Transcript
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS Sealed system equipment for heating for use with high efficiency condensing boilers with ultra low NOx emissions UNVENTED DHW PRODUCTION/STORAGE
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
The new Remeha
Remeha Pressurisation Equipment Compact wall mounted and free standing pressurisation units, utilising the latest microprocessor control. For use on sealed heating and cooling systems, offering accurate control and reliability • Digital equipment comes with a 4 digit bright LED display with scrolling messages including pump operation and alarm modes • Single or twin pump configurations • Complete with integral water break tank utilising an AB air gap and a WRAS approved float valve • Twin pump equipment operates as cyclic duty – standby with automatic changeover • Internal alarm with mute function • Security password protected • Auto resetting low water detection for pump protection • Auto resetting high and low pressure alarm • Digital pressure setpoint with adjustable differential • Flood protection through a pump run limit timer and Excessive Start option • Normally closed, common fault, volt free contact (boiler interlock) • Normally open, individual volt free contacts for pump trip, high pressure, low pressure and sensor health • All volt free contacts are rated for use with electrical supplies up to 230v with a maximum current draw of 5 amps Pumpset
Arrangement
Duty Max working Pump Full load Electrical Head pressure power current supply (bar(g)) (bar(g)) rating (w) (amps)
Flexfiller Midi, Basepak and Flexconpak 125D
Single pump
2.5
10.0
370
2.5
230/50/1
225D
Twin Pump
2.5
10.0
370
2.5
230/50/1
150D
Single pump
5.0
10.0
500
3.4
230/50/1
250D
Twin Pump
5.0
10.0
500
3.4
230/50/1
280DS
Twin Pump
8.0
10.0
750
5.6
230/50/1
Flexconpack cabinet housed and Basepak baseplate mounted packaged sealed system units, Presspak packaged sealed system units, and floorstanding pressurisation units are available with a range of options to suit your specific requirements. For full details please contact our sales office.
2.0 1.5 1.0
3.0
6.0
9.0
12.0
Flexfiller 130D/230
0.5
0.6
2
Flexfiller 125D/225D
3.0 2.5
3.0
6.0
9.0 12.0 15.0 Flow Rate (l/min)
0.9
1.0
6.0 4.0 2.0 0.0
3.0
6.0
18.0
6.0 4.0 2.0 3.0
6.0
9.0 12.0 15.0 Flow Rate (l/min)
12.0
Flexfiller 280DS
10.0
8.0
0.0
9.0
Flow Rate (l/min)
Flexfiller 150D/250D
10.0
2.0 1.5 1.0 0.5 0.0
0.8
8.0
Flow Rate (l/min)
Delivery Pressure (bar)
Delivery Pressure (bar)
Flow Rate (l/min)
0.7
Flexfiller Midi 150/250
10.0
18.0
Delivery Pressure (bar)
0.5 0.0
3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0
Delivery Pressure (bar)
Midi 125/225
3.0 2.5
Delivery Pressure (bar)
Delivery Pressure (bar)
For high specification installations, consider the Flamco digital upgrade. The upgrade features include: • Excessive start alarm (>3 times in 8 hours) • RS 485 Connectivity • Hours run counter (per pump) • Pump pulse option (2 second pulse per pump if inactive for 60 days) • 12-month service reminder • Fill system option (not available on 130D/230D)
8.0 6.0 4.0 2.0 0.0
3.0
6.0
9.0 12.0 Flow Rate (l/min)
15.0
18.0
Flexfiller Midi - Wall mounted pressurisation unit Model
Pump Quantity
Height (mm)
Width (mm)
Depth (mm)
Weight (Kg)
System Connection
Flexfiller Midi 125
1
485
245
245
13.5
1/2" BSP F
Flexfiller Midi 150
1
485
360
276
14
1/2" BSP F
Flexfiller Midi 225
2
485
360
276
16
1/2" BSP F
Flexfiller Midi 250
2
485
360
276
16
1/2" BSP F
Flexfiller Standard - Free standing pressurisation unit Model
Pump Quantity
Height (mm)
Width (mm)
Depth (mm)
Weight (Kg)
System Connection
Flexfiller 125D
1
800
470
320
28
1/2" BSP M
Flexfiller 225D
2
800
470
320
30
1/2" BSP M
Flexfiller 150D
1
800
470
320
28
1/2" BSP M
Flexfiller 250D
2
800
470
320
40
1/2" BSP M
Flexfiller 280Ds
2
800
470
320
42
1/2" BSP M
Basepak Expansion Equipment, Skid mounted Flexfiller pressurisation unit complete with Flexcon Expansion Vessel Model
Pump Quantity
Height (mm)
Width (mm)
Depth (mm)
Weight (Kg)
System Connection
Basepak 25-125D*
1
950
600
940
41
1/2" BSP M
Basepak 50-125D*
1
950
600
940
46
1/2" BSP M
Basepak 80-125D*
1
950
600
940
75
1/2" BSP M
Basepak 110-125D*
1
950
600
940
90
1/2" BSP M
Basepak 140-125D*
1
1400
600
940
98
1/2" BSP M
Basepak 200-125D*
1
1450
600
940
105
1/2" BSP M
Basepak 300-125D*
1
1480
600
940
135
1/2" BSP M
Basepak 425-125D*
1
1330
800
1170
155
1/2" BSP M
Basepak 600-125D*
1
1690
800
1170
190
1/2" BSP M
Basepak 800-125D*
1
2038
800
1170
225
1/2" BSP M
Basepak 1000-125D*
1
2420
800
1170
245
1/2" BSP M
Basepak 2x600-125D*
1
1690
800
2000
323
1/2" BSP M
Basepak 2x800-125D*
1
2038
800
2000
391
1/2" BSP M
Basepak 2x1000-125D
1
2420
800
2000
431
1/2" BSP M
* High head and/or twin pumpsets available on request.
Flexconpak Expansion Equipment, Cabinet housed pressurisation equipment with integral flexcon expansion vessel Model
Pump Quantity
Height (mm)
Width (mm)
Depth (mm)
Weight (Kg)
System Connection
Flexconpak 25-125D*
1
1200
680
730
84
1/2" BSP M
Flexconpak 35-125D*
1
1200
680
730
86
1/2" BSP M
Flexconpak 50-125D*
1
1200
680
730
90
1/2" BSP M
Flexconpak 80-125D*
1
1200
680
730
95
1/2" BSP M
Flexconpak 110-125D*
1
1590
680
730
114
1/2" BSP M
Flexconpak 140-125D*
1
1590
680
730
118
1/2" BSP M
Flexconpak 200-125D*
1
1970
680
730
138
1/2" BSP M
Flexconpak 300-125D*
1
1970
730
780
170
1/2" BSP M
Flexconpak 425-125D*
1
1800
940
990
215
1/2" BSP M
Flexconpak 600-125D*
1
2290
940
990
258
1/2" BSP M
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Remeha Pressurisation Equipment
* High head and/or twin pumpsets available on request.
3
Flexcon Expansion Vessels Sizing Flexcon expansion vessels for domestic heating Calculations in accordance to BS 7074:1990 Code of Practice.
4
Maximum working Static Water Boiler pressure bar (g) Head (m) content (l) Rating (kW)
Boiler Vessel Pre-charge Calculated Rating (BTU) Size (bar) System Efficiency
3
5
3
10
3
15
3
20
10246 17076 37567 54643 81964 112701 160518 228817 365424 502031 638638 908438 1366072 1936406 2732143 10246 17076 37567 54643 81964 112701 160518 228817 365424 502031 638638 908438 1366072 1936406 2732143 10246 17076 37567 54643 81964 112701 160518 228817 365424 502031 638638 908438 1366072 1936406 2732143 10246 17076 37567 54643 81964 112701 160518 228817 365424 502031 638638 908438 1366072 1936406 2732143
36 60 132 192 298 396 564 804 1284 1764 2244 3192 4800 6804 9600 36 60 132 192 288 396 564 804 1284 1764 2244 3192 4800 6804 9600 36 60 132 192 288 396 564 804 1284 1764 2244 3192 4800 6804 9600 36 60 132 192 288 396 564 804 1284 1764 2244 3192 4800 6804 9600
3 5 11 16 24 33 47 67 107 147 187 266 400 567 800 3 5 11 16 24 33 47 67 107 147 187 266 400 567 800 3 5 11 16 24 33 47 67 107 147 187 266 400 567 800 3 5 11 16 24 33 47 67 107 147 187 266 400 567 800
2 4 8 12 18 25 35 50 80 110 140 200 300 425 600 2 4 12 18 25 35 50 80 110 140 200 300 425 600 600 4 8 12 18 35 35 50 80 140 200 200 300 425 800 800 8 5 18 35 50 80 80 110 200 300 300 425 800 1000 2 x 600
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 62.5% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 50.0% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 37.5% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0% 25.0%
Sizing Flexcon expansion vessels
Static height is the vertical distance from the expansion vessel mid point (lower part of the system) to the highest point of the system above the expansion vessel.
Basic Calculation
Expansion Vessel Efficiency (VE)
Vessel System Water Content x Coefficient of Expansion Vessel Size = Efficiency = Expansion Vessel Efficiency
Max. Pressure – Min. Pressure Max. Pressure
Please note the pressure must be in absolute units (gauge pressure + 1 bar(g)) Maximum pressure = maximum working pressure at the expansion vessel Minimum pressure = expansion vessel gas charges (normally dependent on the system static height) + 0.2 bar(g) 0.7 bar(g) Please note the expansion vessel efficiency must not exceed the maximum stated by Flamco UK Ltd. Sizing charts have taken this into consideration
Maximum vessel efficiency Range
Size Litres
Efficiency
Flexcon
2-600
0.625 (62.5%)
Flexcon
800
0.5 (50%)
Flexcon
1000
0.4 (40%)
Airfix P
2-500
0.6 (60%)
Airfix P
750-1000
0.5 (50%)
Airfix DE
50-3000
0.6 (60%)
Example (Basic Sizing) System
Water content = 1000litres Temperature = 82oC Maximum working Pressure = 3 bar(g)
Maximum expansion vessel sizing (Gas charge 1 bar(g)). Coefficient 4-2 VE = = 0.5 (50%) of expansion = 0.032 4 1000 x 0.032 Expansion vessel size = = 64litres 0.5 (Use the nearest higher size. e.g. Flexcon 80/1).
Heating systems – Flexcon standard expansion vessels. Sizing to BS 7074 Heating and Chilled Water Sealed Systems up to 5 bar(g) Using the following criteria far calculations: Water content = system water content + 10% Coefficient of expansion = use system highest temperature (not mean temp) Maximum pressure = safety valve setting – 10% (e.g. for 3 bar(g) Safety valve maximum pressure = 2.7 bar(g)) Miximum pressure = expansion vessel gas charge + 0.2 bar(g) (0.5 + 0.2 = 0.7 bar(g) minimum) For elevated temperature systems it is necessary to ensure that the water at the highest point in the system does not flash to steam. An anti-Flash margin, usually 11oC, should be added to the flow temperature. The corresponding vapour pressure for this temperature should then be added to the static height of the system. This new minimum pressure must be used for the expansion calculations and will protect the system in accordance with BS 7074 part 2. If in doubt please contact Flamco UK Ltd. for advice.
Water at 10ºC expands approx. 0.5% Water at 60ºC expands approx. 1.7%
Expansion coefficient
Remtank Unvented Cylinders Expansion Vessel supplied with kits 0.06 0.05 0.04 0.03 0.02
Using a safety factor of 25% water expands 0.01 between 10ºC and 60ºC @ 1.5% 0 0 10 20 Using the vessel efficiency calculated as above = 42.8% 1000Ltr x 1.5% = 15Ltr expansion; 15 / 42.8% = 35 (35Ltr vessel) 800Ltr x 1.5% = 12Ltr expansion; 15 / 42.8% = 28 (35Ltr vessel) 500Ltr x 1.5% = 7.5Ltr expansion; 15 / 42.8% = 17.5 (24Ltr vessel)
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Flexcon Expansion Vessels
30 40 50 60 70 80 90 100 110 120 Degrees Centigrade (oC) Coefficient of Expansion (water with no additives)
NOTE: The above sizing relates to Cylinder water content ONLY. Any additional system expansion should be calculated independently.
5
Flexcon Expansion Vessels Flexcon 6.0 bar(g) For heating and chilled water installations Flexcon diaphragm expansion vessels are made of top-quality steel and come with a high gloss epoxy coating. Together with the clench ring on vessels 2litres - 80litres the design offers a high quality and reliable product. The rolling action of the Flexcon diaphragm provides the vessel with a longer life. For high specification installations consider the Flamco digital upgrade. The upgrade features include: • Max. working pressure: 6.0 bar(g) • Max. vessel temperature (diaphragm): 70ºC. • Max. supply temperature (boiler): 90ºC. • Max. working temperature (design): 120ºC. Flexcon 2-4 Type
Capacity Gas Dimensions (litres) Charge ø H (bar) (mm) (mm)
Flexcon 2 Flexcon 4
2 4
0.5 0.5
194 194
Syst. conn. BSP (M)
Dry Weight (kg)
3/4” 3/4”
2.2 3.1
152 257
3.0 bar (g) Order Code 1 1
FCST 002 FCST 004
MB2 Mounting Brackets available for 2-25 Litre vessels
Gas charge must be stated on order, e.g. Flexcon 2/05 = 2 litre vessel with 0.5 bar gas charge. Gas charge will determine the maximum working pressure. Other gas charges supplied to suit.
Flexcon 8-25 Type
Capacity Gas Dimensions (litres) Charge ø H (bar) (mm) (mm)
Flexcon 8 Flexcon 12 Flexcon 18 Flexcon 25
8 12 18 25
0.5 0.5 0.5 0.5
245 286 328 358
Syst. conn. BSP (M)
Dry Weight (kg)
3/4” 3/4” 3/4” 3/4”
4.4 5.8 7.5 9.6
Syst. conn. BSP (M)
Dry Weight (kg)
3/4” 3/4” 1”
11.8 15.1 22.1
280 313 306 359
6.0 bar (g) Order Code 1 1 1 1
FCST 008 FCST 012 FCST 018 FCST 025
Flexcon 35-80 Type
Capacity Gas Dimensions (litres) Charge ø H (bar) (mm) (mm)
Flexcon 35 Flexcon 50 Flexcon 80
35 50 80
1.5 1.5 1.5
396 437 519
416 473 540
6.0 bar (g) Order Code 1 1 1
FCST 035 FCST 050 FCST 080
Gas charge must be stated on order, e.g. Flexcon 35/05 = 35 litre vessel with 0.5 bar gas charge. Gas charge will determine the maximum working pressure. Other gas charges supplied to suit.
Flexcon 6.0 - 10.0 bar(g) Flexcon 110-1000 Type
Flexcon 110 Flexcon 140 Flexcon 200 Flexcon 300 Flexcon 425 Flexcon 600 Flexcon 800 Flexcon 1000
Capacity Gas Dimensions (litres) Charge ø H (bar) (mm) (mm) 110 140 200 300 425 600 800 1000
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
484 484 484 600 790 790 790 790
784 950 1330 1330 1180 1540 1888 2268
Syst. conn. BSP (M) 1” 1” 1” 1” 1” 1” 1” 1”
Dry Weight (kg)
Order Code
6.0 10 bar (g) bar (g) 23.8 25.3 38.1 56.9 76.4 92.9 126.9 145.9
38.5 44.6 49.3 73.7 105.5 132.0 181.8 211.0
1 1 1 1 1 1 1 1
6.0 bar (g)
10 bar (g)
FCST 110 FCST 140 FCST 200 FCST 300 FCST 425 FCST 600 FCST 800 FCST 1000
FCST 110 FCST 140 FCST 200 FCST 300 FCST 425 FCST 600 FCST 800 FCST 1000
Gas charge must be stated on order, e.g. Flexcon 110/05 = 110 litre vessel with 0.5 bar gas charge. Gas charge will determine the maximum working pressure. Other gas charges supplied to suit.
6
Boiler
Boiler
LTHW System
Boiler
Boiler
Chilled System
Chiller
Chiller
1. Flexcon floor standing digital flexfiller 2. Flexcon Uni-fil filling set (must be disconnected after filling system) 3. Flexcon expansion vessel sited on heating system return 4. Flexvent Super automatic air vent - mounted vertically where air naturally collects 5. PS Vessel (Intermediate for heating or Buffer for chilled systems) 6. Safety valve and tundish sited on top or above the boiler or plant 7. Flamcovent clean de-aerator - in flow from the boiler before the pump 8. Supastor indirect calorifier 9. PSDpressure step degasser
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
MTHW System
7
Remtank SS Direct Unvented Cylinders Direct unvented cylinders for potable water installations Fluid Flow Sequence Mains Water Isolation Valve (not supplied) 3 bar Pressure Reducing Valve Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve) Expansion Vessel Drain Valve (not supplied) Stainless Supastor Hot Water Calorifier
Tundish
Combined Temperature & Pressure Relief Valve Factory Fitted 7 bar / 95oC
Safety Group c/w Non Return Valve 6 bar Relief Valve
Selection Guide Property Type
Pressure Reducing Valve Pre-Set
Direct Size
Expansion Vessel 120 - 500 3/4” Connection 800 - 1000 1” (Floor Standing Model)
Bedsit 1/2 beds with 1 bath / shower
120
3 beds with 1 bath / shower
150 or 180
4 beds with 1 bath / shower
180 or 210
3kW 230v/50Hz Immersion Heater
2/3 beds with 2 baths / showers 210 4/5 beds with 2 baths / showers 210 or 250
Vessels
Sports club, Restaurant etc.
300 or 500
Hotels, Schools etc
800 or 1000
Direct vessels can be supplied without kits as a storage vessel
Technical Specification Direct (including Kit) Volume (Nominal/litres)
120
150
180
210
250
300
500
800
1000
Direct Height (mm)
977
1167
1347
1569
1759
1750
1823
1960
2360
Diameter (mm)
550
550
550
550
550
606
734
950
950
Weight (dry/kg)
20.8
23.5
26.5
33
35.5
42
59
100
115
Weight (normal full/kg)
141
174
207
243
286
342
559
900
1115
T&P Tapping (inches)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
T&P Pressure Setting (bar)
7
7
7
7
7
7
7
7
7
T&P Temperature Setting (ºC)
95
95
95
95
95
95
95
95
95
Expansion Relief Setting (bar)
6
6
6
6
6
6
6
6
6
Electrical Heater Quantity
2
2
2
2
2
2
2
2
2
Electrical Heater Rating (each/kW)
3
3
3
3
3
3
3
3
3
Re-heat Times (2x3 kW/mins)
34
46
56
69
80
101
159
260
318
Heat Up Times (from cold/mins)
63
78.7
94.4
157.3
262.2
Expansion Vessel (litres)
35
35
35
35
50
110.1 131.1 35
35
419.6 524.5 80
Insulation is interlocked polystyrene to allow for inspection of cylinder if required. N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is the responsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required.
8
80
Secondary Flow (120 - 300) (500 - 1000)
120 to 300 litre
500 to 1000 litre
Technical Specification Connections Volume (Nominal/ litres Direct)
120
150
180
210
250
300
500
800
1000
Height A (mm)
977
1167
1347
1569
1759
1750
1823
1960
2360
Diameter B (mm)
550
550
550
550
550
606
734
950
950
Cold Water C (mm)
51
51
51
51
51
51
52
338
338
Cold Water Connection (BSP (M)/inches)
1
1
1
1
1
1
1 1/2
1 1/2
1 1/2
Immersion D (mm)
289
289
289
289
289
282
317
343
343
T&P Valve J (mm)
749
939
1119
1341
1531
1532
1517
1603
2003
644
834
1014
1236
1426
1444
932
1103
1103
Top Centre
Top Centre
Top Centre
Top Centre
1517
1603
2003
1
1
1
1
1 1/2
1 1/2
1 1/2
500
800
1000
Immersion K (mm) DHW Flow J DHW Connection (BSP (M)/inches)
Top Top Centre Centre 1
1
Supastor Optional Immersion Compatibility Chart SS Supastor Direct Immersion Sizes (litres Direct)
120
150
180
210
250
300
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Remtank SS Direct Unvented Cylinders
3 kW (Standard) 6 kW 9 kW 12 kW 18 kW
9
Remtank SS Indirect Unvented Cylinders Indirect unvented cylinders for potable water installations Fluid Flow Sequence Mains Water Isolation Valve (not supplied) 3 bar Pressure Reducing Valve Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve) Expansion Vessel Drain Valve (not supplied) Stainless Supastor Hot Water Calorifier
Tundish
Combined Temperature & Pressure Relief Valve Factory Fitted 7 bar / 95oC
Safety Group c/w Non Return Valve 6 bar Relief Valve
Selection Guide Property Type
Pressure Reducing Valve Pre-Set
Indirect Size
Bedsit 1/2 beds with 1 bath / shower
120
3 beds with 1 bath / shower
150 or 180
4 beds with 1 bath / shower
180 or 210
3kW 230v/50Hz Immersion Heater
Expansion Vessel 120 - 500 3/4” Connection 800 - 1000 1” (Floor Standing Model) IMIT Combined Thermostat & Safety Relay
2/3 beds with 2 baths / showers 210 4/5 beds with 2 baths / showers 210 or 250 Sports club, Restaurant etc.
300 or 500
Hotels, Schools etc
800 or 1000
Port Valve for use with the IMIT Thermostat controlling the primary flow (boiler) water to the coil
Technical Specification Indirect (including Kit) Volume (Nominal/litres)
120
150
180
210
250
300
500
800
1000
Indirect Height (mm)
976
1167
1347
1569
1759
1750
1823
1960
2360
Diameter (mm)
550
550
550
550
550
606
734
950
950
Weight (dry kg)
23
27
30
38
41
50
68.5
Weight (normal full/kg)
143
177
210
248
291
350
569
911
1245
T&P Tapping (inches)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
110.5 124.5
T&P Pressure Setting (bar)
7
7
7
7
7
7
7
7
7
T&P Temperature Setting (ºC)
95
95
95
95
95
95
95
95
95
Expansion Relief Setting (bar)
6
6
6
6
6
6
6
6
6
Electrical Heater Quantity
1
1
1
1
1
1
1
2
2
Electrical Heater Rating (each/kW)
3
3
3
3
3
3
3
3
3
Re-heat Times (82ºC supply/mins)
17
20
25
22
24
20
31
31
40
Heat Up Times (from cold/mins)
29
31
37
27
30
25
38
40
49
Max. Primary Pressure (coil/bar)
16
16
16
16
16
16
16
16
16
Primary Flow Rate (boiler L/min)
25
34
34
42
42
59
67
92
92
Primary Resistance (mbar)
36
76
76
172
188
475
292
695
695
Continuous Output (Ltr p/h)
409
438
428
572
624
897
959
1528
1479
Coil Rating (kW)
21.8
23.3
22.8
30.5
33.2
47.8
51
81.3
78.7
35
35
35
35
35
35
50
80
80
Expansion Vessel (Ltr)
Insulation is interlocked polystyrene to allow for inspection of cylinder if required. N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is the responsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required.
10
Indirect unvented cylinders for potable water installations
Secondary Flow (120 - 300) (500 - 1000)
120 to 300 litre
500 litre
800 to 1000 litre
Technical Specification Connections Volume (Nominal/ litres Indirect)
120
150
180
210
250
300
500
800
1000
Height A (mm)
976
1167
1347
1569
1759
1750
1823
1960
2360
Diameter B (mm)
550
550
550
550
550
606
734
950
950
Cold Water C (mm)
51
51
51
51
51
51
52
50
338
Cold Water Connection (BSP (M)/inches)
1
1
1
1
1
1
1
1 1/2
1 1/2
Immersion D (mm)
419
419
419
419
419
412
932
343
343
Primary Return E (mm)
379
379
379
554
579
722
832
1038
1038
Primary Flow F (mm)
51
51
51
51
51
51
312
338
338
Primary Connection (BSP (M)/inches)
1
1
1
1
1
1
1
1
1
DHW Return G (mm)
518
518
518
634
659
802
1142
1238
1238
1
1
1
1
1
1
1
1 1/2
1 1/2
Thermostat H (mm)
627
721
845
984
1108
1225
952
1103
1103
T&P Valve J (mm)
749
939
1119
1341
1531
1532
1517
1603
2023
Immersion K (mm)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1103
1103
1517
1603
2003
Secondary Return Connection (BSP (F)/inches)
DHW Flow J DHW Connection (BSP (M)/inches)
Top Top Top Top Top Top Centre Centre Centre Centre Centre Centre 1
1
1
1
1
1
1
1 1/2
1 1/2
250
300
500
800
1000
Supastor Optional Immersion Compatibility Chart SS Supastor Indirect Immersion Sizes (litres Indirect)
120
150
180
210
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Remtank SS Indirect Unvented Cylinders
3 kW 6 kW 9 kW 12 kW 18 kW
11
Remtank SS Solar Unvented Cylinders Solar unvented cylinders for potable water installations Fluid Flow Sequence Mains Water Isolation Valve (not supplied) 3 bar Pressure Reducing Valve Safety Group (6 bar Expansion Relief Valve c/w Non Return Valve) Expansion Vessel Drain Valve (not supplied) Stainless Supastor Hot Water Calorifier
Tundish
Safety Group c/w Non Return Valve 6 bar Relief Valve
Combined Temperature & Pressure Relief Valve Factory Fitted 7 bar / 95oC
3kW 230v/50Hz Immersion Heater
Selection Guide Property Type
Pressure Reducing Valve Pre-Set
Indirect Size
Bedsit 1/2 beds with 1 bath / shower
120
3 beds with 1 bath / shower
150 or 180
4 beds with 1 bath / shower
180 or 210
Expansion Vessel 120 - 500 3/4” Connection 800 - 1000 1” (Floor Standing Model) IMIT Combined Thermostat & Safety Relay
2/3 beds with 2 baths / showers 210 4/5 beds with 2 baths / showers 210 or 250 Sports club, Restaurant etc.
300 or 500
Hotels, Schools etc
800 or 1000
Port Valve for use with the IMIT Thermostat controlling the primary flow (boiler) water to the coil
Technical Specification SS Solar (including Kit) Volume (Nominal/litres)
210
250
300
500
800
1000
Supastor Solar Height (mm)
1568
1754
1750
1823
1960
2360
Diameter (mm)
555
555
606
734
950
950
Weight (dry/kg)
43
46
55
75.5
122.9
136.9
Weight (normal full/kg)
253
296
355
576
923.4
1257.4
T&P Tapping (inches)
3/4
3/4
3/4
3/4
3/4
3/4
T&P Pressure Setting (bar)
7
7
7
7
7
7
T&P Temperature Setting (ºC)
95
95
95
95
95
95
Expansion Relief Setting (bar)
6
6
6
6
6
6
Electrical Heater Quantity
1
1
1
1
2
2
Electrical Heater Rating (each) (kW)
3
3
3
3
3
3
Primary Re-heat Times (82ºC supply/mins)
17
21
23
20
23
30
Primary Heat Up Times (from cold/mins)
22
26
30
25
30
37
Max. Primary Pressure (coil/bar)
16
16
16
16
16
16
Primary Flow Rate (L/min)
42
42
59
67
92
92
Primary Resistance (mbar)
92
92
165
288
695
695
Primary Continuous Output (L)
710
717
769
1451
2050
1983
Primary Coil Rating kW
37.8
38.2
40.9
77.2
109.1
105.6
Expansion Vessel (Ltr)
35
35
35
50
80
80
Max. Auxiliary Pressure (coil/bar)
16
16
16
16
16
16
Auxiliary Flow Rate (L/min)
42
42
59
67
92
92
Auxiliary Resistance (mbar)
130
130
233
192
497
497
Auxiliary Continuous Output (L)
444
444
517
661
1248
1104
Auxiliary Coil Rating (kW)
24
24
28
35
66
59
Insulation is interlocked polystyrene to allow for inspection of cylinder if required. N.B. The expansion vessel provided is sized to accommodate a total hot water system volume of 1.25 times the calorifier size. It is the responsibility of the installer to verify that this vessel size is appropriate for the installation and add additional vessels if required. 12
Solar unvented cylinders for potable water installations
Secondary Flow (120 - 300) (500 - 1000)
120 to 300 litre
500 litre
800 to 1000 litre
Technical Specification Connections Volume (Nominal/litres Solar)
210
250
300
500
800
1000
Height A (mm)
1568
1754
1750
1823
1960
2360
Diameter B (mm)
555
555
606
734
950
950
Cold Water C (mm)
51
51
51
52
338
338
Cold Water Connection (BSP (M)/inches)
1
1
1
1
1.1/2
1.1/2
Immersion D (mm)
881
834
1117
932
343
343
Primary Return E (mm)
379
379
372
832
1038
1038
Primary Flow F (mm)
51
51
51
312
338
338
Primary Connection (BSP (M)/inches)
1
1
1
1
1
1
634
659
774
952
1238
1238
DHW Return G (mm) DHW Return Connection (BSP (F)/inches)
1
1
1
1
1
1
Thermostat H (mm)
1216
1108
1225
952
1103
1103
T&P Valve J (mm)
1341
1531
1532
1517
1603
2023
Immersion K (mm)
N/A
N/A
N/A
N/A
1103
1103
DHW Flow J (mm)
Top Centre
Top Centre
Top Centre
1517
1603
2003
DHW Connection (BSP (M)/inches)
1
1
1
1
1.1/2
1.1/2
Auxiliary Return L (mm)
1098
1288
1017
1077
1193
1443
Auxiliary Flow J (mm)
1341
1531
774
1437
1603
1853
1
1
1
1
1
1
289
289
282
558
1103
1103
800
1000
Secondary Connection (BSP (M)/inches) Thermostat Primary Coil Pocket (mm)
Supastor Optional Immersion Compatibility Chart SS Supastor Solar Immersion Sizes (litres Solar)
210
250
300
500
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Remtank SS Solar Unvented Cylinders
3 kW 6 kW 9 kW 12 kW 18 kW
13
Wiring Details for all Digital Pressurisation Units
Calorifier Thermostat Wiring Thermostat
Safety Limiter
• Supply Voltage 230v- Single Phase • Fuse Rating - 5 Amps • Max Full Load Current - 4.5 Amps
Reset 2
C
1
2
C
1
Brown
Blue
Grey
Orange
Boiler Signal Out
Boiler Signal In
Neutral
Live
2 Port Motorised Valve
ote: Control of hot water via Remeha controls and priority kits: N • When using the Remeha controls and priority kits in conjunction with a supplied HWS immersion
sensor, fit the supplied brass pocket in the secondary return connection and connect immersion sensor into pocket. The secondary return connection should then be connected into the cold feed supply at the base of the calorifier between the safety group and the calorifier. Sensor wiring connections can be found in the boiler control wiring details
• The 2 port valve must be wired as detailed in the diagrams above, with the electrical supply coming
from the Priority Kit/Boiler controls. To ensure the correct operation of the Priority Kit set the control thermostat (connected to the 2 port valve) 10ºC higher than the boiler or controller hot water temperature
• Refer to our schematic and wiring booklet 14
6
5
4
3
2
1
Hot Water Outlet D
D
400mm Maximum Length
Secondary Return (Anode Connection) C
C Drain Valve (Not Supplied)
400mm Minimum Length
T&P Tundish
B
B
Safety Group
150mm Minimum Length
To Drain 200mm Minimum Length A
Pressure Reducing Valve Cold Water Inlet
6
5
6
5
NOTE: The location of the Pressure Reducing Valve, Expansion Vessel, Safety Group and Drain Valve is flexible, as long as the distances shown and written instructions are followed. This clause allows the Expasnion Vessel to be located above the Hot Water Calorifer / Cylinder. 4
4
Designed by
Checked by
Approved by
RJAC
MC
RJAC
Stainless Supastor Direct Assembly
To Drain
Date
25/05/2006
A
Date
02/02/2006
Edition
Appendix 4
3
2
1
3
2
1
Sheet
1/1
Hot Water Outlet 400mm Maximum Length
D
D
Secondary Return (Anode Connection)
C
C
Drain Valve (Not Supplied)
T&P Tundish
400mm Minimum Length
Primary Flow (Boiler)
B
150mm Minimum Length
Safety Group
To Drain
200mm Minimum Length A
Pressure Reducing Valve Cold Water Inlet
6
B
5
To Drain
Primary Return (Boiler) NOTE: The location of the Pressure Reducing Valve, Expansion Vessel, Safety Group and Drain Valve is flexible, as long as the distances shown and written instructions are followed. This clause allows the Expasnion Vessel to be located above the Hot Water Calorifer / Cylinder. 4
REMPRESS PRESSURE SETS AND REMTANK CALORIFIERS
Assembly for Direct, Indirect and Solar
Designed by
Checked by
Approved by
RJAC
MC
RJAC
Stainless Supastor Indirect and Solar Assembly 3
Date
25/05/2006
Appendix 3 2
A
Date
02/02/2006
Edition
1
Sheet
1/1
15
Remeha House Molly Millars Lane Wokingham Berkshire RG41 2QP T: 0118 978 3434 F: 0118 978 6977 E:
[email protected]
www.remeha.co.uk
The data published in this technical sales leaflet is based on the latest information (at date of publication) and may be subject to revisions. It should be read in conjunction with our full technical brochure (available on request). We reserve the right to continuous development in both design and manufacture, therefore any changes to the technology employed may not be retrospective, nor may we be obliged to adjust earlier supplies accordingly. Issue 1 date: 01/11/2012