Transcript
R
F IE
D SYS
(651) 426-2993
(800) 255-4208
FAX (651) 426-9547
www.tjernlund.com
TE
and 460 volt VFD
PROJECT:_____________________________________________________________________ 10' (3m) COMMUNICATIONS CABLE PROVIDED WITH EACH VFD
1
INDUCER TRANSDUCER BOX
WARNING: Improper wiring to this transducer will destroy the transducer. Use caution to ensure that the wiring to the transducer is correct before activating the CPC-3 Controller.
1
R B G
220' (67m)
20 AWG
165' (50m)
22 AWG
110' (34m)
GRAY
RED
WHT/BRN
YELLOW
ENLARGED VIEW
INDUCER TERMINAL STRIP
1
B D+ D- S3 SC S2 S1 M2 M1 MC MB COMBUSTION AIR
B
R
G
B
R
G
SENSORS
2
P2 P1 G R
S1 S2
INDUCER
AUX. SENSOR
B D+ D- S3 SC S2 S1 M2 M1 MC MB INDUCER MOTOR ROTATION SELECTOR
WHT/RED
BLUE
GRN/YEL
N/O
COMBUSTION AIR TERMINAL STRIP
COMBUSTION AIR MOTOR ROTATION SELECTOR
CPC-3
TJERNLUND PRODUCTS, INC.
ALARM
NO C NC
18 AWG
1
BLACK
390' (119m)
VIOLET
16 AWG
COMMON
DIGITAL I/O
600' (183m)
P2 P1 G R
14 AWG
The low voltage VFD communication wiring is to be routed in metal conduit. If longer wiring is desired, see the wire length table at left for maximum wire lengths.
S1 S2 S1 S2
900' (274m)
B D+ D- S3 SC S2 S1 M2 M1MC MB
Max. Distance
12 AWG
COMBUSTION AIR MANUAL MODE PROVING SWITCH
P2 P1 G R
Wire Gage
ORANGE
Route transducer wiring in metal conduit or use Belden Shield Cable #9939 or equivalent. Make sure the transducer wiring does not contain or cross line voltage wiring or undesired transducer performance may result.
CPC-3 CONTROLLER CIRCUIT BOARD
1
MICROCONTROLLERS
CONTROLLER DISPLAY
1
2
KEYPAD CONNECTORS
2
RESET SWITCH
REMOTE ALARM PORT
BOARD ALARM
EXP1
EXP2
EXP3
C O S2 S1
AUX. CONTROL
EXP-4E SIGNAL PORTS
AUXILIARY DEVICE PORT
ANALOG AND DIGITAL POWER SUPPLIES
AC POWER
OFF
ON
MAIN
MAIN AC POWER TERMINAL
L
N
#1
L
N
L
N
L
N
EXP4-E POWER TERMINALS
A
B
1
2
3
4
APPLIANCE 1 PORT
#2 A
B
1
2
3
4
APPLIANCE 2 PORT
#3 A
B
1
2
3
4
APPLIANCE 3 PORT
#4 A
B
1
2
3
4
APPLIANCE 4 PORT
CALL RETURN JUMPERS
11/18/04 8052020 SHEET 1
S
CI
White Bear Lake, MN 55110
Modulating Combustion Air System with VSUB 8/12/16/20 Blower, CPC-3 Controller
R N L UN
M
SP
E
JE
1601 Ninth Street
D
T
Tjernlund Products, Inc.
WARNINGS:
LEGEND: 8052020 SHEET 2
LOW VOLTAGE / DC CONTROL WIRING 230 VAC SUPPLY / LOAD WIRING
1. Improper wiring to the transducer will destroy the transducer. Use caution to ensure that the wiring to the transducer is correct before activating the CPC-3 controller. 2. Verify that the input power voltage matches the VFD's nameplate rating before applying power. Improper supply voltage to the VFD could damage the VFD.
460 VAC SUPPLY / LOAD WIRING VFD COMMUNICATIONS CABLE FIGURE 8052020 11/18/04
3. Verify that the blower (VSUB 8/12/16/20) is wired for the output voltage from the VFD. If not correct, severe damage to the blower and/or the VFD could result. 4. When the system is completely installed, perform the safety interlock and operational test as outlined in the installation manuals. Failure to do these tests could result in an unsafe and/or incorrectly operating system.
2
CAUTIONS:
TJERNLUND DRIVE MODEL VFD- _ _ _ _ _ _ _ 4C3
460 VAC / 3Ø / 60 HZ
1. All wiring must be in metal conduit (best) or shielded cable.
"4" means "460 VAC" "C" means "Closed Loop"
2. Route transducer wiring in metal conduit or use Belden Shield Cable #9939 or equivalent. Make sure the transducer wiring does not contain or cross line voltage wiring or undesired transducer performance may result. 3. Do not run the VFD's input power and output power wiring in the same conduit. Undesired VFD operation could result.
L
L
NC
NC
L3
L2/N
L1
GND
"3" means "CPC-3 Control"
MB MC M1 M2
VFD CONTROL BOX
S1 S2 SC S3 DD+
BLACK
NOTES:
VIOLET
1. If the provided 10-foot, 10-wire VFD control cable is not long enough to meet the application needs, use caution to ensure that the connections from the VFD to the CPC-3 controller are correctly located. MB to MB, MC to MC, etc. In addition, reference the Wire Length Table.
ORANGE BLUE GRN/YEL YELLOW WHT/RED RED
2. Use caulking to seal the electrical box cover to the electrical box, and to seal the conduit holes to hole plugs.
WHT/BRN GRAY
F2
F1
S2
S1
M3
MGND
3
M2
M1
3. If required, non-fused disconnects are to be supplied by the installer. 4. The FFP-1 will disable the combustion air blower when excessively hot or cold room air is detected. Refer to the FFP-1 installation instructions for details. Wiring is to be in dedicated metal conduit. Max. length: 100' (30m) @ 460 VAC
3
VSUB BLOWER
3
2 MOTOR
4 x 4 WEATHERPROOF BOX AND WHIP RED ORANGE
MOTOR LIMIT
BLUE GREEN BLACK
GROUND
BLACK MOTOR WINDINGS
BLACK RED MOTOR HEATER TSTAT
HEAT LIMIT
ARCTIC-DUTY MOTOR HEATER (15 WATTS FOR VSUB8,12,16 & 30 WATTS FOR VSUB20)
FREEZE LIMIT
FFP-1 REFER TO FFP-1 INSTALLATION INSTRUCTIONS FOR DETAILS
INCLUDED CABLE
4