control box, The E-box is safely covered by metal plate, for better fire-resistance, save using.
(12) Add 4 interfaces in body, can be connected with duct to another room. Fresh air makes air quality more healthy and comfortable.
(13) (14) (15)
Multi protection and auto-restart function. Low operation sound level: Well-known stable and quiet running DC fan motor. Standard for wireless controller; option for wired controller.
Standard
10
optional
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1. Specification
Model
CCA-18HVR1
CCA-24HVR1
CCA-36HVR1
V/Ph/Hz
220~240/1/50
220~240/1/50
220~240/1/50
KW
2.0-5.3-5.6
3.5-7.0-8.0
6.6-10.5-12.8
Power input
W
420-1840
600-3000
1050-4600
Current input
A
1.8-7.8
2.5-13
4.2-24.8
SEER
W/W
5.6
5.6
5.1
Capacity
KW
3.0-5.3-6.0
4.5-7.0-8.5
7.35-10.5-13.2
Input
W
640-1640
1500-2600
1100-4150
Rated current
A
3-8.0
5.5-11
4.4-18.5
W/W
4.0
4.0
3.8
Energy rate
Cooling
A+
A+
A
Energy rate
Heating
A+
A+
A+
Max. power input
W
2000
3200
4800
Max. current input
A
10
14
26
Model
DR-310-60Q-8
DR-310-60Q-8
DR-310-100Q-8
Brand
Panasonic
Panasonic
Panasonic
W
60
60
100
r/min
850
850
840/750/650
Insulation class
E
E
E
Number of rows Tube pitch(a) x row pitch(b) Fin spacing
2
2
2
mm
21×13.37
21×13.37
21×13.37
mm
1.45
1.45
1.45
Hydrophilic
Hydrophilic
Hydrophilic
Ф7
Ф7
Ф7
inner grooved
inner grooved
inner grooved
2000×168×26.7
2000×168×26.74
2000×252×26.74
Indoor power supply Capacity Cooling
Heating
SCOP
Indoor fan motor
Power output Speed
Indoor coil
Fin type Tube outside dia. and type Coil length x height x width Number of circuits
mm mm
8
8
12
Indoor air flow(High speed)
3
m /h
900
1100
1800
Indoor noise level
dB(A)
46~58
56~63
53~61
Body(mm)
840×840×230
840×840×230
840×840×285
Panel(mm)
950×950×50
950×950×50
950×950×50
Body(mm)
985×920×265
985×920×265
920×920×310
Panel(mm)
1030×1030×105
1030×1030×105
1030×1030×105
Body(Kg)
25/30
24/30
30.5/36
Panel(Kg)
5.4/8.0
5.4/8.0
5.4/8.0
MPa
3.8
3.8
3.8
Dimension(W*H*D)
Indoor unit
Packing(W*H*D)
Net/Gross weight Max pressure
11
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Refrigerant type Refrigerant Liquid side/Gas side piping Drainage pipe
R410A
R410A
R410A
mm
Φ6.35/Φ12.7
Φ9.52/Φ15.88
Φ9.52/Φ15.88
mm
DN25
DN25
DN25
Standard controller
Standard for remote controller(wired controller for option)
Operation temp
°C
16~32
16~32
16~32
Ambient temp
°C
-5~50
-5~50
-5~50
cooling
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
12
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3. Dimension 3.1 CCA-18HVR1, CCA-24HVR1
13
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3.2 CCA-36HVR1
14
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4. Service Space The indoor unit should be installed in a location that meets the following requirements: 4.1 There is enough interspace for installation and maintenance. 4.2 The ceiling is horizontal, and its structure can endure the weight of the indoor unit. 4.3 The outlet and the inlet are not impeded, and the influence of external air is the least. 4.4 The air flow can reach throughout the room. 4.5 The connecting pipe and drainpipe could be extracted out easily. 4.6 There is no direct radiation from heaters.
15
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
5. Wiring Diagrams CCA-18HVR1 CCA-24HVR1 CCA-36HVR1 Indoor models Select bits ON
Note:Model 10.5 kw ground does not need to connect outdoor
Indoor models
SW2 NO.1,2
Low static pressure duct unit
OFF 1 2 ON
Ceiling cassette unit
OFF 1 2 ON
Standard static pressure duct unit
OFF 1 2 ON
Connect to the outdoor
Floor&Ceiling unit
OFF 1 2
Receive and display light board ON
L1 N1 S
LED
OFF 4 ON
Digital tube
OFF 4
SW2 NO.8 Heating fan stop time SW2 NO.5
ON
power-down memory
OFF 5
4MIN
OFF 8
ON
No power-down memory
OFF 5
SW2 NO.6
ON
ON
8MIN
OFF 8
Heating temperature compensation SW2 NO.7
ON
6℃
OFF 6 ON
ON OFF 7 ON
2℃
OFF 6
Anti-cold wind off the fan temperature selection bit
OFF 7
15℃
NOTE:
L N
SW2 NO.4
ON OFF
1
That DIP to ON
ON OFF
1
That DIP to Digital
24℃
SW2
ON HP POWER SW1
16
2 53 0
2 53 1
2 53 2
2 53 3
2 3 53 70 4 5
3 4 4 4 70 105 105 105 6 7 9 8
OFF
1234 567 8
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
6. Capacity Table
Cooling 6.1 CCA-18HVR1 MODEL COOLING Indoor Conditions Total capacity kW 21ºC D Sensitive capacity kW 15ºC W Input kW. Total capacity kW 24ºC D Sensitive capacity kW 17ºC W Input kW. Total capacity kW 27ºC D Sensitive capacity kW 19ºC W Input kW. Total capacity kW 29ºC D Sensitive capacity kW 19ºC W Input kW. Total capacity kW 32ºC D Sensitive capacity kW 23ºC W Input kW.
21ºC 5.15 4.13 1.0 5.59 4.52 1.06 6.23 5.12 1.09 6.39 5.27 1.21 6.98 5.52 1.3
CCA-18HVR1 OUTDOOR TEMPERATURE DRY 28ºC 35ºC 4.85 4.49 3.91 3.58 1.29 1.49 5.31 4.91 4.25 3.89 1.3 1.57 5.42 5.32 4.61 4.23 1.67 1.69 5.85 5.57 4.75 4.47 1.71 1.93 6.11 5.83 4.92 4.68 1.89 2.18
43ºC 4.21 3.38 1.75 4.61 3.71 1.83 5.01 4.01 1.96 5.33 4.28 2.16 5.78 4.55 2.25
21ºC 7.34 5.42 2.14 7.57 5.68 2.28 7.71 5.71 2.31 7.76 6.54 2.36 7.84 6.63 2.42
CCA-24HVR1 OUTDOOR TEMPERATURE DRY 28ºC 35ºC 7.05 6.68 5.44 5.32 2.32 2.47 7.23 6.83 5.62 5.61 2.47 2.56 7.37 7.18 5.66 5.6 2.45 2.56 7.43 7.16 6.32 6.26 2.52 2.65 7.61 7.42 6.60 6.40 2.53 2.72
43ºC 6.41 5.39 2.55 6.43 5.41 2.67 6.69 5.45 2.71 6.71 6.15 2.73 6.88 6.37 2.82
6.2 CCA-24HVR1 MODEL COOLING Indoor Conditions Total capacity kW 21ºC D Sensitive capacity kW 15ºC W Input kW. Total capacity kW 24ºC D Sensitive capacity kW 17ºC W Input kW. Total capacity kW 27ºC D Sensitive capacity kW 19ºC W Input kW. Total capacity kW 29ºC D Sensitive capacity kW 19ºC W Input kW. Total capacity kW 32ºC D Sensitive capacity kW 23ºC W Input kW.
17
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
6.3 CCA-36HVR1
21ºC D 15ºC W 24ºC D 17ºC W 27ºC D 19ºC W 29ºC D 19ºC W 32ºC D 23ºC W
MODEL COOLING Indoor Conditions Total capacity kW Sensitive capacity kW Input kW. Total capacity kW Sensitive capacity kW Input kW. Total capacity kW Sensitive capacity kW Input kW. Total capacity kW Sensitive capacity kW Input kW. Total capacity kW Sensitive capacity kW Input kW.
21ºC 10.92 8.08 3.11 11.19 8.40 3.29 11.38 8.42 3.36 11.51 9.67 3.39 11.59 9.82 3.54
CCA-36HVR1 OUTDOOR TEMPERATURE DRY 28ºC 35ºC 10.32 9.81 7.98 7.84 3.38 3.52 10.66 10.14 8.29 8.23 3.52 3.67 10.92 10.55 8.40 8.19 3.56 3.63 11.03 10.74 9.32 9.28 3.62 3.77 11.18 11.03 9.71 9.71 3.67 3.96
43ºC 9.38 7.89 3.61 9.52 8.01 3.88 9.75 7.19 4.10 9.91 9.00 3.98 10.11 9.37 4.09
Heating 6.4 CCA-18HVR1 MODEL HEATING Indoor Conditions 15ºC 18ºC 20ºC 22ºC 27ºC
18
Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
24ºC D 18ºC W 9.92 2.95 9.31 2.83 8.61 2.58 7.92 2.41 6.91 2.11
CCA-18HVR1 OUTDOOR CONDITIONS 7ºC D 2ºC DB -5ºC D 6ºC W 1ºC WB -6ºC W 6.62 5.81 4.97 2.01 1.82 1.71 6.22 5.45 4.68 1.88 1.74 1.61 5.89 5.05 4.29 1.65 1.61 1.48 5.32 4.66 4.03 1.58 1.48 1.38 4.63 4.05 3.48 1.38 1.29 1.19
-7ºC D -8ºC W 4.64 1.61 4.38 1.51 4.04 1.40 3.73 1.23 3.27 1.11
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
6.5 CCA-24HVR1 MODEL HEATING Indoor Conditions 15ºC 20ºC 27ºC
Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
24ºC D 18ºC W 10.32 2.31 10.03 2.41 9.41 2.58
CCA-24HVR1 OUTDOOR CONDITIONS 7ºC D 2ºC DB -5ºC D 6ºC W 1ºC WB -6ºC W 8.17 6.85 6.19 2.06 2.0 1.88 7.88 6.43 6.08 2.07 2.05 1.97 7.53 6.11 5.89 2.17 2.11 2.05
-7ºC D -8ºC W 5.84 1.77 5.59 1.87 5.27 1.98
24ºC D 18ºC W 15.22 3.57 14.75 3.87 13.79 4.39
CCA-36HVR1 OUTDOOR CONDITIONS 7ºC D 2ºC DB -5ºC D 6ºC W 1ºC WB -6ºC W 12.31 10.12 9.14 3.15 2.98 2.85 11.63 9.41 8.85 3.18 3.1 2.98 10.94 8.86 8.64 3.55 3.46 3.33
-7ºC D -8ºC W 8.46 2.65 8.21 2.87 7.72 3.07
6.6 CCA-36HVR1 MODEL HEATING Indoor Conditions 15ºC 20ºC 27ºC
19
Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7. Electric Characteristics Model
Indoor Units
Indoor Fan Motor
Hz
Voltage
Min.
Max.
kW
CCA-18HVR1
50
220-240V
198V
254V
0.06
CCA-24HVR1
50
220-240V
198V
254V
0.06
CCA-36HVR1
50
220-240V
198V
254V
0.10
20
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8. Exploded View 8.1 CCA-18HVR1,CCA-24HVR1
21
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
No. Part Name
No. Part Name
1
E-parts box cover
8.4.2
Evaporator
2
Electric control components for indoor unit
8.4.3
collecting pipe welding assy
2.1
E-parts board for indoor unit
8.4.4
Current divider capillary assy
2.2
Temperature sensor
8.5
Main fixing board
2.3
Terminal
9
Upper foam components
2.4
Terminal
10
Pre-assembling assy for water pump
2.5
Relay
10.1
water pump support
2.6
Welded chassis for E-parts box
10.2
Water pump
3
Wind inlet guide assy
10.3
Liquid-level sensor
3.1
Wind inlet guide
10.4
Underlay for water pump support
4
Water pan components
11
Hanger
4.1
Foam pendant
12
Rear brattice
5
Centrifugal fan
13
Chassis assy
6
Fan motor for indoor unit
14
Discharge pipe joint
7
Auxiliary fixing board for evaporator
15
Side maintenance board for water pump
8
Evaporator components
16
Front brattice
8.1
Insulating pipe
17
Lower pipe clamp
8.2
Insulating pipe
18
Lower pipe clamp(φ35)
8.3
Evaporator attached cotton
19
Upper pipe clamp
8.4
Evaporator welding assy
20
Upper pipe clamp(φ35)
21
Valve panel
8.4.1 Installation tube for probe
22
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8.2 CCA-36HVR1
23
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
No. Part Name
No. Part Name
1
E-parts box cover
8.4.2
Evaporator
2
Electric control components for indoor unit
8.4.3
collecting pipe welding assy
2.1
The electric control board base
8.4.4
Current divider capillary assy
2.2
relay
8.5
Main fixing board
2.3
Terminal
9
The chassis plate
2.4
Terminal
10
Upper foam components
2.5
E-parts board for indoor unit
11
Pre-assembling assy for water pump
2.6
Temperature sensor
11.1
water pump support
2.7
Temperature sensor
11.2
Water pump
2.8
Welded chassis for E-parts box
11.3
Liquid-level sensor
3
Wind inlet guide assy
11.4
Underlay for water pump support
3.1
Wind inlet guide
12
Hanger
4
Water pan components
13
Rear brattice
4.1
Foam pendant
14
Chassis assy
5
Centrifugal fan
15
Discharge pipe joint
6
Fan motor for indoor unit
16
Side maintenance board for water pump
7
Auxiliary fixing board for evaporator
17
Front brattice
8
Evaporator components
18
Lower pipe clamp
8.1
Insulating pipe
19
Lower pipe clamp(φ35)
8.2
Insulating pipe
20
Upper pipe clamp
8.3
Evaporator attached cotton
21
Upper pipe clamp(φ35)
8.4
Evaporator welding assy
22
Valve panel
8.4.1 Installation tube for probe
24
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
9. Accessories
Name
Installation Fittings
Tubing & Fittings (optional)
Drainpipe Fittings
Protect Pipe Fittings (optional)
Remote controller
Others
25
Shape
Quantity
Expansible hook
4
Installation hook
4
Installation paper board
1
Bolt M5
4
Connecting pipe group
1
Binding tape
1
Soundproof/insulation sheath
2
Out-let pipe sheath
1
Tightening band
5
Wall conduit
1
Wall conduit cover
1
Remote controller
1
Mounting screw(ST2.9×10-C-H)
2
Alkaline dry batteries (AM4)
2
Operation & installation instruction manual
1
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
10. The Specification of Wiring Model
18kBtu/h
24kBtu/h
Indoor power supply
V/Ph/Hz
220~240/1/50
Outdoor power supply
V/Ph/Hz
220~240/1/50
mm
2
3×2.5
3×2.5
Power supply individually for indoor and outdoor 3×1.5/3×4.0
mm
2
4×2.5
4×2.5
3×1.0
Outdoor Power Supply Connection wiring Power wiring Signal wiring
26
36kBtu/h
From indoor unit
From indoor unit
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
11. Field Wiring
27
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
28
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
12. Trouble shooting Fault codes table
29
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Duct Type 1. Features ........................................................................................... 31 2.Specification ..................................................................................... 35 3. Dimensions ...................................................................................... 37 4. Service Space .................................................................................. 38 5. Wiring Diagrams .............................................................................. 39 6. Capacity Tables ............................................................................... 42 7. Static Pressure ................................................................................ 44 8.Electric Characteristics ..................................................................... 46 9. Accessories ..................................................................................... 47 10.The Specification of Wiring ............................................................. 48 11.Field Wiring ..................................................................................... 49 12. Exploded View ............................................................................... 50 13. Trouble shooting ............................................................................ 53
30
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1. Features
Low Static Pressure Duct
Medium Static Pressure Duct
31
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1.1 Low ESP Ducted Unit 1. Short body, min. 700 mm width, easy to install.
2. Adopting aviation centrifugal fans, and CFD technology design, increasing air-volume and decreasing noise level.
3. Three fan speed, meet different requirement.
4. High efficiency DC fan motor, low noise and more comfortable. 5. E-box is body-side design, convenient installation and maintenance. 6. Standard for wireless remote controller, wired controller for option.
Standard
32
optional
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1.2 Medium ESP Ducted Unit 1. Ultra-thin body design.
2. Adopting aviation centrifugal fans, and CFD technology design, increasing air-volume and decreasing noise level. 3. Three fan speed, meet different requirement.
4. 30-50Pa ESP design for the medium static pressure duct type, duct connected installation meet for different room structure.
5. Filter can be taken out easily for clear. Easy maintenance.
6. E-box is body-side design, convenient installation and maintenance.
33
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7. High efficiency DC fan motor, low noise and more comfortable. 8. Two air return type option: air inlet from back is standard and from bottom is optional
9. Multi protection and auto-restart function. 10. Standard for wireless remote controller, wired controller for option.
Standard
34
optional
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2.
Specification Model
KW
CTA-18HVR1 220~240V/1Ph/50H z 2.0-5.3-5.6
CTA-24HVR1 220~240V/1Ph/5 0Hz 3.5-7.0-8.0
CTB-36HVR1 220~240V/1Ph/50 Hz 6.6-10.5-12.8
Power input
W
420-1840
650-3050
1150-4760
Current input
A
1.8-7.8
2.8-13.3
4.7-25.3
SEER
W/W
5.5
5.5
5.1
Capacity
KW
3.0-5.3-6.0
4.5-7.0-8.5
7.35-10.5-13.2
Input
W
640-1640
1550-2650
1200-4250
Rated current
A
3.0-8.0
5.8-11.3
4.9-19
W/W
3.8
3.8
3.8
Energy rate
Cooling
A
A
A
Energy rate
Heating
A
A
A
Max. power input
W
2000
3250
4800
Max. current input
A
10
14.5
Model
DR-310-68F-8
DR-310-68F-8
26 DR-310-150F-8 + DR-310-75F-8
Brand
Panasonic
Panasonic
Panasonic
W
68
68
150+75
μF
-
-
r/min
1275/1080/880/720
1275/1080/880/7 20
E
E
1350/1240/1140/1 040 + 1350/1270/1200/1 130 E
2*2
2*2
3
mm
20×19.05
20×19.05
22×19.05
mm
1.4
1.4
1.7
Hydrophilic
Hydrophilic
Hydrophilic
Ф7
Ф7
Ф7.94
inner grooved
inner grooved
Indoor power supply Capacity Cooling
Heating
SCOP
Indoor fan motor
Power output Capacitor Speed
V/Ph/Hz
Insulation class Number of rows Tube pitch(a) x row pitch(b) Fin spacing Fin type Indoor coil Tube outside dia. and type
mm
4
5
3
m /h
800
1050
1800
Pa
0-30
0-30
30-50
dB(A)
46~58
56~63
55~63
Dimension(W*H*D)
Body(mm)
1100×467×210
1100×467×210
1425×663×260
Packing(W*H*D)
Body(mm)
1310×240×510
1310×240×510
1490×720×325
Net/Gross weight
Body(Kg)
22.5/25.5
25/28
46/50
Coil length x height x width
mm
Number of circuits Indoor air flow(High speed) Static Pressure Indoor noise level
Indoor unit
35
inner grooved 1136×240×57.1 5 6
920×200×46
920×200×46
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Max pressure Refrigerant type Refrigerant Liquid side / piping Gas side Drainage pipe
MPa
3.8
3.8
3.8
R410A
R410A
R410A
mm
Φ6.35/Φ12.7
Φ9.52/Φ15.88
Φ9.52/Φ15.88
mm
DN25
DN25
DN25
Standard controller
Standard for remote controller(wired controller for option)
Operation temp
°C
16~32
16~32
16~32
Ambient temp
°C
-5~50
-5~50
-5~50
cooling
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2.Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
36
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3. Dimensions 3.1 CTA-18HVR1 CTA-24HVR1
3.2 CTB-36HVR1
37
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4. Service Space Ensure enough space required for installation and maintenance.
38
GD Chigo Heating & Ventilation Equipment Co., Ltd.
ALARM
S
CN37
CN27 Wi re control T1 T2 T 2B
L1 N1 S
COMMUNICATION Line pressing buttons
OUT POWER CN11
CN23 Duct display
L N
POWER
T1
Line pressing buttons
That DIP to ON
SW2 1 2 3 4 5 6 7 8
COM NO
J
PUMP
PUMP
1
NOTE: ON OFF
That DIP to Digital
OFF
ON
FACTORY DEFAULT
1
C10
BR BK
ON OFF
IC4
ALARM
S
CN37 SW1
4 4 4 105 105 105 7 9 8
SW2
3 70 6
CN26 CN4 HEATER REM O_CT RL
3 70 5
N
RY6
5
CN27 Wire control
2 53 4
L CN3
T1 T2 T2B CN17
2 53 3
CN1
RD
COM
SW2
1 2 3 4 5 6 7 8
OFF
ON
PT1
CN18 Water-SW LEFT FAN CN7
IC2
2 53 2
YE/GN
Connect to the outdoor
L1N1 S
NO
OUT POWER CN11
PT2
BR BK
BK
F01
PT3
2 53 1
PUMP
Controller
BR
L N POWER INPUT
CN26 REMO_CTRL
WATER SWITCH
5
DC FAN
YE/GN
PTC
10
C10
IC4
RY4
CN23 Duct display RIGHT FAN CN8
E21
T1
Receive and display light board
2 53 0
The power (PH) of indoor units can be set throughDIP switch SW1(16- bit disc DIP ) on the indoor control panel before delivery, the detailed information is as follows: HP POWER SW1
NOTE: 1. Without the pump type water level switch output cables short circuit.
6
6
7
7
OFF 1 ON
2
2
2
Floor&Ceiling Unit
Standard static pressure duct unit
Low static pressure duct unit
Indoor models
Indoor models Select bits
SW2 NO.1,2
OFF 1 ON
2
OFF 5
OFF 5 ON
ON
ON
OFF 4 ON
OFF 4
High speed
FAN SPEED
Super speed
LED
Digital tube
8MIN
Heating fan stop time 4MIN
24℃
15℃
Anti-cold wind off the fan temperature selection bit
2℃
6℃
Heating temperature compensation
No power-down memory
power-down memory
SW2 NO.4
Receive and display light board
OFF 3
OFF 3 ON
ON
SW2 NO.3
FAN SPEED CHOICE
Ceiling cassette unit OFF 1 ON
ON
OFF 1
SW2 NO.5
OFF ON
ON
SW2 NO.6
OFF
OFF ON
ON
SW2 NO.7
OFF
ON
8
8
SW2 NO.8 OFF
ON OFF
GD Chigo Heating & Ventilation Equipment Co., Ltd.
39
N CN10 L CN3 CN4 CN2 HEATER
R410A50Hz Universal Outdoor Series Technical Manual
5. Wiring Diagrams 5.1 CTA-18HVR1
ALARM
S
CN37
CN27 Wi re control
L1 N1 S
COMMUNICATION
CN1 RY6
CN23 Duct display RY4
L N
POWER
Line pressing buttons
That DIP to ON
Line pressing buttons
T1 T2 CN17
1
OUT POWER CN11
PUMP
ON
That DIP to Digital
NOTE:
1
1 2 3 4 5 6 7 8
SW2
FACTORY DEFAULT ON OFF
PUMP
BR BK
OFF
ON OFF
C10
CN1
ALARM
CN37
S
SW1
4 4 4 105 105 105 7 9 8
IC4
3 70 6
E21
3 70 5
IC2
T1 T2 T2B CN17
RY6
5
CN27 Wire control
2 53
PTC
1 2 3 4 5 6 7 8
OFF
2 53 3
COM NO
J
N CN10 L CN3 CN26 CN4 CN2 HEATER REM O_CT RL
OUT POWER CN11
PT1
CN18 Water-SW LEFT FAN CN7
IC2
2 53 2
PUMP
RD
COM
SW2 PT3
2 53 1
YE/GN
Connect to the outdoor
L1N1 S
NO
F01
PT2
BR BK
BK
ON
Controller
BR
L N POWER INPUT
CN26 REMO_CTRL
WATER SWITCH
5
DC FAN
YE/GN
PTC
10
C10
IC4
RY4
CN23 Duct display RIGHT FAN CN8
E21
T1
Receive and display light board
2 53 0
The power (PH) of indoor units can be set throughDIP switch SW1(16- bit disc DIP ) on the indoor control panel before delivery, the detailed information is as follows: HP POWER SW1
4
NOTE: 1. Without the pump type water level switch output cables short circuit.
6
6
7
7
Floor&Ceiling Unit
Standard static pressure duct unit
Ceiling cassette unit
Low static pressure duct unit
Indoor models
Indoor models Select bits
SW2 NO.1,2 ON OFF 1 2 ON OFF 1 2 ON OFF 1 2 ON
SW2 NO.3
OFF 5
OFF 5 ON
ON
ON
OFF 4 ON
OFF 4
High speed
FAN SPEED
Super speed
Digital tube
LED
8MIN
4MIN
Heating fan stop time
24℃
15℃
Anti-cold wind off the fan temperature selection bit
2℃
6℃
Heating temperature compensation
No power-down memory
power-down memory
SW2 NO.4
Receive and display light board
OFF 3
OFF 3 ON
ON
FAN SPEED CHOICE
OFF 1 2
SW2 NO.5
OFF ON
ON
SW2 NO.6
OFF
OFF ON
ON
SW2 NO.7
OFF
8
8
SW2 NO.8 ON OFF
ON OFF
GD Chigo Heating & Ventilation Equipment Co., Ltd.
40
N CN10 L CN3 CN4 CN2 HEATER
R410A50Hz Universal Outdoor Series Technical Manual
5.2 CTA-24HVR1
R410A50Hz Universal Outdoor Series Technical Manual
5.3 CTB-36HVR1
PUMP
BK BR
BK
COM
HP POWER SW1
NOTE:
2 53 0
2 53 1
2 53 2
2 53 3
2 53 4
SW2
3 70 5
PTC
RY6
5
CN27 Wire control
T1 T2 T2B CN17
3 70 6
DC FAN 5
IC2
LEFT FAN CN7
Water-SW
CN18
WATER SWITCH
C10
IC4
RY4
RIGHT FAN 5
E21
RIGHT FAN CN8
CN23 Duct display
10
4 4 4 105 105 105 7 9 8
T1
Receive and display light board
Note:Model 105 kw ground does not need to connect outdoor
YE/GN Controller
1 2 3 4 5 6 7 8 OFF
SW1
PT3
Connect to the outdoor
L1N1 S
RD
ON
CN26 REMO_CTRL
NO
CN37
S
OUT POWER CN11
N CN10 L CN3 CN4 CN2 HEATER PUMP
CN1
BK
BR
ALARM
BR
L N POWER INPUT
PT1
The power (PH) of indoor units can be set throughDIP switch SW1(16- bit disc DIP ) on the indoor control panel before delivery, the detailed information is as follows:
YE/GN
PT2
1. The factory default CN18 need cables short circuit 2、The water pump outlet are connected by a field installation
COM NO
J CN26 REM O_CT RL
CN37
S
OUT POWER CN11
CN4 HEATER
N CN10 L CN3 CN2
PUMP
CN1 ALARM
L N
POWER
SW2 T1 T2 T 2B CN17
PTC
RY6
CN27 Wi re control
L1 N1 S
IC2
COMMUNICATION Line pressing buttons
That DIP to ON
Line pressing buttons
1
1
That DIP to Digital
NOTE: ON OFF
ON OFF
1 2 3 4 5 6 7 8
SW2
FACTORY DEFAULT ON OFF
E21
CN23 Duct display
C10
IC4
RY4
T1
Low static pressure duct unit
Indoor models
Indoor models Select bits
SW2 NO.1,2 ON
Ceiling cassette unit
1 2
1 2
ON
OFF
OFF ON
Floor&Ceiling unit
Standard static pressure duct unit
SW2 NO.3
OFF 5
OFF 5 ON
ON
ON
OFF 4 ON
OFF 4
FAN SPEED
High speed
Super speed
LED
Digital tube
2℃
6℃
Heating temperature compensation
No power-down memory
power-down memory
SW2 NO.4
Receive and display light board
OFF 3
OFF 3 ON
ON
FAN SPEED CHOICE
1 2
1 2 ON
OFF
OFF
SW2 NO.5
SW2 NO.6 ON OFF 6 ON OFF 6
ON
8MIN
4MIN
Heating fan stop time
24℃
15℃
Anti-cold wind off the fan SW2 NO.7 temperature selection bit OFF 7 ON OFF 7
ON
8
8
SW2 NO.8 OFF
ON OFF
GD Chigo Heating & Ventilation Equipment Co., Ltd.
41
F01
R410A50Hz Universal Outdoor Series Technical Manual
6. Capacity Tables Cooling 6.1 CTA-18HVR1 MODEL COOLING Indoor Conditions 21ºC DB Total capacity kW 15ºC WB Input kW. 24ºC DB Total capacity kW 17ºC WB Input kW. 27ºC DB Total capacity kW 19ºC WB Input kW. 32ºC DB Total capacity kW 23ºC WB Input kW.
21ºC 5.27 1.07 5.78 1.14 6.24 1.18 7.17 1.41
CTA-18HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 4.98 4.68 4.55 4.33 1.24 1.41 1.55 1.74 5.47 5.33 4.99 4.79 1.31 1.47 1.67 1.85 5.94 5.72 5.38 5.18 1.41 1.58 1.72 1.96 6.81 6.58 6.26 5.98 1.61 1.8 2.04 2.26
21ºC 6.95 5.44 7.59 1.63 8.27 1.68 9.43 1.97
CTA-24HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 6.63 6.39 6.03 5.82 5.18 4.96 4.7 4.51 7.23 6.99 6.58 6.33 1.84 2.1 2.3 2.55 7.88 7.61 7.18 6.93 1.94 2.17 2.45 2.66 9.04 8.71 8.25 7.90 2.27 2.56 2.81 3.1
45ºC 5.61 4.52 6.12 2.79 6.68 2.97 7.5 3.53
21ºC 10.21 2.27 11.16 2.4 12.16 2.59 13.8 2.91
CTB-36HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 9.77 9.41 9.6 8.56 2.67 2.97 3.3 3.61 10.69 10.31 9.77 9.37 2.76 3.1 3.46 3.86 11.62 11.18 10.59 10.18 2.94 3.31 3.76 4.05 13.36 12.87 12.18 11.68 3.32 3.8 4.2 4.65
45ºC 8.31 3.98 9.05 4.19 9.88 4.4 11.3 5.08
45ºC 4.24 1.9 4.66 2.0 5.04 2.09 5.82 2.48
6.2 CTA-24HVR1 MODEL COOLING Indoor Conditions 21ºC DB Total capacity kW 15ºC WB Input kW. 24ºC DB Total capacity kW 17ºC WB Input kW. 27ºC DB Total capacity kW 19ºC WB Input kW. 32ºC DB Total capacity kW 23ºC WB Input kW.
6.3 CTB-36HVR1 MODEL COOLING Indoor Conditions 21ºC DB Total capacity kW 15ºC WB Input kW. 24ºC DB Total capacity kW 17ºC WB Input kW. 27ºC DB Total capacity kW 19ºC WB Input kW. 32ºC DB Total capacity kW 23ºC WB Input kW.
42
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Heating 6.4 CTA-18HVR1 MODEL HEATING Indoor Conditions Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
15ºC 18ºC 20ºC 22ºC 27ºC
CTA-18HVR1 OUTDOOR CONDITIONS 24ºC DB 18ºC WB 10.26 3.09 9.64 2.9 9.0 2.67 8.23 2.39 7.24 2.07
12ºC DB 11ºC WB 8.23 2.41 7.74 2.3 7.15 2.1 6.56 1.91 5.73 1.6
7ºC DB 6ºC WB
4ºC DB 3ºC WB
0ºC DB -1ºC WB
-5ºC DB -6ºC WB
-7ºC DB -8ºC WB
6.81 2.01 6.42 1.83 5.88 1.66 5.51 1.58 4.76 1.36
6.17 1.88 5.86 1.8 5.37 1.59 4.87 1.5 4.3 1.27
5.77 1.8 5.52 1.67 5.13 1.57 4.67 1.46 4.11 1.2
5.17 1.71 4.86 1.6 4.53 1.48 4.17 1.35 3.6 1.1
4.88 1.6 4.6 1.51 4.23 1.35 3.85 1.27 3.4 1.07
6.5 CTA-24HVR1 MODEL HEATING Indoor Conditions Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
15ºC 18ºC 20ºC 22ºC 27ºC
CTA-24HVR1 OUTDOOR CONDITIONS 24ºC DB 18ºC WB 13.86 4.24 13.03 3.97 12.12 3.67 11.13 3.35 9.63 2.91
12ºC DB 11ºC WB 11.13 3.34 10.44 3.1 9.61 2.94 8.88 2.64 7.72 2.28
7ºC DB 6ºC WB
4ºC DB 3ºC WB
0ºC DB -1ºC WB
-5ºC DB -6ºC WB
-7ºC DB -8ºC WB
9.29 2.8 8.71 2.58 8.12 2.41 7.5 2.18 6.48 1.9
8.37 2.66 7.83 2.47 7.27 2.27 6.7 2.06 5.82 1.83
7.88 2.5 7.42 2.34 6.83 2.17 6.33 1.94 5.51 1.67
6.94 2.37 6.54 2.21 6.14 2.05 5.55 1.8 4.83 1.59
6.53 2.23 6.12 2.05 5.71 2.01 5.2 1.75 4.51 1.51
6.6 CTB-36HVR1 MODEL HEATING Indoor Conditions 15ºC 18ºC 20ºC 22ºC 27ºC
43
Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
24ºC DB 18ºC WB 19.28 6.24 17.98 5.91 16.76 5.3 15.34 5.0 13.39 4.27
12ºC DB 11ºC WB 15.46 5.05 14.42 4.7 13.4 4.17 12.32 4.01 10.73 3.43
CTB-36HVR1 OUTDOOR CONDITIONS 7ºC DB 4ºC DB 0ºC DB 6ºC WB 3ºC WB -1ºC WB 12.88 11.6 10.94 4.15 3.92 3.68 12.0 10.9 10.3 3.87 3.69 3.49 11.66 10.0 9.6 3.33 3.21 3.09 10.35 9.23 8.8 3.3 3.09 2.96 8.93 8.12 7.67 2.87 2.76 2.56
-5ºC DB -6ºC WB 9.67 3.53 9.15 3.29 8.43 2.97 7.73 2.8 6.7 2.4
-7ºC DB -8ºC WB 9.04 3.32 8.49 3.07 7.85 2.85 7.23 2.61 6.33 2.28
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7. Static Pressure
External static pressure (Pa)
7.1 CTA-18HVR1 CTA-18HVR1
Pa 50 40
Super high speed
30
High speed Mid speed
20
Low speed 10
200
300
400 500 600 700 Air volume(m 3 /h)
800
900
1000 1100 1200
7.2 CTA-24HVR1 CTA-24HVR1
External static pressure (Pa)
Pa 60 50
Super high speed
40
High speed 30 Mid speed Low speed
20 10
700
44
800
900 1000 1100 1200 1300 1400 Air volume(m 3 /h)
1500
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7.3 CTB-36HVR1 Pa
CTB-36HVR1
External static pressure (Pa)
60 50 40
Super high speed High speed
30
Mid speed
20
Low speed
10
1100 1200 1400 1600 1800 2000 2200 Air volume(m 3 /h)
45
2400
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8 Electric Characteristics
Model
Indoor Units
Indoor Fan Motor
Hz
Voltage
Min.
Max.
kW
CTA-18HVR1
50
220-240V
198V
254V
0.068
CTA-24HVR1
50
220-240V
198V
254V
0.068
CTB-36HVR1
50
220-240V
198V
254V
0.225
46
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
9 Accessories Name Soundproof/insulation sheath Tubing & Fittings
Drainpipe Fittings
others
47
Shape
Quantity 2
Binding tape
1
Seal sponge
1
Seal ring
1
Remote controller (optional)
1
Operation & installation instruction manual
1
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
10 The Specification of Wiring Model
18kBtu/h
24kBtu/h
Indoor power supply
V/Ph/Hz
220~240/1/50
Outdoor power supply
V/Ph/Hz
220~240/1/50
mm
2
3×2.5
3×2.5
Power supply individually for indoor and outdoor 3×1.5/3×4.0
mm
2
4×2.5
4×2.5
3×1.0
Outdoor Power Supply Connection wiring Power wiring Signal wiring
48
36kBtu/h
From indoor unit
From indoor unit
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
11 Field Wiring
49
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
12. Exploded View 12.1 CTA-18HVR1, CTA-24HVR1
50
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual No.
Part Name
No.
Part Name
1
Cover attached cotton assay
9
Evaporator
1.1
Cover plate assay
9.1
Evaporator assy
1.1.1
Cover
9.1.1
Up evaporator
1.1.2
Hook
9.1.2
Down evaporator
1.2
cover cotton
9.1.3
Collecting pipe assy
1.3
Cotton on outlet
9.1.4
Shunt assy
1.4
Cotton on the cover
9.2
Damped rubber
2
panel upper air inlet channel
9.3
Damped rubber
3
panel bellow air inlet channel
9.4
sheath insullation
4
Motor assy
9.5
sheath insullation
4.1
Cotton on fan fixing board assy
10
Left clapboard attached cotton assy
4.2
Holder for fan motor
10.1
Left clapboard
4.3
Wind turbine volute
10.2
Left clapboard cotton
4.4
Biaxial indoor DC
10.3
Left and right outlet cotton
4.5
Motor support joint
11
Left inlet clapboard attached cotton assy
4.6
Right fixing clamp for motor
11.1
Left clapboard of air inlet channel
4.7
Left fixing clamp for motor
11.2
The right plate of air inlet channel
4.8
Axis
12
Cotton posted a pipe cover assy
12.1
Output pipe of left clapboard
4.9
Bearing holder
4.10
The holder of axis assy
12.2
Cotton posted a pipe cover
5
The right plate of air inlet channel
13
Pump holder attached cotton assy
6
panel bellow attached cotton assy
13.1
Pump holder
6.1
Down Panel assy
13.2
Pump cover sponge
6.1.1
Down Panel
14
Up foam
6.1.2
fan fixed plate
15
E-parts assy
6.2
Down outlet cotton
15.1
Base for electric control
6.3
Dowm panel cotton
15.2
Electric control cover
7
Right clapboard cotton assy
15.3
Plastic base for PCB
7.1
Right clapboard
15.4
Electronic control board for indoor unit
7.2
Right clapboard cotton
15.5
Terminal
8
Bubble water pan
15.6
Relay
51
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
12.2 CTB-36HVR1
52
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
13.Trouble shooting 13.1 Fault code table
53
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Floor & Ceiling
1.Features ........................................................................................... 55 3. Specifications ................................................................................... 57 3.Dimensions ....................................................................................... 59 4.Service Space .................................................................................. 60 5.Wiring Diagrams ............................................................................... 61 6.Capacity Table .................................................................................. 62 7.Electric Characteristics ..................................................................... 64 8. Exploded View ................................................................................. 65 9.Accessories ...................................................................................... 67 10.The Specification of Power ............................................................. 68 11.Field Wiring ..................................................................................... 69 12.Troubleshooting .............................................................................. 70
54
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1 Features 1. Flexible installation, ceiling suspended and floor standing.
2. Adopting centrifugal fans, higher ESP and longer air flow distance.
3. Two way auto-swing function, built-in two louver motor, vertical and horizontal air-flow adjustment.
4. Washable air filter
55
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
5. LED display optional.
6. High efficiency DC fan motor, low noise and more comfortable. 7. New upper and lower buckle type wheel case, the upper plastic wheel case can be removed Alone, which is convenient adjust the wheel motor.
8. Water pump optional, pumping head is up to 1200mm. 9. Adopting waterproof plastic film on water collector, avoiding water leakage.
10. Self-diagnostic function and multi protection; Auto-restart function.
11. Standard for wireless controller; option for wired controller
Standard
56
Optional
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2 Specifications Model
KW
CUA-18HVR1 220~240V/1Ph/ 50Hz 2.0-5.3-5.6
CUA-24HVR1 220~240V/1Ph/5 0Hz 3.5-7.0-8.0
CUA-36HVR1 220~240V/1Ph/50 Hz 6.6-10.5-12.8
Power input
W
420-1840
600-3000
1050-4660
Current input
A
1.8-7.8
2.5-13
4.2-24.8
SEER
W/W
5.5
5.5
5.1
Capacity
KW
3.0-5.3-6.0
4.5-7.0-8.5
7.35-10.5-13.2
Input
W
640-1640
1500-2600
1100-4150
Rated current
A
3.0-8.0
5.5-11
4.4-18.5
W/W
3.8
3.8
3.8
Energy rate
Cooling
A
A
A
Energy rate
Heating
A
A
A
Max. power input
W
2000
3200
4800
Max. current input
A
10
14
26
Model
DR-310-120LD -8
DR-310-120LD-8
DR-310-120LD-8
Brand
Panasonic
Panasonic
Panasonic
W
120
120
120
r/min
1400
1400
1400
Insulation class
E
E
E
Number of rows Tube pitch(a)xrow pitch(b) Fin spacing
2
2
3
mm
21×13.37
21×13.37
21×13.37
mm
1.4
1.4
1.4
Hydrophilic
Hydrophilic
Hydrophilic
Ф7 inner grooved 1000x252x26.7 4 2
Ф7
Ф7
inner grooved
inner grooved
1000x252x26.74
1000x252x26.74
2
4
Indoor power supply Capacity Cooling
Heating
SCOP
Indoor fan motor
Power output Speed
Indoor coil
V/Ph/Hz
Fin type Tube outside dia. and type Coil length x height x width Number of circuits
mm mm
Indoor air flow(High speed)
3
m /h
900
1150
1800
Indoor noise level
dB(A)
46~58
56~63
53~63
Dimension(W*H*D)
Body(mm)
1245×680×244
1245×680×244
1245×680×244
Packing(W*H*D)
Body(mm)
1325×770×330
1325×770×330
1325×770×330
Net/Gross weight
Body(Kg)
34/40
34/40
35/41
MPa
3.8
3.8
3.8
R410A
R410A
R410A
mm
Φ6.35/Φ12.7
Φ9.52/Φ15.88
Φ9.52/Φ15.88
mm
DN25
DN25
DN25
Indoor unit
Max pressure Refrigerant type Refrigerant Liquid side/Gas side piping Drainage pipe Standard controller 57
Standard for remote controller(wired controller for option)
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Operation temp Ambient temp
°C
16~32
16~32
16~32
cooling
°C
-5~50
-5~50
-5~50
heating
°C
-15~30
-15~30
-15~30
20-35
28-50
40-70
75/165/189
75/165/189
75/165/189
2
Application area
m
Stuffing Quantity(20'/40'/40'HQ)
set
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal) 2.Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
58
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3 Dimensions 3.1 CUA-18HVR1 CUA-24HVR1 CUA-36HVR1
150
200
680
1245
1119
59
235 247
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4 Service Space
60
GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor models Select bits Indoor models Low static pressure duct unit Ceiling cassette unit Standard static pressure duct unit
S
CN37
4 4 4 105 105 105 7 9 8
Floor&Ceiling Unit
3 70 6
F0 1
SW2
1 2 3 4 5 6 7 8
OFF
5
That DIP to ON ON
1 2 1 2 1 2 1 2
2 53 4
3 70 5
SW2 NO.1,2
OFF ON
ON
OFF
ON
OFF
OFF
2 53 3 Controller
SW1
OUT POWER CN11
CN2
PUMP
CN1
ALARM
L CN10 N
CN26 CN4 REMO_CTRL HEATER
ON
NOTE: ON
1
That DIP to Digital
SW2
2 53 2
1 2 3 4 5 6 7 8
2 53 1
WATER SWITCH
CN27 Wire control
CN17 T2B T2 T1
Water-SW
CN18
RY6
PTC
RD BK
PUMP
SW2 NO.3
Super speed
High speed
FAN SPEED
FAN SPEED CHOICE ON OFF 3 ON OFF 3
OFF 4
OFF 4 ON
ON
Digital tube
LED
Receive and display light board
SW2 NO.4
POWER INPUT Connect to the outdoor
OFF
1
ON OFF
2 53 0
SWING2 CN19
IC2
YE/GN
ON OFF
HP POWER SW1
10
Receive and display light board
5
LEFT FAN CN7
SWING1 CN20
RIGHT FAN CN8
RY4
CN23 Duct display
T1
E21
COM
SW2 NO.5
OFF ON
6
6
ON
ON OFF 5 ON OFF 5
SW2 NO.6
OFF
OFF ON
7
7
ON
SW2 NO.7
OFF
ON
8
8
SW2 NO.8 OFF
ON OFF
power-down memory
No power-down memory
Heating temperature compensation
6℃
2℃
Anti-cold wind off the fan temperature selection bit
15℃
24℃
4MIN
Heating fan stop time
8MIN
Note:Model 105 kw ground does not need to connect outdoor
GD Chigo Heating & Ventilation Equipment Co., Ltd.
61
RD BK RD
BK
NO
RD
L1N1 S L N YE/GN
IC4
C10
DC FAN1
CN3
R410A50Hz Universal Outdoor Series Technical Manual
5 Wiring Diagrams
5.1 CUA-18HVR1 CUA-24HVR1 CUA-36HVR1
PT3
PT2
PT1
R410A50Hz Universal Outdoor Series Technical Manual
6. Capacity Table Cooling 6.1 CUA-18HVR1 MODEL COOLING Indoor Conditions 21ºC D Total capacity Kw 15ºC W Input kW. 24ºC D Total capacity kW 17ºC W Input kW. 27ºC D Total capacity kW 19ºC W Input kW. 32ºC D Total capacity kW 23ºC W Input kW.
21ºC 5.21 1.1 5.7 1.13 6.2 1.22 7.13 1.4
CUA-18HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 4.98 4.79 4.52 4.36 1.25 1.41 1.56 1.71 5.47 5.26 4.95 4.78 1.31 1.49 1.62 1.83 5.95 5.71 5.3 5.16 1.4 1.59 1.66 1.96 6.84 6.57 6.22 5.94 1.60 1.83 2.03 2.22
45ºC 4.21 1.91 4.61 2.02 5.01 2.12 5.77 2.43
21ºC 6.85 1.52 7.52 1.63 8.15 1.73 9.37 2.02
CUA-24HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 6.55 6.31 5.94 5.71 1.79 2.03 2.28 2.53 7.18 6.91 6.52 6.26 1.88 2.15 2.32 2.65 7.79 7.51 7.10 6.81 2.01 2.22 2.4 2.8 8.96 8.63 8.16 7.82 2.3 2.61 2.87 3.22
45ºC 5.54 2.78 6.05 2.87 6.58 3.07 7.57 3.51
21ºC 10.12 2.2 11.1 2.32 12.06 2.41 13.86 2.87
CUA-36HVR1 OUTDOOR TEMPERATURE DRY 25ºC 30ºC 35ºC 40ºC 9.68 9.33 8.81 8.45 2.52 2.88 3.25 3.53 10.61 10.23 9.64 9.26 2.7 3.02 3.4 3.8 11.54 11.12 10.50 10.1 2.89 3.23 3.61 4.0 13.26 12.78 12.06 11.58 3.28 3.78 4.21 4.58
45ºC 8.18 3.89 8.96 4.13 9.75 4.31 11.21 5.0
6.2 CUA-24HVR1 MODEL COOLING Indoor Conditions 21ºC DB Total capacity kW 15ºC WB Input kW. 24ºC DB Total capacity kW 17ºC WB Input kW. 27ºC DB Total capacity kW 19ºC WB Input kW. 32ºC DB Total capacity kW 23ºC WB Input kW.
6.3 CUA-36HVR1 MODEL COOLING Indoor Conditions 21ºC DB Total capacity kW 15ºC WB Input kW. 24ºC DB Total capacity kW 17ºC WB Input kW. 27ºC DB Total capacity kW 19ºC WB Input kW. 32ºC DB Total capacity kW 23ºC WB Input kW.
62
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Heating 6.4 CUA-18HVR1 MODEL HEATING Indoor Conditions Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
15ºC 18ºC 20ºC 22ºC 27ºC
24ºC D 18ºC W 10.28 3.02 9.67 2.81 8.87 2.6 8.21 2.36 7.15 2.0
12ºC D 11ºC W 8.21 2.4 7.72 2.19 7.12 2.01 6.56 1.88 5.72 1.63
CUA-18HVR1 OUTDOOR CONDITIONS 7ºC D 4ºC D 0ºC D 6ºC W 3ºC W -1ºC W 6.88 6.2 5.85 2.0 1.86 1.76 6.45 5.81 5.49 1.85 1.73 1.64 5.8 5.38 5.08 1.57 1.59 1.52 5.51 4.96 4.66 1.5 1.42 1.37 4.78 4.3 4.06 1.33 1.26 1.18
-5ºC D -6ºC W 5.16 1.65 4.85 1.54 4.49 1.41 4.13 1.3 3.58 1.11
-7ºC D -8ºC W 4.81 1.54 4.52 1.44 4.18 1.32 3.85 1.21 3.37 1.0
12ºC D 11ºC W 10.91 3.62 10.27 3.3 9.48 3.12 8.76 2.81 7.57 2.32
CUA-24HVR1 OUTDOOR CONDITIONS 7ºC D 4ºC D 0ºC D 6ºC W 3ºC W -1ºC W 9.12 8.24 7.78 3.0 2.82 2.66 8.56 7.68 7.31 2.69 2.62 2.48 7.8 7.16 6.78 2.2 2.19 2.13 7.31 6.58 6.24 2.13 2.1 2.07 6.34 5.72 5.42 2.02 1.98 1.85
-5ºC D -6ºC W 6.86 2.55 6.42 2.32 5.92 2.08 5.5 1.96 4.68 1.7
-7ºC D -8ºC W 6.42 2.41 6.01 2.24 5.58 2.02 5.12 1.85 4.46 1.53
12ºC D 11ºC W 15.74 4.66 14.78 4.37 13.7 4.04 12.62 3.7 11.03 3.19
CUA-36HVR1 OUTDOOR CONDITIONS 7ºC D 4ºC D 0ºC D 6ºC W 3ºC W -1ºC W 13.12 11.82 11.15 3.89 3.68 3.45 12.32 11.12 10.49 3.61 3.47 3.26 11.55 10.25 9.7 3.25 3.1 3.0 10.51 9.45 8.94 3.04 2.88 2.78 9.13 8.22 7.74 2.65 2.5 2.35
-5ºC D -6ºC W 9.81 3.39 9.21 3.19 8.54 2.96 7.88 2.71 6.86 2.35
-7ºC D -8ºC W 9.19 3.07 8.63 2.85 8.02 2.66 7.35 2.41 6.39 2.09
6.5 CUA-24HVR1 MODEL HEATING Indoor Conditions Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
15ºC 18ºC 20ºC 22ºC 27ºC
24ºC D 18ºC W 13.68 4.65 12.85 4.34 11.89 3.95 10.95 3.64 9.51 3.14
6.6 CUA-36HVR1 MODEL HEATING Indoor Conditions Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW. Capacity kW Input kW.
15ºC 18ºC 20ºC 22ºC 27ºC
63
24ºC D 18ºC W 19.64 5.88 18.49 5.51 17.12 5.1 15.75 4.68 13.66 4.02
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7 Electric Characteristics Model CUA-18HVR1 CUA-24HVR1 CUA-36HVR1
64
Hz 50 50 50
Indoor Units Voltage Min. 220-240V 198 220-240V 198 220-240V 198
Max. 254 254 254
Indoor Fan Motor kW 0.12 0.12 0.12
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8. Exploded View 8.1 CUA-18HVR1 CUA-24HVR1 CUA-36HVR1
65
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual No.
Part Name
Quantity
No.
Part Name
Quantity
1
Rear cover with cotton
1
17
Supporting board for motor
1
2
Chassis assembly
1
18
Weld assembly for intermediate transverse girder
1
3
Electric box cover
1
19
Right mounting plate of evaporator
1
4
E-part box mat
1
20
Right cover
1
5
Indoor PCB assembly
1
21
Right sealplate
1
5.1
E-part box
1
22
Right separating board
1
5.2
Indoor PCB
1
23
Evaporator component
1
5.3
Relay
1
23.1
Left mounting plate of evaporator
1
5.4
plastic base of Electric control board
1
23.2
Shunt capillary assembly
1
5.5
Terminal
1
23.3
Air inlet header pipe assembly of evaporator
1
6
Left sealplate
1
23.4
Evaporator assembly
1
7
Left cover
1
24
Air-out frame component
1
8
Left hoisting pate
1
24.1
Fixing board assembly for air-out frame
1
9
Lelf separating board Ⅰ
1
24.2
Display film
1
10
Motor holder
1
24.3
Display lamp panel
1
11
Wheel volute
3
24.4
Vertical step motor
1
12
Indoor fan motor
1
24.5
Horizontal step motor
1
13
Connecting shaft
1
24.6
Endbearing of louver
2
14
Air inlet grille
2
24.7
Intermediate bearing of louver
8
15
Top Cover assembly
1
24.8
Guard vane
10
16
Weld assembly of Water drain pan
1
25
Upper horizontal louver
1
16.1
Water outlet rubber cover
1
26
Down horizontal louver
1
66
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
9 Accessories
Name
Shape
Quantity
Installation fittings 1.Hanging arm
2
2. Remote controller
1
3. Remote controller holder (optional)
1
5. Mounting screw (ST2.9×10-C-H)
2
6. Alkaline dry batteries (AM4)
2
7. Installation & operation instruction manual
1
Controller
Others
67
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
10 The Specification of Power Model
18kBtu/h
24kBtu/h
Indoor power supply
V/Ph/Hz
220~240/1/50
Outdoor power supply
V/Ph/Hz
220~240/1/50
Power wiring
mm
2
3×2.5
3×2.5
Power supply individually for indoor and outdoor 3×1.5/3×4.0
Signal wiring
mm
2
4×2.5
4×2.5
3×1.0
Outdoor Power Supply Connection wiring
68
36kBtu/h
From indoor unit
From indoor unit
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
11 Field Wiring
69
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
12 Troubleshooting Fault code Table
70
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Part 3 Outdoor Units
1.Specification ..................................................................................... 72 2.Dimensions ....................................................................................... 74 3.Service Space .................................................................................. 76 4.Wiring Diagrams ............................................................................... 77 5.Electric Characteristics ..................................................................... 79 6.Operation Limits ............................................................................... 80 7.Sound Levels .................................................................................... 81 8.Exploded View .................................................................................. 82 9.Troubleshooting ................................................................................ 89
71
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Outdoor Unit
1 Specification Model
COU-18HDR1
COU-24HDR1
COU-36HDR1
V/Ph/Hz
220~240/1/50
220~240/1/50
220~240/1/50
KW
2.0-5.3-5.6
4.5-7.0-8.0
7.35-10.5-12.8
Power input
W
330-1750
540-2940
950-4560
Current input
A
1.2-7.2
2.2-12.7
3.5-24
KW
3.0-5.3-6.0
4.5-7.0-8.5
7.35-10.5-13.2
Power input
W
550-1550
1440-2540
1000-4050
Current input
A
5.2-10.7 TNB220FFEM C DC/ROTARY
3.7-17.8 MNB36FAAMC
Type
2.4-7.0 DA131S1B-28F Z DC/ROTARY
Brand
GMCC
Mitsubishi
Mitsubishi
Outdoor power supply Capacity Cooling
Capacity Heating
Model
Compressor
Outdoor fan motor
Frequency range
Hz
12-120
20-220
30-360
Capacity
W
3925
6940
11900
Input
W
1005
2150
3580
Current(RLA)
A
7.1
8.7
13.6
Refrigerant oil
ml
450
520
1400
Model
DR-310-50-8
DR-310-72-8
DR-380-100-8
Brand
Panasonic
Panasonic
Panasonic
W
50
72
100
r/min
800
800
800
Insulation class
E
E
E
Number of rows Tube pitch(a)xrow pitch(b) Fin spacing
2
2
2
mm
22×19.05
25×21.65
22×19.05
mm
1.6
1.8
1.6
Hydrophilic
Hydrophilic
Hydrophilic
7.94
9.52
7.94
inner grooved
inner grooved
623×660×38.1
626×800×43.3
4
4
inner grooved 610×1280× 38.1 10
Power output Speed
Outdoor coil
DC/ROTARY
Fin type Tube outside dia. and type Coil length x height x width Number of circuits
mm mm
Outdoor air flow(High speed)
m /h
3
4000
5000
7000
Outdoor noise level
dB(A)
63
67
68
Dimension(W*H*D)
mm
930×370×700
911×400×1335
Packing(W*H*D)
mm
990×410×770
Net/Gross weight
kg
45/49
960×390×835 1025×430×88 0 59/69
g
R410A/1800
R410A/2400
R410A/4400
EXV
EXV
EXV
4.4/1.1
4.4/1.1
4.4/1.1
Outdoor unit
Refrigerant type/quantity Throttle part Design pressure 72
MPa
964×402×1445 96/101
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Max pressure Connection wire
Refrigerant piping
Ambient temp Stuffing Quantity
73
MPa
3.8
3.8
3.8
mm
2
3×2.5
3×2.5
3×1.5/3×4.0
Signal wiring
mm
2
4×2.5
4×2.5
3×1.0
Liquid side/Gas side
mm
φ6.35/φ12.7
Φ9.52/Φ15.88
Φ9.52/Φ15.88
Max. pipe length
m
15
20
20
Max. high drop
m
8
10
10
cooling
°C
-5~50
-5~50
-5~50
heating
°C 20'/40'/40'H Q
-15~30
-15~30
-15~30
100/200/208
70/140/144
32/64/64
Power wiring
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2 Dimensions 1.1 COU-18HDR1
2.2 COU-24HDR1
74
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1335
2.3 COU-36HDR1
400 360
400
585 911
75
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3 Service Space >30cm
Air inlet
>30cm
Obstacle >50cm
(Wall or obstacle)
Fix with bolt
Air inlet
Maintain channel >150cm
>60cm
Air outlet
Deep foundation Necessary width
300mm is necessary between 2 outdoor units
300mm
M10 bolt 4pieces per unit
76
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4 Wiring Diagrams 4.1 COU-18HDR1 COU-24HDR1 (Power supply from indoor unit) ELECTRICAL WIRING DIAGRAM Current Mutual
BK
inductor BK
RD
PFC Ctrl
S
N
INDOOR COMM
1 2
SW4
ON
SW5
J2
CHECK
SW1 SW2
COOL
1 2
LP HP
P-OUT
Trans In
Relay1
CN26
HEAT1 4-WAY Relay1
YE/GN
4-WAY
N
SW3
1 2
T5 ON
BR
DOWN-DC FAN
YE/GN
SW3
SW4
YE/GN
N-OUT
Reactor
SW5
BK
N'
DC FAN
Factory default
RD
1 2
1 2
1 2
E
Filter P'
BL
N P
BK BK RD
Caution 1: The Current Mutual inductor must be through with power cord.
77
GD Chigo Heating & Ventilation Equipment Co., Ltd.
Power supply Connect to Indoor
INV Comp.
UP-DC FAN
5 BL
WV U
T4 T3
2
BR
T1
6
DC+
E3 CN6
BL
I-CHECK
CPU
DC-
IC6
BK RD
L-IN
2
Exhaust Ambient temp. Condensing temp. temp.
RD YE
P+
NN-
6
CAP
E2
P+
N-
BR
P+
BL
CAP
E1
-N P+ W V U
ON
BL
CAP
T1
L-OUT 2
6
YE
YE
IPM COMM
4 DISPLAY
RY1
-15V +15V
Trans Out
P-IN
DC-2 AC-1
BL
P-BL
2
N-IN
Hi.Prss Lo.Prss swicth. swicth.
N-OUT P-L
RD
YE/GN
C
P-OUT
Bridge
2
B
BR
BL
DC-1
C11
N-IN
BR
A
Relay
AC-2
VGND
BL
N
YE
R410A50Hz Universal Outdoor Series Technical Manual
4.2 COU-36HDR1 (Power supply independently)
BK
78
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
5 Electric Characteristics Outdoor Unit Model
79
Hz
254
Min.
Max.
Outdoor motor (kw)
COU-18HDR1
50
254
198
254
0.050
COU-24HDR1
50
254
198
254
0.072
COU-36HDR1
50
418V
198
254
0.100
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
6 Operation Limits Operation mode
Outdoor temperature(℃)
Room temperature(℃)
Cooling operation
-5~50
16~32
Heating operation
-15~30
16~32
80
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
7. Sound Levels 18kBtu/h-24kBtu/h
36kBtu/h
Outdoor Unit
Microphone
H
1.0m
Note: H= 0.5 × height of outdoor unit
81
Note: The point A is in the middle of the whole outdoor panel.
Model
Noise level dB(A)
COU-18HDR1
63
COU-24HDR1
67
COU-36HDR1
68
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8. Exploded View 8.1 COU-18HDR1
82
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Part Name
Quantity
No.
Part Name
Quantit y
Cover plate assay
1
10
Maintenance board
1
1.1
cover
1
11
Chassis assy
1
1.2
Specifications sponge
1
12
4-Ways valve assy
1
Electronic control components
1
13
Compressor
1
2.1
E-box welded components
1
14
Throttle part
1
2.2
Cover for E-parts
1
14. 1
Electric expansive valve (EEV)
1
2.3
Capacitor plates
1
14. 2
Control wire for EEV
1
2.4
Current transformer
1
15
Plastic front nets
1
2.5
Electric control
1
16
Front clapboard
1
3
Amorphous PFC inductor
1
17
Left clapboard
1
4
Middle separating board
1
18
Small handle
1
5
Right side board
1
19
Condenser assy
1
6
Large handle
1
20
Holder for fan motor assy
1
7
cut-off valve C
1
21
Uniaxial fan DC motor
1
8
cut-off valve C
1
22
Propeller fan
1
9
Valve holder
1
No 1
2
83
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8.2 COU-24HDR1
84
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual No.
Part Name
Quantity
Part Name
Quantity
Cover attached cotton assay
1
14
Inverter compressor
1
1.1
Cover
1
15
Separating board
1
1.2
Specifications sponge
1
16
Discharge pipe assy
1
2
Back frame
1
16.1
Discharge pipe
1
3
Left clapboard
1
16.2
Probe of copper pipe
1
4
Condenser welding assy
1
17
4-Ways valve assy
1
4.1
Condenser
1
17.1
4-Ways valve
1
4.2
Collector welding components
1
17.2
4-Ways valve connecting pipe
1
4.3
Distributing capillary assy
1
17.3
4-Ways valve connecting pipe
1
4.4
EEV welding assy
1
17.4
Length of straight pipe
1
5
Front top net
1
18
Big handle
1
6
Front panel
1
19
connecting pipe of 4-Ways valve
1
7
Holder for fan motor
1
20
Suction pipe
1
8
Propeller fan
1
21
E-parts assy
1
9
Holder for fan motor welding assy
1
21.1
Heatsink
1
10
Maintenance panel
1
21.2
fixing board for heatsink
1
11
Chassis
1
21.3
E-parts welding assy
1
12
Vapour-liquid separator
1
21.4
E-parts module board
1
13
Valve holder assy
1
21.5
Main control board
1
13.1
Valve holder
1
22
Right clapboard
1
13.2
Cut-off valve
1
23
Handle
2
13.3
Cut-off valve
1
1
85
No.
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
8.3 COU-36HDR1
86
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual No.
Part Name
Quantity
Part Name
Quantity
Condenser
1
16.3
Oil return pipe filter
1
1.1
Condenser assy
1
16.4
Transition pipe
1
1.2
Flute shunt components
1
16.5
Connection pipe of Oil separator
1
1.3
Confluence components
1
16.6
Transition pipe
1
1.4
Cold out pipe
1
16.7
Oil return pipe capillary
1
1.5
Damping rubber
1
16.8
discharge pipe B
1
2
Top net
2
17
Valve holder
1
3
Right clapboard
1
18
Rail
1
4
Handle
3
19
Contactor
1
5
High pressure cut-off valve assy
1
20
After backplane
1
5.1
High pressure cut-off valve pipe
1
21
4-Ways valve assy
1
5.2
Cut-off valve DN8
1
21.1
4-Ways valve
1
6
Front panel
1
21.2
Filter
1
7
Separating board welding assy
2
21.3
High-pressure switch
1
7.1
Separating board
1
21.4
cut-off valve DN13
1
7.2
Winding card
1
21.5
Length of straight pipe
2
8
Chassis assy
1
21.6
4-Ways valve connecting pipe A
1
8.1
Foot
2
21.7
4-Ways valve connecting pipe C
1
8.2
Chassis
1
21.8
4-Ways valve connecting pipe D
1
8.3
Unit foot bolt
3
21.9
4-Ways valve connecting pipe E
1
9
Inverter compressor
1
22
Column
1
10
EXV assy
1
23
Cover attached cotton assay
1
10.1
Transition pipe
1
23.1
Cover board
1
10.2
Length of straight pipe
1
23.2
Specifications cotton
1
10.3
Capillary
1
23.3
Specifications sponge
1
10.4
filter
1
24
E-parts assy
1
10.5
EXV
1
24.1
E-parts welding assy
1
10.6
Oil return pipe filter
1
24.2
Flap welding assy
1
Suction pipe assy
1
24.3
Heatsink cover
1
11.1
Suction pipe A
1
24.4
Capacitor clamp
1
11.2
Suction pipe B
1
24.5
E-parts heat sink
1
11.3
Low-pressure swicth
1
24.6
Main control board
1
12
discharge pipe assy
1
24.7
PFC board
1
12.1
discharge pipe
1
24.8
IPM module board
1
12.2
Probe of copper pipe
1
25
Holder for fan motor connect board
1
1
11
87
No.
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual 13
Vapour-liquid separator
1
26
Holder for fan motor assy
1
14
Rear side of the valve panel
1
26.1
Propeller fan
2
15
The right side of the valve panel
1
26.2
Holder for fan motor welding assy
1
16
Oil separator assy
1
26.3
fixing board for fan welding assy
1
16.1
Oil separator
1
26.4
Fan motor
2
16.2
Connection pipe
1
88
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
9 Troubleshooting 9.1 Fault display
89
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
9.2 Parameter table for spot inspection of outdoor unit
90
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Part 4 Installation
1.Precaution on Installation ..................................................................92 2.Vacuum Dry and Leakage Checking .................................................93 3.Additional Refrigerant Charge ...........................................................95 4.Water Drainage .................................................................................96 5.Insulation Work ..................................................................................99 6.Test Operation .................................................................................101
91
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1. Precaution on Installation 1.1. Measure the necessary length of the connecting pipe, and make it by the following way. a. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. CAUTIONS:
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds With hands before fasten the flare nuts. Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Φ6.4
15~16N.m (153~163 kgf.cm) 25~26N.m (255~265kgf.cm) 35~36N.m (357~367kgf.cm) 45~47N.m (459~480 kgf.cm) 65~67N.m (663~684kgf.cm)
Φ9.5 Φ12.7 Φ15.9 Φ19.1 b.
c.
Flare dimension A Min (mm) Max 8.3
8.7
12.0
12.4
15.4
15.8
18.6
19.1
22.9
23.3
Flare shape
The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
1.2. Locate The Pipe a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover. b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation. c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing. 1.3. Connect the pipes. 1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow. 1.5. Be sure of no leakage by checking it with leak detector or soap water. 1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
92
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2 Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100℃. Use vacuum pump to make the pressure in the pipe near vacuum state, the boiling point of water falls relatively. When it falls under outdoor temperature, the moisture in the pipe will be vaporized.
2.2 Vacuum dry procedure There are two methods of vacuum dry due to different construction environment: common vacuum dry, special vacuum dry. ①. Common vacuum dry procedure Vacuum dry (for the first time)---connect the all-purpose detector to the inlet of liquid pipe and gas pipe, and run the vacuum pump more than two hours (the vacuum pump should be below -755mmHg) If the pump can’t achieve below -755mmHg after pumping 2 hours, moisture or leakage point will still exist in the pipe. At this time, it should be pumped 1 hour more. If the pump can’t achieve -755mmHg after pumping 3 hours, please check if there are some leakage points. Vacuum placement test: place 1 hour when it achieves -755mmHg, pass if the vacuum watch shows no rising. If it rises, it shows there’s moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure.
93
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
②. Special vacuum dry procedure This vacuum dry method is used in the following conditions: There’s moisture when flushing the refrigerant pipe. Rainwater may enter into the pipe. Vacuum dry for the first time ······2h pumping ③. Vacuum destroy for the second time ······Fill nitrogen to 0.5Kgf/cm 2 Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water. ④. Vacuum dry for the second time······1h pumping Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat procedure ③ and ④. ⑤. Vacuum placing test ······1h ⑥. Sketch map of special vacuum dry procedure
94
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
3 Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged after performing the leak test and the vacuum pumping. ● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. ● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. ● Refrigerant containers shall be opened slowly. ● Always use protective gloves and protect your eyes when charging refrigerant. The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit R(g)
D(mm)
L(m) Less than 5m (One-way) Added Refrigerant When Over 5m(One-way)
φ6.4
Φ9.5
Φ12.7
—
—
—
30g/m×(L-5)
65g/m×(L-5)
120g/m×(L-5)
Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping
95
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4 Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop stand.
Hard PVC pipe
Diameter
Distance between the prop stands
25~40mm
1~1.5m
4.1.3. Precautions ① The diameter of drainpipe should meet the drainage requirement at least. ② The drainpipe should be heat-insulated to prevent atomization. ③ Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the drain pump can operate correctly. ④ All connection should be firm. ⑤ Wipe color on PVC pipe to note connection. ⑥ Climbing, horizontal and bending conditions are prohibited. ⑦ The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. ⑧ Heat-insulation should be done well to prevent condensation. ⑨ Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap 4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning.
96
50cm 50cm
P l u g
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4.3 Upwards drainage (drain pump) For Four-way cassette(compact)
For Four-way cassette
4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
4.4.3. Selecting the diameter Number of connecting indoor units → Calculate drainage volume → Select the diameter Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) Allowed volume(lean 1/50) (l/ hr) I.D. (mm) Thick Hard PVC ∽≤14 ¢25 3.0 集中排水管 Hard PVC 14<∽≤88 ¢30 3.5 Hard PVC 88<∽≤334 ¢40 4.0 Hard PVC 175<∽≤334 ¢50 4.5 Hard PVC 334<∽ ¢80 6.0
97
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
4.5 Drainage test 4.5.1Drainage without drain pump After finishing drainpipe installation, pour some water into the water receiver plate to check if the water flows smoothly. 4.5.2 Drainage with drain pump ① Poke the Water Level Switch, remove the cover, use water pipe to pour 2000ml water into the water receipt plate through the water inlet.
② Turn on the power to Cooling operation. Check the pump’s operation and switch on the Water Level Switch. Check the pump’s sound and look into the transparent hard pipe in the outlet at the same time to check if the water can discharge normally. ③ Stop the air conditioner running, turn off the power, and put back the cover.
Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate. Keep on pouring water until it gives an alarm signal for high water level, check if the pump drains water at once. If the water level can’t fall below the alarmed water level after 3 minutes, the air conditioner will stop. Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage.
98
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
5 Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.) Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120℃) Cooling only type----Polyethylene foam (withstand above 100℃) 5.1.2. Thickness choice for insulation material Insulation material thickness is as follows:
Refrigerant pipe Drainage pipe
Pipe diameter (mm) Φ6.4—Φ25.4 Φ28.6—Φ38.1 Inner diameterΦ20—Φ32
Adiabatic material thickness 10mm 15mm 6mm
5.2 Refrigerant pipe insulation 5.2.1. Work Procedure ① Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated. ② When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat insulated 5.2.2. Insulation for non-jointing parts and non-connection parts wrong Gas pipe and liquid pipe should not be put together to insulate
99
right Insulate the gas pipe (cooling only)
Insulate the gas pipe and liquid pipe
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be welded and check the leakage after laying the pipes. 5.2.3. Insulate for the jointing area, expanding area and the flange area ① Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes ② Make sure there’s no clearance in the joining part of the accessorial insulation material and local preparative insulation material.
5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit
100
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
6. Test Operation (1) The test operation must be carried out after the entire installation has been completed. (2) Please confirm the following points before the test operation. The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded. The ground wiring is connected correctly. The length of the tubing and the added stow capacity of the refrigerant have been recorded. The power voltage fits the rated voltage of the air conditioner. There is no obstacle at the outlet and inlet of the outdoor and indoor units. The gas-side and liquid-side stop values are both opened. The air conditioner is pre-heated by turning on the power. (3) According to the user's requirement, install the remote controller when the remote controller's signal can reach the indoor unit smoothly. (4) Test operation Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points. Indoor unit Whether the switch on the remote controller works well. Whether the buttons on the remote controller works well. Whether the air flow louver moves normally. Whether the room temperature is adjusted well. Whether the indicator lights normally. Whether the temporary buttons works well. Whether the drainage is normal. Whether there is vibration or abnormal noise during operation. Outdoor unit Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked.
101
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
Control
Part 5 Controller
1.Wireless Remote Controller ............................................................ 103 2.Wire Controller ................................................................................ 106
150
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
1 Wireless Remote Controller 1.1 Jingling TB-YKQ-D02b
USE OF REMOTE CONTROLLER The controller below is the Jingling Common Remote Controller, SWING key, TURBO key, LAMP key and CLEAN key is applicable for special latest developed new models instead of normal ones.
FUNCTION KEY A. ON/OFF key: Press the key and the remote control will switch circularly in the order: ON→OFF→ON. When it is powered on at first from off state to on state, the default setting of work condition is ( The set temperature is 25℃ and the mode , wind speed, swing and air door are all automatic and there is no lamp, no turbo, no purification, no sleep, no timing and no hold function ). When it is not powered on firstly from off state to on state, the work condition is as the same as the state before stopping. It will cancel damp, purification, sleep, turbo and timing 103
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual running mode. B. MODE key: Press the key to switch modes in the order: automatic cooling →dehumidify →heating →ventilating →automatic. C. "▼" key: In dehumidifying mode and automatic mode, pressing the key cannot change the temperature. In other mode, press the key once and the temperature will decrease 1℃ in the order: 32℃→31℃→…→17℃→16℃ . D. "▲"key: In dehumidifying mode and automatic mode, pressing the key cannot change the temperature. In other mode, press the key once and the temperature will increase 1℃ in the order: 16℃→17℃→…→31℃→32℃. E. SWING key: In dehumidifying mode, the swing mode is in the stable wind mode without change. In other mode, press the key to switch modes in the order: swing → stable wind→ natural wind →swing F. AIR FLOW key: The default air flow is in the swing mode when starting firstly and press the key to switch modes in the order: swing →stop →swing. G. WIND SPEED key: The default wind speed is in the automatic wind mode when starting firstly. The remote control won’t react by pressing the key because the wind speed can’t be adjusted and in low speed in dehumidifying mode. In other mode, press the key to switch modes in the order: Automatic wind→ high speed →middle speed→ low speed →automatic wind H. TIMER key: The default mode is in no timing state, press the key to set timing time with hour as its union. The switch order is: 1H→2H→…→24H→cancel→1H…. Press the key to set timing starting in the off state and set timing stopping in the on state. After setting timing function, the time keeps decreasing per hour until the time decreasing to the timing on or timing off and the timing display will be cancelled at the same time. Pressing MODE key can’t cancel timing in timing mode which will send out the order of timing time by pressing other key. I. TURBO key: The default state for the control is no turbo and the key don’t work in the automatic mode, dehumidifying mode and ventilating mode (It will not display any contents and not send out any codes). The control, however, will 104
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual switch between on and off by pressing the key in other mode. The wind speed isn’t indicated in turbo mode and it will be cancelled for changing modes and setting sleep mode. J. SLEEP key: Press the key to switch modes in the order: sleep→ cancel sleep→ sleep. The sleep function won’t be cancelled for changing modes. Press the key to set sleep mode and the wind speed will automatically be switched to low speed and it can adjust the wind speed by pressing the WIND SPEED key (except dehumidifying mode). K. LOCK key: The default state is in no LOCK key state, press the key to select modes in order: LOCK key →cancel LOCK key→ LOCK key; In LOCK key mode, all keys except LOCK key of the remote control can’t work . (NOTE: In LOCK key mode, the remote and operation panel of the unit both will be locked automatically by pressing the key and press the key again, they will be unlocked. As for the split unit, it only holds the control rather than urgent keys and the panel will make a reaction.) L. LAMP key: The default state is in no LAMP key state, press the key to select modes in order: LAMP key →cancel LAMP key→ LAMP key; In LAMP key mode, pressing MODE key can’t cancel the show of LAMP key. M. CLEAN key: The default state is in no purification state, press the key to select modes in order: CLEAN →cancel CLEAN→ CLEAN; In purification mode, pressing CLEAN key can’t cancel purification function. Press the key when the remote control is closed, the control will switch modes in the order: CLEAN →cancel CLEAN→ CLEAN; when you stop the unit and turn on the purification switch, except the wind, the stable swing and air door swing speed aren’t adjusted.
105
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
2 Wire Controller ZKX-CMVE-05
106
GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual
107
GD Chigo Heating & Ventilation Equipment Co., Ltd.