Thermostatic Expansion Valves Type Te 5 – Te 55

   EMBED


Share

Transcript

Data sheet Thermostatic expansion valves Type TE 5 – TE 55 The TE 5 - TE 55 series expansion valve regulate the injection of refrigerant into evaporators. It controls the refrigerant flow based on the superheat. The exchangeable power element is produced with the well known Danfoss laser welding technology for extended lifetime capability. The TE 5 - TE 55 series is available with a wide range of orifices which will cover a wide range of applications. Applications: - Air conditioning system - Chiller - Cold room - Freezer - Other refrigeration systems Features • Wide operating range: -40 – 10 °C / -40 – 50 °F -60 – -25 °C / -75 – -15 °F • Refrigerants: R407F, R407A, R404A, R507, R22, R134a and R407C. • Interchangeable orifice assembly: - easy storage - easy capacity matching - better service • Laser welded stainless steel power element, capillary tube and bulb. © Danfoss | DCS (sw) | 2016.10 • Wide capacity range, rated capacity from: 11.0 – 250 kW / 3.14 – 71.0 TR for R407F 8.17 – 182 kW / 2.33 – 52.0 TR for R404A/R507 • MOP function is available. • Superior charge performance. • PS / MWP (maximum working pressure): 28 bar / 400 psig. • Minimized capacity gap and overlap between orifices. • TE 55 has balanced port design. • Patented bulb strap design. DKRCC.PD.AB0.A5.02 | 1 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Technical data Max. temperature Bulb, when valve is assembled:100 °C / 210 °F. Complete valve when not assembled: 70 °C / 160 °F. Min. temperature: -60 °C / -75 °F. Max. test pressure: 32 bar / 465 psig. Maximum working pressure: 28 bar / 400 psig. US units SI units MOP-points Range -40 − 10 °C Refrigerant Range -40 − -5 °C Range -40 − -15 °C Range -60 − -25 °C Range -40 – 50 °F Range -40 – 25 °F Range -40 – 5 °F Range -75 – -15 °F MOP-point in evaporating temperature te and evaporating pressure pe MOP-point in evaporating temperature te and evaporating pressure pe 15 °C 0 °C -10 °C -20 °C 60 °F 32 °F 15 °F -5 °F R407F/R407A 7.5 bar 4.2 bar 2.6 bar 1.5 bar 110 psig 60 psig 40 psig 20 psig R404A/R507 8.6 bar 5.1 bar 3.4 bar 2.0 bar 120 psig 70 psig 45 psig 30 psig R22 6.9 bar 4.0 bar 2.6 bar 1.5 bar 100 psig 60 psig 35 psig 20 psig R134a 3.9 bar 2.0 bar 1.0 bar 0.3 bar 55 psig 30 psig 15 psig 5 psig R407C 6.6 bar 3.6 bar 2.2 bar 1.1 bar 95 psig 50 psig 30 psig 15 psig MOP = Max. Operating Pressure SS OS SH Qnom Qmax = static superheat = opening superheat = SS + OS = total superheat = rated capacity = maximum capacity SS can be adjusted with setting spindle. The standard factory SS setting is 4 K / 7.2 °F. The OS is 4 K / 7.2 °F from when opening begins to where the valve reaches its rated capacity Qnom. OS is determined by the design and cannot be changed. SS OS SH SH = 4 K / 7.2 °F = 4 K / 7.2 °F = 4 + 4 = 8 K = 7.2 + 7.2 = 14.4 °F Using orifice with range B element, please check superheat under running conditions and readjust SS setting, if necessary. The thermostatic element is fitted with a label (on top of the diaphragm). The type code refers to the refrigerant for which the valve is designed (only for refrigerants with type letter): R22/R407C 1) R134a R404A/R507 R407C R407F/R407A =X =N =S =Z ) For R407C plants, please select valves from the dedicated R407C program 1 Production place and date (BE1315B) mean: BE = Wuqing, China 13 = Week 15 = Year 2015 B = Tuesday 2 06 MA E1 IN CHIN DE The label holds information like valve type, evaporating temperature range, MOP point, refrigerant, max. working pressure PS / MWP and production date. Element label 1315 T 09 Identification Example Static superheat Opening superheat Total superheat 67B A 0 27 Superheat Orifice assembly marking for TE 5 – TE 55 Orifice assembly for TE 5 – TE 55 The orifice assembly is marked on top of the spring cup, e.g. as shown in the figure. TE 12 = For valve type 06 = Orifice no. 067B2709 = Orifice code no. for sales order 1315 = week 13, year 2015 Capillary tube tag for TE 5 – TE 55 The label gives the orifice size (06). A new label always accompanies a new orifice assembly. © Danfoss | DCS (sw) | 2016.10 6 Capillary tube tag TE 5 – TE 55 DKRCC.PD.AB0.A5.02 | 2 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Design/Function General TE 5 – TE 55 valves have an interchangeable orifice assembly. 1 TE 5 – TE 55 valves are built up of three main components (Parts program): 1. Thermostatic element 2. Orifice assembly 3. Valve body with connections 4 5 2 3 TE 5 Danfoss 67B02.10 10 1. Thermostatic element 1 4 2. Orifice assembly 5 2 3 3. Valve body with connections TE 12 / TE 20 Danfoss 67B03.10 The orifice is refrigerant and range independend. All valves are equipped with external pressure equalization. To ensure long operating life, the valve cone and seat are made of a special alloy with particularly good wear properties. 1 4 5 1. Thermostatic element. 2. Interchangeable orifice assembly. 3. Valve body. 4. Superheat setting spindle. 5. External pressure equalizing connection with 1⁄4 in / 6 mm flare nut (solder is available on TE 5). Select valve type 2 3 TE 55 SI units Rated capacities TE 5 R407F [kW] 11.0 – 49.0 R407A [kW] 10.3 – 45.3 R404A/R507 [kW] 8.17 – 35.7 R22 [kW] 10.4 – 46.0 R134a [kW] 6.68 – 29.7 R407C [kW] 10.7 – 47.4 TE 12 71.0 – 115 56.0 – 96.0 50.7 – 81.3 57.2 – 97.8 37.7 – 65.7 55.8 – 94.3 TE 20 141 – 161 126 – 148 87.1 – 102 128 – 150 77.8 – 92.3 118 – 136 TE 55 124 – 250 112 – 242 84.8 – 182 113 – 245 77.9 – 166 112 – 232 R407F [TR] R407A [TR] R404A/R507 [TR] R22 [TR] R134a [TR] R407C [TR] TE 5 3.14 – 13.9 2.92 – 12.9 2.33 – 10.2 2.97 – 13.1 1.91 – 8.49 3.06 – 13.5 TE 12 20.3 – 32.7 16.1 – 27.5 14.5 – 23.5 16.3 – 27.9 10.8 – 18.8 15.9 – 26.9 TE 20 40.0 – 45.9 36.0 – 42.1 24.9 – 29.1 36.6 – 42.9 22.2 – 26.4 33.7 – 38.9 TE 55 35.3 – 71.0 31.8 – 69.0 24.1 – 52.0 32.2 – 70.0 21.9 – 47.4 31.7 – 66.3 Valve type US units Rated capacities Valve type The rated capacity is based on: © Danfoss | DCS (sw) | 2016.10 Evaporating temperature Condensing temperature Refrigerant temperature ahead of valve te = tc = tl = 4.4 °C / 40 °F 38 °C / 100 °F 37 °C / 98 °F DKRCC.PD.AB0.A5.02 | 3 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Ordering R407F/R407A 1) Element for expansion valve - including bulb strap. Pressure equalization Valve type Size Type /4 in / 6 mm Flare /4 in / 6 mm Flare /4 in / 6 mm Flare /4 in [m] [in] - - -40 – 10 -40 – 50 3 118 067B3501 0 32 -40 – -5 -40 – 25 3 118 067B3502 -10 15 -40 – -15 -40 – 5 3 118 067B3503 Solder ODF - - -40 – 10 -40 – 50 3 118 067B3504 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3532 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3531 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3533 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3561 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3560 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3562 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067G3500 1 1 1 1 1 1 1 TE 55 Code no. [°F] 1 TE 20 Capillary tube [°C] 1 TE 12 Range [°F] 1 TE 5 MOP 1 [°C] 1) On systems charged with R407A, SS will different from standard 4K / 7.2 °F. For range -40 – 10 °C / -40 – 50 °F, SS = 2.7 K / 4.9 °F. For range -40 − -5 °C / -40 – 25 °F and range -40 − -15 °C / -40 – 5 °F, SS = 2.8K / 5.0 °F. R404A/R507 Element for expansion valve - including bulb strap. Pressure equalization Valve type Size [°C] [°F] [m] [in] /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3342 /4 in Solder ODF - - -40 – 10 -40 – 50 3 118 067B3380 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3238 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3357 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3358 /4 in Solder ODF -10 15 -40 – -15 -40 – 5 3 118 067B3384 /4 in / 6 mm Flare - - -60 – -25 -75 – -15 3 118 067B3344 6 mm Solder ODF - - -60 – -25 -75 – -15 3 118 067B3392 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3343 /4 in Solder ODF -20 -5 -60 – -25 -75 – -15 3 118 067B3381 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3347 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3345 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3348 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3349 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3346 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3350 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3352 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3351 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3353 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3354 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3356 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3355 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067G3302 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067G3303 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067G3304 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067G3305 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067G3301 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067G3306 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 TES 55 1 1 1 1 © Danfoss | DCS (sw) | 2016.10 Code no [°F] 1 TES 20 Capillary tube [°C] 1 TES 12 Range Type 1 TES 5 MOP DKRCC.PD.AB0.A5.02 | 4 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Ordering R22/R407C 1) Element for expansion valve - including bulb strap. Pressure equalization Valve type Size [°F] [m] [in] /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3250 /4 in Solder ODF - - -40 – 10 -40 – 50 3 118 067B3420 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3267 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3249 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3253 /4 in / 6 mm Flare - - -60 – -25 -75 – -15 3 118 067B3263 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3251 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3210 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3209 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3227 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3207 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3213 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3211 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3212 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3274 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3290 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3286 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067B3273 /4 in / 6 mm Flare -10 15 -40 – -15 -40 – 5 3 118 067B3275 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067B3276 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067B3287 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067G3205 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067G3209 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067G3220 /4 in / 6 mm Flare 0 32 -40 – -5 -40 – 25 3 118 067G3206 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 3 118 067G3207 /4 in / 6 mm Flare -20 -5 -60 – -25 -75 – -15 5 197 067G3217 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 TEX 55 Code no. [°C] 1 TEX 20 Capillary tube [°F] 1 TEX 12 Range [°C] 1 TEX 5 MOP Type 1 1 1 ) For R407C plants. please select elements from the dedicated R407C program 1 R134a Element for expansion valve - including bulb strap. Pressure equalization Valve type Size [°C] [°F] [m] [in] /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3297 /4 in Solder ODF - - -40 – 10 -40 – 50 3 118 067B3430 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3298 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3232 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3233 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3363 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067B3292 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067B3293 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3370 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 3 118 067G3222 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 3 118 067G3223 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067G3230 1 1 1 1 1 1 1 1 1 1 R407C Element for expansion valve - including bulb strap. Pressure equalization Valve type TEZ 5 TEZ 12 Size Type /4 in / 6 mm Flare /4 in / 6 mm Flare /4 in / 6 mm Flare /4 in / 6 mm TEZ 55 © Danfoss | DCS (sw) | 2016.10 MOP Capillary tube Code no. [°C] [°F] [m] [in] - - -40 – 10 -40 – 50 3 118 067B3278 15 60 -40 – 10 -40 – 50 3 118 067B3277 - - -40 – 10 -40 – 50 3 118 067B3366 Flare 15 60 -40 – 10 -40 – 50 3 118 067B3367 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067B3371 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 5 197 067B3372 /4 in / 6 mm Flare - - -40 – 10 -40 – 50 5 197 067G3240 /4 in / 6 mm Flare 15 60 -40 – 10 -40 – 50 5 197 067G3241 1 1 1 1 1 1 [°C] Range [°F] 1 1 TEZ 20 Code no. [°F] 1 TEN 55 Capillary tube [°C] 1 TEN 20 Range Type TEN 5 TEN 12 MOP DKRCC.PD.AB0.A5.02 | 5 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Ordering Orifice for expansion valves. Rated capacity. R404A Valve Orifice R407F R407A /R507 R22 type no. [kW] TE 5 TE 12 TE 20 TE 55 R407F R407A R404A /R507 R22 R134a R407C Code no. [TR] 0.5 11.0 10.3 8.17 10.4 6.68 10.7 3.14 2.92 2.33 2.97 1.91 3.06 067B2788 01 20.3 18.8 14.9 19.1 12.2 19.6 5.76 5.35 4.26 5.46 3.49 5.60 067B2789 02 28.1 25.9 20.5 26.3 17.0 27.2 8.00 7.37 5.86 7.51 4.86 7.77 067B2790 03 35.8 33.3 26.3 33.8 21.8 34.8 10.2 9.48 7.51 9.66 6.23 9.94 067B2791 04 49.0 45.3 35.7 46.0 29.7 47.4 13.9 12.9 10.2 13.1 8.49 13.5 067B2792 05 71.0 56.0 50.7 57.2 37.7 55.8 20.3 16.1 14.5 16.3 10.8 15.9 067B2708 06 95.0 75.0 64.0 76.3 50.1 73.9 27.1 21.4 18.3 21.8 14.3 21.1 067B2709 07 115 96.0 81.3 97.8 65.7 94.3 32.7 27.5 23.2 27.9 18.8 26.9 067B2710 08 141 126 87.1 128 77.8 118 40.0 36.0 24.9 36.6 22.2 33.7 067B2771 1) 09 161 148 102 150 92.3 136 45.9 42.1 29.1 42.9 26.4 38.9 067B2773 1) 9B 124 112 84.8 113 77.9 112 35.3 31.8 24.1 32.2 21.9 31.7 067G2705 2) 10 173 166 128 169 111 161 49.1 47.4 36.6 48.3 31.7 46.0 067G2701 11 188 181 138 184 122 175 53.0 52.0 39.4 52.6 34.9 50.0 067G2704 12 207 199 152 202 134 191 59.0 57.0 43.4 57.7 38.3 54.6 067G2707 13 250 242 182 245 166 232 71.0 69.0 52.0 70.0 47.4 66.3 067G2710 The rated capacity is based on: Evaporating temperature Condensing temperature Refrigerant temperature ahead of valve © Danfoss | DCS (sw) | 2016.10 R134a R407C te = 4.4 °C / 40 °F tc = 38 °C / 100 °F tl = 37 °C / 98 °F 1 ) Recommend to use orifice no. 9B as alternative for orifice no. 08 and 09 on TE 55 when selecting the valve to work in range -60 – -25 °C / -75 – -15 °F. Extend capacity tables for range -60 – -25 °C / -75 – -15 °F are not provided. 2 ) Alternative for orifice no. 8 and 9 in range -60 – -25 °C / -75 – -15 °F. Extend capacity tables for range -40 – 10 °C / -40 –50 °F are not provided. DKRCC.PD.AB0.A5.02 | 6 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Ordering Valve body for expansion valves Connection Inlet × Outlet Type Solder angleway ODF × ODF 067B4009 /2 × 7/8 - Solder angleway ODF × ODF 067B4010 5 /8 × 7/8 - Solder angleway ODF × ODF 067B4011 /8 × 11/8 - Solder angleway ODF × ODM 067B4034 /2 × 5/8 - Solder straightway ODF × ODF 067B4007 /2 × 7/8 - Solder straightway ODF × ODF 067B4008 5 /8 × 7/8 - Solder straightway ODF × ODF 067B4032 /8 × 11/8 - Solder straightway ODF × ODM 067B4033 - 12 × 16 Solder angleway ODF × ODF 067B4004 - 12 × 22 Solder angleway ODF × ODF 067B4005 1 1 7 16 × 22 Solder angleway ODF × ODF 067B4012 - 22 × 28 Solder angleway ODF × ODM 067B4037 - 12 × 16 Solder straightway ODF × ODF 067B4002 - 12 × 22 Solder straightway ODF × ODF 067B4003 - 16 × 22 Solder straightway ODF × ODF 067B4035 - 22 × 28 Solder straightway ODF × ODM 067B4036 5 /8 × 7/8 - Solder angleway ODF × ODF 067B4022 /8 × 11/8 - Solder angleway ODF × ODM 067B4023 5 /8 × 7/8 - Solder straightway ODF × ODF 067B4020 /8 × 11/8 - Solder straightway ODF × ODM 067B4021 - 22 × 28 Solder angleway ODF × ODM 067B4017 - 16 × 22 Solder straightway ODF × ODF 067B4018 - 22 × 28 Solder straightway ODF × ODM 067B4016 /8 × 7/8 - Solder flanges ODF × ODF 067B4025 /8 × 1 - Solder flanges ODF × ODF 067B4026 - 16 × 22 Solder flanges ODF × ODF 067B4027 - 22 × 25 Solder flanges ODF × ODF 067B4015 7 7 Solder straightway 5 7 TE 12 /8 × 11/8 - Solder angleway ODF × ODM 067B4023 - 22 × 28 Solder angleway ODF × ODM 067B4017 7 TE 55 Solder angleway Flare angleway - Solder straightway TE 20 067B4013 - 7 Flanges - 12 × 16 /2 × 5/8 1 TE 12 Code no. /2 × 5/8 1 TE 5 Connection type 1) [mm] 1 Flare angleway Connections / Flow direction [in] /8 × 11/8 - Solder straightway ODF × ODM 067B4021 - 22 × 28 Solder straightway ODF × ODM 067B4016 7 11/8 × 13/8 - Solder angleway ODM × ODM 067G4004 - 28 × 35 Solder angleway ODM × ODM 067G4002 11/8 × 13/8 - Solder straightway ODM × ODM 067G4003 - 28 × 35 Solder straightway ODM × ODM 067G4001 ) ODF = Internal diameter ODM = External diameter 1 Spareparts Bulb strap for TE 5 – TE 55 delivered with the element © Danfoss | DCS (sw) | 2016.10 Type Length TE 5 / TE 12 225 mm Max. tube diameter 2 1/8 in / 53 mm 067N0557 Code no. TE 20 / TE 55 350 mm 3 1/8 in / 78 mm 067N0559 DKRCC.PD.AB0.A5.02 | 7 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 How to select a valve Example: Q (capacity) = 45 kW Tcon (condensing temperature) Tevap (evaporator temperature) Tsub (subcooling temperature) Dpd (distributer pressure drop) = 25 °C = -30 °C =10 K = 2 bar Valve type Orifice no. 8 9 10 11 12 13 TE 20 Q (capacity) = 45 kW fsub (subcooling correction factor) = 1.09 SI units TE 55 fp (distributer correction factor) = 0.92 Q fsub x fp 50 1.09 x 0.92 = Selected capacity = 44.9 kW The selection will be: TE 20 orifice 9 (54.2 kW > 44.9 kW) SI units R404A/R507 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Cond. temp. [°C] Evap. temp. [°C] -40 25 25 25 25 25 25 35.7 39.5 46.5 51.1 54.8 66.5 Subcooling correction factor, fsub Subcooling [K] 2 Correction factor 0,97 1 0.96 0.94 2 0.92 -20 48.4 54.2 64.9 71.2 76.8 93.7 4 1,00 10 1,09 62.2 71.3 86.1 94.4 103 126 15 1,16 SI units R404A/R507 Distributer correction factor, fp Pressure drop [bar] -40 ∆p 0 1 1.5 -30 Evap. temp. [°C] -30 -20 Correction factor 1 1 0.96 0.96 0.94 0.94 0.92 0.91 -10 1 0.95 0.93 0.90 Calculated at 32 °C condensing temperature. US units Q (capacity) = 14 TR Tcon (condensing temperature) = 75 °F Tevap (evaporator temperature) = -20 °F Tsub (subcooling temperature) = 10 °F Dpd (distributer pressure drop) = 30 psi Valve type Orifice no. 08 09 10 11 12 13 TE 20 Q (capacity) = 14 TR fsub (subcooling correction factor) = 1.03 TE 55 fp (distributer correction factor) = 0.92 Q fsub x fp 14 1.03 x 0.92 = Selected capacity = 14.8 TR The selection will be: TE 20 orifice 9 (16.1 TR > 14.8 TR) US units R404A/R507 Capacity in kW. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Cond. temp. [°F] Evap. temp. [°F] -40 75 75 75 75 75 75 Subcooling correction factor, fsub Subcooling [°F] 2 Correction factor 0.96 Distributer correction factor, fp Pressure drop [psi] -40 ∆p 0 15 25 1 0.96 0.94 30 0.92 -20 10.2 11.3 13.4 14.7 15.8 19.2 14.2 16.1 19.2 21.1 22.8 27.9 7 1.00 10 1.03 0 18.6 21.5 26.0 28.5 31.1 38.2 20 1.11 US units R404A/R507 Evap. temp. [°F] -20 0 Correction factor 1 1 0.96 0.96 0.93 0.92 0.92 0.91 20 1 0.95 0.91 0.89 Calculated at 90 °F condensing temperature. © Danfoss | DCS (sw) | 2016.10 DKRCC.PD.AB0.A5.02 | 8 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R407F Evap. temp. [°C] -40 -30 -20 -10 0 10 4.70 8.60 12.0 15.3 20.3 26.1 32.8 42.6 52.3 56.6 65.7 72.3 77.7 94.7 5.94 10.9 15.3 19.4 26.0 34.7 44.3 59.2 69.5 76.3 86.2 94.9 103 126 7.36 13.5 19.0 24.1 32.6 45.0 58.4 77.5 90.2 101 111 123 133 163 8.83 16.2 22.7 28.8 39.4 56.7 74.6 96.2 113 130 139 153 167 206 10.06 18.4 25.5 32.8 44.7 67.3 89.4 113 131 155 164 180 200 245 10.5 19.1 26.1 34.1 46.1 70.9 94.4 124 134 162 177 193 216 262 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R407F Evap. temp. [°C] -40 -30 -20 -10 0 10 4.70 8.60 12.0 15.2 20.0 25.8 31.9 43.6 51.2 54.3 61.4 67.2 70.7 84.6 5.98 11.0 15.4 19.4 26.0 33.8 42.6 58.0 67.4 71.9 81.6 89.3 94.5 113 7.49 13.8 19.4 24.4 33.0 43.6 56.1 75.1 87.6 94.9 107 117 124 150.1 9.14 16.8 23.6 29.7 40.6 55.6 72.8 93.7 112 123 137 150 160 195 10.7 19.7 27.4 34.8 47.7 68.8 91.3 112 136 156 167 182 200 243 11.9 21.7 29.9 38.5 52.0 79.0 106 129 153 181 191 208 233 282 25 1.23 30 1.28 2 0.98 4 1.00 10 1.07 15 1.12 -40 0 1 1.5 1 0.97 0.95 1 0.96 0.95 2 0.93 0.93 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407F Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 75 75 75 75 75 75 75 75 75 75 75 75 75 75 1.33 2.44 3.41 4.34 5.76 7.42 9.32 12.0 14.9 16.1 18.8 20.7 22.3 27.2 1.72 3.17 4.44 5.64 7.58 10.2 13.0 17.4 20.4 22.5 25.3 27.9 30.3 37.1 2.17 4.00 5.60 7.11 9.66 13.5 17.6 23.2 27.0 30.6 33.4 36.8 40.1 49.3 2.62 4.81 6.70 8.55 11.7 17.2 22.7 29.0 33.8 39.5 42.0 46.1 50.8 62.6 2.91 5.32 7.32 9.48 12.9 19.7 26.2 33.6 37.8 45.4 48.4 52.9 59.1 72.3 2.92 5.32 7.26 9.49 12.8 19.7 26.2 34.7 37.3 45.1 49.4 53.9 60.3 73.2 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407F Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 1.33 2.44 3.41 4.32 5.69 7.33 9.07 12.4 14.6 15.4 17.4 19.1 20.1 24.0 1.74 3.20 4.49 5.67 7.57 9.87 12.5 17.0 19.7 21.1 23.9 26.2 27.7 33.3 2.23 4.11 5.77 7.26 9.83 13.1 16.9 22.5 26.3 28.6 32.2 35.3 37.4 45.3 2.75 5.06 7.09 8.95 12.2 17.0 22.4 28.4 34.1 38.1 41.8 45.7 49.3 59.8 3.21 5.89 8.17 10.4 14.3 21.1 28.1 34.2 41.3 47.9 50.9 55.4 61.4 74.5 3.37 6.16 8.48 10.9 14.9 22.6 30.2 36.6 43.5 51.3 54.3 58.9 66.2 80.1 20 1.17 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 30 1.15 US units R407F SI units R407F Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.96 0.94 0.94 0.92 0.91 0 10 1 0.95 0.93 1 0.94 0.91 0.90 0.87 Pressure drop [psi] ∆p Evap. temp. [°C] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.94 30 0.93 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.92 0.91 40 50 1 0.95 0.91 0.89 1 0.94 0.89 0.87 DKRCC.PD.AB0.A5.02 | 9 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R407F Evap. temp. [°C] -40 -30 -20 -10 0 10 4.58 8.36 11.7 14.7 19.2 25.2 30.7 41.9 49.5 51.5 55.2 60.0 62.3 73.1 5.86 10.7 15.1 18.9 25.0 32.3 40.2 54.0 64.2 66.8 74.2 80.8 83.9 99.0 7.39 13.6 19.1 23.9 32.2 41.2 52.5 69.3 82.8 86.9 98.8 108 112 132 9.11 16.8 23.6 29.5 40.2 52.3 68.0 87.0 106 113 129 140 146 175 10.9 20.0 28.0 35.2 48.3 65.6 87.0 106 132 145 162 175 187 224 12.4 22.7 31.5 40.0 54.8 79.5 107 125 157 179 192 207 229 274 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 55 55 55 55 55 55 55 55 55 55 55 55 55 55 SI units R407F Evap. temp. [°C] -40 -30 -20 -10 0 10 4.33 7.89 11.0 13.7 17.7 24.3 29.1 37.6 47.3 48.6 47.2 51.0 53.0 61.0 5.56 10.2 14.3 17.8 23.4 30.6 37.5 47.1 60.3 61.6 64.2 69.3 71.9 83.3 7.06 13.0 18.3 22.7 30.3 38.3 48.1 60.4 76.8 78.6 86.7 93.7 96.3 112 8.77 16.2 22.9 28.2 38.4 48.0 61.8 76.7 97.4 101 115 124 127 150 10.6 19.5 27.5 34.1 46.8 59.8 79.0 95.2 122 130 148 159 166 196 12.3 22.6 31.6 39.5 54.3 73.6 99.2 115 149 163 180 194 208 247 25 1.23 30 1.28 2 0.98 4 1.00 10 1.07 15 1.12 -40 0 1 1.5 1 0.97 0.95 1 0.96 0.95 2 0.93 0.93 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407F Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 1.29 2.36 3.29 4.14 5.40 7.12 8.66 11.8 14.0 14.5 15.5 16.8 17.4 20.4 1.70 3.12 4.38 5.48 7.27 9.37 11.7 15.6 18.6 19.4 21.5 23.4 24.2 28.6 2.19 4.04 5.69 7.10 9.58 12.3 15.6 20.5 24.6 25.9 29.5 32.1 33.2 39.4 2.75 5.07 7.13 8.90 12.2 15.9 20.8 26.2 32.2 34.6 39.3 42.7 44.7 53.3 3.29 6.05 8.45 10.6 14.6 20.3 27.1 32.3 40.6 45.1 49.6 53.7 57.9 69.5 3.52 6.47 8.97 11.4 15.6 22.4 30.2 35.2 44.4 50.4 54.2 58.6 64.5 77.3 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407F Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 135 135 135 135 135 135 135 135 1.21 2.20 3.06 3.82 4.91 6.84 8.16 10.3 13.3 13.6 12.8 13.8 14.5 16.5 1.60 2.93 4.10 5.10 6.69 8.78 10.8 13.2 17.3 17.6 18.1 19.5 20.3 23.4 2.08 3.83 5.40 6.66 8.92 11.2 14.1 17.4 22.6 23.0 25.3 27.3 28.1 32.6 2.63 4.85 6.86 8.44 11.5 14.3 18.6 22.7 29.2 30.3 34.5 37.2 38.2 44.7 3.19 5.89 8.29 10.3 14.1 18.2 24.3 28.6 37.3 39.7 44.9 48.3 50.6 59.8 3.45 6.37 8.91 11.1 15.3 20.4 27.5 31.8 41.5 45.1 50.0 53.7 57.3 67.9 20 1.17 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 30 1.15 US units R407F SI units R407F Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.96 0.94 0.94 0.92 0.91 0 10 1 0.95 0.93 1 0.94 0.91 0.90 0.87 Pressure drop [psi] ∆p Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.94 30 0.93 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.92 0.91 40 50 1 0.95 0.91 0.89 1 0.94 0.89 0.87 DKRCC.PD.AB0.A5.02 | 10 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R407A Evap. temp. [°C] -40 -30 -20 -10 0 10 4.36 8.00 11.2 14.2 19.0 19.7 25.1 32.6 46.6 51.3 60.0 66.1 71.2 86.9 5.50 10.1 14.2 18.0 24.2 26.4 33.8 43.9 59.8 66.8 77.7 85.6 92.4 113 6.80 12.5 17.5 22.3 30.2 34.3 44.4 58.1 75.2 85.6 99.1 109 118 146 8.10 14.9 20.7 26.6 36.2 42.7 56.0 74.1 91.3 106 123 135 148 182 9.14 16.7 23.1 29.9 40.6 49.9 66.1 88.2 104 124 145 159 176 216 9.44 17.2 23.5 30.5 41.2 52.8 70.3 94.2 107 130 156 171 191 232 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R407A Evap. temp. [°C] -40 -30 -20 -10 0 10 4.25 7.79 10.9 13.7 18.2 18.9 23.7 30.1 43.9 47.2 54.5 59.7 63.7 76.4 5.41 9.93 14.0 17.5 23.5 25.0 31.7 39.9 56.5 61.3 71.5 78.2 83.7 100 6.78 12.5 17.5 22.1 29.8 32.6 41.9 52.9 72.0 79.3 92.8 101 109 132 8.30 15.2 21.3 27.1 36.8 41.6 54.2 68.9 89.9 101 118 129 139 169 9.75 17.9 24.8 31.8 43.3 50.8 67.1 86.3 107 124 146 159 173 211 10.8 20.0 27.0 34.8 47.2 57.9 77.2 100 120 142 169 184 203 246 25 1.24 30 1.30 2 0.98 4 1.00 10 1.07 15 1.13 -40 0 1 1.5 1 0.96 0.95 1 0.96 0.94 2 0.93 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 Cond. temp. [°F] US units R407A Evap. temp. [°F] 75 75 75 75 75 75 75 75 75 75 75 75 75 75 -40 -20 0 20 40 50 1.24 2.27 3.19 4.03 5.40 5.62 7.16 9.32 13.3 14.7 17.2 19.0 20.0 25.0 1.60 2.94 4.13 5.24 7.07 7.75 9.96 13.0 18.0 20.0 22.8 25.2 27.2 33.4 2.01 3.69 5.15 6.60 8.95 10.3 13.4 17.6 22.4 25.7 29.7 32.7 35.6 43.9 2.40 4.39 6.09 7.86 10.7 12.9 16.9 22.5 27.2 32.1 37.1 40.8 44.8 55.3 2.63 4.79 6.59 8.56 11.6 14.6 19.4 26.0 30.0 36.2 42.8 46.9 52.1 63.9 2.63 4.77 6.52 8.49 11.5 14.7 19.6 26.3 29.8 36.2 43.6 47.8 53.4 64.9 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407A Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 1.21 2.21 3.10 3.89 5.15 5.36 6.73 8.55 12.5 13.4 15.5 16.9 18.1 21.7 1.58 2.89 4.07 5.11 6.84 7.31 9.30 11.7 16.5 17.9 20.9 22.9 24.5 29.5 2.02 3.71 5.20 6.57 8.89 9.80 12.6 15.9 21.5 23.8 27.9 30.5 32.8 39.7 2.50 4.59 6.40 8.15 11.1 12.7 16.6 21.2 27.3 31.0 36.2 39.6 42.9 52.2 2.92 5.34 7.38 9.49 12.9 15.5 20.5 26.5 32.4 37.9 44.7 48.7 53.4 64.9 3.06 5.58 7.66 9.88 13.4 16.4 21.9 28.5 34.0 40.2 48.1 52.3 57.7 69.9 20 1.19 Subcooling [°F] Correction factor 40 1.23 50 1.29 2 0.97 7 1.00 10 1.02 20 1.09 30 1.16 US units R407A SI units R407A Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.96 0.94 0.93 0.92 0.91 0 10 1 0.95 0.92 1 0.94 0.90 0.89 0.87 Pressure drop [psi] ∆p Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.91 0.90 40 50 1 0.94 0.90 0.88 1 0.93 0.89 0.86 DKRCC.PD.AB0.A5.02 | 11 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R407A Evap. temp. [°C] -40 -30 -20 -10 0 10 4.00 7.33 10.3 12.8 16.8 17.5 21.7 27.4 40.2 42.2 47.4 51.6 54.6 64.3 5.11 9.39 13.2 16.4 21.8 22.8 28.7 35.3 51.4 54.3 62.9 68.4 72.5 85.8 6.47 11.9 16.8 20.8 28.0 29.6 37.8 46.1 65.7 70.2 82.9 90.0 95.8 114 8.05 14.8 20.8 26.0 35.4 38.1 49.3 60.1 83.4 90.6 108 117 125 150 9.73 17.9 25.0 31.6 43.2 47.8 62.9 77.1 103 115 137 149 160 193 11.2 20.6 28.5 36.3 49.6 57.3 76.4 95.0 121 139 167 181 197 236 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 55 55 55 55 55 55 55 55 55 55 55 55 55 55 SI units R407A Evap. temp. [°C] -40 -30 -20 -10 0 10 3.65 6.68 9.34 11.6 15.0 15.9 19.4 24.5 35.6 36.8 39.3 42.5 44.6 51.4 4.66 8.56 12.0 14.8 19.5 20.2 25.1 30.7 45.1 46.6 52.7 57.0 59.8 69.4 5.91 10.9 15.4 18.8 25.2 25.8 32.7 39.0 57.4 59.6 70.3 75.8 79.9 93.4 7.42 13.7 19.4 23.8 32.3 33.1 42.6 50.0 73.2 76.9 93.0 100 106 125 9.12 16.9 23.8 29.4 40.3 42.0 55.0 64.3 92.5 99.2 121 130 139 164 10.83 20.0 27.9 35.0 48.2 51.9 69.1 81.3 113 124 152 164 176 209 25 1.24 30 1.30 2 0.98 4 1.00 10 1.07 15 1.13 -40 0 1 1.5 1 0.96 0.95 1 0.96 0.94 2 0.93 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407A Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 1.13 2.06 2.89 3.60 4.72 4.92 6.10 7.67 11.3 11.8 13.2 14.4 15.2 17.9 1.48 2.72 3.82 4.74 6.30 6.58 8.28 10.2 14.8 15.6 18.1 19.7 20.9 24.6 1.92 3.53 4.97 6.17 8.32 8.78 11.2 13.6 19.5 20.8 24.6 26.7 28.4 33.8 2.43 4.48 6.29 7.86 10.7 11.6 15.0 18.3 25.3 27.5 32.9 35.7 38.2 45.7 2.96 5.44 7.58 9.58 13.1 14.7 19.4 23.8 31.6 35.5 42.5 46.0 49.7 59.6 3.18 5.85 8.10 10.3 14.1 16.2 21.5 26.6 34.3 39.2 47.1 50.9 55.4 66.5 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407A Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 135 135 135 135 135 135 135 135 1.01 1.85 2.58 3.20 4.13 4.39 5.34 6.78 9.80 10.1 10.6 11.5 12.0 13.8 1.32 2.43 3.42 4.19 5.52 5.70 7.08 8.63 12.7 13.1 14.7 15.9 16.7 19.3 1.72 3.17 4.49 5.47 7.34 7.47 9.46 11.2 16.6 17.1 20.3 21.9 23.0 26.8 2.21 4.08 5.77 7.06 9.63 9.80 12.7 14.7 21.7 22.8 27.8 29.9 31.6 37.1 2.75 5.09 7.16 8.86 12.2 12.7 16.7 19.4 27.9 30.1 37.0 39.7 42.3 50.1 3.02 5.58 7.81 9.73 13.4 14.2 19.0 22.0 31.2 34.1 41.9 45.0 48.2 57.2 20 1.19 Subcooling [°F] Correction factor 40 1.23 50 1.29 2 0.97 7 1.00 10 1.02 20 1.09 30 1.16 US units R407A SI units R407A Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.96 0.94 0.93 0.92 0.91 0 10 1 0.95 0.92 1 0.94 0.90 0.89 0.87 Pressure drop [psi] ∆p Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.91 0.90 40 50 1 0.94 0.90 0.88 1 0.93 0.89 0.86 DKRCC.PD.AB0.A5.02 | 12 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R404A/R507 Evap. temp. [°C] -40 -30 -20 -10 0 10 3.68 6.76 9.49 12.0 16.1 20.7 24.9 32.5 35.7 39.5 46.5 51.1 54.8 66.5 4.77 8.76 12.3 15.6 21.1 28.0 34.1 43.9 48.4 54.2 64.9 71.2 76.8 93.7 5.91 10.8 15.1 19.4 26.3 36.0 44.5 57.6 62.2 71.3 86.1 94.4 103 126 6.93 12.7 17.6 22.6 30.8 43.9 55.0 71.9 75.2 88.4 108 118 130 159 7.54 13.7 18.8 24.4 33.1 48.9 61.7 81.4 82.9 100 124 136 151 183 7.30 13.2 17.9 23.3 31.2 47.2 59.6 78.3 79.7 97.0 125 135 152 181 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R404A/R507 Evap. temp. [°C] -40 -30 -20 -10 0 10 3.45 6.34 8.90 11.1 14.9 18.7 22.3 27.8 32.4 34.9 40.6 44.3 47.1 56.0 4.55 8.37 11.8 14.8 19.9 25.3 30.7 37.9 44.3 48.2 57.7 62.9 67.2 80.5 5.78 10.6 14.9 18.8 25.5 33.3 41.0 50.7 58.4 64.6 78.7 85.7 92.1 110 7.05 12.9 18.0 22.9 31.2 42.3 52.7 66.0 73.6 83.5 103 112 121 146 8.12 14.8 20.4 26.3 35.7 50.5 63.6 81.2 86.9 101 126 137 150 181 8.61 15.6 21.3 28.0 37.1 54.4 68.7 89.1 92.6 110 141 153 170 203 25 1.30 30 1.37 2 0.97 4 1.00 10 1.09 -40 0 1 1.5 1 0.96 0.94 1 0.96 0.94 2 0.92 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R404A/R507 Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 75 75 75 75 75 75 75 75 75 75 75 75 75 75 1.05 1.93 2.71 3.42 4.59 5.94 7.14 9.36 10.2 11.3 13.4 14.7 15.8 19.2 1.39 2.56 3.58 4.56 6.17 8.23 10.1 13.1 14.2 16.1 19.2 21.1 22.8 27.9 1.74 3.20 4.45 5.71 7.76 10.8 13.4 17.4 18.6 21.5 26.0 28.5 31.1 38.2 2.03 3.70 5.11 6.61 8.98 13.0 16.4 21.6 22.2 26.4 32.4 35.5 39.2 47.9 2.11 3.83 5.21 6.78 9.15 13.8 17.4 22.9 23.2 28.2 35.6 38.8 43.4 52.3 2.02 3.65 4.93 6.43 8.62 13.1 16.5 21.7 22.0 26.8 34.6 37.5 42.2 50.3 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R404A/R507 Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 0.98 1.80 2.53 3.16 4.21 5.29 6.32 7.90 9.18 9.89 11.5 12.6 13.4 15.9 1.33 2.44 3.43 4.31 5.81 7.42 9.02 11.1 13.0 14.1 17.0 18.5 19.8 23.7 1.72 3.16 4.42 5.60 7.60 10.0 12.4 15.3 17.5 19.5 23.8 25.9 27.9 33.6 2.11 3.87 5.37 6.86 9.34 12.9 16.1 20.3 22.3 25.5 31.5 34.2 37.2 45.0 2.39 4.37 5.98 7.71 10.5 15.1 19.0 24.5 25.8 30.4 38.3 41.4 45.7 54.9 2.44 4.44 6.04 7.80 10.5 15.4 19.5 25.3 26.3 31.3 40.1 43.4 48.2 57.5 15 1.16 20 1.23 Subcooling [°F] Correction factor 40 1.28 50 1.37 2 0.96 7 1.00 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.95 0.94 0.93 0.91 0.90 0 10 1 0.94 0.91 1 0.92 0.88 0.88 0.84 Pressure drop [psi] ∆p 10 1.03 20 1.11 30 1.20 US units R404A/R507 SI units R404A/R507 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.92 0.91 0.91 0.89 40 50 1 0.93 0.89 0.86 1 0.92 0.87 0.84 DKRCC.PD.AB0.A5.02 | 13 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R404A/R507 Evap. temp. [°C] -40 -30 -20 -10 0 10 3.08 5.65 7.94 9.85 13.0 16.1 19.1 23.1 28.0 29.5 33.5 36.2 38.3 44.6 4.11 7.57 10.7 13.2 17.7 21.9 26.4 31.4 38.4 40.7 48.5 52.5 55.5 65.3 5.32 9.81 13.8 17.2 23.3 29.1 35.6 42.0 51.3 55.0 67.4 72.9 77.5 91.8 6.67 12.3 17.2 21.6 29.4 37.8 46.9 55.7 66.6 73.0 90.6 97.9 104 125 8.02 14.7 20.4 25.9 35.4 47.4 59.6 71.9 82.8 93.2 117 126 136 162 9.05 16.5 22.7 29.0 39.4 55.3 70.1 86.8 95.2 110 140 150 165 196 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 55 55 55 55 55 55 55 55 55 55 55 55 55 55 SI units R404A/R507 Evap. temp. [°C] -40 -30 -20 -10 0 10 2.60 4.76 6.69 8.24 10.8 13.3 15.5 18.6 23.1 23.8 25.7 27.7 28.9 33.1 3.50 6.44 9.10 11.1 14.9 16.0 21.4 24.9 31.5 32.6 38.1 41.0 42.9 49.6 4.57 8.45 11.9 14.6 19.8 23.8 28.9 33.0 42.1 43.9 53.8 57.8 60.8 70.7 5.83 10.8 15.2 18.7 25.6 31.1 38.4 43.4 55.4 58.6 73.7 79.0 83.6 97.9 7.20 13.3 18.6 23.2 31.9 40.0 50.3 56.9 71.1 77.2 97.8 105 112 131 8.50 15.7 21.7 27.3 37.5 49.4 63.1 72.4 86.8 97.3 124 132 142 168 25 1.30 30 1.37 2 0.97 4 1.00 10 1.09 -40 0 1 1.5 1 0.96 0.94 1 0.96 0.94 2 0.92 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R404A/R507 Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 0.86 1.58 2.22 2.75 3.63 4.48 5.29 6.41 7.79 8.19 9.25 10.0 10.6 12.3 1.18 2.18 3.07 3.81 5.11 6.29 7.59 8.97 11.1 11.7 14.0 15.1 16.0 18.6 1.57 2.90 4.07 5.07 6.88 8.60 10.6 12.4 15.2 16.3 20.1 21.7 23.1 27.3 2.00 3.69 5.15 6.48 8.84 11.4 14.3 16.9 20.1 22.2 27.6 29.8 32.0 38.0 2.41 4.42 6.11 7.77 10.6 14.4 18.2 22.1 25.1 28.5 35.9 38.6 41.9 49.9 2.56 4.69 6.43 8.21 11.2 15.6 19.8 24.3 26.9 31.1 39.5 42.4 46.3 55.1 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R404A/R507 Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 135 135 135 135 135 135 135 135 0.70 1.29 1.81 2.22 2.90 3.57 4.15 4.99 6.21 6.38 6.78 7.29 7.61 8.67 0.98 1.80 2.55 3.10 4.14 4.98 5.93 6.87 8.76 9.00 10.5 11.3 11.8 13.6 1.31 2.42 3.43 4.18 5.67 6.77 8.24 9.33 12.0 12.5 15.4 16.5 17.4 20.2 1.71 3.16 4.45 5.47 7.50 9.07 11.3 12.6 16.2 17.2 21.8 23.3 24.6 28.8 2.14 3.95 5.52 6.87 9.47 11.9 15.1 16.9 21.2 23.1 29.5 31.5 33.6 39.5 2.34 4.31 5.98 7.50 10.3 13.4 17.1 19.3 23.7 26.3 33.5 35.7 38.4 45.2 15 1.16 20 1.23 Subcooling [°F] Correction factor 40 1.28 50 1.37 2 0.96 7 1.00 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.95 0.94 0.93 0.91 0.90 0 10 1 0.94 0.91 1 0.92 0.88 0.88 0.84 Pressure drop [psi] ∆p 10 1.03 20 1.11 30 1.20 US units R404A/R507 SI units R404A/R507 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -40 -20 0 1 1 15 0.96 0.96 25 0.94 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.92 0.91 0.91 0.89 40 50 1 0.93 0.89 0.86 1 0.92 0.87 0.84 DKRCC.PD.AB0.A5.02 | 14 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -60 – -25 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] 20 20 20 20 20 20 20 20 20 20 20 20 20 SI units R404A/R507 Evap. temp. [°C] -60 -50 2.01 3.66 5.09 6.38 8.32 10.3 12.8 16.5 20.6 24.1 26.6 28.6 34.7 -40 2.87 5.25 7.33 9.22 12.2 14.7 18.6 24.0 29.2 34.7 38.4 41.3 50.5 3.92 7.21 10.1 12.8 17.1 20.5 26.2 33.9 40.1 49.0 54.1 58.5 71.9 Capacity in kW. Range: -60 – -25 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] 30 30 30 30 30 30 30 30 30 30 30 30 30 -30 -25 5.12 9.41 13.2 16.8 22.8 27.3 35.5 46.1 52.4 66.8 73.8 80.2 99.2 5.73 10.5 14.7 18.8 25.6 30.8 40.5 52.6 58.5 76.6 84.6 92.3 114 SI units R404A/R507 Evap. temp. [°C] -60 -50 1.88 3.42 4.72 5.87 7.54 9.33 11.4 14.4 18.5 21.2 23.2 24.8 29.5 -40 2.72 4.97 6.93 8.63 11.3 13.6 16.9 21.3 26.6 31.0 34.0 36.3 43.6 -30 3.79 6.96 9.76 12.2 16.2 19.3 24.4 30.8 37.3 44.3 48.7 52.1 61.0 -25 5.04 9.29 13.1 16.5 22.3 26.3 33.9 43.0 50.0 61.7 67.7 72.8 88.6 5.72 10.5 14.8 18.7 25.5 30.2 39.3 49.9 56.6 71.7 78.6 84.8 104 2 0.97 4 1.00 -60 0 1 1.5 1 0.97 0.95 2 0.93 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] US units R404A/R507 Evap. temp. [°F] -75 65 65 65 65 65 65 65 65 65 65 65 65 65 -60 0.59 1.07 1.49 1.87 2.44 3.01 3.77 4.87 6.04 7.10 7.84 8.45 10.3 10 1.09 15 1.16 20 1.23 25 1.30 30 1.37 1 0.96 0.95 Evap. temp. [°C] -40 Correction factor 1 0.96 0.94 1 0.96 0.94 1 0.96 0.94 0.93 0.92 0.92 0.92 -50 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 -45 0.79 1.44 2.01 2.53 3.35 4.06 5.13 6.63 8.08 9.62 10.6 11.5 14.1 Valve type TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] -30 1.03 1.89 2.64 3.34 4.46 5.36 6.85 8.87 10.6 12.8 14.2 15.4 18.9 Capacity in TR. Range: -75 – -15 °F. Opening superheat sh = 7.2 °F. -15 1.30 2.39 3.35 4.25 5.74 6.87 8.90 11.6 13.4 16.8 18.5 20.1 24.9 1.58 2.91 4.06 5.19 7.07 8.52 11.2 14.6 16.3 21.3 23.5 25.6 31.9 US units R404A/R507 Evap. temp. [°F] -75 85 85 85 85 85 85 85 85 85 85 85 85 85 -60 0.55 1.00 1.38 1.71 2.20 2.72 3.34 4.22 5.39 6.18 6.79 7.25 8.66 -45 0.75 1.36 1.90 2.36 3.08 3.73 4.63 5.85 7.32 8.49 9.32 9.97 12.0 Subcooling [°F] Correction factor 2 0.96 7 1.00 10 1.03 -30 0.99 1.81 2.54 3.18 4.20 5.02 6.30 7.97 9.73 11.5 12.6 13.5 16.3 -15 1.27 2.34 3.29 4.13 5.55 6.57 8.39 10.6 12.6 15.3 16.8 18.0 21.9 1.58 2.91 4.09 5.18 7.06 8.35 10.9 13.8 15.7 19.8 21.7 23.5 28.6 -30 -25 Pressure drop [psi] ∆p 20 1.11 30 1.20 40 1.28 50 1.37 US units R404A/R507 SI units R404A/R507 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -75 – -15 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -75 -60 -30 -15 Correction factor 0 1 1 1 1 15 0.96 0.96 0.96 0.96 25 0.94 0.94 0.94 0.93 30 0.93 0.93 0.92 0.92 Calculated at 90 °F condensing temperature. -45 1 0.96 0.93 0.92 DKRCC.PD.AB0.A5.02 | 15 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -60 – -25 °C. Opening superheat sh = 4 K Valve type Orifice no. TE 5 TE 12 TE 55 Cond. temp. [°C] SI units R404A/R507 Evap. temp. [°C] -60 -50 -40 40 40 40 40 40 1.69 3.06 4.21 5.17 6.52 2.48 4.53 6.29 7.75 9.96 3.51 6.44 9.03 11.2 14.7 4.75 8.76 12.4 15.4 20.8 5.43 10.0 14.2 17.7 24.1 05 40 8.10 12.0 17.4 24.2 28.0 06 07 9B 10 11 12 13 40 40 40 40 40 40 40 9.70 12.0 15.8 17.7 19.2 20.4 23.8 14.6 18.1 23.1 26.2 28.6 30.3 35.7 21.5 26.6 33.0 38.2 41.6 44.2 52.3 30.7 37.9 45.1 54.0 58.8 62.7 74.8 36.0 44.6 51.8 63.3 68.9 73.6 88.3 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 -25 0.5 01 02 03 04 Capacity in kW. Range: -60 – -25 °C. Opening superheat sh = 4 K Valve type -30 Cond. temp. [°C] 50 50 50 50 50 50 50 50 50 50 50 50 50 SI units R404A/R507 Evap. temp. [°C] -60 -50 1.47 2.64 3.61 4.36 5.35 6.68 7.75 9.28 12.7 13.8 14.9 15.6 17.8 -40 2.18 3.97 5.50 6.66 8.39 10.1 12.0 14.4 18.9 21.0 22.7 23.8 27.4 -30 3.13 5.73 8.04 9.81 12.7 14.9 18.1 21.6 27.5 31.1 33.6 35.4 41.0 -25 4.29 7.92 11.2 13.8 18.4 21.1 26.3 31.5 38.5 44.7 48.3 51.0 59.5 4.95 9.15 13.0 16.1 21.7 24.8 31.2 37.4 44.6 52.8 57.0 60.3 70.8 2 0.97 4 1.00 -60 0 1 1.5 1 0.97 0.95 2 0.93 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] US units R404A/R507 Evap. temp. [°F] -75 105 105 105 105 105 105 105 105 105 105 105 105 105 -60 0.49 0.88 1.21 1.49 1.88 2.33 2.79 3.44 4.52 5.06 5.51 5.83 6.81 10 1.09 15 1.16 20 1.23 25 1.30 30 1.37 1 0.96 0.95 Evap. temp. [°C] -40 Correction factor 1 0.96 0.94 1 0.96 0.94 1 0.96 0.94 0.93 0.92 0.92 0.92 -50 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 -45 0.67 1.22 1.70 2.09 2.68 3.25 3.93 4.84 6.23 7.05 7.68 8.14 9.56 Valve type TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] -30 0.90 1.65 2.31 2.86 3.73 4.43 5.46 6.72 8.43 9.68 10.6 11.2 13.2 Capacity in TR. Range: -75 – -15 °F. Opening superheat sh = 7.2 °F. -15 1.18 2.17 3.05 3.80 5.06 5.91 7.41 9.13 11.1 13.1 14.2 15.1 18.0 1.49 2.75 3.88 4.86 6.60 7.66 9.80 12.1 14.2 17.2 18.7 20.0 23.9 US units R404A/R507 Evap. temp. [°F] -75 125 125 125 125 125 125 125 125 125 125 125 125 125 -60 0.41 0.74 1.02 1.23 1.50 1.87 2.15 2.56 3.51 3.81 4.11 4.30 4.89 -45 0.58 1.05 1.45 1.75 2.19 2.65 3.12 3.71 4.93 5.43 5.87 6.15 7.04 Subcooling [°F] Correction factor 2 0.96 7 1.00 10 1.03 -30 0.79 1.44 2.01 2.44 3.13 3.70 4.42 5.25 6.80 7.60 8.21 8.61 9.92 -15 1.04 1.92 2.70 3.30 4.34 5.02 6.13 7.29 9.14 10.4 11.2 11.8 13.7 1.33 2.47 3.50 4.31 5.81 6.61 8.27 9.85 11.9 13.9 15.0 15.9 18.5 -30 -25 Pressure drop [psi] ∆p 20 1.11 30 1.20 40 1.28 50 1.37 US units R404A/R507 SI units R404A/R507 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -75 – -15 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -75 -60 -30 -15 Correction factor 0 1 1 1 1 15 0.96 0.96 0.96 0.96 25 0.94 0.94 0.94 0.93 30 0.93 0.93 0.92 0.92 Calculated at 90 °F condensing temperature. -45 1 0.96 0.93 0.92 DKRCC.PD.AB0.A5.02 | 16 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R22 Evap. temp. [°C] -40 -30 -20 -10 0 10 4.53 8.33 11.7 14.9 19.9 24.4 31.4 41.2 54.5 60.1 65.5 72.3 78.1 95.8 5.73 10.5 14.8 18.8 25.5 31.2 40.5 53.1 70.9 79.7 86.3 95.2 103 127 7.00 12.9 18.0 23.1 31.4 38.8 50.8 67.0 88.6 102 110 121 132 163 8.17 15.0 20.8 26.8 36.6 46.0 60.9 80.9 104 123 133 147 161 199 8.87 16.2 22.3 28.9 39.3 50.7 67.5 90.4 113 136 150 165 183 225 8.56 15.5 21.2 27.5 37.0 49.4 65.7 88.3 105 127 149 163 183 221 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R22 Evap. temp. [°C] -40 -30 -20 -10 0 10 4.67 8.56 12.0 15.2 20.1 24.6 31.2 40.3 54.1 58.0 62.5 68.6 73.3 88.3 5.93 10.9 15.3 19.3 26.0 31.2 40.1 51.3 70.2 76.4 83.4 91.4 98.2 119 7.34 13.5 18.9 24.0 32.5 39.0 50.8 64.7 88.9 98.7 108 118 128 156 8.80 16.2 22.6 28.8 39.2 47.6 62.7 80.1 109 124 136 149 162 197 10.0 18.4 25.4 32.7 44.5 55.3 73.6 95.0 125 146 162 177 194 237 10.6 19.3 26.5 34.2 46.2 59.5 79.5 103 130 155 178 194 215 260 25 1.19 30 1.23 2 0.98 4 1.00 10 1.05 15 1.10 -40 0 1 1.5 1 0.96 0.93 1 0.95 0.93 2 0.91 0.90 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R22 Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 75 75 75 75 75 75 75 75 75 75 75 75 75 75 1.28 2.35 3.30 4.20 5.64 6.93 8.91 11.7 15.5 17.1 18.7 20.6 22.3 27.4 1.66 3.05 4.28 5.45 7.39 9.08 11.8 15.5 20.7 23.4 25.2 27.9 30.3 37.4 2.05 3.77 5.26 6.76 9.20 11.4 15.1 19.9 26.2 30.4 32.6 36.0 39.4 48.8 2.38 4.35 6.02 7.80 10.6 13.5 17.9 24.0 30.5 36.4 39.4 43.4 48.0 59.3 2.47 4.49 6.16 8.01 10.8 14.2 18.9 25.5 31.1 37.6 42.5 46.6 52.1 63.6 2.35 4.26 5.80 7.56 10.2 13.6 18.1 24.4 29.1 35.1 41.0 44.8 50.4 60.8 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R22 Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 1.33 2.43 3.41 4.30 5.72 6.98 8.85 11.5 15.4 16.5 17.8 19.5 20.8 25.1 1.73 3.17 4.46 5.62 7.57 9.08 11.7 15.0 20.5 22.3 24.4 26.8 28.8 34.9 2.18 4.01 5.61 7.12 9.67 11.6 15.1 19.3 26.5 29.6 32.5 35.5 38.4 46.8 2.63 4.82 6.71 8.58 11.7 14.3 18.9 24.3 32.6 37.4 41.2 45.0 49.1 60.0 2.96 5.40 7.44 9.59 13.0 16.4 21.9 28.4 36.6 43.2 48.5 52.9 58.5 71.0 3.02 5.49 7.51 9.72 13.1 16.9 22.6 29.5 36.9 44.0 50.6 55.0 61.2 73.8 20 1.14 Subcooling [°F] Correction factor 40 1.17 50 1.22 2 0.97 7 1.00 10 1.02 20 1.07 30 1.12 US units R22 SI units R22 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.95 0.94 0.92 0.91 0.90 0.88 0 10 1 0.93 0.90 1 0.91 0.86 0.86 0.81 Pressure drop [psi] ∆p Evap. temp. [°F] -40 -20 0 1 1 15 0.95 0.95 25 0.92 0.92 30 0.91 0.90 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.95 0.94 0.91 0.89 0.89 0.87 40 50 1 0.92 0.87 0.84 1 0.91 0.84 0.80 DKRCC.PD.AB0.A5.02 | 17 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R22 Evap. temp. [°C] -40 -30 -20 -10 0 10 4.71 8.62 12.1 15.2 20.0 24.2 30.3 38.8 52.6 55.0 58.0 63.2 67.0 79.1 5.98 11.0 15.4 19.3 25.7 30.3 38.6 48.4 67.8 71.5 78.1 85.0 90.4 107 7.45 13.7 19.3 24.1 32.6 37.8 48.9 60.4 86.0 92.1 102 112 119 143 9.06 16.67 23.4 29.4 40.1 46.6 61.1 75.1 107 117 132 143 154 185. 10.6 19.5 27.2 34.5 47.1 55.8 74.2 91.7 127 144 163 176 191 231 11.8 21.6 29.8 38.1 51.9 63.7 85.3 107 142 165 190 205 225 271 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 55 55 55 55 55 55 55 55 55 55 55 55 55 55 SI units R22 Evap. temp. [°C] -40 -30 -20 -10 0 10 4.68 8.55 11.9 14.9 19.4 23.5 29.1 37.0 50.5 51.7 52.5 56.8 59.7 69.1 5.92 10.9 15.3 18.9 25.0 29.0 36.5 45.0 64.3 66.0 71.1 76.9 81.0 94.6 7.38 13.6 19.2 23.6 31.8 35.8 45.9 55.1 81.1 84.1 94.3 102 108 127 9.02 16.7 23.4 29.0 40.0 44.0 57.4 68.0 101 107 123 132 141 167 10.74 19.8 27.8 34.6 47.5 53.3 70.7 83.5 123 134 155 167 179 213 12.3 22.6 31.4 39.6 54.2 62.7 84.2 101 143 161 187 201 218 260 25 1.19 30 1.23 2 0.98 4 1.00 10 1.05 15 1.10 -40 0 1 1.5 1 0.96 0.93 1 0.95 0.93 2 0.91 0.90 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R22 Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 1.34 2.45 3.42 4.30 5.65 6.85 8.58 11.0 14.9 15.5 16.3 17.8 18.8 22.2 1.74 3.20 4.50 5.61 7.50 8.79 11.2 14.0 19.7 20.7 22.7 24.7 26.2 31.2 2.22 4.08 5.74 7.17 9.70 11.2 14.5 17.8 25.5 27.4 30.7 33.3 35.6 42.6 2.73 5.03 7.04 8.85 12.1 14.0 18.5 22.7 32.2 35.5 40.1 43.5 46.9 56.4 3.21 5.88 8.16 10.4 14.2 16.9 22.6 27.9 38.4 43.8 49.8 53.9 58.7 70.7 3.39 6.19 8.53 10.9 14.8 18.1 24.3 30.3 40.6 47.0 53.9 58.3 63.9 76.8 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 US units R22 Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 1.32 2.42 3.38 4.22 5.48 6.61 1.72 3.15 4.43 5.47 7.24 8.32 2.18 4.03 5.68 6.98 9.40 10.5 2.71 5.01 7.05 8.71 11.9 13.1 3.25 6.00 8.39 10.5 14.4 16.1 3.50 6.44 8.94 11.2 15.4 17.6 06 135 8.17 10.5 13.5 17.2 21.5 23.6 07 08 09 10 11 12 13 135 135 135 135 135 135 135 10.4 14.2 14.5 14.5 15.7 16.5 19.0 12.8 18.5 18.9 20.4 22.0 23.1 26.9 16.0 23.8 24.6 27.8 30.0 31.7 37.2 20.2 30.3 32.0 37.0 39.9 42.4 50.2 25.2 37.2 40.7 47.4 50.9 54.7 65.1 27.9 40.4 45.0 52.5 56.4 60.9 72.6 20 1.14 40 1.17 50 1.22 Subcooling [°F] Correction factor 2 0.97 7 1.00 10 1.02 20 1.07 30 1.12 US units R22 SI units R22 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -20 -10 Correction factor 1 1 0.95 0.94 0.92 0.91 0.90 0.88 0 10 1 0.93 0.90 1 0.91 0.86 0.86 0.81 Pressure drop [psi] ∆p Evap. temp. [°F] -40 -20 0 1 1 15 0.95 0.95 25 0.92 0.92 30 0.91 0.90 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.95 0.94 0.91 0.89 0.89 0.87 40 50 1 0.92 0.87 0.84 1 0.91 0.84 0.80 DKRCC.PD.AB0.A5.02 | 18 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -60°C – -25°C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] SI units R22 Evap. temp. [°C] -60 20 20 20 20 20 20 20 20 20 20 20 20 20 -50 2.63 4.80 6.68 8.39 11.0 12.2 15.9 20.8 30.7 36.3 40.6 43.3 53.1 -40 3.66 6.71 9.38 11.9 15.7 16.9 22.1 29.0 41.9 50.4 55.9 60.4 74.6 -30 4.87 8.95 12.6 15.9 21.4 22.5 29.9 39.2 54.5 67.5 74.9 81.4 101 6.18 11.4 15.9 20.3 27.6 28.8 38.7 51.1 67.2 86.3 95.9 104 131 Capacity in kW. Range: -60°C – -25°C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] -25 6.84 12.6 17.6 22.5 30.6 32.0 43.3 57.3 72.9 95.7 106 117 147 SI units R22 Evap. temp. [°C] -60 30 30 30 30 30 30 30 30 30 30 30 30 30 -50 2.70 4.90 6.78 8.43 10.8 12.1 15.6 19.9 30.0 34.7 38.1 40.8 49.1 -40 3.78 6.90 9.61 12.0 15.7 16.9 21.8 28.0 41.3 48.7 53.6 57.5 69.7 -30 5.07 9.30 13.0 16.4 21.8 22.8 29.9 38.6 54.6 66.0 72.8 78.5 95.9 -25 6.52 12.0 16.8 21.3 28.8 29.7 39.5 51.2 68.7 86.0 95.0 103 127 7.28 13.4 18.8 23.8 32.4 33.4 44.8 58.1 75.5 96.4 107 116 143 Correction factor 2 4 10 15 20 25 30 0.98 1.00 1.05 1.10 1.14 1.19 1.23 0 1 1.5 2 -60 1 0.96 0.94 0.91 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] Evap. temp. [°F] -75 65 65 65 65 65 65 65 65 65 65 65 65 65 -60 0.76 1.38 1.93 2.43 3.19 3.53 4.60 6.04 8.89 10.6 11.7 12.6 15.5 1.00 1.83 2.56 3.23 4.29 4.61 6.06 7.96 11.5 13.9 15.4 16.7 20.6 -30 1.27 2.34 3.28 4.16 5.58 5.89 7.81 10.3 14.4 17.8 19.7 21.4 26.7 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] Evap. temp. [°F] -75 85 85 85 85 85 85 85 85 85 85 85 85 85 -60 0.78 1.42 1.96 2.44 3.15 3.51 4.49 5.77 8.69 10.1 11.1 11.9 14.3 -50 1 0.96 0.93 0.91 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 1.88 3.45 4.82 6.18 8.41 8.80 11.9 15.8 20.2 26.5 29.5 32.3 40.7 US units R22 -45 1.03 1.89 2.63 3.29 4.29 4.63 5.98 7.69 11.4 13.4 14.7 15.8 19.2 -15 1.57 2.89 4.06 5.17 7.00 7.31 9.80 12.9 17.4 22.1 24.6 26.8 33.6 Capacity in TR. Range: -75°F – -15°F. Opening superheat sh = 7.2 °F. Valve type US units R22 -45 -30 1.33 2.44 3.41 4.29 5.68 5.98 7.82 10.1 14.4 17.3 19.1 20.6 25.1 -15 1.66 3.05 4.29 5.41 7.27 7.53 9.97 12.9 17.7 21.9 24.2 26.1 32.1 Subcooling [°F] Correction factor 2.01 3.71 5.20 6.60 8.95 9.23 12.4 16.1 21.0 26.8 29.6 32.1 39.8 2 7 10 20 30 40 50 0.97 1.00 1.02 1.07 1.12 1.17 1.22 US units R22 SI units R22 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Capacity in TR. Range: -75°F – -15°F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -40 Correction factor -30 1 0.96 0.93 0.91 1 0.95 0.93 0.90 -25 1 0.95 0.93 0.90 Pressure drop [psi] ∆p 0 15 25 30 Evap. temp. [°F] -75 -60 -45 -30 -15 1 0.95 0.92 0.90 1 0.95 0.92 0.90 Correction factor 1 0.96 0.93 0.91 1 0.96 0.93 0.91 1 0.95 0.92 0.91 Calculated at 90 °F condensing temperature. DKRCC.PD.AB0.A5.02 | 19 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -60°C – -25°C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] SI units R22 Evap. temp. [°C] -60 40 40 40 40 40 40 40 40 40 40 40 40 40 -50 2.72 4.92 6.76 8.31 10.5 11.8 14.8 18.6 28.6 32.3 35.3 37.5 44.2 -40 3.82 6.96 9.66 11.9 15.3 16.5 21.0 26.4 39.8 45.8 50.1 53.3 63.3 -30 5.16 9.45 13.2 16.5 21.6 22.5 29.1 36.8 53.2 62.7 68.7 73.4 88.0 6.70 12.3 17.3 21.7 29.1 29.7 39.1 49.6 68.0 82.7 90.8 97.5 118 Capacity in kW. Range: -60°C – -25°C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 TE 5 TE 12 TE 55 Cond. temp. [°C] -25 7.53 13.9 19.5 24.5 33.1 33.6 44.6 56.8 75.3 93.5 103 111 135 SI units R22 Evap. temp. [°C] -60 50 50 50 50 50 50 50 50 50 50 50 50 50 -50 2.71 4.87 6.65 8.08 9.94 11.2 13.8 17.0 26.9 29.6 32.0 33.7 38.8 -40 3.81 6.91 9.55 11.7 14.7 15.8 19.8 24.3 37.6 42.1 45.7 48.2 56.1 -30 5.17 9.44 13.2 16.2 21.0 21.7 27.7 34.2 50.6 58.1 63.2 66.9 78.6 -25 6.75 12.4 17.5 21.6 28.8 29.0 37.6 46.6 65.4 77.4 84.3 89.7 107 7.62 14.0 19.8 24.6 33.0 33.0 43.3 53.7 73.0 88.0 95.9 102 122 Correction factor 2 4 10 15 20 25 30 0.98 1.00 1.05 1.10 1.14 1.19 1.23 0 1 1.5 2 -60 1 0.96 0.94 0.91 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] Evap. temp. [°F] -75 105 105 105 105 105 105 105 105 105 105 105 105 105 -60 0.79 1.43 1.96 2.41 3.03 3.40 4.26 5.35 8.26 9.33 10.2 10.8 12.7 1.05 1.90 2.64 3.26 4.17 4.51 5.73 7.19 10.9 12.5 13.6 14.5 17.2 -30 1.35 2.48 3.46 4.29 5.60 5.87 7.56 9.51 14.0 16.3 17.9 19.0 22.8 TE 5 TE 12 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 9B 10 11 12 13 Cond. temp. [°F] Evap. temp. [°F] -75 125 125 125 125 125 125 125 125 125 125 125 125 125 -60 0.78 1.41 1.92 2.33 2.86 3.21 3.96 4.83 7.68 8.42 9.12 9.57 11.0 -50 1 0.96 0.93 0.91 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 2.09 3.84 5.41 6.79 9.16 9.29 12.3 15.6 20.9 25.8 28.3 30.5 37.0 US units R22 -45 1.04 1.89 2.60 3.17 3.97 4.29 5.35 6.54 10.2 11.3 12.3 12.9 15.0 -15 1.70 3.13 4.39 5.48 7.29 7.48 9.76 12.3 17.4 20.8 22.8 24.4 29.4 Capacity in TR. Range: -75°F – -15°F. Opening superheat sh = 7.2 °F. Valve type US units R22 -45 -30 1.35 2.46 3.43 4.20 5.39 5.62 7.12 8.72 13.2 14.9 16.2 17.1 20.0 -15 1.71 3.13 4.40 5.42 7.11 7.22 9.28 11.4 16.5 19.2 20.8 22.1 26.0 Subcooling [°F] Correction factor 2.11 3.88 5.47 6.79 9.08 9.05 11.8 14.6 20.1 24.0 26.1 27.8 33.1 2 7 10 20 30 40 50 0.97 1.00 1.02 1.07 1.12 1.17 1.22 US units R22 SI units R22 Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Capacity in TR. Range: -75°F – -15°F. Opening superheat sh = 7.2 °F. Evap. temp. [°C] -40 Correction factor -30 1 0.96 0.93 0.91 1 0.95 0.93 0.90 -25 1 0.95 0.93 0.90 Pressure drop [psi] ∆p 0 15 25 30 Evap. temp. [°F] -75 -60 -45 -30 -15 1 0.95 0.92 0.90 1 0.95 0.92 0.90 Correction factor 1 0.96 0.93 0.91 1 0.96 0.93 0.91 1 0.95 0.92 0.91 Calculated at 90 °F condensing temperature. DKRCC.PD.AB0.A5.02 | 20 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R134a Evap. temp. [°C] -40 -30 -20 -10 0 10 2.59 4.76 6.69 8.55 11.5 15.2 19.7 26.3 30.2 34.8 40.0 44.6 48.5 60.6 3.33 6.12 8.60 11.0 14.9 19.3 25.2 33.8 39.1 45.4 52.7 58.7 64.0 80.4 4.16 7.65 10.7 13.8 18.7 24.1 31.6 42.6 49.3 58.0 67.7 75.4 82.6 104 5.00 9.18 12.8 16.5 22.5 29.0 38.4 51.9 59.8 71.5 84.0 93.4 103 130 5.65 10.3 14.4 18.6 25.4 33.0 43.9 59.5 67.8 82.4 98.1 109 121 152 5.72 10.4 14.4 18.7 25.4 33.6 44.8 60.8 68.3 84.0 102 113 127 156 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R134a Evap. temp. [°C] -40 -30 -20 -10 0 10 2.65 4.86 6.81 8.70 11.6 15.3 19.6 26.1 30.3 34.1 38.2 42.3 45.6 56.0 3.42 6.29 8.83 11.3 15.2 19.5 25.1 33.3 39.2 44.4 51.0 56.4 61.0 75.3 4.34 7.98 11.2 14.3 19.3 24.5 31.9 42.1 50.0 57.3 66.8 73.9 80.3 99.4 5.36 9.85 13.8 17.6 24.0 30.3 39.8 52.5 62.3 72.6 85.5 94.4 103 128 6.35 11.6 16.2 20.8 28.4 36.1 47.8 63.2 74.4 88.3 105 116 128 159 7.03 12.8 17.7 22.9 31.1 40.2 53.6 71.1 82.4 99.3 121 133 148 182 25 1.22 30 1.28 2 0.98 4 1.00 10 1.06 15 1.12 -40 0 1 1.5 1 0.93 0.90 1 0.93 0.89 2 0.86 0.85 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R134a Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 75 75 75 75 75 75 75 75 75 75 75 75 75 75 0.73 1.35 1.89 2.42 3.27 4.29 5.57 7.47 8.57 9.88 11.4 12.7 13.8 17.3 0.96 1.78 2.49 3.19 4.33 5.61 7.32 9.85 11.4 13.3 15.4 17.2 18.8 23.6 1.22 2.25 3.15 4.06 5.53 7.12 9.36 12.7 14.6 17.3 20.2 22.5 24.7 31.2 1.47 2.70 3.76 4.87 6.64 8.59 11.4 15.5 17.7 21.3 25.2 28.0 31.0 39.0 1.61 2.94 4.06 5.27 7.18 9.42 12.6 17.1 19.3 23.6 28.4 31.5 35.2 43.9 1.57 2.87 3.95 5.14 6.97 9.26 12.4 16.8 18.8 23.1 28.1 31.1 34.9 43.2 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R134a Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 0.75 1.38 1.93 2.47 3.30 4.35 5.57 7.42 8.60 9.69 10.8 12.0 113.0 15.9 1.00 1.84 2.58 3.29 4.43 5.67 7.34 9.70 11.4 13.0 14.9 16.5 17.9 22.1 1.30 2.38 3.34 4.26 5.78 7.31 9.54 12.6 14.9 17.2 20.1 22.2 24.2 29.9 1.62 2.97 4.15 5.33 7.25 9.17 12.1 15.9 18.9 22.1 26.6 28.9 31.6 39.3 1.91 3.49 4.84 6.24 8.50 10.9 14.5 19.1 22.4 26.8 32.1 35.4 39.1 48.5 2.00 3.65 5.03 6.51 8.84 11.4 15.2 20.2 23.4 28.2 34.3 37.7 41.9 51.7 20 1.17 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.92 0.92 0.88 0.87 0.84 0.82 0 10 1 0.90 0.84 1 0.87 0.79 0.79 0.71 Pressure drop [psi] ∆p 30 1.15 US units R134a SI units R134a Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -40 -20 0 1 1 15 0.93 0.93 25 0.88 0.87 30 0.86 0.85 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.92 0.91 0.86 0.84 0.83 0.81 40 50 1 0.89 0.80 0.75 1 0.86 0.76 0.70 DKRCC.PD.AB0.A5.02 | 21 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R134a Evap. temp. [°C] -40 -30 -20 -10 0 10 2.64 4.83 6.75 8.62 11.4 15.0 19.0 25.2 29.5 32.6 35.1 38.6 41.4 49.8 3.42 6.28 8.80 11.2 14.9 19.0 24.3 31.7 38.0 42.1 47.5 52.1 56.0 67.8 4.37 8.04 11.3 14.3 19.2 24.0 31.0 39.9 48.7 54.4 63.1 69.4 74.7 90.9 5.49 10.1 14.1 17.9 24.3 30.0 39.1 50.1 61.6 69.9 82.6 90.6 98.1 120 6.70 12.3 17.2 21.9 29.8 36.7 48.5 62.1 76.1 87.7 105 115 126 154 7.80 14.3 19.8 25.4 34.5 43.2 57.5 73.9 89.3 105 128 140 153 189 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 55 55 55 55 55 55 55 55 55 55 55 55 55 55 SI units R134a Evap. temp. [°C] -40 -30 -20 -10 0 10 2.56 4.68 6.52 8.34 10.9 14.4 18.0 23.8 28.1 30.5 31.2 34.0 36.1 42.7 3.32 6.09 8.54 10.8 14.3 18.0 22.8 29.4 35.9 38.9 42.6 46.5 49.4 58.7 4.27 7.84 11.0 13.8 18.5 22.6 29.0 36.6 45.9 49.9 57.3 62.6 66.7 79.8 5.41 9.95 14.0 17.5 23.7 28.3 36.8 45.8 58.4 64.2 76.2 83.1 89.0 107 6.72 12.4 17.3 21.8 29.6 35.2 46.4 57.3 73.4 82.0 99.2 108 117 141 8.06 14.8 20.6 26.1 35.7 42.8 56.9 70.4 89.4 102 125 136 148 179 25 1.22 30 1.28 2 0.98 4 1.00 10 1.06 15 1.12 -40 0 1 1.5 1 0.93 0.90 1 0.93 0.89 2 0.86 0.85 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R134a Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 0.75 1.37 1.91 2.44 3.23 4.25 5.38 7.12 8.34 9.19 9.86 10.8 11.6 13.9 1.00 1.83 2.57 3.25 4.34 5.51 7.04 9.15 11.1 12.2 13.8 15.1 16.2 19.6 1.31 2.40 3.37 4.27 5.75 7.12 9.21 11.8 14.5 16.2 18.9 20.8 22.3 27.2 1.67 3.08 4.31 5.47 7.42 9.10 11.9 15.2 18.8 21.3 25.4 27.8 30.1 36.8 2.06 3.78 5.26 6.71 9.14 11.3 15.0 19.1 23.4 27.1 32.7 35.8 39.1 47.9 2.23 4.08 5.66 7.25 9.87 12.3 16.4 20.9 25.4 29.8 36.2 39.6 43.5 53.2 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R134a Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 135 135 135 135 135 135 135 135 0.72 1.32 1.83 2.34 3.06 4.05 5.04 6.67 7.87 8.49 8.57 9.34 9.89 11.6 0.96 1.76 2.47 3.11 4.11 5.16 6.53 8.37 10.3 11.1 12.1 13.2 14.0 16.6 1.27 2.33 3.27 4.09 5.48 6.63 8.50 10.6 13.5 14.6 16.9 18.4 19.6 23.4 1.64 3.02 4.24 5.31 7.19 8.51 11.1 13.7 17.6 19.3 23.2 25.2 27.0 32.4 2.07 3.81 5.33 6.71 9.15 10.8 14.3 17.5 22.6 25.3 30.8 33.5 36.2 43.6 2.29 4.20 5.86 7.40 10.1 12.0 16.0 19.6 25.2 28.5 35.0 38.0 41.2 49.8 20 1.17 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.92 0.92 0.88 0.87 0.84 0.82 0 10 1 0.90 0.84 1 0.87 0.79 0.79 0.71 Pressure drop [psi] ∆p 30 1.15 US units R134a SI units R134a Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -40 -20 0 1 1 15 0.93 0.93 25 0.88 0.87 30 0.86 0.85 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.92 0.91 0.86 0.84 0.83 0.81 40 50 1 0.89 0.80 0.75 1 0.86 0.76 0.70 DKRCC.PD.AB0.A5.02 | 22 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 25 25 25 25 25 25 25 25 25 25 25 25 25 25 SI units R407C Evap. temp. [°C] -40 -30 -20 -10 0 10 4.62 8.48 11.9 15.0 20.1 20.9 26.6 34.5 49.3 54.3 63.6 70.1 75.5 92.1 5.82 10.7 15.0 19.0 25.6 27.9 35.8 46.5 63.2 70.6 82.2 90.5 97.8 120 7.18 13.2 18.4 23.6 31.9 36.2 46.9 61.4 79.4 90.4 105 115 125 154 8.56 15.7 21.8 28.1 38.2 45.1 59.1 78.2 96.4 112 130 143 156 192 9.66 17.7 24.4 31.6 42.9 52.7 69.8 93.2 110 131 153 168 186 228 10.0 18.2 24.9 32.4 43.7 55.9 74.5 99.8 114 138 166 181 202 246 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 35 35 35 35 35 35 35 35 35 35 35 35 35 35 SI units R407C Evap. temp. [°C] -40 -30 -20 -10 0 10 4.54 8.34 11.7 14.7 19.4 20.2 25.4 32.2 47.0 50.5 58.3 63.9 68.2 81.8 5.77 10.6 14.9 18.7 25.0 26.7 33.9 42.6 60.3 65.4 76.3 83.5 89.4 108 7.22 13.3 18.6 23.5 31.7 34.7 44.7 56.3 76.7 84.4 98.9 108 116 141 8.82 16.2 22.7 28.8 39.1 44.2 57.6 73.2 95.6 108 126 138 149 181 10.4 19.0 26.4 33.8 46.0 54.0 71.3 91.7 114 132 155 169 185 225 11.5 20.9 28.7 37.0 50.2 61.6 82.1 107 127 151 180 196 216 262 25 1.23 30 1.28 2 0.98 4 1.00 10 1.07 15 1.12 -40 0 1 1.5 1 0.96 0.94 1 0.96 0.94 2 0.92 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407C Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 75 75 75 75 75 75 75 75 75 75 75 75 75 75 1.31 2.41 3.38 4.27 5.71 5.95 7.58 9.87 14.1 15.5 18.2 20.1 21.6 26.5 1.69 3.11 4.36 5.54 7.47 8.19 10.5 13.7 18.5 20.8 24.1 26.6 28.8 35.3 2.12 3.89 5.44 6.96 9.45 10.9 14.1 18.6 23.6 27.2 31.3 34.5 37.6 46.3 2.53 4.63 6.42 8.29 11.3 13.6 17.9 23.8 28.7 33.9 39.1 43.0 47.3 58.3 2.78 5.07 6.96 9.05 12.3 15.4 20.5 27.5 31.7 38.3 45.2 49.6 55.1 67.5 2.78 5.06 6.91 9.00 12.2 15.6 20.8 27.9 31.6 38.4 46.3 50.6 56.6 68.8 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407C Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 95 95 95 95 95 95 95 95 95 95 95 95 95 95 1.29 2.37 3.32 4.16 5.52 5.74 7.21 9.15 13.4 14.4 16.6 18.1 19.4 23.2 1.68 3.09 4.34 5.45 7.30 7.80 9.92 12.5 17.6 19.1 22.3 24.4 26.1 31.5 2.15 3.95 5.54 7.00 9.46 10.4 13.5 17.0 22.9 25.4 29.7 32.4 34.9 42.3 2.66 4.88 6.81 8.67 11.8 13.5 17.7 22.5 29.0 32.9 38.5 42.1 45.6 55.5 3.10 5.68 7.85 10.1 13.7 16.4 21.8 28.2 34.4 40.2 47.6 51.8 56.8 69.0 3.25 5.93 8.15 10.5 14.3 17.5 23.3 30.3 36.1 42.9 51.2 55.7 61.4 74.4 20 1.18 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.95 0.94 0.93 0.91 0.91 0 10 1 0.95 0.92 1 0.93 0.90 0.89 0.86 Pressure drop [psi] ∆p 30 1.15 US units R407C SI units R407C Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.93 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.91 0.90 40 50 1 0.94 0.90 0.88 1 0.93 0.88 0.86 DKRCC.PD.AB0.A5.02 | 23 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] 45 45 45 45 45 45 45 45 45 45 45 45 45 45 SI units R407C Evap. temp. [°C] -40 -30 -20 -10 0 10 4.34 7.96 11.1 13.9 18.2 19.0 23.6 29.7 43.6 45.8 51.5 56.0 59.3 69.8 5.52 10.2 14.3 17.7 23.6 24.6 31.0 38.2 55.5 58.7 68.0 73.9 78.4 92.7 6.96 12.8 18.1 22.4 30.2 31.9 40.7 49.6 70.8 75.6 89.2 97.0 103 123 8.65 15.9 22.4 28.0 38.0 40.9 53.0 64.5 89.6 97.4 116 126 135 161 10.4 19.2 26.8 33.9 46.3 51.3 67.4 82.7 111 123 147 160 172 207 12.0 22.1 30.5 38.9 53.1 61.4 81.9 102 130 149 179 194 211 253 Capacity in kW. Range: -40 – 10 °C. Opening superheat sh = 4 K Valve type Orifice no. TE 5 TE 12 TE 20 TE 55 Cond. temp. [°C] SI units R407C Evap. temp. [°C] -40 -30 -20 -10 0 10 0.5 01 02 55 55 55 4.04 7.38 10.3 5.12 9.40 13.2 6.46 11.9 16.8 8.08 15.0 21.1 9.91 18.3 25.8 11.7 21.7 30.3 03 55 12.8 16.3 20.6 25.9 31.9 37.9 04 05 06 07 08 09 10 11 12 13 55 55 55 55 55 55 55 55 55 55 16.6 17.5 21.4 27.1 39.4 40.6 43.5 47.0 49.3 56.8 21.4 22.2 27.6 33.7 49.6 51.2 57.9 62.6 65.7 76.3 27.6 28.2 35.7 42.6 62.8 65.2 76.9 82.9 87.4 102 35.2 36.0 46.4 54.5 79.8 83.8 101 109 116 136 43.8 45.6 59.8 69.9 100 109 132 142 151 179 52.2 56.2 74.9 88.1 122 135 165 178 191 227 2 0.98 4 1.00 10 1.07 15 1.12 -40 0 1 1.5 1 0.96 0.94 1 0.96 0.94 2 0.92 0.92 -30 Calculated at 32 °C condensing temperature. © Danfoss | DCS (sw) | 2016.10 TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407C Cond. temp. [°F] Evap. temp. [°F] -40 -20 0 20 40 50 115 115 115 115 115 115 115 115 115 115 115 115 115 115 1.22 2.24 3.14 3.91 5.13 5.35 6.63 8.34 12.2 12.8 14.4 15.6 16.5 19.4 1.60 2.94 4.13 5.12 6.82 7.12 8.96 11.0 16.0 16.9 19.6 21.3 22.6 26.7 2.07 3.80 5.36 6.65 8.97 9.46 12.1 14.7 21.0 22.4 26.5 28.8 30.6 36.4 2.61 4.81 6.76 8.45 11.5 12.4 16.2 19.6 27.2 29.6 35.4 38.3 41.0 49.1 3.17 5.84 8.13 10.3 14.1 15.8 20.9 25.6 33.9 38.1 45.6 49.3 53.3 64.0 3.42 6.27 8.69 11.1 15.1 17.3 23.1 28.6 36.8 42.1 50.6 54.7 59.4 71.3 Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Valve type TE 5 TE 12 TE 20 TE 55 Orifice no. 0.5 01 02 03 04 05 06 07 08 09 10 11 12 13 US units R407C Evap. temp. [°F] Cond. temp. [°F] -40 -20 0 20 40 50 135 135 135 135 135 135 135 135 135 135 135 135 135 135 1.12 2.05 2.87 3.55 4.59 4.88 5.94 7.54 10.9 11.2 11.8 12.7 13.3 15.3 1.46 2.68 3.78 4.63 6.10 6.29 7.82 9.53 14.0 14.4 16.3 17.5 18.4 21.3 1.89 3.48 4.92 6.01 8.06 8.20 10.4 12.3 18.2 18.8 22.3 24.0 25.3 29.5 2.41 4.46 6.31 7.72 10.5 10.7 13.8 16.1 23.7 24.9 30.3 32.6 34.5 40.5 3.00 5.54 7.80 9.65 13.3 13.8 18.2 21.1 30.4 32.7 40.3 43.2 46.1 54.5 3.28 6.07 8.50 10.59 14.6 15.5 20.6 24.0 33.9 37.1 45.6 49.0 52.5 62.2 20 1.18 25 1.23 30 1.28 Subcooling [°F] Correction factor 40 1.21 50 1.27 2 0.97 7 1.00 10 1.02 20 1.08 Evap. temp. [°C] -20 -10 Correction factor 1 1 0.96 0.95 0.94 0.93 0.91 0.91 0 10 1 0.95 0.92 1 0.93 0.90 0.89 0.86 Pressure drop [psi] ∆p 30 1.15 US units R407C SI units R407C Distributer correction factor, fp Distributer correction factor, fp Pressure drop [bar] ∆p Valve type Subcooling correction factor, fsub Subcooling correction factor, fsub Subcooling [K] Correction factor Capacity in TR. Range: -40 – 50 °F. Opening superheat sh = 7.2 °F. Evap. temp. [°F] -40 -20 0 1 1 15 0.96 0.96 25 0.93 0.93 30 0.92 0.92 Calculated at 90 °F condensing temperature. 0 20 Correction factor 1 1 0.96 0.95 0.93 0.92 0.91 0.90 40 50 1 0.94 0.90 0.88 1 0.93 0.88 0.86 DKRCC.PD.AB0.A5.02 | 24 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 Dimensions and weights ØD3 35 mm 42 mm 2.76 in 1.69 in 1.26 in 2.95 in 2.76 in TE 5 - Solder, straightway Weight: 2.02 lbs ØD3 ØD3 Ø 19.2 mm 35 mm 42 mm © Danfoss | DCS (sw) | 2016.10 2.95 in Danfoss 67B35.10 1.38 in 1.65 in TE 5 - Solder, straightway Weight: 1 kg 32 mm Angle way 42 mm TE 5 - Solder, angleway Weight: 1 kg 2.95 in Straight way 1.26 in 3.82 3.82 3.82 3.82 2.91 2.05 2.05 1.57 7⁄₈ × 11⁄₈ 22 X 28 mm ⁵⁄₈ × 7⁄₈ 16 X 22 mm Others 7⁄₈ × 11⁄₈ 22 × 28 mm Others Ø 0.76 in 2.76 in 97 97 97 97 74 52 52 40 Valve body Ø 19.2 mm 35 mm 1.26 in L4 [in] Angle way Danfoss 67B38.10 L4 [mm] Straight way 0.59 in L3 [in] 1.10 1.10 1.10 1.10 0.98 1.54 1.54 1.10 TE 5 - Flare, angleway Weight: 2.43 lbs Danfoss 67B39.10 L3 [mm] 7⁄₈ × 11⁄₈ 28 22 X 28 mm 28 ⁵⁄₈ × 7⁄₈ 28 16 X 22 mm 28 Others 25 7⁄₈ × 11⁄₈ 39 22 × 28 mm 39 Others 28 Valve body 75 mm L1 [in] 0.47 0.67 0.98 2.17 in Ø 0.76 in ØD3 75 mm L1 [mm] 12 17 25 1.65 in ØD3 32 mm Outlet side ØD2 ⁵⁄₈ In. / 16 mm ODF 7⁄₈ In. / 22 mm ODF 11⁄₈ In. / 28 mm ODM 1.38 in TE 5 - Flare, angleway Weight: 1.1 kg Danfoss 67B37.10 L1 [in] 0.39 0.47 0.67 Ø 19.2 mm 15 mm L1 [mm] 10 12 17 55 mm Danfoss 67B40.10 Inlet side ØD1 ½ In. / 12 mm ODF 5 ⁄₈ In. / 16 mm ODF 7⁄₈ In. / 22 mm ODF 75 mm 43 mm ØD3 [in] 2.09 2.36 70 mm Standard Range -60 – -25 °C (-75 – -15 °F) ØD3 [mm] 53 60 70 mm Element 70 mm 32 mm Danfoss 67B36.10 ØD3 Ø 0.76 in 1.38 in 1.65 in TE 5 - Solder, angleway Weight: 2.02 lbs DKRCC.PD.AB0.A5.02 | 25 Data sheet | Thermostatic expansion valves, type TE 5 – TE 55 L1 [in] 0.67 Outlet side ØD2 L1 [mm] L1 [in] 11/8 in. / 28 mm ODM 25 0.98 42 mm L2 3.23 in ØD2 1.14 in L2 82 mm 29 mm ØD2 39 mm ØD2 L1 L1 ØD1 37 mm 52 mm Ø 19.2 mm L1 TE 12 and TE 20 Solder, angleway Weight: TE 12: 1.5 kg TE 20: 1.6 kg ØD1 1.46 in 2.05 in Ø 0.76 in TE 12 and TE 20 Solder, angleway Weight: TE12: 3.31 lbs TE20: 3.53 lbs ØD3 L2 87 mm 33 mm 35 mm Danfoss 67B45.10 ØD3 1.65 in L2 L1 [mm] 17 TE12 / TE20 3.23 in Inlet side ØD1 7 /8 in. / 22 mm ODF 1.54 in 4.72 ØD3 ØD3 1.53 in 120 3.82 in ØD2 4.72 Ø 0.76 in TE 12 and TE 20 Solder, straightway Weight: TE 12: 3.31 lbs TE 20: 3.75 lbs 1.46 in Danfoss 67B44.10 120 TE 12 Standard TE 12 Range -60 – -25 °C (-75 – -15 °F) TE 20 97 mm 1.65 in L1 L2 [in] 2.95 ØD1 L2 [mm] 75 Bulb L1 L2 2.83 L1 TE 12 and TE 20 Solder, straightway Weight: TE 12: 1.5 kg TE 20: 1.7 kg 37 mm 42 mm 82 mm 72 L1 39 mm 2.83 Ø 19.2 mm 29 mm 72 TE 12 Standard TE 12 Range -60 – -25 °C (-75 – -15 °F) TE 20 L1 Danfoss 67B43.10 ØD3 [in] 2.36 ØD1 ØD3 [mm] 60 Element Danfoss 67B42.10 ØD3 Danfoss 67B41.10 ØD3 1.14 in Dimensions and weights Ø 19.2 mm 37 mm 42 mm 115 mm 80 mm TE 12 - Solder flanges, straightway Weight: Without filter: 2.3 kg Weight: Without filter: 7.72 lbs ØD3 1.65 in 1.46 in L2 3.42 in 1.3 in 1.38 in Danfoss 67B46.10 ØD3 Ø 0.76 in 3.15 in 4.53 in © Danfoss | DCS (sw) | 2016.10 DKRCC.PD.AB0.A5.02 | 26 Ø 2.83 in 42 mm TE 55 L1 [in] /8 in. / 22 mm ODF 17 0.67 11/8 in. / 28 mm ODM 25 0.98 Outlet side ØD2 L2 [mm] L2 [in] 11/8 in. / 28 mm ODF 22 0.87 13/8 in. / 35 mm ODM 27 1.06 3.74 in 4.72 in Ø 0.76 in 4.29 in TE 55 - Solder, straightway Weight: 1.7 kg TE 55 - Solder, straightway Weight: 3.75 lbs Ø 2.83 in Ø 72 mm 3.74 in Danfoss 67B49.10 53 mm L2 ØD1 1.61 in 120 mm 95 mm 41 mm ØD1 L1 Ø 19.2 mm 42 mm ØD2 37 mm 51 mm TE 55 - Solder, angleway Weight: 1.6 kg © Danfoss | DCS (sw) | 2016.10 1.18 in ØD1 ØD2 1.6 in 95 mm 120 mm 109 mm L2 1.46 in 1.65 in Danfoss 67B48.10 7 Ø 19.2 mm L1 2.09 in L1 [mm] L1 L2 L2 Inlet side ØD1 37 mm 4.72 in L1 30 mm ØD1 ØD2 41 mm Danfoss 67B47.10 Danfoss 67B50.10 Ø 72 mm Ø 0.76 in 1.65 in ØD2 1.46 in 2.01 in TE 55 - Solder, angleway Weight: 3.53 lbs DKRCC.PD.AB0.A5.02 | 27