Transcript
Republic of the Philippines CAGAYAN DE ORO CITY WATER DISTRICT Corrales Avenue, Cagayan de Oro City
TECHNICAL SPECIFICATIONS PR No. 14-19755 - 1 Lot Supply, Delivery, Installation and Configuration of UNIFIED STORAGE (SAN & NAS) Production Site, UNIFIED STORAGE (SAN & NAS) Disaster Recovery Site and DATA CENTER POWER BACKUP 1. Proposed Unified Storage (Storage Area Network & Network Attached Storage) and Data Center Power Backup Design and Scope of Works detail The minimum requirement or specification for the Unified Storage (Storage Area Network & Network Attached Storage) and the Backup Power of Data Center are detailed in the following subsections. While it is mandatory for the supplier to meet these minimum requirements, if the design of a particular requirement would need a higher category of product, the supplier should provide as such. The supplier should however provide basis for arriving at the solution being proposed as part of the offer. The supplier should design the solution to provide scalability to Cagayan de Oro Water District (COWD). Basic Requirement: To have a solution or architecture, unified not only across protocols and disks, but also in storage efficiency, processes, data management, data replication and data protection. This level of unification is essential for COWD’s Data Center to respond to consolidation of data. Data Protection includes safeguard against corruption of data due to unreliable power sources or power failures. Data Replication includes real-time block level backup to remote Disaster Recovery (DR) site. The overall Scope of Work (SoW) includes the following: • • •
To provide a Unified Storage Equipment for the consolidation of data from the system. To supply, deliver, install and configure the said Unified Storage Equipment that supports the direction of COWD for storage efficiency, data management, replication and protection. To provide a backup source of power for the entire Data Center in case there will be a power failure.
Note: The above scope of work is indicative and may not be exhaustive in any manner. The supplier shall be assumed to have accounted for best practices, all services and equipment necessary for the Unified Storage and Data Center Power Backup. 2. Bill of Materials: ITEM
DESCRIPTION
1.0
UNIFIED STORAGE FOR MAIN SITE (PRODUCTION SITE)
2.0
UNIFIED STORAGE FOR REMOTE SITE (DISASTER RECOVERY SITE)
3.0
GENERATOR SET FOR DATA CENTER POWER BACKUP
QTY
UOM
1
LOT
TECHNICAL SPECIFICATIONS 1. UNIFIED STORAGE FOR MAIN SITE (PRODUCTION USE) The storage equipment should support Storage Area Network (SAN) and Network Attached Storage (NAS) a)
HARDWARE No. of Controller Capacity, Raw Maximum Raw Capacity Internal Drives Maximum Internal Drives Internal + External Drives (Max) Supported Internal Drives o Performance HDD o Capacity HDD o SSD Self-encrypting Drives
Processor
ECC Memory Controller & Form Factor Maximum Flash Pool NVMEM/NVRAM Convert to Shelf Mirroring Software Power Supply Warranty
: Dual (2) : 10.8TB (12 x 900GB 10K RPM SAS Drive) : Not less than 749TB : 12 drives, Serial Attached SCSI (SAS) : Not less than 24 Drives : Not less than 144 Drives : Capable for 600GB, 900GB, 1.2TB Drives : N/A : Capable for 200GB, 400GB, 800GB, 1.6TB Drives : Capable for 900GB at 10K RPM, 800GB SSD AES 256, FIPS 140-2 compliant : 2 x 64-bit 2-core with HT 1.73 Ghz (1 per Controller) : 36GB (18GB per Controller) : Dual, 2U Chassis : 16TB : 4GB (2GB per Controller) : Yes : Included(up to block level) : Redundant : 1-Year
Rear Panel Onboard I/O; UTA 2 Onboard I/O; 6Gb SAS Onboard I/O; GbE Onboard I/O; Mgmt Port Onboard I/O; USB Onboard I/O; Console Port Alternate Control Path
: 8 x SFP Ports (8Gb FC, 16Gb FC, FCoE, 10GbE) : 4 x QSFP Ports : 4 x RJ45 Ports : 2 x Private Mgmt Port : 2 x USB Port : 2 x RJ45 Port : 2 x RJ45 Port
Others Cables
: 1 x 10GbE Twinax Cable, 5m
b) CONFIGURATIONS Storage protocols supported
OS Version High-Availability Features
: iSCSI, FCoE, and FC; NFS V2/V3/V4 over UDP or TCP, PCNFSD V1/V2 for (PC) NFS client authentication; Microsoft® CIFS, HTTP 1.0, HTTP 1.1 virtual hosts : Appropriate Proprietary OS of the OEM : Alternate Control Path (ACP);
Ethernet-based service processor and OS management
Supported Configurations
Disk Shelves Supported Maximum RAID
Host/Client OS supported
Max. Number of LUNs Number of Supported Hosts
Flexible Volumes Snapshot Copies Maximum Volume Size Maximum Aggregate Size Operating Acoustic Noise
interface; redundant hot-swappable controllers, cooling fans, and power supplies : Equipment is capable for Cluster Configurations or supported for 2 Controllers : Cluster Configurations Single-node cluster Two-node switchless cluster Two-node switched cluster Clusters of HA pairs : 7-Mode Configurations : Controllers: Single controller Active-active controllers in an HA pair Active-passive controllers in an HA pair : Back-End Disks: Single path with single controller or HA Pair Dual path with single controller MP-HA with HA pair (best practice) : 2U; 24 Drives, 2.5” SFF or 4U; 24 Drives, 3.5” LFF : RAID 6 (RAID-DP) SAS and FC: 28 (26 data disks plus 2 parity disks) SATA: 20 (18 data disks plus 2 parity disks) RAID 4 SAS and FC: 14 (13 data disks plus 1 parity disk) SATA: 7 (6 data disks plus 1 parity disk) RAID 6 + RAID 1 or RAID 4 + RAID 1 : Windows 2000, Windows Server 2003, Windows Server 2008, Windows Server 2012, Windows XP, Linux, Oracle Solaris, AIX, HP-UX, Mac OS, VMware, ESX : 2048 per controller : Up to 6 ports per controller configured as front-end (host) connectivity ports Up to 12 directly connected servers per activeactive configuration Connected hosts per HA pair: Up to 512 SAN connected servers : Not less than 500 per controller : Not less than 255,000 per controller :60TB :120TB :Declared sound power (LwAd) per ISO 9296: 6.2 Bel :Sound pressure (LpAm) (bystander positions): 49.6 dB
c) SOFTWARE With data replication technology that provides disaster recovery protection (offsite block level replication) and simplifies the management and replication Efficiency: Flexible volumes, Up to block level of deduplication, compression, and thin provisioning Availability: Multipath I/O , secure multi-tenancy Data protection: RAID-Distributed Parity, Snapshot Performance: Storage QoS Management: System Setup, System Manager, Unified Manager 2. UNIFIED STORAGE FOR REMOTE SITE (DISASTER RECOVERY) The storage equipment should support Storage Area Network (SAN) and Network Attached Storage (NAS) a)
HARDWARE No. of Controller Capacity, Raw Maximum Raw Capacity Internal Drives Maximum Internal Drives Internal + External Drives (Max) Supported Internal Drives Performance HDD Capacity SSD Self-encrypting Drives
Processor ECC Memory Controller & Form Factor Maximum Flash Pool NVMEM/NVRAM Convert to Shelf Power Supply Warranty
Rear Panel Onboard I/O; UTA 2 Onboard I/O; 6Gb SAS Onboard I/O; GbE Onboard I/O; 10GbE Onboard I/O; Mgmt Port Onboard I/O; USB Onboard I/O; Console Port Alternate Control Path b) CONFIGURATIONS Storage protocols supported
: Single (1), Capable for Dual : 24TB (12 x 2TB 10K RPM SATA Drive) : Not less than 504TB : 12 drives, SATA : Not less than 12 Drives : Not less than 84 Drives : Capable for 600GB, 900GB, 1.2TB Drives : Capable for 2TB, 3TB, 4TB Drives : Capable for 200GB, 400GB, 800GB, 1.6TB Drives : Capable for 900GB at 10K RPM, 800GB SSD AES256, FIPS 140-2 compliant : 1 x 64-bit 2-core with HT 1.73 Ghz : 18GB : Single, 2U Chassis : 16TB : 2GB : No : Redundant : 1-Year
: None : 2 x QSFP Ports : 2 x RJ45 Ports : 4 x RJ45 Ports : 1 x Private Mgmt Port : 1 x USB Port : 1 x RJ45 Port : 1 x RJ45 Port : iSCSI; NFS V2/V3/V4 over UDP or TCP, PCNFSD V1/V2 for (PC) NFS client authentication; Microsoft® CIFS, HTTP 1.0, HTTP 1.1 virtual hosts
OS Version High-Availability Features
Supported Configurations
Disk Shelves Supported Maximum RAID
Host/Client OS supported
Max. Number of LUNs Number of Supported Hosts
Flexible Volumes Snapshot Copies Maximum Volume Size Maximum Aggregate Size Operating Acoustic Noise
: Appropriate Proprietary OS of the OEM : Alternate Control Path (ACP);
Ethernet-based service processor and OS management interface; redundant hot-swappable controllers, cooling fans, and power supplies : Equipment is capable for Cluster Configurations or supported for 2 Controllers : Cluster Configurations Single-node cluster Two-node switchless cluster Two-node switched cluster Clusters of HA pairs : 7-Mode Configurations : Controllers: Single controller Active-active controllers in an HA pair Active-passive controllers in an HA pair : Back-End Disks: Single path with single controller or HA Pair Dual path with single controller MP-HA with HA pair (best practice) : 2U; 24 Drives, 2.5” SFF or 4U; 24 Drives, 3.5” LFF : RAID 6 (RAID-DP) SAS and FC: 28 (26 data disks plus 2 parity disks) SATA: 20 (18 data disks plus 2 parity disks) RAID 4 SAS and FC: 14 (13 data disks plus 1 parity disk) SATA: 7 (6 data disks plus 1 parity disk) RAID 6 + RAID 1 or RAID 4 + RAID 1 : Windows 2000, Windows Server 2003, Windows Server 2008, Windows Server 2012, Windows XP, Linux, Oracle Solaris, AIX, HP-UX, Mac OS, VMware, ESX : 2048 per controller : Up to 6 ports per controller configured as frontend (host) connectivity ports : Not less than 500 per controller : Not less than 255,000 per controller :60TB :120TB :Declared sound power (LwAd) per ISO 9296: 6.2 Bel :Sound pressure (LpAm) (bystander positions): 49.6 dB
c) SOFTWARE With data replication technology that provides disaster recovery protection (offsite block level replication) and simplifies the management and replication Efficiency: Flexible volumes, Up to block level of deduplication, compression, and thin provisioning Availability: Multipath I/O , secure multi-tenancy Data protection: RAID-Distributed Parity, Snapshot Performance: Storage QoS Management: System Setup, System Manager, Unified Manager 3. GENERATOR SET
Standby Power
: 35kVA/28kW
Prime Power
: 32.5kVA/26kW
Cylinders
: 3-in-line
Aspiration
: Turbocharged
Fuel Type
: Diesel
Fuel Consumption @ 100% Load
: 7 Liters per hour or less
Rated Voltage
: 220V
Phase
: 3-Phase
Current Distortion
: ≤ 7%
Frequency and Speed
: 60Hz@1800rpm
Current (A)
: 79/99
Power Factor
: 0.8
Type
: Open Set
Insulation Grade
:H
Protection Grade
: IP23
Certificates
: ISO9001:2008, CE,
With Generator Set Controller Module Description: Automatic Start Control Module designed to automatically start and stop the Generator with the close/open signal for the Generator Circuit Breaker. The module also monitors and protects the engine, indicating operational status, fault conditions and metering on the front panel LCD and LED's. Features: 128 x 64 graphic LCD True RMS measuring Configuration of parameters by front panel push buttons or communication software RS485, RS232, or USB port for remote communication. Configurable fuel output energise to stop or energise to run.
7 Configurable inputs. 5 Configurable outputs, 1 used for GCR. 2 Analogue inputs configurable for different senders for Oil pressure and Engine temperature. 2 Aux.configurable analogue inputs Push Button for manual control of GCR Specifications: DC supply: 8.0V to 35V continuous Cranking drop outs: 0V for 100mS, assuming DC supply was at least 10V before dropout and recovers to 5V AC input voltage: phase voltage 15-300 VAC RMS (AC frequency 40 Hz) AC input frequency: 3-70Hz (voltage 15V) Max operating current: @12V 0.4A, @24V 0.2A Max frequency input of the speed sender: 10000Hz Voltage input of the speed sender: 1-70 VDC Accuracy 0.5% Start relay output: 16A/30VDC Fuel relay output: 16A/30 VDC Aux. control relay output: 3A/30 VDC Protection: Controller fascia IP65 when correctly installed Operating temperature: -20 to 70 C Storage temperature: -30 to 80 C
Soundproof Enclosure Buffers/silences noise produced by Genset operation. Locally manufactured using gauge 14 steel sheets, stainless steel locks and hinges, stainless steel fasteners and double-coated with automotive enamel paint, and lined with industrial-grade, flameretardant foam.
Accessories Set-mounted tropical radiator Skid-based with anti-vibration mounts Skid-based diesel tank Exhaust silencer C/W flexible pipe Lead acid batteries with cables Set of engine and operation manuals
Running and load test must be conducted as prerequisite before acceptance - Test up to 100% load
4. QUALIFICATIONS:
Should have Certification as Authorized Reseller and Service Provider of the following: 1) Unified Storage; 2) Power Backup System (Generator Set).
The above certifications should be issued by the Manufacturer/Distributor of the brand as proof of support.
5. TRAINING
Provide a Unified Storage System Administrator’s Training for 2 personnel. (Please see Annex 4 for the training course outline)
The trainer should be a certified instructor of the manufacturer's storage system.
Provide in-house training upon implementation of the system upon turn-over.
ANNEX 1 CONTRACTOR QUALIFICATIONS AND TRAINING 1) The Contractor shall be fully conversant and capable in the Storage Solutions and Power Backup. 2) The supplier shall ensure that configuration and implementation should be as per the requirement of the end-user. Proper Documentation and over-all design transfer is part of the submittals before final acceptance of the project. ANNEX 2 WARRANTY The supplier shall submit a warranty certificate for the following: 1) Storage Equipment - 1 year 2) Data Center Power Backup - 1 year
ANNEX 3 DESIGN & LAYOUT The supplier shall submit design and layout.
ANNEX 4
TRAINING COURSE OUTLINE The training should cover at the least the following topics/subjects/modules: 1) The Storage Environment - Key features and functions of the storage systems. 2) The file system - Data written to and read from the file system on a volume; 3) Basic Administration - Connect remotely to a storage system by using the console and a remote host 4) Physical Storage - Storage system supported RAID technology 5) Logical Storage - Concepts related to volumes in the storage operating system 6) Administration Security - Restrict administrative access 7) Networking - Configuration of network settings and components in the storage operating system 8) NFS - NFS implementation in the storage operating system 9) CIFS - CIFS environment 10) NAS Management - Security methods for protecting data 11) SAN- Purpose of a SAN 12) LUN and LUN attributes 13) Snapshot Copies - Function of Snapshot copies 14) Space Management - Storage efficiency techniques that are available within the storage operating system 15) High-Availability - High-availability (HA) solutions 16) Virtualization Solutions - Virtualize a storage controller by using the unified storage software 17) Backup and Recovery Methods - Methods available to back up and recover data 18) Data Collection Tools