Please read these instructions carefully as they will enable you to get maximum efficiency and reliability from your new Calorex Dehumidifier
Technical Manual DH30(7)/33(7)50(7)/55(7)/60(7) WALL HUNG DEHUMIDIFIERS (D139460 ISSUE 21) 21/12/11
HEALTH AND SAFETY WARNING As the dehumidifier embodies electrical and rotational equipment, ONLY competent persons should carry out any work on this type of machine. (See Guarantee).
Contents 1.0 INSTALLATION DETAILS ..................................................................................................................... 2 2.0 DATA SHEET ........................................................................................................................................ 5 3.0 WIRING DIAGRAMS ............................................................................................................................ 7 4.0 PERFORMANCE GRAPHS ................................................................................................................. 14 5.0 DIMENSIONS ..................................................................................................................................... 17 6.0 SPARE PARTS LISTS ........................................................................................................................ 25 7.0 OPTIONAL KITS ................................................................................................................................ 70 7.1 LPHW ASSEMBLIES ......................................................................................................................... 70 7.2 12V REMOTE HUMIDISTAT KIT ......................................................................................................... 71 7.3 12V REMOTE HUMIDISTAT CONNECTIONS ..................................................................................... 72 7.4 WEIR KIT ........................................................................................................................................... 73 7.5 AIR FILTER KITS ............................................................................................................................... 74 7.6 FLOOR STAND KITS ......................................................................................................................... 76 7.7 REMOVAL AND SERVICING OF DRIPTRAY ...................................................................................... 77 8.0 WARRANTY CONDITIONS ................................................................................................................. 78
page1
SD139460 ISSUE 21
1.0 INSTALLATION DETAILS LATEST EDITION REGULATIONS AND CALOREX UNITS
1,25 - 2,0M MUST BE FITTED WITH AN RCD AND BE AT LEAST 300mm FROM FLOOR
CAN BE WITHIN 1,25M BUT MUST THEN BE 2,5M ABOVE POOL SURFACE
2,0-3,5M
MUST BE FITTED WITH RCD ANY HEIGHT ACCEPTABLE
ALTHOUGH THE UNIT IS 2,5M ABOVE THE HEIGHT OF THE POOL IT IS NOT ACCESSIBLE FOR SERVICE & SO BREAKS THE NEW REGULATIONS
2,5M
1) N.B. THE RCD IS AN EARTH LEAKAGE TRIP & ALTHOUGH NOT ALWAYS REQUIRED IT IS RECOMMENDED THAT IT IS USED ON ALL INSTALLATIONS. WHEN FITTED, A 30mA RCD SHOULD BE USED. 2)THE ISOLATOR FOR THE DEHUMIDIFIER MUST COMPLY TO THE APPROPRIATE IPX REGULATION
page2
IF THE UNIT IS WITHIN 1,25M OF THE POOL HORIZONTALLY THEN IT MUST BE 2,5M ABOVE THE POOL SURFACE.
SD139460 ISSUE 21
INSTALLATION INSTRUCTIONS MODELS DH30/33/50/55/60/A/AX/ARH/AP HEALTH & SAFETY WARNING As the Heat Pump contains electrical and rotational equipment, it is recommended that ONLY competent persons carry out any work on this type of machine (see guarantee). Isolate electrically before entering machine or removing panels. 13. It is recommended that isolating valves are fitted to enable isolation of the machine in the event of service. INSTALLATION - WALL MOUNTING ALL MODELS Complete water circuit as per diagrams overleaf. 1. Remove machine from packaging and locate fixing bracket. (a) Circulating pump must be sized to take into account the design flow rate of the machine plus the water system resistance. D DH30/33 RH DH50/55/60 RH Unit Flow Rate - l/min Unit Pressure Drop - m/hd
A
8/12 1.0/2.2
12/16 1.0/2.0
.
MODELS WITH L.P.H.W. FITTED
B C 2. Locate bracket on wall in required position. Drill hole Ø 6.0mm (no. 10) by 60mm deep as shown at 'A'. Insert wall plug and screw bracket in place. 3. Set bracket level with spirit level 'D' as shown, drill through and fix it at 'B' with wall plug and screw. 4. Ensure bracket still level, tighten screws 'A' and 'B', finally drill and fix as above at position(s) 'C'. 5. Check all screws are tight. 6. Lift dehumidifier on to locating lugs on wall bracket. 7. Remove front cover as shown FIG 1.
14. Connect water circuit piping to 15mm stubs projecting from side of machine as per diagram below:15. It is recommended that isolating valves are fitted to enable isolation of the machine in the event of service. Complete water circuit as per diagrams overleaf. (a) Circulating pump must be sized to take into account the design flow rate of the machine plus the water system resistance. DH33 DH55 Unit Flow Rate - l/min Unit Pressure Drop - m/hd
5 0.7
5 0.7
WATER FLOW AS SHOWN 15mm STUBS
FIG 1
WATER FLOW AS SHOWN 15mm STUBS DH33
HINGE AND LIFT COVER AWAY
.
DH55
12v REMOTE HUMIDISTAT OR THERMOSTAT CONNECTIONS
REMOVE COVER FIXING SCREWS
16. Remove link wire from mains in terminal block marked 'Remote Control Interface'. Connect remote humidistat as shown below, ensure knob on humidistat in machine is set fully clockwise (ie maximum dehumidifcation).
8. Electrical supply to the unit must be sized according to data on serial number label paying special attention to I.E.E. regulations latest edition regarding the special conditions governing electrical supply to machines in potentially damp areas. 9. The electrical supply should be connected to the terminal block mounted on the side of the bracket supporting the compressor or on side panel for CALOTHERM versions Humidistat or Brown/red to 'live', blue/black to neutral and earth to the stud provided. Air stat (not 10. Fan mode switch (if fitted) can be set to cycle fan when humidistat senses demand but supplied) should be set to continuous to promote good air circulation and reduce Remote Control condensation. Interface Note that on models fitted with LPHW the fan(s) will start automatically whenever 250M MAX there is an air heating demand. On 'X' models fan(s) will stop during defrost cycle. 1mm SQ CABLE 11. Locate pipe from drip tray and run it away to waste. A short length of 10mm pipe is provided which should be led into a fixed waste pipe. Two pipe outlet holes 'P' MODELS WITH RESISTANCE HEATER are provided, one to rear of unit, one below the unit. 17. Connect remote air thermostat as shown above to mains in terminal block marked 'Remote Control Interface' 18. Ensure safety thermostat(s) below are set, ie push red button(s).
'RH' MODEL WITH HEAT RECLAIM TO WATER 12. Connect water circuit piping to 15mm stubs projecting from side of machine as per diagram below:-
HEAT RECOVERED
Safety thermostat press to reset (red button)
FIG 2
WATER OUT HINGE AND LIFT COVER AWAY
HEAT RECOVERED WATER IN
REMOVE COVER FIXING SCREWS Remove cover to gain access to manual reset thermostat. 19. Replace front cover, turn on electrical supply and turn humidistat towards 'max'. (Unless remote humidistat fitted , see note 16 above) unit fan will start, followed 6 minutes later by the compressor.
page3
SD139460 ISSUE 21
PLUMBING CIRCUITS HEAT RECOVERY 'RH' MODELS HEAT RECOVERY TO HOT WATER
HEAT RECOVERY TO POOL/SPA
DEHUMIDIFIED SPACE
DEHUMIDIFIER
COLD WATER FEED HOT WATER DRAIN OFF
DRAIN
DRAIN
3 P.S.I. NRV SANITISER
PUMP
CYLINDER STAT
WATER PUMP
WATER CIRCUIT COMPONENTS REQUIRED INSULATED DIRECT HOT WATER CYLINDER WATER PUMP THERMOSTAT PIPING INSULATED
FILTER
ELECTRICAL SUPPLY CIRCUITS
HOT WATER CYLINDER INSULATED
LPHW PLUMBING SCHEMATIC
INCOMING SUPPLY CAPACITY TO SUIT PUMP AND DEHUMIDIFIER
3 WAY MOTORISED VALVE CONTROLLED BY CUSTOMERS THERMOSTAT
E AUX FUSEBOARD
N DEHUMIDIFIER
L
PUMP
L
ISOLATOR TO SUIT PUMP
LPHW CONNECTIONS LOCATED ON DEHUM CABINET
FLOW BALANCE VALVE
BOILER
RADIATORS IF FITTED
FLOW METER
N
N
L WATER PUMP
SINGLE PHASE LOCAL ISOLATOR CAPACITY TO SUIT DEHUMIDIFIER
WATER PUMP IS HEAT RECOVERY ,POOL/SPA FOR OR HOT WATER APPLICATIONS ONLY
USER CHECK LIST OPERATION
MACHINE NOT RUNNING AT ALL
A normal humidistat setting (50-60% RH) is a mid way point on the knob provided. Minimum Air Temp DH 30/33/50/55/60 A = 15°C Minimum Air Temp DH 30/33/50/55/60 AX = 0°C Note :- On 'X' models fan stops during defrost. On machines with resistance heaters DH30/50/60 'P' heating control is governed by the remote mounted air thermostat , adjust to desired air temp, heater will run automatically as required. On machines with LPHW, fans will start automatically as required.
MAINTENANCE a. Ensure air inlet/outlets are kept clear and clean. Filter kits available. b. Wipe clean with damp cloth or cleaning fluid suitable for fibreglass and/or PVC Note: The Reply Paid Warranty Registration Card must be returned to ensure the correct warranty is given. If you do not find a Registration Card with your machine please contact CALOREX Service Department giving your name address and serial number of your machine. A card will then be sent to you for completion.
HEALTH & SAFETY WARNING As the Heat Pump contains electrical and rotational equipment, it is recommended that ONLY competent persons carry out any work on this type of machine (see guarantee) Isolate machine electrically before entering machine or removing panels.
CHECK THE FOLLOWING :1. Is supply switched on. 2. Is supply fuse healthy 3. Turn humidistat knob fully clockwise. 4. Check air inlet and outlet for obstructions. 5. On 'P' models reset thermostat(s) see Fig 2 6. If, after carring out the above and waiting 1 hour, the machine does not start phone for service.
MACHINE FAN ONLY RUNNING 7. Turn humidistat knob fully clockwise 8. Check air inlet and outlet for obstructions, if after 30 mins the machine has not restarted phone for service.
WATER LEAKING FROM BASE OF UNIT 9. Check connection from machine to drain for blockages and clear accordingly, Check fall is adequate. 10. Check that machine is level both vertically and horizontally. The user check list should be carried out before initiating a service call. Do not attempt to interfere with any internal control settings as these have been factory calibrated and sealed. If in doubt or if advice is required, contact Calorex Service Dept. Telephone (01621) 857171 or 856611
PLEASE LEAVE INSTRUCTIONS FOR USER
page4
SD139460 ISSUE 21
kW
kW
RESISTANCE HEATER ONLY
TOTAL HEAT TO WATER
kW
kW
kW
DEHUM' (COMP & FAN)
DEHUM & HEATER
HEATER & FAN
page5
kg
40/50
0.5
n/a
n/a
52
700
15.8
4.4
3.4
10.0
230v50hz
n/a
n/a
0.75
0.05
n/a
n/a
n/a
40/50
0.5
n/a
n/a
52
700
15.8
4.4
3.4
10.0
230v50hz
n/a
n/a
0.75
0.05
n/a
n/a
n/a
1.9
40/50
0.5
n/a
n/a
52
700
15.8
12.7
11.7
20.0
230v50hz
2.05
2.75
0.75
0.05
n/a
2.0
2.89
1.9
30.0
1.25
DH30(7)AP/AXP
45/55
1.04
1.6
10
52
700
15.8
4.4
3.4
10.0
230v50hz
n/a
n/a
0.75
0.05
1.4
n/a
n/a
0.5
30.0
1.25 2.5 2.5
1L/min=0.22gall/min
e) IP rating for all units is IP45
f) R134a Global warming potential (GWP) 1300.
f) R407c Global warming potential (GWP)1700
1m hd =1.4psi
65/80
1.64
1.5
14
54
1280
30.0
7.5
5.6
13.0
230v50hz
n/a
n/a
1.2
0.11
2.8
n/a
n/a
0.65
60.0
1mm Wg =9.8Pa
60/75
0.8 AXP
0.75 AP
n/a
n/a
54
1280
30.0
24.2
22.3
32.0
230v50hz
4.11
5.2
1.2
0.11
n/a
4.0
5.55
3.5
60.0
d) Maximum operating conditions for AP versions air temp 32ºC and 62% RH
60/75
0.8
n/a
n/a
54
1280
30.0
7.5
5.6
13.0
230v50hz
n/a
n/a
1.2
0.11
n/a
n/a
n/a
3.5
60.0
2.5
70/78
0.8
R134a
n/a
n/a
55
1750
30.0
23.0
22.2
33.0
230v50hz
4.18
5.1
1.1
0.16
n/a
4.0
6.0
2.2
50
2.1
DH50(7)/60(7)AX DH50(7)/60(7)AP/AXP DH50(7)/60(7)ARH *DH60AHP
d) Maximum operating conditions air temp 35ºC and 90% RH
c) Minimum air temperature on standard models 15°C and 0°C on defrost 'X' models
b) Humidistat adjustable from 20% to 80%
*a) These performance figures are based on air @ 36ºC, 60% RH
60/75
0.75
n/a
n/a
54
1280
30.0
7.5
5.6
13.0
230v50hz
n/a
n/a
1.2
0.11
n/a
n/a
n/a
3.5
60.0
2.5
DH30(7)ARH DH50(7)/60(7)A
a) These performance figures are based on air @ 30ºC, 60% RH & poolwater @ 28ºC and boiler water @ 80ºC
WEIGHT UNPACKED/PACKED
kg R407c
m hd
REFRIGERANT CHARGE
PRESSURE DROP
m3/h
AIR FLOW
dB/A
AMP
COMPRESSOR L.R.A.
L/min
AMP
FULL LOAD AMPS
WATER FLOW RATE
AMP
NOMINAL RUNNING AMPS
NOISE LEVEL @ 3m
AMP
FUSE
SUPPLY
kW
FAN ONLY
NOMINAL POWER CONSUMED:-
kW
DEHUM & RESISTANCE HEATER
1.9
30.0
30.0
kW
1.25
1.25
L/hr
DH30(7)A DH30(7)AX
L/day
DEHUMIDIFIER ONLY
TOTAL HEAT TO AIR:
DEHUMIDIFICATION
MODEL
2.0 DATA SHEET
SD139460 ISSUE 21
DH55(7)ARH 2.5 60.0
DH55(7)AX 2.5 60.0
DH55(7)A 2.5 60.0
DH33(7)ARH 1.25 30.0
1.25 30.0
1.25 30.0
L/day
5.4 5.0 2.8
6.5 5.0 n/a
6.5 5.0 n/a
3.4 3.0 1.4
3.9 3.0 n/a
3.9 3.0 n/a
kW kW kW
DEHUM & LPHW
LPHW ONLY
TOTAL HEAT TO WATER
page6
740 48 14 1.5 5.0 1.8 0.85 1.64
65/80
740 48 n/a n/a 5.0 1.8 0.85 0.8
60/75
740 48 n/a n/a 5.0 1.8 0.85 0.76
60/75
440 48 10 1.6 5.0 1.1 0.5 1.04
45/55
440 48 n/a n/a 5.0 1.1 0.5 0.5
40/50
440 48 n/a n/a 5.0 1.1 0.5 0.5
40/50
dB/A L/min m hd L/min m hd l kg R407c
kg
NOISE LEVEL @ 3m
WATER FLOW RATE
PRESSURE DROP
LPHW FLOW RATE
LPHW PRESSURE DROP
1m hd = 1.4psi 1L/min = 0.22 gal/min
e) Maximum operating conditions for AP versions air temp 32ºC and 62% RH
f) IP rating for all units is IP45
g) R407c Global warming potential (GWP) 1700.
1mm Wg = 9.8Pa
SEE NOTE d
e) Maximum operating conditions air temp 35ºC and 90% RH
d) Reduced LPHW output when DH operating is 1kW less on 33 model and 2KW less on 55 model
c) Minimum air temperature on standard models 15°C and 0°C on defrost 'X' models
b) Humidistat adjustable from 20% to 80%
a) These performance figures are based on air @ 30ºC, 60% RH & poolwater @ 28ºC and boiler water @ 80ºC
WEIGHT UNPACKED/PACKED
REFRIGERANT CHARGE
LPHW VOLUME
30.0
30.0
30.0
15.8
15.8
15.8
AMP m3/h
7.5
7.5
7.5
4.4
4.4
4.4
AMP
FULL LOAD AMPS
AIR FLOW
5.6
5.6
5.6
3.4
3.4
3.4
AMP
NOMINAL RUNNING AMPS
COMPRESSOR L.R.A.
13.0
13.0
13.0
10.0
10.0
10.0
AMP
FUSE
1.2 230v50hz
1.2 230v50hz
1.2 230v50hz
0.75 230v50hz
0.75 230v50hz
0.75 230v50hz
kW
DEHUM' (COMP & FAN)
SUPPLY
0.11
0.11
0.11
0.05
0.05
0.05
kW
FAN ONLY
NOMINAL POWER CONSUMED:-
0.65
3.5
3.5
0.5
1.9
1.9
kW
DH33(7)A DH33(7)AX L/hr
DEHUMIDIFIER ONLY
TOTAL HEAT TO AIR:
DEHUMIDIFICATION
MODEL
2 DATA SHEET CONT
SD139460 ISSUE 21
C L DF STAT FT
DEHUMIDI STAT SH
O/BL
CYCLE
'SCHRAK' & 'FINDER' DELETED FROM RELAY
TECASA NOTE ADDED
BUTT CONNECTOR NOTE MODIFIED
INTERCONTROL WIRING ADDED
LPHW SWITCH TERMINAL CHG'D
BUTTS USED ON TTW55 ONLY
HARD KICK CAP ADDED
RELAY NOTE CHANGED
RELAY CHANGED
VARIOUS WIRE COLOURS CHG'D
15
14
13
12
11
10
9
8
7
6
G/Y
EARTH STUD
C/N
946
955
955
962
1056
DH
1167
APPD
GSM
GSM
GSM
GSM
CJW
BJS
MDW
DH
GSM
KW
KW
1173
1167/1
1477
1643
1642
C L DF STAT FT
DEHUMIDI STAT
SH
O/BL
CYCLE
R/BL
R
DATE
28:07:97
18:05:98
29:06:96
05:11:98
25:09:03
24:05:04
17:05:07
24:07:07
28:08:07
17:06:10
10/08/11
16/09/11
K
9
7
RELAY A
B
R
DEHUMIDISTAT DEFROST THERMOSTAT LPHW THERMOSTAT FAN MODE SWITCH HIGH PRESSURE SWITCH LOW PRESSURE SWITCH DELAY TIMER RELAY COMPRESSOR MOTOR FAN MOTOR COMPRESSOR CAPACITOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER
CALOREX HEAT PUMPS LTD U.C.C.
SH FT TH S1 HP LP D K MC MV C1 C2/C3 C4 Y A T
C
4
6
D
TIMER
FAN DIAPHRAGM /WALL PANEL
BL
R/B
C1
COMP' CAP
G/Y
G/Y C4
FAN CAP C2
B
R/B
MV
HARDKICK CAP/RELAY DH75/150 & AW175/350 ONLY
GR/B GR
G/Y
TTW55 ONLY
FAN MOTOR
MV
BUTT CONNECTORS FITTED ON TTW55 DH30/33/50/55 & 60 MACHINES
TTW55/150 ONLY
FAN CAP C3
N(L2)
C3
C2
C1
FINISH
MATERIAL
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
TOLERANCE UNLESS SPECIFIED
VIOLET GREEN
V G
B
6(7)
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
GRAU
BRUAN
BLAU
SCHWARZ
FT
6 mins
A
4
K
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
GRIS
MARRON
BLEU
NOIR
1
CYCLE
DH30/33/50/55A/ARH/75/150D TTW33/55A
---
CONT'
DRG No.
1
SHT No
APPD
1 (2)
30:5:95
DATE
TH
D372750
GSM
DRAWN
(1)
2 P
(4)
SH
S1
NTS
SCALE
1
CYCLE
(SOPAC JAEGER)
TECASA
LPHW VERSION
CHANGE FOR
S1
FT
SH
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
WHITE
W
WIRING DIAGRAM
TITLE
P
RED
PINK
O R
GREY ORANGE
GR
BLUE BROWN
B BR
HP
LP
D
BLACK
C
BL
MV
MV
R
TTW55 ONLY
MC
S
L(L1)
DRG No. D372750
CONTINUOUS
IF IN DOUBT ASK
CIRCUIT DIAGRAM
C4 (IF FITTED)
HYGROSTAT HYGROSTAT THERMOSTAT DE DEGIVRAGE VEREISUNGSSCHUTZTHERMOSTAT PWW-STAT THERMOSTAT LPHW SELECTEUR DE MODE DU VENTILATEUR GEBLASESCHALTER REINITIALISATION DEFAUT HAUTE PRESSION HOCHDRUCKSCHALTER REINITIALISATION DEFAUT BASSE PRESSION NIEDERDRUCKSCHALTER TEMPORISATEUR VERZOGERUNGSRELAIS RELAIS RELAIS COMPRESSEUR KOMPRESSORMOTOR MOTEUR DU VENTILATEUR VENTILATORMOTOR CONDENSATEUR DU COMPRESSEUR KONDENSATOR KOMPRESSOR CONDENSATEUR DU VENTILATEUR KONDENSATOR VENTILATOR AUTOM. START KAPAZITOR COND./RELAI DE DEMARRAGE VANNE ELECTROMAGNETIQUE MAGNETVENTIL THERMOSTAT DE DEGIVRAGE TEMPORISE ABTAUTHERMOSTAT/-UHR TRANSFORMATOR TRANSFORMATEUR
FOR DH30/33/TTW33 CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250)
R
BR
BR
CONNECTIONS FOR DH/TTW50/55/60/75/150 AS SHOWN. (RELAY SD092151)
BR
O
CONT'
G/Y
B R/BL
P
ROCKER SWITCH S1
DRAWING CHANGE
AND LPHW DETAIL ADDED
WIRE COLOUR REFS CLARIFIED
16
ISS
RELAY SD219250 WAS SD154650
DETAIL OF WIRING CHANGE FOR LPHW VERSIONS
BR
V
R/BL
ROCKER SWITCH CONT'
BR
17
(1)
(2) (4)
LPHW STAT O 1 BR 2 V P TH
(SOPAC JAEGER)
TECASA
TERM'BLOCK
L (L1)
N (L2)
B
G/Y
R(P) BR GR
S(A)
LP SWITCH
W W
HP SWITCH
R/O R/O
FAN MOTOR
W(BL) BL
COMPRESSOR MC
B
BR
BL
WIRE FAN DIRECTLY TO COMPONENTS
W
G/Y
P
B
C
B
BR W
E (GRO)
BR
O
page7
W
R
W/BL
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY) R B
BL B
ON MACHINES EXCEPT TTW55
LABEL D380750 ISS14 CONTINUOUS
DO NOT SCALE PRINT OVERLOAD PROTECTOR
3.0 WIRING DIAGRAMS
SD139460 ISSUE 21
B
C/N
BUTTS USED ON TTW55 ONLY
HARD KICK CAP ADDED
RELAY NOTE CHANGED
RELAY CHANGED
10
9
8
DRAWING CHANGE
GSM
APPD
955
LPHW SWITCH TERMINAL CHG'D
11
7
955
INTERCONTROL WIRING ADDED
12
962
1056
1167
1173
BUTT CONNECTOR NOTE MODIFIED
13
GSM
GSM
CJW
BJS
DH
MDW
DH
1167/1
TECASA NOTE ADDED
GSM
1477
15 'SCHRAK' & 'FINDER' DELETED FROM RELAY
14
KW
KW
1642
1643
ISS
W W L
R
BR
DEHUM STAT
SH
C
BR
R
4
6
R/BL
R/O R/O
B
7 A
K RELAY
9
D
TIMER
/WALL PANEL
DIAPHRAGM
FAN
C1
B
BL
R/B
COMP' CAP
BL C4
16/09/11
DATE
18:05:98
29:06:96
05:11:98
25:09:03
24:05:04
17:05:07
24:07:07
28:08:07
17:06:10
10/09/11
R BL
R
DEHUMIDISTAT DEFROST THERMOSTAT LPHW THERMOSTAT FAN MODE SWITCH HIGH PRESSURE SWITCH LOW PRESSURE SWITCH DELAY TIMER RELAY COMPRESSOR MOTOR FAN MOTOR COMPRESSOR CAPACITOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER
CALOREX HEAT PUMPS LTD U.C.C. C
SH FT TH S1 HP LP D K MC MV C1 C2/C3 C4 Y A T
B R/BL GR
R/B
HARDKICK CAP/RELAY DH75/150 & AW175/350 ONLY
C2 FAN CAP
B
BR GR
MV
W(BL) BL
FAN MOTOR
GR/B
G/Y
TTW55/150 ONLY
MACHINES
FITTED ON TTW55/ DH30/33/50/55 & 60
BUTTS CONNECTORS
C3 FAN CAP
G/Y
FAN MOTOR MV TTW55 ONLY
N(L2)
C3
C2
C1
Y
MC
C4 (IF FITTED)
FINISH
MATERIAL
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
TOLERANCE UNLESS SPECIFIED
R
C
MV TTW55 ONLY
MV
S
DH30/33/50/55AX/75/150D TTW33/55AX
B
3
2
SH
1
CYCLE
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
GRAU
BRUAN
BLAU
SCHWARZ
6(7)
TECASA
BLEU
NOIR
TH
1 (2)
2 P
GRIS
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
---
1
DRG No.
CONT'
SHT No
APPD
D372751
GSM
DRAWN
31:5:95
DATE
1 S1
NTS
SCALE
CYCLE
SH
CHANGE FOR LPHW VERSION
(SOPAC JAEGER) (4) (1)
A
MARRON
4
1
S1
CONTINUOUS
D372751
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
GREEN
WHITE
W G
RED VIOLET
PINK
P R V
GREY
BROWN ORANGE
BR O
BLUE
B GR
BLACK
6 mins
BL
HP
LP
D
A
4
K
L(L1)
DRG No.
CIRCUIT DIAGRAM
IF IN DOUBT ASK
WIRING DIAGRAM
TITLE
HYGROSTAT HYGROSTAT VEREISUNGSSCHUTZTHERMOSTAT THERMOSTAT DE DEGIVRAGE PWW-STAT THERMOSTAT LPHW GEBLASESCHALTER SELECTEUR DE MODE DU VENTILATEUR HOCHDRUCKSCHALTER REINITIALISATION DEFAUT HAUTE PRESSION NIEDERDRUCKSCHALTER REINITIALISATION DEFAUT BASSE PRESSION VERZOGERUNGSRELAIS TEMPORISATEUR RELAIS RELAIS KOMPRESSORMOTOR COMPRESSEUR VENTILATORMOTOR MOTEUR DU VENTILATEUR KONDENSATOR KOMPRESSOR CONDENSATEUR DU COMPRESSEUR KONDENSATOR VENTILATOR CONDENSATEUR DU VENTILATEUR AUTOM. START KAPAZITOR COND./RELAI DE DEMARRAGE MAGNETVENTIL VANNE ELECTROMAGNETIQUE ABTAUTHERMOSTAT/-UHR THERMOSTAT DE DEGIVRAGE TEMPORISE TRANSFORMATOR TRANSFORMATEUR
FOR DH30/33/TTW33 CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250) R Y B DF VALVE
CONNECTIONS FOR DH/TTW50/55/60/75/150 AS SHOWN. (RELAY SD092151)
DF STAT/ TIMER
RELAY SD219250 WAS SD154650
C L SH DEHUM STAT
4
3
R
A
1
2
BL
B
CYCLE
CONT'
O
G/Y
ROCKER SWITCH S1
R(P)
WIRE COLOURS REFS CLARIFIED
2 1 3 4 A DF STAT/ TIMER
BR
G/Y
17
BL R
CYCLE O
STAT ROCKER SWITCH O S1 BR V CONT'
P
EARTH STUD
S(A)
BR
LP SWITCH
P
HP SWITCH
B
COMPRESSOR MC
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY) B
WIRE FAN DIRECTLY TO COMPONENTS
BL
ON MACHINES EXCEPT TTW55
W B
BR
C
B
16
JAEGER) ( SOPAC
TECASA
LPHW (2) 1 (4) 2 (1) P TH
DETAIL OF WIRING CHANGE FOR LPHW VERSION
L (L1)
BR
B
R
W/R
N (L2)
W/R
R/BL
E (GRO)
R/BL
W/BL
G/Y
W
page8
BR
W
G/Y
LABEL D380751 ISS14 CONTINUOUS
DO NOT SCALE PRINT OVERLOAD PROTECTOR
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
L (L1)
P
TECASA
V
BUTTS ADDED FOR TRANS' ON P.B.
HARD KICK CAP ADDED
8
7
DRAWING CHANGE
BUTTS USED ON TTW55 ONLY
9
ISS
LPHW SWITCH TERMINAL CHG'D
INTERCONTROL WIRING ADDED
11
10
TECASA NOTE ADDED
BUTT CONNECTION NOTE MODIFIED
GSM
APPD
C/N
CJW
CJW
BJS
DH
MDW
DH
GSM
KW
KW
L
R/O R
BR
R
D
TIMER
B
4
7
A
9 RELAY
6 K
C4
FAN DIAPHRAGM /WALL PANEL
HARDKICK CAP/RELAY DH75/150 & AW175/350 ONLY
DATE
05:11:98
08:11:02
25:09:03
24:05:04
17:05:07
24:07:07
28:08:07
17:06:10
10/08/11
16/09/11
R
DEHUMIDISTAT DEFROST THERMOSTAT LPHW THERMOSTAT FAN MODE SWITCH HIGH PRESSURE SWITCH LOW PRESSURE SWITCH DELAY TIMER RELAY COMPRESSOR MOTOR FAN MOTOR COMPRESSOR CAPACITOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER
CALOREX HEAT PUMPS LTD U.C.C. C
SH FT TH S1 HP LP D K MC MV C1 C2/C3 C4 Y A T
FOR DH30/33/TTW33 CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250)
CONNECTIONS FOR DH/TTW50/55/60/75/150 AS SHOWN (RELAY SD092151)
FT
C
SH
O/BL
DF STAT
O
R/BL CYCLE
G/Y
CONT'
R(P)
DEHUMIDI STAT
V
BR
962
1015
1056
1167
1173
1167/1
14
13
1477
'SCHRAK' & 'FINDER' DELETED FROM RELAYS
12
1643
WIRE COLOUR REFS CLARIFIED
1642
15
C L DF STAT FT
G/Y
RELAY SD219250 WAS SD154650
DEHUMIDI STAT SH
O/BL
CYCLE
B
ROCKER SWITCH S1
EARTH STUD
S(A)
W W
G/Y
FAN MOTOR
A
7
4
B
9
6
0
RELAY K
GR 12V COIL
GR/B
B FAN CAP C2
R/B
B
MV
TRANSFORMER T
BUTT CONNECTOR
12v
230v
TTW55/150 ONLY
MACHINES
DH30/33/50/55 & 60
BUTT CONNECTORS FITTED ON TTW55/
FAN CAP C3
G/Y
TTW55 ONLY
FAN MOTOR MV
B
C3
C2
C1
FINISH
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
MV
GREY
GREEN
G
K
4
1
A
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
GRAU
BRUAN
BLAU
SCHWARZ
FT
6 mins
B
6(7)
SH
K
BLEU
NOIR
1
FT
CYCLE
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
GRIS
MARRON
7
B
DH30/33/55A/ARH/75/150D TTW33/55A WITH REMOTE HUMIDISTAT
---
CONT'
DRG No.
1
SHT No
APPD
S1
1
LABEL D380752 ISS15 S1
NTS
SCALE
CYCLE
21:11:95
DATE
TH
1 (2)
2 P
TECASA
(SOPAC JAEGER) (4) (1)
SH
CHANGE FOR LPHW VERSION
D372752
GSM
DRAWN
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
WHITE VIOLET
V
RED W
PINK
P R
ORANGE
BROWN
BR GR O
BLUE
B
HP
LP
D
A
4
BLACK
C
BL
MV TTW55 ONLY
R
S
T
D372752
L(L1)
DRG No.
12V SIDE
CIRCUIT DIAGRAM
IF IN DOUBT ASK
WIRING DIAGRAM
MC
C4 (IF FITTED)
N(L2)
HYGROSTAT HYGROSTAT VEREISUNGSSCHUTZTHERMOSTAT THERMOSTAT DE DEGIVRAGE PWW-STAT THERMOSTAT LPHW GEBLASESCHALTER SELECTEUR DE MODE DU VENTILATEUR HOCHDRUCKSCHALTER REINITIALISATION DEFAUT HAUTE PRESSION NIEDERDRUCKSCHALTER REINITIALISATION DEFAUT BASSE PRESSION VERZOGERUNGSRELAIS TEMPORISATEUR RELAIS RELAIS KOMPRESSORMOTOR COMPRESSEUR VENTILATORMOTOR MOTEUR DU VENTILATEUR KONDENSATOR KOMPRESSOR CONDENSATEUR DU COMPRESSEUR KONDENSATOR VENTILATOR CONDENSATEUR DU VENTILATEUR AUTOM. START KAPAZITOR COND./RELAI DE DEMARRAGE MAGNETVENTIL VANNE ELECTROMAGNETIQUE ABTAUTHERMOSTAT/-UHR THERMOSTAT DE DEGIVRAGE TEMPORISE TRANSFORMATOR TRANSFORMATEUR TOLERANCE UNLESS SPECIFIED TITLE MATERIAL
V
COMP' CAP C1
P
LP SWITCH W(BL) BL
HP SWITCH
B
BL
C
BL
WIRE FAN DIRECTLY TO COMPONENTS
CONTINUOUS
ON MACHINES EXCEPT TTW55
REMOTE CONTROL INTERFACE
DO NOT SCALE PRINT
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY) R B
BR
COMPRESSOR MC
P
16
V
(SOPAC JAEGER)
R/BL
ROCKER SWITCH CONT'
DETAIL OF WIRING CHANGE FOR LPHW VERSIONS
LPHW STAT O (2) 1 BR (4) 2 V (1) P
TH
P
O
BR
B
G/Y
FIT WIRE LINK WHEN REMOTE NOT USED
BR
W/BL
N (L2)
O
R/O BR
E (GRO)
R
R/B
W B
TERM'BLOCK
W
BL P
BR BR
G/Y P
W
BR GR B
R/BL BR P
page9 O
REMOTE CONTROL INTERFACE
CONTINUOUS
OVERLOAD PROTECTOR
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
L (L1)
N (L2)
1 4
1477
1167/1
DRAWING CHANGE
9
C/N
1167
INTERCONTROL WIRING ADDED
LPHW SWITCH TERMINAL CHG'D
10
ISS
1173
11
TECASA NOTE ADDED
13 'SCHRAK' & 'FINDER' DELETED FROM RELAY
12
1642
1643
RELAY SD219259 WAS SD154650
C L SH DEHUM STAT
WIRE COLOUR REFS CLARIFIED
A DF STAT/ TIMER
2 3
O
KW
APPD
BJS
DH
MDW
DH
GSM
KW
R/BL
BR
W L
W SH
DEHUMIDI STAT
C V R
BR
R
BR
D
4
RELAY
6
R/O TIMER
7 A
K
9 B
FAN DIAPHRAGM /WALL PANEL
G/Y
C4
DATE
24:05:04
17:05:07
24:07:07
28:08:07
17:06:10
10/08/11
16/09/11
DF VALVE Y
R
DEHUMIDISTAT DEFROST THERMOSTAT LPHW THERMOSTAT FAN MODE SWITCH HIGH PRESSURE SWITCH LOW PRESSURE SWITCH DELAY TIMER RELAY COMPRESSOR MOTOR FAN MOTOR COMPRESSOR CAPACITOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER
CALOREX HEAT PUMPS LTD U.C.C. C
SH FT TH S1 HP LP D K MC MV C1 C2/C3 C4 Y A T
COMP' CAP C1
P
LP SWITCH
R/O
FOR DH30/33/TTW33 CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250)
CONNECTIONS FOR DH/TTW50/55/60/75/150 AS SHOWN (RELAY SD092151)
4
DF STAT/ TIMER A
1
3
O
2
15
BL R
B
CYCLE
G/Y
R
14
(SOPAC JAEGER)
TECASA
R(P)
BL
B
CYCLE
P
S1
CONT'
LPHW STAT O ROCKER SWITCH (2) 1 S1 BR BR (4) 2 V (1) P CONT' TH
B
ROCKER SWITCH
EARTH STUD
P
W
O
BR
B
DETAIL OF WIRING CHANGE FOR LPHW VERSION
FIT WIRE LINK WHEN REMOTE NOT FITTED
REMOTE CONTROL INTERFACE
S(A)
W/R
V
GR/B
BL
FAN MOTOR
A
9
0
B
R/B
12v
230v
BUTT CONNECTORS FITTED ON TTW55/ DH30/33/50/55 & 60 MACHINES
BUTT CONNECTOR
TRANSFORMER T
TTW55/150 ONLY
FAN CAP C3
G/Y
TTW55 ONLY
FAN MOTOR MV
C4
C1
C3
C2
(IF FITTED)
N(L2)
FINISH
MATERIAL
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
TOLERANCE UNLESS SPECIFIED
MC
MV TTW55 ONLY
MV
HP
LP
D
R
S
6 mins
C
VIOLET GREEN
V G
DH30/33/50/55AX/75/150 TTW33/55AX WITH REMOTE HUMIDISTAT
K
SH
4
1
A
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
GRAU
BRUAN
BLAU
SCHWARZ
1
CYCLE
3
2
7
B
4
1
D372753
(1)
BLEU
NOIR
TH
1 (2)
2 P
(4)
GRIS
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
---
CONT'
GSM
DRAWN
APPD
DATE 22:11:95
DRG No. D372753
1
SHT No
1 S1
NTS
SCALE
CYCLE
(SOPAC JAEGER)
TECASA
SH
CHANGE FOR LPHW VERSION
MARRON
A
S1
CONTINUOUS
L(L1)
DRG No. REMOTE CONTROL INTERFACE
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
RED
PINK WHITE
P R W
GREY ORANGE
BROWN
BR O
BLUE
B GR
BLACK
B
6(7)
T
12V SIDE
BL
Y
A
4
K
CIRCUIT DIAGRAM
WIRING DIAGRAM
TITLE
HYGROSTAT HYGROSTAT VEREISUNGSSCHUTZTHERMOSTAT THERMOSTAT DE DEGIVRAGE PWW-STAT THERMOSTAT LPHW GEBLASESCHALTER SELECTEUR DE MODE DU VENTILATEUR HOCHDRUCKSCHALTER REINITIALISATION DEFAUT HAUTE PRESSION NIEDERDRUCKSCHALTER REINITIALISATION DEFAUT BASSE PRESSION VERZOGERUNGSRELAIS TEMPORISATEUR RELAIS RELAIS KOMPRESSORMOTOR COMPRESSEUR VENTILATORMOTOR MOTEUR DU VENTILATEUR KONDENSATOR KOMPRESSOR CONDENSATEUR DU COMPRESSEUR KONDENSATOR VENTILATOR CONDENSATEUR DU VENTILATEUR AUTOM. START KAPAZITOR COND./RELAI DE DEMARRAGE MAGNETVENTIL VANNE ELECTROMAGNETIQUE ABTAUTHERMOSTAT/-UHR THERMOSTAT DE DEGIVRAGE TEMPORISE TRANSFORMATOR TRANSFORMATEUR
7
6
RELAY K 12V COIL 4
B FAN CAP C2
BR B
MV
WIRE FAN DIRECTLY TO COMPONENTS
ON DH50/55/60 MSCHINES
W(BL) BL
HP SWITCH
B
B
IF IN DOUBT ASK
BR
BR
C
W B
BL
COMPRESSOR MC
B
O
G/Y
W/R
W/BL
E (GRO)
G/Y
R/BL
R/B
W
TERM'BLOCK
R
R
HARDKICK CAP/RELAY DH75/150 & AW175/350 ONLY
BL
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY) R BL P
B BR
G/Y GR P
R/BL BR P
GR B B O
page10
V
LABEL D380753 ISS15 CONTINUOUS
OVERLOAD PROTECTOR
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
L (L1)
N (L2)
'SCHRACK' & 'FINDER' DELETED FROM RELAY
10
ISS
DRAWING CHANGE
GSM
APPD
C/N
GSM
955
5
946
GSM
955
RELAY NOTE CHANGED
RELAY & WIRING CHANGES
6
4 VARIOUS WIRE COLOURS CHANGED
CJW
CJW
GSM
MDW
1477
1643
1173
KW
KW
1642
1056
R
9 B RELAY 7 A
K 4
W/BL
6
C L DF STAT FT
16/09/11
DATE
1:8:97
9:6:98
29:6:98
08:11:02
25:09:03
24:07:07
17:06:10
10/08/11
3 6
4
C1
COMP' CAP
0
GR/B
12v
230v
R
FINISH
MATERIAL
DEHUMIDISTAT DEFROST THERMOSTAT LPHW THERMOSTAT FAN MODE SWITCH HIGH PRESSURE SWITCH LOW PRESSURE SWITCH DELAY TIMER RELAY COMPRESSOR MOTOR FAN MOTOR COMPRESSOR CAPACITOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER RESISTANCE HEATER THERMAL CUTOUT
7 9 12V COIL B RELAY A K
SH FT TH S1 HP LP D K MC MV C1 C2/C3 C4 Y A T RH TC
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY)
DIAPHRAGM
FAN
G/Y
MV
FAN MOTOR
G/Y
MACHINES
DH30/50 & 60AP
FITTED ON TTW50AP/
C3
C2
C1
RH
MC
DH50 ONLY
DH30/50
N(L2)
BUTT CONNECTORS
TTW50AP ONLY
FAN CAP C3
TTW50AP ONLY
FAN MOTOR MV
MV
MV
TC
TC
C
ONLY
TTW50AP
R
S
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
IF IN DOUBT ASK
DH30/50AP TTW50AP RESISTANCE HEATERS
WIRING DIAGRAM
GREEN
G
GRUN
VIOLETT
WEIß
ROT
ROSA
NOIR
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
GRIS
MARRON
BLEU
LABEL D380754 ISS12 ---
DRG No.
1
CONT'
APPD
DATE 23:11:95
D372754
GSM
DRAWN
NTS
SCALE
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
WHITE VIOLET
V
RED W
PINK
P R
ORANGE
GRAU
BRUAN GREY
BROWN ORANGE
BR O
BLUE GR
BLAU
BLACK
SCHWARZ
S1
CONT'
SH
B
A
B
1
9
3 6
CYCLE
1 4
7
K
12V SIDE
T
D372754
L(L1)
DRG No.
BL
FT
6 mins
B
6(7)
SHT No
HP
LP
D
A
4
K
CIRCUIT DIAGRAM
HYGROSTAT HYGROSTAT VEREISUNGSSCHUTZTHERMOSTAT THERMOSTAT DE DEGIVRAGE SELECTEUR DE MODE DU VENTILATEUR PWW-STAT GEBLASESCHALTER THERMOSTAT LPHW HOCHDRUCKSCHALTER REINITIALISATION DEFAUT HAUTE PRESSION NIEDERDRUCKSCHALTER REINITIALISATION DEFAUT BASSE PRESSION VERZOGERUNGSRELAIS TEMPORISATEUR RELAIS RELAIS KOMPRESSORMOTOR COMPRESSEUR VENTILATORMOTOR MOTEUR DU VENTILATEUR KONDENSATOR KOMPRESSOR CONDENSATEUR DU COMPRESSEUR KONDENSATOR VENTILATOR CONDENSATEUR DU VENTILATEUR AUTOM. START KAPAZITOR COND./RELAI DE DEMARRAGE MAGNETVENTIL VANNE ELECTROMAGNETIQUE ABTAUTHERMOSTAT/-UHR THERMOSTAT DE DEGIVRAGE TEMPORISE TRANSFORMATOR TRANSFORMATEUR ELEKTROHEIZUNG RESISTANCE DE CHAUFFAGE UBERHITZUNGSSCHUTZ PROTECTION THERMIQUE TOLERANCE UNLESS SPECIFIED TOLERANCE UNLESS SPECIFIED TITLE
BUTT CONNECTOR
TRANSFORMER T
FAN CAP C2
B
G/Y
FAN DIRECTLY TO COMPONENTS
BR GR
DH30/50
1
CALOREX HEAT PUMPS LTD U.C.C. C
D
TIMER
FOR DH30AP CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250)
7 BUTTS ADDED FOR P,BR,B ON TRANSFORMER 1015
THERMAL CUTOUTS SHOWN FOR DH50AXP
8 BUTTS FOR FAN CONNS USED ON TTW50AP ONLY 2ND FAN MOTOR & C3 ADDED FOR TTW50AP
9 BUTT CONNECTOR NOTE MODIFIED
RELAY SD219250 WAS SD154650
WIRE COLOUR REFS CLARIFIED
G/Y
11
BR
BR
DEHUMIDI STAT SH
O/BL
CONNECTIONS FOR DH50AP AS SHOWN (RELAY SD092151)
BR
O CYCLE
R/BL
ROCKER SWITCH CONT' BR
WHITE SILICON (2.5)
EARTH STUD
P
12
P
O
BR BR 2,5
B
G/Y
B
BR
E (GRO)
O/BL
TERM'BLOCK
REMOTE CONTROL INTERFACE
W
G/Y
R R/O R/O
R(P)
W
S(A) WHITE SILICON (2.5) P
LP SWITCH
P
HP SWITCH
BL
W BL
COMPRESSOR MC
R/B
B
ON MACHINES EXCEPT TTW50AP WIRE
B
MANUAL RESET AUTO RESET
RED SILICON (2.5) O
B
C THERMAL CUTOUTS
O/BL BR
B R/BL R/B
BL
RESISTANCE HEATERS DH50 ONLY
P
B BR BR 2,5
BL GR B
W W
BR
DO NOT SCALE PRINT
B
R BR P
page11 O
R
REMOTE CONTROL INTERFACE
OVERLOAD PROTECTOR
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
BUTT CONNECTOR NOTE MODIFIED
BUTTS FOR FAN CONNS USED ON TTW50AXP ONLY. 2ND FAN & FAN CAP ADDED FOR TTW50AXP
9
8
BUTTS ADDED FOR P,B,BR ON TRANSFORMER
'SCHRACK' & 'FINDER' DELETED FROM RELAY
10
3
R
DF STAT/ TIMER A
2
B
1
4
C/N
DRAWING CHANGE
GSM
APPD
934
GSM
GSM
SYMBOLS & KEY TABLE ADDED
3
ISS
955
946
RELAY & WIRING CHANGES
VARIOUS WIRE COLOURS CHANGED
5
4
GSM
CJW
CJW
MDW
GSM
KW
KW
RELAY NOTE CHANGED
955
1015
1056
1173
1477
1643
1642
R
BR
BR 9
4
7
K RELAY
6
SH
DH STAT
BR
O CYCLE
BR
CONT'
R
A
B
W/BL
D
TIMER
DATE
3:7:96
1:8:97
10:6:98
29:6:98
08:11:02
25:09:03
24:07:07
17:06:10
10/08/11
16/09/11
RELAY K
O
W
FAN DIAPHRAGM
3 6 9 B
7 A 12v
230v
R/B
COMPRESSOR MOTOR FAN MOTOR FAN CAPACITOR HARD KICK CAP/RELAY SOLENOID VALVE DEFROST THERMOSTAT/TIMER TRANSFORMER RESISTANCE HEATER THERMAL CUTOUT
FINISH
MATERIAL
C4 Y A T RH TC
C2/C3
COMPRESSOR CAPACITOR
MV C1
MC
DELAY TIMER RELAY
LOW PRESSURE SWITCH
D K
HIGH PRESSURE SWITCH
LP
FAN MODE SWITCH
HP
LPHW THERMOSTAT
S1
DEFROST THERMOSTAT
DEHUMIDISTAT
BUTT CONNECTOR
TRANSFORMER T
FAN CAP C2
B
MV
FAN MOTOR TTW50AXP ONLY
FAN MOTOR MV
WIRE DIRECTLY TO COMPONENTS
ON MACHINES EXCEPT TTW50AXP
TH
FT
SH
0
COMP' CAP C1
4
12V COIL
R
G/Y
1
CALOREX HEAT PUMPS LTD U.C.C. C
FOR DH30AXP CONNECT BROWN WIRES TO TERM No7 (RELAY SD219250)
6
7 THERMAL CUTOUTS ADDED FOR DH50AXP
BR
ROCKER SWITCH
CONNECTIONS FOR DH50AXP AS SHOWN (RELAY SD092151)
WIRE COLOUR REFS CLARIFIED
G/Y
WHITE SILICON (2.5)
R(P)
W
LP SWITCH
R/O R/O
HP SWITCH
RED SILICON (2.5)
DH30/50
GR/B
3rd ANGLE PROJECTION
B R/BL
C
EARTH STUD
S(A)
11
G/Y
RELAY SD219250 WAS SD154650
DF VALVE
Y
P
O
BR 2.5
BR
B
G/Y
P
12
REMOTE CONTROL INTERFACE
L (L1)
N (L2)
E (GRO)
B
TERM'BLOCK
R
B
W/R
BL
BR GR
COMPRESSOR MC
W/R
W BL
R
THERMAL CUTOUTS AUTO RESET MANUAL RESET BR
W HOLES TO BS 4500 E12 INSPECTION LEVEL
R
HYGROSTAT
MV
TC
TC
C
THERMOSTAT LPHW
THERMOSTAT DE DEGIVRAGE
DH50 ONLY
RH
DH30/50
RH
MC
S
DIMS
DH30/50AXP RESISTANCE HEATERS
WIRING DIAGRAM
TITLE
COND./RELAI DE DEMARRAGE VANNE ELECTROMAGNETIQUE THERMOSTAT DE DEGIVRAGE TEMPORISE TRANSFORMATEUR RESISTANCE DE CHAUFFAGE PROTECTION THERMIQUE
CONDENSATEUR DU VENTILATEUR
CONDENSATEUR DU COMPRESSEUR
MOTEUR DU VENTILATEUR
COMPRESSEUR
RELAIS
TEMPORISATEUR
REINITIALISATION DEFAUT BASSE PRESSION
REINITIALISATION DEFAUT HAUTE PRESSION
A
4
Y
P
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
GRAU
BRUAN
BLAU
SCHWARZ
ONLY
3
2
MV TTW50AP
1
4
A
VERT
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
GRIS
MARRON
BLEU
NOIR
1
S1
---
CONT'
GSM
DRAWN
APPD
23:11:95
DATE
NTS
SCALE
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
GREEN
G
WHITE VIOLET
V
W
RED
PINK
O R
GREY ORANGE
GR
B
A
L(L1)
D372755
DRG No. D372755
1
BLUE
BLACK BROWN
SH
3 6
9
CYCLE CONT'
1 4
K 7
12V SIDE
T
DRG No.
BR
B
BL
C3
6 mins
SHT No
HP
B
6(7)
LP
D
K
CIRCUIT DIAGRAM
IF IN DOUBT ASK
SELECTEUR DE MODE DU VENTILATEUR
C2
TOLERANCE UNLESS SPECIFIED
AUTOM. START KAPAZITOR MAGNETVENTIL ABTAUTHERMOSTAT/-UHR TRANSFORMATOR ELEKTROHEIZUNG UBERHITZUNGSSCHUTZ
KONDENSATOR VENTILATOR
KONDENSATOR KOMPRESSOR
VENTILATORMOTOR
KOMPRESSORMOTOR
RELAIS
VERZOGERUNGSRELAIS
NIEDERDRUCKSCHALTER
HOCHDRUCKSCHALTER
GEBLASESCHALTER
PWW-STAT
VEREISUNGSSCHUTZTHERMOSTAT
FAN CAP C3
HYGROSTAT
MACHINES
FITTED ON TTW50AXP/ DH30/50 & 60
C1
N(L2)
BUTT CONNECTORS
BL
DH50 ONLY
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY)
B
B
W
W
R/BL
BR
WHITE SILICON (2.5) R/B BL
P P
BL B
BL B BR 2.5
G/Y R/B
G/Y B
BR
RESISTANCE HEATER
LABEL D380755 ISS12
DO NOT SCALE PRINT
P
R GR
BR P
page12 O
REMOTE CONTROL INTERFACE
OVERLOAD PROTECTOR
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
6
5
4
P
O
BR BR
B
G/Y
G/Y
S(A) R(P)
G/Y
BUTT
APPD
C/N
DRAWING CHANGE
----
CJW
MDW
4
----
ISS
9 B
D
TIMER
DATE
09:10:02
25:09:03
24:07:07
7 A
K1 RELAY
6
3 SILICON WIRE SIZE ADDED
1173
RED
BR
W/BL
1056
+ BROWN WIRE MOVED TO TERM 7 RELAY K3 BUTT CONN. ADDED
BUTT
HP SWITCH C H
BLUE
G/Y
WHITE SILICON (2,5)
G/Y
EARTH STUD
WIRE COLOUR ON TERM 6 KI RELAY WAS BLK
REMOTE HUMIDISTAT
P
COMPRESSOR MC
R
BR
LP SWITCH
BUTT BLU
6 9 B
4 7 A
RED/BLU
P
3
1
RELAY K3 12V COIL
BLU
CALOREX HEAT PUMPS LTD U.C.C. C
R/O R/O
P
LOWER
G/Y
R
3
B
9
6
H
12V
FINISH
MATERIAL
HP PINK SWITCH
C
P
2001
A
7
4
1
RELAY K2 12V COIL
C1
COMP' CAP
MV
FAN MOTOR
GR/B
300 PSI
FAN DIAPHRAGM
BUTT
TERMINAL
WHITE FLYING LEAD
MANUAL RESET
400 PSI
BLU
BUTT
LINK RED SILICON
C
B
4 BUTTS REMOVED FOR FAN
5
L (L1)
3
2
INTERFACE
N (L2)
1
RED/BLU
O/BL
W/BL
TERM'BLOCK
R
RED SILICON (2,5)
TERMINAL
WHITE SILICON (2,5)
UPPER
THERMAL CUTOUTS
RESISTANCE HEATERS
P
OVERLOAD PROTECTOR
R/B
E (GRO)
REMOTE
BLK
W/BL
B GRN/
REMOTE THERMOSTAT
CONTROL
O/BL BR
B RED
G/Y BR BR 2,5
3rd ANGLE PROJECTION
FAN CAP C2
0
12v
230v
BL
R
PINK RED WHITE VIOLET GREEN
O P R W V G
GRAU
GRUN
VIOLETT
WEIß
ROT
ROSA
ORANGE
VERT
C2
HOLES TO BS 4500 E12 INSPECTION LEVEL
DIMS
TOLERANCE UNLESS SPECIFIED
CONDENSATEUR DU COMPRESSEUR CONDENSATEUR DU VENTILATEUR HARD KICK CAP/RELAY
C4
THERMOSTAT DE DEGIVRAGE TEMPORISE
THERMAL CUTOUT
RESISTANCE HEATER
DH60AHP (134a)
WIRING DIAGRAM
TITLE
TC
RH
PROTECTION THERMIQUE
RESISTANCE DE CHAUFFAGE
---
CONT'
DRG No.
1
SHT No
APPD
D372756
MJH
DRAWN
09:08:01
DATE
ALL SHARP EDGES AND BURRS TO BE REMOVED
UBERHITZUNGSSCHUTZ
ELEKTROHEIZUNG
TRANSFORMATEUR
VANNE ELECTROMAGNETIQUE
TRANSFORMATOR
ABTAUTHERMOSTAT/-UHR TRANSFORMER
DEFROST THERMOSTAT/TIMER A T
MAGNETVENTIL SOLENOID VALVE Y
COND./RELAI DE DEMARRAGE
MOTEUR DU VENTILATEUR
KONDENSATOR VENTILATOR FAN CAPACITOR C2/C3
AUTOM. START KAPAZITOR
COMPRESSEUR
KONDENSATOR KOMPRESSOR COMPRESSOR CAPACITOR C1
RELAIS
VENTILATORMOTOR FAN MOTOR MV
TEMPORISATEUR
KOMPRESSORMOTOR
RELAIS RELAY COMPRESSOR MOTOR
VERZOGERUNGSRELAIS DELAY TIMER
MC
REINITIALISATION DEFAUT BASSE PRESSION NIEDERDRUCKSCHALTER LOW PRESSURE SWITCH
K
HOCHDRUCKSCHALTER HIGH PRESSURE SWITCH HP
D
REINITIALISATION DEFAUT HAUTE PRESSION
GEBLASESCHALTER FAN MODE SWITCH S1
LP
THERMOSTAT LPHW SELECTEUR DE MODE DU VENTILATEUR
PWW-STAT
LPHW THERMOSTAT
TH
THERMOSTAT DE DEGIVRAGE
B
A
HYGROSTAT
3 6
9
HP (300psi)
B
VEREISUNGSSCHUTZTHERMOSTAT
1 4
7
K3
3 6
1 4
A
HYGROSTAT
6 mins
9
7
K2
12V SIDE
DEFROST THERMOSTAT
B
6(7)
LP
D
HP (400psi)
TC
A
4
K1
L(L1)
REMOTE HUMIDISTAT NTS
SCALE
D372756
DEHUMIDISTAT
MV
TC
C
T
DRG No.
FT
R
S
IF IN DOUBT ASK
SH
MC
RH
VIOLETTE
BLANC
ROUGE
ROSE
ORANGE
GRIS
MARRON
BLEU
NOIR
C1
N(L2)
G/Y GREEN/YELLOW GROEN/GELB VERT/JAUNE
GREY ORANGE
GR
BLAU
BLUE
BRUAN
SCHWARZ
BLACK BROWN
B
WIRES NOT CONNECTED (TWIN FAN ASSY ONLY)
BR
BL
TRANSFORMER T
L BLK
O
REMOTE THERMOSTAT
UNCONTROLLED WHEN PRINTED
BR
CAP BRN BR R/B BR P
B B
BRN
COM BUTT
BLU BUTT CONNECTOR
page13
ISSUE 5 LABEL D380756
DO NOT SCALE PRINT
3 WIRING DIAGRAMS CONT
SD139460 ISSUE 21
AIR TEMPERATURE (° C)
page14
20 30 40
50
90%
60
80%
1.9
2.4
* = AT 60%RH
0.75
0.85
MAX OPERATING TEMP 40ºC (R22 GAS) MAX OPERATING TEMP 35ºC (R407c GAS)
MOISTURE EXTRACTION LITRES/24HOURS
0.55
10
70%
1.2
60%
10°C
50%
0.65
40%
ELECTRICAL INPUT kW *
1.5
0
30%
SENSIBLE HEAT OUTPUT kW *
20°C
30°C
40°C
DH30/30(7)/33/33(7) PERFORMANCE.
4.0 PERFORMANCE GRAPHS
SD139460 ISSUE 21
AIR TEMPERATURE (°C)
page15
10°C
20°C
30°C
40°C
0 40
40%
60
50%
MAX OPERATING TEMP' 40ºC (R22 GAS) MAX OPERATING TEMP' 35ºC (R407c GAS)
MOISTURE EXTRACTION LITRES/24HOURS
20
30%
80
60%
100
70%
DH50/50(7)/55/55(7)/60/60(7) PERFORMANCE.
120
90%
80%
0.8 1.9
* = AT 60%RH
1.0
1.2
1.4
ELECTRICAL INPUT kW *
2.6
3.5
4.6
OUTPUT kW *
SENSIBLE HEAT
4 PERFORMANCE GRAPHS CONT
SD139460 ISSUE 21
LITRES PER HOUR
page16
0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
-5 0
5
90%
10
AIR ON TEMPERATURE DRY BULB °C
-10
DH30/33
40%
50%
60%
70%
80%
0
0.4
0.8
1.2
1.6
2.0
2.4
2.8
-5
0
5
10 AIR ON TEMPERATURE DRY BULB °C
-10
DH50/55/60
40%
50%
60%
70%
80%
90%
4 PERFORMANCE GRAPHS CONT
SD139460 ISSUE 21
RELATIVE HUMIDITY
LITRES PER HOUR
RELATIVE HUMIDITY
5.0 DIMENSIONS POSITION OF BRACKETS RELATIVE TO WALL 780.00
203.00
436.00
653.00
203.00
30 SERIES WALLHUNG DEHUMIDIFIER
1245.00
242.00
242.00
436.00
653.00
242.00
50 SERIES WALLHUNG DEHUMIDIFIER
page17
SD139460 ISSUE 21
830.00
DH30 SERIES
PACKED DEHUMIDIFIERS
page18 'X'
3120
FRAGILE HANDLE WITH CARE
1295.00
DH50 SERIES
MACHINE TYPE DIMENSION X
340.00
5 DIMENSIONS CONT
SD139460 ISSUE 21
850.00
page19
172
19
40
38
WATER IN/OUT TUBES DIA 15
250
270
PACKED DIMENSIONS 860.00L x 340.00W x 850.00H
IN
OUT
MOUNTING SLOTS 450
REHEAT SECTION ADDED TO BACK OF M/C
AIR IN
MAINS IN
MAINS IN T.B.
AIR OFF
100 15
56 112 CONDENSATE DRAIN
COVER FIXINGS IN 2 POSN'S HUMIDISTAT CONTROL KNOB
780
DH30 DIMENSIONS
655 250
3rd ANGLE PROJECTION
5 DIMENSIONS CONT
SD139460 ISSUE 21
page20
40
172
19
IN
OUT
LPHW CONNECTIONS 15mm DIA WHEN FITTED
35 MOUNTING SLOTS
PACKED DIMENSIONS 860.00L x 330.00W x 850.00H
WATER IN/OUT TUBES DIA 15
510
38.00
REHEAT SECTION ADDED TO BACK OF M/C 25
250
MAINS IN T.B.
AIR IN
AIR OFF
653 100
56 MAINS IN
15
450
112
780
COVER FIXINGS IN 2 POSN'S
DH33 DIMENSIONS
CONDENSATE DRAIN
HUMIDISTAT CONTROL KNOB
3rd ANGLE PROJECTION
5 DIMENSIONS ONT
SD139460 ISSUE 21
250
172
236
AIR IN
MAINS IN T.B.
AIR OFF
648 HUMIDISTAT CONTROL KNOB
WATER IN/OUT TUBES DIA 15mm.
PACKED DIMENSIONS 860.00L x 340.00W x 850.00H
19
IN
OUT
38
40
MOUNTING SLOTS 450
256
100
page21
15
REHEAT SECTION ADDED TO BACK OF M/C
57 113
782
DH30 WITH METAL COVER
CONDENSATE DRAIN MAINS IN
COVER FIXINGS IN 2 POSITIONS
3rd ANGLE PROJECTION
5 DIMENSIONS CONT
SD139460 ISSUE 21
page22
19
IN
OUT
172
AIR IN
250
MAINS IN T.B.
AIR OFF
1310.00L x 330.00W x 850.00H
PACKED DIMENSIONS
DIA 15mm
WATER IN/OUT TUBES
40
MOUNTING SLOTS
450.00
38
250
REHEAT SECTION ADDED TO BACK OF M/C
655 15
163
CONDENSATE DRAIN
1245
HUMIDISTAT CONTROL KNOB
50 54
DH50/60 DIMENSIONS
COVER FIXINGS IN 3 POSN'S
3rd ANGLE PROJECTION
100 MAINS IN
5 DIMENSIONS CONT
SD139460 ISSUE 21
163
50 243
COVER FIXINGS IN 3 POSN'S
HUMIDISTAT CONTROL KNOB
CONDENSATE DRAIN
RH WATER PIPES
1245
AIR IN
AIR OFF
57
MAINS IN
100
page23
653
250
MAINS IN T.B.
25
250
WATER IN/OUT TUBES DIA 15. OUT OTHER SIDE
IN
OUT
PACKED DIMENSIONS 1310.00L x 340.00W x 850.00H
450 MOUNTING SLOTS
19
REHEAT SECTION ADDED TO BACK OF M/C 38 LPHW CONNECTIONS 15mm DIA WHEN FITTED 35 510
270
DH55 DIMENSIONS
172 40
3rd ANGLE PROJECTION
5 DIMENSIONS CONT
SD139460 ISSUE 21
19
page24
172
236
256
AIR IN
PACKED DIMENSIONS 1310.00L x 340.00W x 850.00H
WATER IN/OUT TUBES O/D 15mm
40
38
450 MOUNTING SLOT
REHEAT SECTION ADDED TO BACK OF M/C
AIR OFF
648 236
164
CONDENSATE DRAIN
HUMIDISTAT CONTROL KNOB
COVER FIXINGS IN 3 POSITIONS
1247
3rd ANGLE PROJECTION
50 55
DH60 ( METAL COVER)
100 15
MAINS IN
5 DIMENSIONS CONT
SD139460 ISSUE 21
58
30
6
i
57
14
page25
7
3
5
32
29
31 GAS CHARGE
4
26
2
38
37
36
35
SA64390101 DH30(7)A
FRIDGE/ELEC BOX ASSY DH30(7)A
6.0 SPARE PARTS LISTS
SD139460 ISSUE 21
ASSY No SA390101 DH30(7)A FRIDGE/ELECT ASSY ITEM NO. PART No.
2 3 4 5 *6 7 14 26 29 30 31 32 35 36 37 38 57 58
5
DESCRIPTION
QUAN
UNITS
EVAP/COND ASSY DH30A COMPRESSOR ASSEMBLY AE5470C 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH30A & ARH DRIP TRAY (EVAPORATOR) DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT SWITCH HIGH PRESSURE ACB-DB64 OWNERS INSTALLATION MANUAL REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE WALL BRACKET ANTI VIBRATION BUFFER WIER KIT (OPTIONAL)
1 1 1 1 1 1 1 2 1 1 0.5 1 1 1 1 0.864 1 2 1
off off off off off off off off off off kg off off off off m off off off
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144501 ELECT BOX ASSY DH30A & ARH
1
off
AND FIT SA144509
1
off
1
off
SD140453 SA144154 SD101450 SA144501 SD139050 SD146951 SD066350 SD144250 SD266450 SD139451 SP182554 SD266550 SD138052 SD136950 SD141250 SD318250 SD138851 D458450 SD229503
ELECT BOX ASSY DH30A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page26
SD139460 ISSUE 21
page27
SD139460 ISSUE 21
58
57
30
i
6
14
7
3
35
5
2 36 37 38 39
31 GAS CHARGE
34
26
4
28
29
SA64400802
FRIDGE/ELEC ASSY DH30AX
ASSY No SA400802 DH30(7)AX FRIDGE ELECT ASSY ITEM NO. PART No. 2 3 4 5 *6 7 14 26 28 29 30 31 34 35 36 37 38 39 57 58
5
DESCRIPTION
QUAN
UNITS
EVAP/COND ASSY R407C COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH33AX DRIPTRAY DH30/DH33 DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT SOLENOID VALVE SOLENOID COIL 240V OWNER INSTALLATION MANUAL REFRIGERANT R407c SWITCH HIGH PRESSURE ACB-DB64 LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE WALL BRACKET ANI VIBRATION BUFFER WIER KIT (OPTIONAL)
1 1 1 1 1 1 1 2 1 1 1 0.5 1 1 1 1 1 0.864 1 2 1
off off off off off off off off off off off kg off off off off off m off off off
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144502 ELECT BOX ASSY DH30AX
1
off
AND FIT SA144510
1
off
1
off
SD140454 SA144154 SD101450 SD144502 SD139050 SD146951 SD066350 SD144250 SD146150 SD146250 SD139451 SP182554 SD266450 SD266550 SD138051 SD136950 SD141250 SD318250 SD138851 D458450 SD229503
ELECT BOX ASSY DH30AX + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page28
SD139460 ISSUE 21
30
31
30
40
i
57
6
14 7
3
28
5
35
36
46 GAS CHARGE
2
4 26
29
2
39
38
53
TEV PHIAL
52
14 0. 00
SA64239207
FRIDGE/ELEC ASSY DH30ARH
15.00 15.00
page29
SD139460 ISSUE 21
ASSY No SA239207 DH30ARH FRIDGE/ELECT ASSY ITEM NO. PART No. 2 3 4 5 6 7 14 26 28 29 30 31 35 36 38 39 40 46 52 53 57
5
QUAN
UNITS
1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1.04 1 1 1 1
off off off off off off off off off off off off off off off off off kg off off off off
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144501 ELECT BOX ASSY DH30A & ARH
1
off
AND FIT SA144509
1
off
1
off
SA140452 SA144154 SD101450 SA144501 SD139050 SD146951 SD066350 SD144250 SD155750 SD155751 SD155850 SD172650 SD266450 SD266550 SD138050 SD136050 SD139451 SP182554 SD141250 SD086752 SD152650 SD229503
DESCRIPTION EVAP COND ASSY DH30ARH COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH30A & ARH DRIP TRAY (EVAPORATOR) DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT BRACKET WATER COIL BRACKET WATER COIL BRACKET WATER COIL CONDENSER CO-AXIAL SERPENTINE SWITCH HIGH PRESSURE ACB-DB64 LP SWITCH LCB-DA15 EVAPORATOR CONDENSER OWNER INSTALLATION MANUAL REFRIGERANT R407c DRIER HRP 274151 TEV 0.5INE-GA-BP10 WALL BRACKET WIER KIT
ELECT BOX ASSY DH30A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page30
SD139460 ISSUE 21
page31
SD139460 ISSUE 21
58
57
30
i
6
14
7
3
29
5
31 GAS CHARGE AT 130 PSI-G
32
62
61
63
60
4 26 2
2
39
38
37
36
SA390103
FRIDGE/ELEC ASSY DH30AP
ASSY No SA390103 DH30(7)AP FRIDGE/ELECT ASSY ITEM NO. PART No. 2 3 4 5 *6 7 14 26 29 30 31 32 36 37 38 39 57 58 60 61 62 63
SD140453 SA144154 SD101450 SA144507 SD139050 SD146951 SD066350 SD144250 SD062553 SD139451 SP182554 SD266550 SD138052 SD136050 SD141250 SD318250 SD138851 D458450 SD362850 SD362950 SD103251 SD103252 SD229503
DESCRIPTION
QUAN
UNITS
EVAP/COND ASSY DH30A COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH30AP DRIPTRAY (EVAPORATOR) DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT HP SWITCH 400PSI OWNER INSTALLATION MANUAL REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D WALL BRACKET ANTI VIBRATION BUFFER AIR HEATER ELEMENT HEATER COVER THERMAL CUTOUT AUTO RESET THERMAL CUTOUT MANUAL RESET WEIR KIT (OPTIONAL)
1 1 1 1 1 1 1 2 1 1 0.5 1 1 1 1 0.864 1 2 1 1 1 1 1
off off off off off off off off off off kg off off off off m off off off off off off off
1
off
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page32
SD139460 ISSUE 21
page33
SD139460 ISSUE 21
58
57
30
i
6
14
7
3
5
34
27
33 GAS CHARGE
4 2
26
39
38
37
36
2
31
SA64390102
FRIDGE/ELEC ASSY DH33A
ASSY No SA390102 DH33(7)A FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION
QUAN
UNITS
EVAP/COND ASSY DH33(7)A COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH30A & ARH DRIPTRAY DH30/DH33 DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT SWITCH HIGH PRESSURE ACB-DB64 OWNER INSTALLATION MANUAL BLANKING PLATE DH33 REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D WALL BRACKET ANTI VIBRATION BUFFER
1 1 1 1 1 1 1 2 1 1 1 0.5 1 1 1 1 0.813 1 2
off off off off off off off off off off off kg off off off off m off off
2 3 4 5 6 7 14 26 27 30 31 33 34 36 37 38 39 57 58
SD140407 SA144154 SD101450 SA144501 SD139050 SD146951 SD066350 SD144250 SD266450 SD139451 SD264550 SP182554 SD266550 SD138052 SD136951 SD141250 SD318250 SD138851 D458450
5
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144501 ELECT BOX ASSY DH30A & ARH
1
off
AND FIT SA144509
1
off
1
off
ELECT BOX ASSY DH30A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page34
SD139460 ISSUE 21
page35
SD139460 ISSUE 21
58
57
30
i
6
14
7
3
40
5
27
39 GAS CHARGE
4 26 2
38
37
36
35
2
33
34
SA64400801
31
FRIDGE/ELEC ASSY DH33AX
ASSY No SA400801 DH33(7)AX FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION
QUAN
UNITS
EVAP/COND ASSY DH33(7)AX COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH33AX DRIP TRAY (EVAPORATOR) DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT SWITCH HIGH PRESSURE ACB-DB64 OWNER INSTALLATION MANUAL BLANKING PLATE SOLENOID VALVE SOLENOID COIL 240V EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D REFRIGERANT R407c LP SWITCH LCB-DA15 WALL BRACKET ANTI VIBRATION BUFFER
1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 0.864 0.5 1 1 2
off off off off off off off off off off off off off off off off m kg off off off
2 3 4 5 *6 7 14 26 27 30 31 33 34 35 36 37 38 39 40 57 58
SD140408 SA144154 SD101450 SA144502 SD139050 SD146951 SD066350 SD144250 SD266450 SD139451 SD264550 SD146150 SD146250 SD138051 SD136051 SD141250 SD318250 SP182554 SD266550 SD138851 D458450
5
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144502 ELECT BOX ASSY DH30AX
1
off
AND FIT SA144510
1
off
1
off
ELECT BOX ASSY DH30AX + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page36
SD139460 ISSUE 21
35
38
35
30
57
i
6
14
7
3
36
46
5
27
45 GAS CHARGE 2
4 26
37
41
40
2
53
TEV PHIAL
52
14
0. 00
31
SA64239216
FRIDGE/ELEC ASSY DH33ARH
15.00 15.00
page37
SD139460 ISSUE 21
ASSY No SA239216 DH33ARH FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP/COND ASSY DH33ARH COMPRESSOR ASSY AE5470C 1PH N 230V 50HZ FAN CENTRIFUGAL 1050RPM ELECT BOX ASSY DH30A & ARH DRIP TRAY (EVAPORATOR) DRIP TRAY (COMPRESSOR) SCHRADER VALVE U TYPE NUT SWITCH HIGH PRESSURE ACB-DB64 OWNER INSTALLATION MANUAL BLANKING PLATE BRACKET WATER COIL BRACKET WATER COIL BRACKET WATER COIL CONDENSER CO-AXIAL SERPENTINE EVAPORATOR CONDENSER REFRIGERANT R407c LP SWITCH LCB-DA15 DRIER HRP 274151 TEV 0.5INE-GA-BP10 WALL BRACKET
QUAN
UNITS
1 1 1 1 1 1 1 2 1 1 1 2 1 1 1 1 1 1.04 1 1 1 1
off off off off off off off off off off off off off off off off off kg off off off off
2 3 4 5 6 7 14 26 27 30 31 35 36 37 38 40 41 45 46 52 53 57
SD140406 SA144154 SD101450 SA144501 SD139050 SD146951 SD066350 SD144250 SD266450 SD139451 SD264550 SD155850 SD155750 SD155751 SD172650 SD138050 SD136051 SP182554 SD266550 SD141250 SD086752 SD156250
5
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144501 ELECT BOX ASSY DH30A & ARH
1
off
AND FIT SA144509
1
off
1
off
ELECT BOX ASSY DH30A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD139051
DRIP TRAY (EVAPORATOR)
page38
SD139460 ISSUE 21
page39
SD139460 ISSUE 21
57
A1
5
2
A2
35 36 37 38
33 GAS CHARGE AT 130 PS1-G
32
34
8
15
4
30
SA64390201
6
i
58
FRIDGE/ELEC ASSY DH50/60A/ DH60(7)A
7
ASSY No SA390201 DH50(7)/60(7) FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP/COND ASSY DH50A COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55A DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL SWITCH HIGH PRESSURE ACB-DB64 REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D WALL BRACKET ANTI VIBRATION BUFFER
QUAN
UNITS
1 1 1 1 1 1 1 1 1 0.75 1 1 1 1 2 X 0.94 1 2
off off off off off off off off off kg off off off off m off off
2 4 5 *6 7 8 15 30 32 33 34 35 36 37 38 57 58
SD140753 SD132653 SD378201 SD140950 SA144801 SD146850 SD066350 SD139451 SD266450 SP182554 SD266550 SD139152 SD137850 SD141250 SD318250 SD141751 D458450
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144801 ELECT BOX ASSY DH55A
1
off
AND FIT SA144811
1
off
1
off
ELECT BOX ASSY DH55A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page40
SD139460 ISSUE 21
page41
SD139460 ISSUE 21
32
33
57
A1
5
65
2
31 GAS CHARGE AT 130 PSI-G
40 41 42
A2
43
37
38
8
15
4
6
30
SA64401102
i
58
7
FRIDGE/ELEC ASSY DH50/60AX
ASSY No SA401102 DH50(7)/60(7)AX FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP COND ASSY DH50AX COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55AX DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL REFRIGERANT R407c SOLENOID VALVE SOLENOID COIL 240V SWITCH HIGH PRESSURE ACB-DB64 LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP274151 CAPILLARY TUBE 0.052 I/D WALL BRACKET ANTI VIBRATION BUFFER
QUAN
UNITS
1 1 1 1 1 1 1 1 0.8 1 1 1 1 1 1 1 2 X 1.118 1 2
off off off off off off off off kg off off off off off off off m off off
2 4 5 *6 7 8 15 30 31 32 33 37 38 40 41 42 43 57 58
SD140754 SD132653 SD378201 SD140950 SA144802 SD146850 SD066350 SD139451 SP182554 SD146150 SD146250 SD266450 SD266550 SD139151 SD137850 SD141250 SD318250 SD141751 D458450
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144802 ELECT BOX ASSY DH55AX
1
off
AND FIT SA144812
1
off
1
off
ELECT BOX ASSY DH55AX + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page42
SD139460 ISSUE 21
56
30
15.00
15.00
page43
SD139460 ISSUE 21
i
TEV PHIAL
55
57
37
A1
5
2
31 GAS CHARGE AT 130 PS1-G
44 45
43
62 38
8
15
6
4
SA64252207
FRIDGE/ELEC ASSY DH50/60ARH
39
7
40
39
ASSY No SA252207 DH50/60ARH FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP/COND ASSY DH50ARH COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55A DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL REFRIGERANT R407c BRACKET WATER COIL BRACKET WATER COIL BRACKET CONDENSER CO-AXIAL SERPENTINE SWITCH HIGH PRESSURE ACB-DB64 EVAPORATOR CONDENSER EXPANSION VALVE INE-1.5GA DRIER HRP 274151 WALL BRACKET (RH) LP SWITCH LCB-DA15
QUAN
UNITS
1 1 1 1 1 1 1 1 1.64 1 1 2 1 1 1 1 1 1 1 1
off off off off off off off off kg off off off off off off off off off off off
2 4 5 6 7 8 15 30 31 37 38 39 40 43 44 45 55 56 57 62
SA140752 SD132653 SD378201 SD140950 SA144801 SD146850 SD066350 SD139451 SP182554 SD155750 SD155751 SD155650 SD168150 SD266450 SD139150 SD137850 SD086751 SD141250 SD156050 SD266550
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144801 ELECT BOX ASSY DH55A
1
off
AND FIT SA144811
1
off
ELECT BOX ASSY DH55A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT
page44
SD139460 ISSUE 21
page45
SD139460 ISSUE 21
57
A1
70
5
72
73 33
70 72
GAS CHARGE
71 73
2
71
40 41 42 43
,00 100
34
8
15
32
4
6
SA390203
30
i
58
7
FRIDGE/ELEC ASSY DH50/60AP
ASSY No SA390203 DH50(70/60(7)AP FRIDGE/ELECT ASSY ITEM NO. PART No. 2 4 5 *6 7 8 15 30 32 33 34 40 41 42 43 57 58 70 71 72 73
SD140753 SD132653 SD378201 SD140950 SA144808 SD146850 SD066350 SD139451 SD062553 SP182554 SD266550 SD139152 SD137850 SD131250 SD318250 SD141751 D458450 SD362950 SD362850 SD103251 SD103252 SD229504
DESCRIPTION EVAP/COND ASSY DH50A COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH50AP DRIP TRAY (COMPRESSSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL HP SWITCH 400PSI REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D WALL BRACKET ANTI VIBRATION BUFFER HEATER COVER AIR HEATER ELEMENT THERMAL CUTOUT AUTO RESET THERMAL CUTOUT MANUAL RESET WEIR KIT (OPTIONAL)
QUAN
UNITS
1 1 1 1 1 1 1 1 1 0.75 1 1 1 1 2 X 0.94 1 2 2 2 2 2 1
off off off off off off off off off kg off off off off m off off off off off off off
1
off
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page46
SD139460 ISSUE 21
page47
SD139460 ISSUE 21
51
28
i
48
57
39
41
5
2
40 39 40
27
31
8
14
29
47
4
30
(COMPRESSOR)
BLUE SEAL
(HEATERS)
PINK SEAL
GAS CHARGE AT 130 PSI-G
HP SWITCH --- 400 psi
HP SWITCH ---300 psi
SA390204
FRIDGE/ELECT ASSY DH60AHP (134a)
6
58
7
ASSY No SA390204 DH60AHP FRIDGE/ELECT ASSY ITEM NO. PART No. 2 4 5 *6 7 8 14 28 29 30 31 39 40 41 47 48 51 57 58
SA140752 SD132653 SD378202 SD140950 SD144810 SD146850 SD066350 SD139451 SD062553 SP182555 SD266550 SD362950 SD362850 SD103252 SA062554 SD447350 SD141250 SD141751 D458450
DESCRIPTION EVAP/COND ASSY DH50ARH COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY ELECT BOX ASSY DH60AHP DRIP TRAY PLASTIC BLACK ABS SCHRADER VALVE OWNER INSTALLATION MANUAL HP SWITCH 400PSI REFRIGERANT R134a LP SWITCH LCB-DA15 HEATER COVER AIR HEATER ELEMENT THERMAL CUTOUT MANUAL RESET HP SWITCH 300PSI TEV EBF JE A CP60 DRIER HRP 274151 WALL BRACKET ANTI VIBRATION BUFFER
QUAN
UNITS
1 1 1 1 1 1 1 1 1 0.8 1 2 2 2 1 1 1 1 2
off off off off off off off off off kg off off off off off off off off off
1
off
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page48
SD139460 ISSUE 21
page49
SD139460 ISSUE 21
5
57
2
46
47
48
49 2 OFF
100.00
8
15
32
45
33
6
4
30
i
GAS CHARGE AT 130 PSI-G
SA64390202
FRIDGE/ELEC ASSY DH55A
7
58
51
ASSY No SA390202 DH55(7)A FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP COND ASSY (R407C) DH55A COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55A DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL SWITCH HIGH PRESSURE ACB-DB64 REFRIGERANT R407c LP SWITCH LCB-DA15 EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052I/D BLANKING PLATE DH33 WALL BRACKET ANTI VIBRATION BUFFER
QUAN
UNITS
1 1 1 1 1 1 1 1 1 0.76 2 1 1 1 2 X 0.889 1 1 2
off off off off off off off off off kg off off off off m off off off
2 4 5 6 7 8 15 30 32 33 45 46 47 48 49 51 57 58
SD140707 SD132653 SD378201 SD140950 SA144801 SD146850 SD066350 SD139451 SD266450 SP182554 SD266550 SD139152 SD137851 SD141250 SD318250 SD264551 SD141751 D458450
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144801 ELECT BOX ASSY DH55A
1
off
AND FIT SA144811
1
off
1
off
ELECT BOX ASSY DH55A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page50
SD139460 ISSUE 21
page51
SD139460 ISSUE 21
30
i
5
6
36
37
57
2
32
2 off
45
40 41 42 43
100.00
8
15
38
51
58
7
4
GAS CHARGE AT 130 PSI-G
SA64401101
FRIDGE/ELEC ASSY DH55AX
ASSY No SA401101 DH55(7)AX FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP/COND ASSY DH55AX COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55AX DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL SWITCH HIGH PRESSURE ACB-DB64 SOLENOID VALVE COIL 240V REFRIGERANT R407c EVAPORATOR CONDENSER DRIER HRP 274151 CAPILLARY TUBE 0.052 I/D LP SWITCH LCB-DA15 BLANKING PLATE DH50 WALL BRACKET ANTI VIBRATION BUFFER
QUAN
UNITS
1 1 1 1 1 1 1 1 1 1 1 0.76 1 1 1 2 X 1.118 2 1 1 2
off off off off off off off off off off off kg off off off m off off off off
2 4 5 6 7 8 15 30 32 36 37 38 40 41 42 43 45 51 57 58
SD140708 SD132653 SD378201 SD140950 SA144802 SD146850 SD066350 SD139451 SD266450 SD146150 SD146250 SP182554 SD139151 SD137851 SD141250 SD318250 SD266550 SD264551 SD141751 D458450
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144802 ELECT BOX ASSY DH55AX
1
off
AND FIT SA144812
1
off
1
off
ELECT BOX ASSY DH55AX + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page52
SD139460 ISSUE 21
56
30
15.00
15.00
page53
SD139460 ISSUE 21
i
55
12
TEV PHIAL
57
37
5
A1
2
A
47 48
8
15
43
45
38
4
51
31 GAS CHARGE AT 130 PSI-G
SA64252216
FRIDGE/ELEC ASSY DH55ARH
39
7
40
39
ASSY No SA252216 DH55ARH FRIDGE/ELECT ASSY ITEM NO. PART No.
DESCRIPTION EVAP/COND ASSY DH55ARH COMPRESSOR HERM AJ5512C FAN ASSY DRIP TRAY (EVAPORATOR) ELECT BOX ASSY DH55A DRIP TRAY (COMPRESSOR) SCHRADER VALVE OWNER INSTALLATION MANUAL REFRIGERANT R407c BRACKET WATER COIL BRACKET WATER COIL BRACKET CONDENSER CO-AXIAL SERPENTINE SWITCH HIGH PRESSURE ACB-DB64 LP SWITCH LCB-DA15 BLANKING PLATE DH50 EXPANSION VALVE INE-1.5GA DRIER HRP 274151 WALL BRACKET DH50(RH)
QUAN
UNITS
1 1 1 1 1 1 1 1 1.64 1 1 2 1 1 1 1 1 1 1
off off off off off off off off kg off off off off off off off off off off
2 4 5 *6 7 8 15 30 31 37 38 39 40 43 45 51 55 56 57
SA140706 SD132653 SD378201 SD140950 SA144801 SD146850 SD066350 SD139451 SP182554 SD155750 SD155751 SD155650 SD168150 SD266450 SD266550 SD264551 SD086751 SD141250 SD156050
7
VARIATION WHEN HUMIDISTAT OPTION FITTED AS ABOVE BUT DROP SA144801 ELECT BOX ASSY DH55A
1
off
AND FIT SA144811
1
off
1
off
ELECT BOX ASSY DH55A + REMOTE STAT
* FOR MURPROTEC VERSIONS FIT SD140951
DRIP TRAY (EVAPORATOR)
page54
SD139460 ISSUE 21
page55
SD139460 ISSUE 21
6
11
4
14
13
8
2
7
0.3
5
MINUTES
10
10
5
TIMER
MAKE
ON
DELAY
9
SA144501-10
15
16
12
THESE 2 ITEMS USED ON VERSIONS WITH REMOTE HUMIDISTAT OR RESISTANCE HEATERS
ELEC BOX ASSY DH30/30(7)/33/33(7) RANGE
ELEC BOX ASSY DH30/30(7)/33/33(7)A-ARH SA144501 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230V AC COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072851
3 WAY TERM' BLOCK
1.000
12
SA145901
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
ELEC BOX ASSY DH30/30(7)/33/33(7)A-ARH WITH REMOTE HUMIDISTAT SA144509 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230V AC COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072853
5 WAY TERMINAL BLOCK 15A
1.000
12
SA145903
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
15
SD336550
TRANSFORMER 12V
1.000
16
SD378350
RELAY 25A C/O 12V
1.000
page56
SD139460 ISSUE 21
ELEC BOX ASSY DH30/30(7)/33/33(7)AX SA144502 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SA145803
TIMER DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230V AC COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072851
3 WAY TERM' BLOCK
1.000
12
SA146401
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
ELEC BOX ASSY DH30/30(7)/33/33(7)AX WITH REMOTE HUMIDISTAT
SA144510 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SA145803
TIMER DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230V AC COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072653
5 WAY TERM' BLOCK 15A
1.000
12
SA146403
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
15
SD336550
TRANSFORMER 12V
1.000
16
SD378350
RELAY 25A C/O 12V
1.000
page57
SD139460 ISSUE 21
ELEC BOX ASSY DH30/30(7)AP SA144507 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230vac COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072650
6 WAY TERM' BLOCK
1.000
12
SA145902
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
15
SA336550
TRANSFORMER 12v
1.000
16
SD378350
RELAY C/O 25A 12v COIL
1.000
ELEC BOX ASSY DH30/30(7)AXP SA144508 2
SD041450
CONTROL KNOB
1.000
4
SD349350
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SA145803
TIMER DEFROST STAT
1.000
7
SD106550
FAN CAP 2µF
1.000
8
SD219250
RELAY C/O 2 POLE 25A 230vac COIL
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072650
6 WAY TERM' BLOCK
1.000
12
SA146402
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
D211050
COVER
1.000
15
SA336550
TRANSFORMER 12v
1.000
16
SD378350
RELAY C/O 25A 12v COIL
1.000
page58
SD139460 ISSUE 21
page59
SD139460 ISSUE 21
3
5
9
12
10
15
16
THESE 2 ITEMS USED ON VERSIONS VERSIONS WITH RESISTANCE HEATERS OR REMOTE HUMIDISTATS
1
7
6
VERSION ONLY
FITTED ON 'AX'
14
FITTED ON 'A' / 'ARH' VERSIONS ONLY
13
4 17
SA64144801 TO 09,11 AND 12
8
ELEC BOX ASSY DH50/50(7)/55/55(7)/60/60(7) RANGE
ELEC BOX ASSY DH50/50(7)/55/55(7)/60/60(7)A-ARH SA144801 1
SD139750
ELECTRICS BOX
1.000
3
SD041450
CONTROL KNOB
1.000
4
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF ( R407c version)
1.000
11
SD072851
3 WAY TERM' BLOCK
1.000
12
SA146001
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
17
SD219350
COVER
1.000
ELEC BOX ASSY DH50/50(7)/55/55(7)/60/60(7)A-ARH WITH REMOTE HUMIDISTAT SA144811 1
SD139750
ELECTRICS BOX
1.000
3 4
SD041450
CONTROL KNOB
1.000
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072853
5 WAY TERM' BLOCK
1.000
12
SA146002
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
15
SD336550
TRANSFORMER 12V
1.000
16
SD378350
RELAY 25A C/O 12V
1.000
17
SD219350
COVER
1.000
page60
SD139460 ISSUE 21
ELEC BOX ASSY DH50/50(7)/55/55(7)/60/60(7)AX SA144802 1
SD139750
ELECTRICS BOX
1.000
3
SD041450
CONTROL KNOB
1.000
4
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072851
3 WAY TERM' BLOCK
1.000
12
SA146501
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
SD145803
TIMER / DEFROST STAT
1.000
17
D219350
COVER
1.000
ELEC BOX ASSY DH50/50(7)/55/55(7)/60/60(7)AX WITH REMOTE HUMIDISTAT SA144812 1
SD139750
ELECTRICS BOX
1.000
3
SD041450
CONTROL KNOB
1.000
4
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD64092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072851
3 WAY TERM' BLOCK
1.000
12
SA146503
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
SD145803
TIMER / DEFROST STAT
1.000
15
SD336550
TRANSFORMER 12V
1.000
16
SD378350
RELAY 25A C/O 12V
1.000
17
D219350
COVER
1.000
page61
SD139460 ISSUE 21
ELEC BOX ASSY DH50/50(7)/60/60(7)AP SA144808 1
SD139750
ELECTRICS BOX
1.000
3
SD041450
CONTROL KNOB
1.000
4
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
6
SD118351
DEFROST STAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072650
6 WAY TERM' BLOCK
1.000
12
SA146003
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
15
SA336550
TRANSFORMER 12v
1.000
16
SD378350
RELAY C/O 25A 12v COIL
1.000
17
D219350
COVER
1.000
ELEC BOX ASSY DH50/50(7)/60/60(7)AXP SA144809 1
SD139750
ELECTRICS BOX
1.000
3
SD041450
CONTROL KNOB
1.000
4
SD349351
GASKET
1.000
5
SD062350
HUMIDISTAT
1.000
7
SD022150
FAN CAP 6µF
1.000
8
SD092151
RELAY
1.000
9
SD089550
TIMER
1.000
10
SD038750
RUN CAP 15µF
1.000
11
SD072650
6 WAY TERM' BLOCK
1.000
12
SA146502
LOOM ASSY
1.000
13
SD188950
ROCKER SWITCH
1.000
14
SD145803
TIMER/DEFROST STAT
1.000
15
SA336550
TRANSFORMER 12v
1.000
16
SD378350
RELAY C/O 25A 12v COIL
1.000
17
D219350
COVER
1.000
page62
SD139460 ISSUE 21
10 23
18
21
4 12
FAN CONTINUOUS
22
2
20
5
34
19
17
16
1
SA144810
FAN
ELECTRIC BOX ASSEMBLY DH60AHP
CYCLE
ASSY No SA144810 AT ISS 4 (15/09/2011). ELECTRIC BOX ASSY DH60AHP ITEM NO. PART No. 1 2 4 5 10 12 16 17 18 19 20 21 22 23 34
SD139750 SD336551 SD219350 SD378350 SD189050 SD349351 SD118351 SD382450 SD092151 SD089550 SD038750 SD072650 SA146004 SD188950 SP147450
DESCRIPTION ELECTRIC BOX TRANSFORMER 12V 12VA COVER RELAY 25A C/O 12V COIL LABEL ROCKER SWITCH GASKET FOR COVER THERMOSTAT PRESET CAPACITOR 5uF 440V 50/60Hz RELAY N/O 1POLE 30A 230V AC COIL DELAY TIMER 7 SEC TO 9 MIN CAPACITOR RUN CAP 15µF+/-5% 400V TERMINAL BLOCK 6 WAY DH60AHP LOOM ASSY ROCKER SWITCH 1 POLE C/O DOUBLE SIDED ADHESIVE PAD 25mm page63
QUAN
UNITS
1 1 1 2 1 1 1 1 1 1 1 1 1 1 3
off off off off off off off off off off off off off off off SD139460 ISSUE 21
DH30/30(7) GRP COVER ASSY SA223101
3
2
ITEM 1 2 3
PART No D140050 D139550 D141650
1
DESCRIPTION :COVER GRP LOUVRE SUPPORT (HONEYSUCKLE) LOUVRE (HONEYSUCKLE)
page64
QUANTITY 1 3 4
SD139460 ISSUE 21
DH30/30(7) METAL COVER ASSY'S. SEE PARTS LISTS
3
4 off
2
3 off
1 DH30 /37 PLASTISOL COVER ASSY SA210801 :ITEM 1 2 3
PART No D163601 D139551 D141652
DESCRIPTION COVER PLASTISOL GREY LOUVRE SUPPORT GREY LOUVRE GREY
QUANTITY 1 3 4
DH30 /37 STAINLESS STEEL COVER ASSY SA210802 :ITEM 1 2 3
PART No D163602 D139552 D141654
DESCRIPTION QUANTITY COVER STAINLESS STEEL 1 LOUVRE SUPPORT ALUMINIUM 3 LOUVRE ALUMINIUM 4
page65
SD139460 ISSUE 21
DH33/33(7) GRP COVER ASSY'S SEE PARTS LISTS
SEE FIG 1
2
1
8.00 ± 2.00
3
FIG 1. 4
5
LOUVRE MOULDED COVER
LOUVRE IS FIXED TO COVER WITH FIXING PIN ITEM 3 AND HELD IN POSN' WITH SPRING ITEM 5 AND PUSH NUT ITEM 4. TO DIM' AS SHOWN.(IN 2 POSNS) COVER ASSY HONEY BEIGE SA223103 :ITEM 1 2 3 4 5
PART No SD263050 SD264201 SD264450 SD279550 SD284550
DESCRIPTION QUANTITY MOULDED COVER 1 LOUVRE ASSY (3 LOUVRES) 1 MOULDED FIXING PIN 2 PUSH NUT 2 COMPRESSION SPRING 2
COVER ASSY WHITE SA223105 :ITEM 1 2 3 4 5
PART No SD263052 SD264203 SD264451 SD279550 SD284550
DESCRIPTION QUANTITY MOULDED COVER 1 LOUVRE ASSY (3 LOUVRES) 1 MOULDED FIXING PIN 2 PUSH NUT 2 COMPRESSION SPRING 2
page66
SD139460 ISSUE 21
page67
SD139460 ISSUE 21
1
4 off
ITEM 1 2 3
PART No D140350 D139550 D141651
PARTS LIST :-
3 4 off
SA223102
DH50/50(7) GRP COVER ASSY
DESCRIPTION QUANTITY GRP COVER 1 LOUVRE SUPPORT HONEYSUCKLE 4 LOUVRE HONEYSUCKLE 4
2
page68
SD139460 ISSUE 21
1
DESCRIPTION QUANTITY COVER PLASTISOL GREY 1 LOUVRE SUPPORT GREY 4 LOUVRE GREY 4
ITEM 1 2 3
DESCRIPTION COVER STAINLESS STEEL LOUVRE SUPPORT ALUMINIUM LOUVRE ALUMINIUM
QUANTITY 1 4 4
PART No D166002 D139552 D141655
PART No D166001 D139551 D141653
ITEM 1 2 3
SEE PARTS LISTS
DH60/60(7) STAINLESS STEEL COVER SA64210804 :-
3
DH60/60(7) PLASTISOL COVER ASSY SA210803 :-
2
DH60/60(7) METAL COVER ASSY'S
page69
SD139460 ISSUE 21
5
4
3
PART No SD263060 SD264205 SD264450 SD279550 SD284550
DESCRIPTION MOULDED COVER HONEY BEIGE LOUVRE ASSY HONEY BEIGE (2 LOUVRES) FIXING PIN PUSH NUT COMPRESSION SPRING
FIG 1.
LOUVRE IS FIXED TO COVER WITH FIXING PIN ITEM 3 AND HELD IN POSN' WITH SPRING ITEM 5 AND PUSH NUT ITEM 4 TO DIM' AS SHOWN.(IN 4 POSN'S)
MOULDED COVER
LOUVRE
8.00 +/-2.00
PARTNo SD263061 SD264206 SD264451 SD279550 SD284550
DESCRIPTION QUANTITY MOULDED COVER WHITE 1 LOUVRE ASSY WHITE (2 LOUVRES) 2 FIXING PIN 2 PUSH NUT 2 COMPRESSION SPRING 2
ITEM 1 2 3 4 5 QUANTITY 1 2 2 2 2
2
ITEM 1 2 3 4 5
1
COVER ASSY WHITE SA223108 :-
2
COVER ASSY HONEYBEIGE SA223107 :-
SEE FIG 1.
SEE PARTS LISTS
DH55/55(7) GRP COVER ASSY'S
7.0 OPTIONAL KITS 7.1 LPHW ASSEMBLIES
L.P.H.W. ASSEMBLIES FOR DH33/33(7) & DH55/55(7)
6
1
8
7
LPHW ASSY DH33 SA281901 ITEM 1 6 7 8
PART No SD251750 SD284450 SA253954 SD091050
DESCRIPTION QUANTITY LPHW FIN BLOCK 1 AIR BLEED VALVE 1 THERMOSTAT CALIBRATED TO 40°C 1 PHIAL CLIP 1
LPHW ASSY DH55 SA281902 ITEM PART No DESCRIPTION 1 SD251751 LPHW FIN BLOCK 6 SD284450 AIR BLEED VALVE 7 SA253954 THERMOSTAT CALIBRATED 40°C 8 SD091050 PHIAL CLIP
page70
QUANTITY 1 1 1 1
SD139460 ISSUE 21
7.2 12V REMOTE HUMIDISTAT KIT
IF NOT ALREADY FACTORY FITTED
01/03 02/04
D372752 D372753
DH33/33(7)/55/55(7)A DH33/33(7)/55/55(7)AX
NOTES 1. SEE WIRING DIAGRAMS FOR CONNECTION & ALTERATIONS T0 ELEC BOX ASSY'S
5
THIS ITEM REPLACES MAINS IN TB ON ELEC BOX ASSY 2
3
BLUE PINK ORANGE BROWN B
12V REMOTE HUMIDISTAT KIT SA381001/02/03/04
ITEM 2 3 5
PART No SD336550 SD378350 SD072853
DESCRIPTION TRANSFORMER 0-12 (12V) RELAY 25A 12V COIL 15A 5 WAY TERM BLOCK
page71
QUANTITY 1.000 1.000 1.000
SD139460 ISSUE 21
7.3 12V REMOTE HUMIDISTAT CONNECTIONS
12v REMOTE HUMIDISTAT CONNECTIONS
HUMIDISTAT (NOT SUPPLIED, WE RECOMMEND CALOREX PART SD385250. SIEBE PART No.119 1701 91100)
E N L
Remote Control Interface 250M MAX 1mm SQ CABLE WITH REMOTE HUMIDISTAT FITTED ENSURE HUMIDISTAT IN MACHINE IS SET FULLY CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
12v REMOTE AIR THERMOSTAT CONNECTIONS
AIR STAT (NOT SUPPLIED, WE RECOMMEND CALOREX PART SD385251. SOPAC JAEGER TYPE TA630.01, INTERCONTROL PART No.Q302.07).
E N L
Remote Control Interface 250M MAX 1mm SQ CABLE 12v REMOTE AIR THERMOSTAT CONNECTIONS FOR M/C WITH RESISTANCE HEATERS
page72
SD139460 ISSUE 21
7.4 WEIR KIT
AUXILIARY DRIP TRAY (WEIR) KIT
2 2 off
EV AP OR AT
OR
1
64 ,0
0
APERTURE
KIT FOR DH30/33 SD64229501 :ITEM 1 - SD64218750 DRIP TRAY ITEM 2 - D64229650 STRIP
KIT FOR DH50/55/60 SD64229502 :ITEM 1 - SD64218751 DRIP TRAY ITEM 2 - D64229650 STRIP
page73
SD139460 ISSUE 21
7.5 AIR FILTER KITS
FRONT COVER WALL
4
5
FIXING TAPE
OR FILTER REAR SUPPORT BRACKET
2
1
3
AIR FILTER KIT DH30/30(7) GRP COVER ITEM 1 2 3 4 5
PART No SD171950 SD172350 SD180250 SD180450 SD180451
DESCRIPTION FILTER HOLDER FILTER SUPPORT BRACKET FILTER MEDIA FIXING TAPE HOOK FIXING TAPE LOOP
QUANTITY 1.000 1.000 1.000 0.700 M 0.700 M
AIR FILTER KIT DH50/50(7) GRP COVER ITEM 1 2 3 4 5
PART No SD171951 SD172351 SD180251 SD180450 SD180451
DESCRIPTION FILTER HOLDER FILTER SUPPORT BRACKET FILTER MEDIA FIXING TAPE HOOK FIXING TAPE LOOP
QUANTITY 1.000 1.000 1.000 1.150 M 1.150 M
AIR FILTER KIT DH30/30(7) STEEL COVER ITEM 1 2 3 4 5
PART No SD171952 SD172451 SD180250 SD180450 SD180451
DESCRIPTION FILTER HOLDER FILTER SUPPORT BRACKET FILTER MEDIA FIXING TAPE HOOK FIXING TAPE LOOP
QUANTITY 1.000 1.000 1.000 0.730 M 0.730 M
AIR FILTER KIT DH60/60(7) STEEL COVER ITEM 1 2 3 4 5
PART No SD171953 SD172450 SD180251 SD180450 SD180451
DESCRIPTION FILTER HOLDER FILTER SUPPORT BRACKET FILTER MEDIA FIXING TAPE HOOK FIXING TAPE LOOP
page74
QUANTITY 1.000 1.000 1.000 1.190 M 1.190 M
SD139460 ISSUE 21
7.5 AIR FILTER KITS CONT
FRONT COVER
2
1
AIR FILTER KIT DH33/33(7) GRP COVER(282101) ITEM 1 2
PART No DESCRIPTION QUANTITY SD268650 FILTER SUPPORT CHANNEL 1.000 SD264650 FILTER ASSY 1.000
AIR FILTER KIT DH55/55(7) GRP COVER(282102) ITEM ITEM 1 ITEM 2
PART No DESCRIPTION QUANTITY SD268651 FILTER SUPPORT CHANNEL 1.000 SD264651 FILTER ASSY 1.000
page75
SD139460 ISSUE 21
7.6 FLOOR STAND KITS
SA64180901/02
105.00
758.00
300.00
'X' SEE TABLE
280.00
USED ON DH30/33/3010 DH50/55/5010
STAND PART No SD64172050 SD64172051
DIMENSION 'X' 750.00mm 1070.00mm
ASSEMBLY INSTRUCTIONS SHEET SD64326450
page76
SD139460 ISSUE 21
7.7 REMOVAL AND SERVICING OF DRIPTRAY 1.IMPORTANT BEFORE REMOVING COVER, ISOLATE POWER FROM DEHUMIDIFIER.
2. REMOVE SCREWS FROM POSITION SHOW AND REMOVE COVER OF MACHINE
DRIPTRAY
BRACKET
3. LOOSEN SCREWS FROM BUSHES SHOWN AND SLIDE BOTTOM BRACKET AWAY.
4. PULL DRIPTRAY DOWN TO REMOVE AND SERVICE AS REQUIRED.
5. REVERSE STEPS 1-4 TO REPLACE DRIPTRAY, BRACKET AND COVER.
NOTE: DH33 STYLE DEHUMIDIFIER SHOWN.
page77
SD139460 ISSUE 21
8.0 WARRANTY CONDITIONS The following exclusions apply to the Warranty given by Calorex Heat Pumps Ltd. No claims will be accepted if :1. The dehumidifier is incorrectly sized for the application. 2. The dehumidifier is installed in any way that is not in accordance with the current procedures as defined by Calorex Heat Pumps Ltd. 3. The dehumidifier has been worked upon or is adjusted by anyone other than a person authorised to do so by Calorex Heat Pumps Ltd. 4. The air flow through the machine is outside the specified limits. 5. The water flow through the machine is outside the specified limits. 6. The water pH level and/or chemical balance is outside the following limits:-
Acidity pH Total Alkalinity, as CaCO3
pH ppm
7.4 - 7.8 80 - 120
Total Hardness, as CaCO3
ppm
150 - 250
Total Dissolved Solids
ppm
1000
Maximum Salt Content Free Chlorine Range
wt/wt ppm
8mg/l 1 - 2 Domestic
Free Chlorine Range Superchlorination
ppm max
3 - 6 Commercial 30ppm for 24 hrs
Bromine Baquacil
ppm ppm
2-5 25 - 50
Ozone Maximum Copper Content Aquamatic Ionic Purifier
ppm ppm ppm
0.9 Max 1 2 Max
7. The dehumidifier has suffered frost damage. 8. The electrical supply is insufficient or in anyway incorrect. IF IN DOUBT PLEASE ASK Note:- The Reply Paid Warranty Registration Card must be returned, to ensure that the correct warranty is given. If you do not find a Registration Card with your Dehumidifier please contact the Calorex Service Department giving your name, address and serial number of your Dehumidifier. A card will be sent to you for completion. Please give MODEL NUMBER and SERIAL NUMBER of your Dehumidifier when making technical or service enquiries. This will assist in correct diagnosis and ensure service can provide with a minimum delay. PHONE 01621 857171
FAX 01621 850871
Email
[email protected]
Web Site http://www.calorex.com
page78