Thermal Overload Relays TR series General information
Standard type thermal overload relays Description Highly reliable thermal overload relays FUJI thermal overload relays are designed to provide overload protection to meet the thermal characteristics of low voltage induction motors. Adjustable thermal overload relays give motors positive overcurrent protection. The starter contacts cannot be held closing under overload conditions. However, once the bimetal element has cooled, the reset button can be depressed and the motor can be restarted in the normal manner. Ordinarily this reset is carried out manually but the starter can be changed over to ‘automatic reset’ by means of a screw-driver. • FUJI thermal overload relay is subjected to stringent testing in the factory to check performance and actual values are calibrated with the markings on the adjustable dial. Consequently, they provide a positive protection. • Relays are also provided with ambient temperature compensators, so that their performance will be maintained in spite of temperature changes. The ambient temperature is regulated for 20°C. • The heater elements are available for either 2- or 3-pole use. ■
•
Long time operating type In the case of loads having large inertia moments such as blowers, winders or centrifuges the starting time is extended. This will cause the standard-type thermal overload relay to operate during starting so isolating the motor. If necessary FUJI will supply thermal relays with saturable reactors. (Timedelay type). Quick operating type overload relays The windings of submersible pump and compressor motors normally have a smaller overload capacity than those of standard motors, since they are generally cooled by the water and other medium being pumped. Q type overload relays will operate more quickly than the standard type in the face of a locked rotor current.
AF00-139
AF00-141
TR-N8/3
TR-N6/3
■
• • • • • • • •
■
AF00-143
TR-N3/3
TR-5-1N/3
Features Isolated NO and NC contacts can be used with different potentials. Gold-flashed silver contact assures high contact reliability (TR-0N/3 to N14/3). Stable operating characteristics protect motors from burnout due to overload or locked rotor currents. Easy setting of current value with a calibrated dial. Both manual and auto reset available. A manual trip button is provided to facilitate sequence testing. Mechanical trip indication Trip-free mechanism is provided. Reset release button and trip indicator are optional accessories.
AF00-282
TR-N12H/3
■ Warning All FUJI thermal overload relays have been tested and calibrated at the factory. They should not be tampered with or stripped down at the job site since this would affect their accuracy. A special feature of the FUJI starter series is the ease by which the relay current ratings can be varied to match the requirements of the load. The changeover is effected by simply turning a dial to the new value required. The range of adjustment is approximately 100%–125%–150% and details are given overleaf.
■ Ordering information Specify the following: 1. Ordering code 2. Setting range code See page 01/89.
Type number nomenclature T R –0 N 씲 H/ 3 A
Basic type TR: Standard type TK: With phase-loss protective device
Reset Blank: A:
Frame size 0N to N14
No. of heater elements Blank: 2-element (TR) 3-element (TK, TR-Q) 3: 3-element (TR)
Operation Blank: Standard operation L: Long time operation Q: Quick operation
01/88
AF88-1379
AF-1383
TR-0N/3
Manual reset Auto reset
Mounting Blank: On-contactor mounting H: Separate mounting
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series
01 Ordering code system T R 20 B N W — T A — — —— — — — ——
■
햲 햳
햲
햴햵
햶
햷
햸
햹 햺
햷
Product category
Description
Code
Thermal overload relay
T
햳
Description
No. of element
Code
Standard
2 3
N D
Long time operation
2 3
L F
Quick operation
3
S
With phase-loss
3
E
Series category
Description
Code
TR-N씲 series
R
햴햵
Frame size
Frame size 0N 5-1N N2 N3 N5 N6 N7 N8 N10 N12 N14
햶
햹
Version
Code
햸
햴
햵
1 2 3 6 9 1 1 1 2 4 6
3 0 5 5 3 C F J C A A
Mounting
Description
Code
On-contactor mounting Separate mounting
W H
햺
Reset
Description
Code
Manual reset Auto reaet
Blank A
Index
Type
Code
TR-0N, 5-1N TR-N2 to N14
Blank B
Thermal overload relay ampere setting range
Ampere setting range (A)
Code
0.1 0.13 0.15 0.2 0.24 0.3 0.36 0.48 0.64 0.8
— — — — — — — — — —
0.15 0.2 0.24 0.3 0.36 0.45 0.54 0.72 0.96 1.2
A B C D E F G H J K
0.95 1.4 1.7 2.2 2.8 4 5 6 7
— — — — — — — — —
1.45 2.2 2.6 3.4 4.2 6 8 9 11
L M N P R S T U V
9 12 16 18 24 28 32 34
— — — — — — — —
13 18 22 26 36 40 42 50
W X Q B E F I G
45 48 53 65 85 85 110 125 160 200 240 300 400
— — — — — — — — — — — — —
65 68 80 95 105 125 160 185 240 300 360 450 600
J O L M I N P R S T U V W
Ordering example 햲 Thermal overload relay ................................................... T 햳 TR-씲N series .................................................................. R 햴햵 Frame size: 5-1N ........................................................... 20 햶 Index ......................................................................... Blank 햷 Standard type, 3-element ............................................... D 햸 On-contactor mounting .................................................. W 햹 햺
— Ampere setting range 4-6A ............................................ S Auto reset ....................................................................... A TR20DW-SA
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
햲 Thermal overload relay ................................................... T 햳 TR-N씲 series .................................................................. R 햴햵 Frame size: N3 .............................................................. 65 햶 Index ............................................................................... B 햷 With phase-loss protection ............................................. E 햸 On-contactor mounting .................................................. W 햹 햺
— Ampere setting range 24-36A ........................................ E Manual reset ............................................................. Blank TR65BEW-E
01/89
Thermal Overload Relays TR series
Features Manual trip These relays can be manually tripped for sequence inspection by pressing manual trip bar (TR-0N/3, TR-5-1N/3). A sequence inspection will be performed when the test button is pulled out. When the test button is pressed in, only the NC contact will turn OFF. The original status will be restored when the test button is then released.(TR-N2/3 to N8/3) ■ ●
Trip-free mechanism Even if the reset button is carelessly pressed, this relay trips without trouble (Trip-free mechanism).
Reset button
Current setting dial
Manual trip bar
Auxiliary contact terminal (1NO + 1NC)
AF00-291
Reset release Main circuit terminal
●
Easy visual checking of operating status Trip indicator and manual trip bar permit visual check of tripping status. ●
Versatile optional accessories Trip indicator
■
AF88-1383
TR-0N/3
Reset button Current setting Test button dial Auxiliary contact terminal (1NO + 1NC)
AF00-585
Trip indicator
Base unit for separate mounting AF90-743
TR-N3/3
Main circuit terminal
● Dial ampere setting The setting dial uses a RC (Rated Current) marking which is set to the motor full load current. AF00-159
■
Optional accessories
Description Reset release You can reset these relays remotely on the front panels of switchboards.
Trip indicator
Type Lead length
300 mm 500 mm 700 mm Lead length 300 mm 500 mm 700 mm 100–110V AC 50/60Hz 200–220V AC 50/60Hz 100–110V AC 50/60Hz 200–220V AC 50/60Hz
Easier checking of trip status Dial cover For protection against the current setting being changed in error Base unit for separate mounting The unit can be screw-mounted and rail-mounted.
Terminal cover
01/90
SZ-R1 SZ-R2 SZ-R3 SZ-R4 SZ-R5 SZ-R6 SZ-L100 SZ-L200 SZ-L100N2 SZ-L200N2 SZ-DA
Ordering code TZ1R1 TZ1R2 TZ1R3 TZ2R4 TZ2R5 TZ2R6 TZ1L100 TZ1L200 TZ2L100N2 TZ2L200N2 SZ1DA
SZ-HB SZ-HC SZ-HD SZ-HE SZ-T10 SZ-T11 SZ-T14 SZ-T15 SZ-RN6T SZ-T12 SZ-T13 SZ-T16 SZ-T17
TZ1HB TZ1HC TZ2HD TZ2HE SZ1T10 SZ1T11 SZ2T14 SZ2T15 SZ2RN6T TZ1T12 TZ1T13 SZ2T16 SZ2T17
Used with thermal overload relay TR-0N/3, TR-5-1N/3, TK-0N, TK-5-1N TR-N10 to N14, TK-N10 to N14 TR-N2/3 to N8/3, TK-N2 to N8 TR-0N/3, TR-5-1N/3, TK-0N, TK-5-1N TR-N10 to N14, TK-N10 to N14 TR-N2/3 to N8/3, TK-N2 to N8 TR-0N/3, TR-5-1N/3, TK-0N, TK-5-1N TR-N2/3 to N14/3, TK-N2 to N14 TR-0N/3, TK-0N TR-5-1N/3, TK-5-1N TR-N2/3, TK-N2 TR-N3/3, TK-N3 Base unit for separate mounting SZ-HB Base unit for separate mounting SZ-HC For separate mounting TR-N2H/3, TK-N2H For separate mounting TR-N3H/3, TK-N3H For separate mounting TR-N6H/3, TK-N6H TR-0N/3, TK-0N TR-5-1N/3, TK-5-1N TR-N2/3, TK-N2 TR-N3/3, TK-N2
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series Standard type
01 ■
Selection guide/Standard type
On-contactor mounting
3-element 2-element
Separate mounting
3-element 2-element
Contactor to be combined Ampere Code setting range (A)
Specify the setting range code when ordering.
On-contactor mounting
A B C D E F G H J K L M N P R S T U V W X Q B E F I G J O L M I
3-element 2-element
Separate mounting
3-element 2-element
Contactor to be combined Ampere Code B setting range E (A) F G J L M I N P R S T U V W
TR-0N/3 (TR13DW) TR-0N (TR13NW) TR-0NH/3 (TR13DH) TR-0NH (TR13NH) SC-03 0.1 – 0.15 0.13 – 0.2 0.15 – 0.24 0.2 – 0.3 0.24 – 0.36 0.3 – 0.45 0.36 – 0.54 0.48 – 0.72 0.64 – 0.96 0.8 – 1.2 0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11
SC-0 SC-05 0.1 – 0.15 0.13 – 0.2 0.15 – 0.24 0.2 – 0.3 0.24 – 0.36 0.3 – 0.45 0.36 – 0.54 0.48 – 0.72 0.64 – 0.96 0.8 – 1.2 0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 9 – 13
TR-5-1N/3 (TR20DW) TR-5-1N (TR20NW) TR-5-1NH/3 (TR20DH) TR-5-1NH (TR20NH) SC-4-0 0.1 – 0.15 0.13 – 0.2 0.15 – 0.24 0.2 – 0.3 0.24 – 0.36 0.3 – 0.45 0.36 – 0.54 0.48 – 0.72 0.64 – 0.96 0.8 – 1.2 0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 9 – 13 12 – 18
SC-4-1 SC-5-1 0.1 – 0.15 0.13 – 0.2 0.15 – 0.24 0.2 – 0.3 0.24 – 0.36 0.3 – 0.45 0.36 – 0.54 0.48 – 0.72 0.64 – 0.96 0.8 – 1.2 0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 9 – 13 12 – 18 16 – 22
TR-N2/3 (TR35BDW) TR-N2 (TR35BNW) TR-N2H/3 (TR35BDH) TR-N2H (TR35BNH) SC-N1
SC-N2
4–6 5–8 6–9 7 – 11 9 – 13 12 – 18
4–6 5–8 6–9 7 – 11 9 – 13 12 – 18
18 – 26 24 – 36
18 – 26 24 – 36
TR-N3/3 (TR65BDW) TR-N3 (TR65BNW) TR-N3H/3 (TR65BDW) TR-N3H (TR65BNW) SC-N2S
SC-N3
7 – 11 9 – 13 12 – 18
7 – 11 9 – 13 12 – 18
18 – 26 24 – 36 28 – 40
18 – 26 24 – 36 28 – 40
34 – 50 45 – 65
34 – 50 45 – 65 48 – 68 53 – 80* 65 – 95* 85 – 105*
TR-N12/3 (TR4ABDW) TR-N12 (TR4ABNW) TR-N12H/3 (TR4ABDH) TR-N12H (TR4ABNH) SC-N11 SC-N12
TR-N14/3 (TR8ABDW) TR-N14 (TR8ABNW) TR-N14H/3 (TR8ABDH) TR-N14H (TR8ABNH) SC-N14
32 – 42
TR-N5/3 (TR80BDW) TR-N5 (TR80BNW) – – SC-N4 18 – 26 24 – 36 28 – 40 34 – 50 45 – 65 53 – 80
SC-N5A 18 – 26 24 – 36 28 – 40 34 – 50 45 – 65 53 – 80 65 – 95 85 – 105
TR-N6/3 (TR1CBDW) TR-N6 (TR1CBNW) TR-N6H/3 (TR1CBDW) TR-N6H (TR1CBNW) SC-N6
TR-N7/3 (TR1FBDW) TR-N7 (TR1FBNW) –
TR-N8/3 (TR1JBDW) TR-N8 (TR1JBNW) –
–
–
SC-N7
SC-N8
45 – 65 53 – 80 65 – 95
45 – 65 53 – 80 65 – 95
85 – 125 85 – 125 110 – 160* 110 – 160
Notes: • TR-N10/3 to N14/3 types are provided with CTs. • Max. setting ranges of these starters are as shown in the table on the right. • When ordering the thermal overload relays for starter use, select the applicable setting range. ( ): Basic ordering code (When ordering phase-loss protective type, enter the version code E instead of D) *: Separate mounting only
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
TR-N10/3 (TR2CBDW) TR-N10 (TR2CBNW) TR-N10H/3 (TR2CBDH) TR-N10H (TR2CBNH) SC-N10
65 – 95 85 – 125 110 – 160 125 – 185
85 – 125 110 – 160 125 – 185 160 – 240
Motor starter SW-03/3H SW-4-0/3H SW-N1/3H SW-N2S/3H SW-N4/3H SW-N6/3H
110 – 160 125 – 185 160 – 240 200 – 300
110 – 160 125 – 185 160 – 240 200 – 300 240 – 360 300 – 450
240 – 360 300 – 450 400 – 600
Maximum applicable heater range (A) 200–240V 380–440V 7–11 6–9 12–18 12–18 24–36 24–36 34–50 34–50 53–80 53–80 85–125 85–125
01/91
Thermal Overload Relays TR series Long time operating type
■
Selection guide/Long time operating type
On-contactor mounting
Separate mounting
3-element
–
–
2-element
–
–
3-element
TR-0NLH/3 (TR13FH) TR-0NLH (TR13LH) SC-03
2-element Contactor to be combined Ampere setting range (A)
On-contactor mounting
Code L M N P R S T U V W X B E F G J L M
0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11
3-element
TR-N5L/3 (TR80BFW) TR-N5L (TR80BLW) –
2-element Separate mounting
3-element 2-element
Contactor to be combined Ampere Code B setting range E (A) F G J L Specify the setting M range code when ordering. N P R S T U V W
SC-0 SC-05 0.95 – 1.45 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 9 – 13
– SC-N4 18 – 26 24 – 36 28 – 40 34 – 50 45 – 65 53 – 80
SC-N5A 18 – 26 24 – 36 28 – 40 34 – 50 45 – 65 53 – 80 65 – 95
TR-5-1NLH/3 (TR20FH) TR-5-1NLH (TR20LH) SC-4-0 SC-4-1 SC-5-1 0.95 – 1.45 0.95 – 1.45 1.4 – 2.2 1.4 – 2.2 1.7 – 2.6 1.7 – 2.6 2.2 – 3.4 2.2 – 3.4 2.8 – 4.2 2.8 – 4.2 4–6 4–6 5–8 5–8 6–9 6–9 7 – 11 7 – 11 9 – 13 9 – 13 12 – 18 12 – 18
TR-N6L/3 (TR1CBFW) TR-N6L (TR1CBLW) TR-N6LH/3 (TR1CBFH) TR-N6LH (TR1CBLH) SC-N6
TR-N7L/3 (TR1FBFW) TR-N7L (TR1FBLW) – – SC-N7
TR-N2L/3 (TR35BFW) TR-N2L (TR35BLW) TR-N2LH/3 (TR35BFH) TR-N2LH (TR35BLH) SC-N1
4–6 5–8 6–9 7 – 11 9 – 13 12 – 18 18 – 26
TR-N10L/3 (TR2CBFW) TR-N10L (TR2CBLW) TR-N10LH/3 (TR2CBFH) TR-N10LH (TR2CBLH) SC-N8 SC-N10
45 – 65 45 – 65 53 – 80 53 – 80 65 – 95 65 – 95 85 – 125 85 – 125 85 – 125 110 – 160* 110 – 160 110 – 160 125 – 185
Notes:Maximum setting ranges of the these starters are as shown in the table below. Select the applicable setting range when ordering the thermal overload relays for starter use.
Motor starter SW-03/2L, 3L SW-N2S/2L, 3L SW-N4/2L, 3L SW-N6/2L, 3L
01/92
85 – 125 110 – 160 125 – 185 160 – 240
SC-N2
4–6 5–8 6–9 7 – 11 9 – 13 12 – 18 18 – 26 24 – 36
TR-N3L/3 (TR65BFW) TR-N3L (TR65BLW) TR-N3LH/3 (TR65BFH) TR-N3LH (TR65BLH) SC-N2S
7 – 11 9 – 13 12 – 18 18 – 26 24 – 36 28 – 40 34 – 50
TR-N12L/3 (TR4ABFW) TR-N12L (TR4ABLW) TR-N12LH/3 (TR4ABFH) TR-N12LH (TR4ABLH) SC-N11 SC-N12
110 – 160 125 – 185 160 – 240 200 – 300
110 – 160 125 – 185 160 – 240 200 – 300 240 – 360 300 – 450
SC-N3
7 – 11 9 – 13 12 – 18 18 – 26 24 – 36 28 – 40 34 – 50 45 – 65 53 – 80* 65 – 95*
TR-N14L/3 (TR8ABFW) TR-N14L (TR8ABLW) TR-N14LH/3 (TR8ABFH) TR-N14LH (TR8ABLH) SC-N14
240 – 360 300 – 450 400 – 600
( ): Basic ordering code *: Separate mounting only
Maximum applicable heater range (A) 200–240V 380–440V 7–11 34–50 53–80 85–125
6–9 34–50 53–80 85–125
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series Quick operating type
01 ■
Selection guide/Quick operating type
On-contactor mounting
3-element
Separate mounting
3-element
TR-0NQ (TR13SW) –
Rated operational current (A)
200–240V 380–440V
Ampere setting range (A)
–
SC-03
Contactor to be combined
Code
S T U V W X B E
Specify the setting range code when ordering.
11 9 1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 *1
M N P R
TR-5-1NQ (TR20SW)
SC-4-0
–
SC-0 SC-05 13 12
18 16
SC-4-1 SC-5-1 22 22
1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 *1 9 – 13 *1
1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 *1 9 – 13 *1
1.4 – 2.2 1.7 – 2.6 2.2 – 3.4 2.8 – 4.2 4–6 5–8 6–9 7 – 11 *1 9 – 13 *1
12 – 18 *1
12 – 18 *1
On-contactor mounting
3-element
TR-N3Q (TR65BSW)
Separate mounting
3-element
TR-N3Q (TR65BSW)
–
SC-N2S
SC-N3
SC-N4
SC-N5A
52 48
65 65
80 80
105 105
18–26 24–36 28–40 34–50
18–26 24–36 28–40 34–50 45–65 53–80*2 65–95*2
18–26 24–36 28–40 34–50 45–65 53–80
18–26 24–36 28–40 34–50 45–65 53–80 65–95
Contactor to be combined Rated operational current (A)
200–240V 380–440V
Ampere setting range (A)
Code
Specify the setting range code when ordering.
B E F G J L M
TR-N2Q (TR35BSW)
SC-N1
SC-N2
27 30
39 37
12 – 18 18 – 26
12 – 18 18 – 26 24 – 36
TR-N5Q (TR80SW)
Notes: *1
Thermal overload relay with phase-loss protection is available with *1 marked setting ranges of TR-0NQ, TR-5-1NQ and all setting ranges of TRN2Q to N5Q. Type numbers are TK-0NQ, TK-5-1NQ, TK-N2Q to N5Q. The setting ranges of these TK-씲Q type relays are as same as those of the above setting ranges. 2 Separate mounting only. * ( ) Basic ordering code
■
Ratings of auxiliary contact
Type
Rated thermal current (A)
Rated voltage (V)
Rated AC operational current (A)
Rated DC operational current (A)
TR-0N, 5-1N TR-0N/3, 5-1N/3 TK-0N, 5-1N TR-0NQ, 5-1NQ
3
24 100-120 200-240 380-440 500-600
3 (0.3)* 2.5 (0.3)* 2 (0.3)* 1 (0.3)* 0.6 (0.3)*
1.1 (0.3)* 0.28 0.14 – –
TR-N2 to N8 TR-N2/3 to N8/3 TK-N2 to N8 TR-N2Q to N5Q
5
24 100-120 200-240 380-440 500-600
3 (0.5)* 2.5 (0.5)* 2 (0.5)* 1 (0.5)* 0.6 (0.5)*
1.1(0.3)* 0.28 0.14 – –
TR-N10 to N14 TR-N10/3 to N14/3 TK-N10 to N14
5
24 100-120 200-240 380-440 500-600
3 (0.3)* 2.5 (0.3)* 2 (0.3)* 1 (0.3)* 0.6 (0.3)*
1.1(0.3)* 0.28 0.14 – –
Notes: Conforming to Class AC-15, DC-13, IEC, JIS, and JEM. ( )* NO contact of auto reset type.
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
01/93
Thermal Overload Relays TR series
Dimensions, mm Standard and quick operating types TR-0N/3, TR-0NQ
■
TR-N2/3, TR-N2Q On-contactor mounting 16.5
17
9.6
46.8
Aux.terminal M3.5
27.2
78
22 32.5 41.5
Aux.terminal M3.5
Reset button (Stroke 3mm) 47
4.9
44
92
16.5
5
Main terminal M3.5 73.5
Reset button (Stroke 4mm)
8.5
Mounting hole 2-M4 5
10.5
14.2
4.5
Aux.terminal M3.5
7.7 10 26.5 44
94.5 (Mounting rail height 15) Main terminal M3.5
On-contactor mounting
On-contactor mounting
60.5
20.5 20.5 14.5
67.4 14
Reset button (Stroke 4mm)
89.7
46.5
37
14
Aux.terminal M3.5
77
9.7 13 7.7 26.5 53
3
12.4 16.5 10.5
7
TR-N3/3, TR-N3Q
Reset button (Stroke 3mm)
Main terminal M5 Mounting hole 7 2-M4 16.5 54
TR-5-1N/3, TR-5-1NQ
28
61 90
99 55.5 100.5 102.5 (Mounting rail height 7.5) 110 (Mounting rail height 15)
53.5 69.2
87 (Mounting rail height 7.5)
5 6
Aux.terminal M3.5
28.7
4.5
3
84
5
5
5
35
72
52
60 46 Reset button (Stroke 3mm)
52.5
Main terminal M4
97.5
5 Main terminal M6
4.9 20.5 20.5 30.5 16.7
TR-N3H/3 67.5 7.7
13
35 9.7
50
69.2 100
54.7
109.5 53.5
60 72
Main terminal M6
7.7 61 106 108 (Mounting rail height 7.5) 115.5 (Mounting rail height 15)
5
Mounting hole 2-M4
9
20.5 20.5 68 78.5
TR-N5/3, TR-N5Q
Reset button (Stroke 4mm)
On-contactor mounting
32
32 14.5 9.5
67.4
78.6 28.7
Aux.terminal M3.5(NO) 씲
: Mounting pitch Mass: See page 01/96.
01/94
52.5 97.5
Aux.terminal M3.5(NC)
16.7 13.5
39.9 55.6
Main terminal M4
9.7 13 26.5 53
28.7
8
3
13.5
Aux.terminal M3.5(NO)
5
50
84 87 (Mounting rail height 7.5) 94.5 (Mounting rail height 15)
Reset button (Stroke 4mm)
8.5
68
50 20.5 20.5 29.9
5 29
35
Reset button (Stroke 3mm)
35
76
Mounting hole 2-M4
10.5
Aux.terminal M3.5
Aux.terminal M3.5
14.2
TR-5-1NH/3 7
10.5
54 40 16.5 16.5 24.9
29
35
Aux.terminal M3.5
TR-N2H/3
47.9
35 34 7.5 10 7.7
67.5 7
16.5
12.4
45
TR-0NH/3
Main terminal M5
10 6
7.7 26.5
3
4.5
77
5
28
16.5
Reset button (Stroke 4mm)
6
65
60.5
61
On-contactor mounting
5
Main terminal M6
Aux.terminal M3.5(NC) 4.9 20.5 20.5 13.5 16.7
68
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series
01 Dimensions, mm Standard and quick operating types TR-6N/3
■
Reset button (Stroke 3mm)
32
146
17
3
22
47
40
54.5 84.5 32
32
Main terminal M8
18
Mounting hole 4-M5
51.5
12
99.5 43 74 118
47
Aux.terminal M3.5
6.5 Aux.terminal M3.5
28 20 36.5
133
65 138
15
5
70 94 121
4.9
26
Reset button (Stroke 4mm)
80.8
TR-N10H/3 32
7
On-contactor mounting
Main terminal M10
100
TR-N12/3
TR-N6H/3
On-contactor mounting Reset button (Stroke 3mm)
169 125
56
56 20 4.5
56
56
13
67
128 160
3
73.5
Aux.terminal M3.5 76.5
95.6 91.5
24
Aux.terminal M3.5
45.5
12
32
8.5
32 21.4
Reset button (Stroke 4mm)
75.5 60
11
5
3
18 Main terminal M8
35
32.5
81
TR-N12H/3 146
17
Reset button (Stroke 3mm) Aux.terminal M3.5
6.5
54.5 84.5 43
99.5 74
32 5
32
18
28
57.5 38.5
15
65 142
TR-N14/3
100
Main terminal M12
30
On-contactor mounting
TR-N8/3 4.9
70
70 4.5
70
70
28.5
3 78.5 127
55
133.5 67
81.5
Aux.terminal M3.5
Reset button (Stroke 3mm)
105
Aux.terminal M3.5
23
109
170
47 22.8
61.5
117
130 47
Reset button (Stroke 4mm)
10.5
On-contactor mounting
3.2 47
180
119
197
TR-N10/3
TR-N14H/3 22
75
47
47 138
Main terminal M10
: Mounting pitch Mass: See page 01/96. Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
64.5
51.5 20
13.5
3
3
47 4.5
87.5
47
Aux.terminal M3.5
56
3
28.5
70
90.5
169 113
70 Reset button (Stroke 3mm) 3 Aux. terminal M3.5
92 118
Reset button (Stroke 3mm)
53
On-contactor mounting
Main terminal M16
38
80
47
136 142 182
Mounting hole 2-M6
3
Mounting hole 4-M8
3 80 167 180
35.5 58.5
80 197
38
20
5
Main terminal M10
45
25
115 154
씲
15
56
Mounting hole 4-M5 Main terminal M8
118
56
44
4.9
Aux.terminal M3.5
3
70 124 158.5
80.8
40
69.5
40
40
Reset button (Stroke 4mm)
On-contactor mounting
7
TR-N7/3
Main terminal M12
30
142
100
27
118
32 32 15
17
Mounting hole 2-M5
74
Main terminal M16
01/95
Thermal Overload Relays TR series
Dimensions, mm Base unit for separate mounting SZ-HB 83 44
SZ-HD
54 Main 10.5 16.5 terminal 12.4 7 M5 L1 L2 L3
98.5 73.5 8.5
9 70
52 60
35
8.5100.5
Mass: 40g
1 L1 3 L2 5 L3
70
60
109.5
35
2
8.5
106
5
50
68 Mounting hole 2-M4
35
Mass: 50g
■
100
13
101.5 76 8.5
14.2
53
7
Mass: 90g
SZ-HE
Main terminal M4
40
54 Mounting hole 2-M4 68 Main 13.5 20.5 9 terminal 16.7 M6
50
83 67.5
10.5
SZ-HC
5
5
2
34 35
90
Main terminal M3.5
10
99 14.2
7
45
67.5
7
4.5
■
Mass: 110g
Mass/Standard and quick operating types
On-contactor mounting Type Mass
Separate mounting Type Mass
On-contactor mounting Type Mass
TR-0N TR-0N/3 TR-0NQ
0.09kg 0.10kg 0.10kg
TR-0NH TR-0NH/3
0.13kg 0.14kg
TR-N7 TR-N7/3
0.61kg 0.61kg
–
TR-5-1N TR-5-1N/3 TR-5-1NQ
0.11kg 0.12kg 0.12kg
TR-5-1NH TR-5-1NH/3
0.16kg 0.17kg
TR-N8 TR-N8/3
1.2kg 1.2kg
–
TR-N2, N2/3 TR-N2Q
0.2kg 0.2kg
TR-N2H TR-N2H/3
0.29kg 0.29kg
TR-N10 TR-N10/3
1.85kg 1.85kg
TR-10NH TR-10NH/3
1.5kg 1.5kg
TR-N3, N3/3 TR-N3Q
0.27kg 0.27kg
TR-N3H, N3H/3 0.38kg
TR-N12, N12/3
2.3kg
TR-12NH, 12NH/3
2.25kg
TR-N5, N5/3 TR-N5Q
0.27kg 0.27kg
TR-N14, N14/3
3.5kg
TR-14NH, 14NH/3
4kg
TR-N6, N6/3
0.61kg
– TR-N6H, N6H/3 0.67kg
■ Dimensions, mm Long time operating type TR-0NLH, 0NLH/3
–
–
7.5
Mounting 4.5 hole 4-M4
10 7.7
5
92
88.5
83
01/96
46.5 27 88 124.5 35 128
4.9 35
28
40 16.5 16.5 10.5 25
Mounting hole 2-M4
90 88 137
46.5
47.5
14
Aux. terminal M3.5
45
44 5
5 Reset button (Stroke 4mm)
4.5
100.5 73.5 8.5
50 90 100
Main terminal M5
27
Aux. terminal M3.5 Main terminal M4 3
16
TR-N2LH, N2LH/3 Mounting hole 4-M4
8 13 10
Mass: See page 01/97.
(For 2 element type 4/T2) 47 51(2/T1,6/T3) (For 3 element type 4/T2) 53
7.7 10 6 49 22.5
3
Reset button (Stroke 3mm)
39.5
54.5
47 90 100
Main terminal M5
TR-5-1NLH, 5-1NLH/3 1
16.5 9.6
20
Aux. terminal M3.5
45
Aux. terminal M3.5 Main terminal M3.5
72
16.5
Reset button (Stroke 4mm)
65
5
Reset button (Stroke 3mm)
On-contactor mounting 6
72
88.5
Mass
TR-N2L, N2L/3 44 35
1
39.5
Separate mounting Type
88
9.7 13 8 35 9 53 18.5
55.5 59.5 61.5
(For 2 element type 4/T2) (For 3 element type 4/T2) (2/T1,6/T3)
42.5
12 35 35 128
16 28
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series
01 Dimensions, mm Long time operating type TR-N3L, N3L/3
■
On-contactor mounting 7
118 80.8
17
5 41 41 *1 140
(For 2 element type 4/T2) 16 (For 3 element type 4/T2)
28
54.5
For TR-N3L/3 and TR-N3L type with setting of 45 to 65A *1: 149, *2: 137
TR-N3LH, N3LH/3
100 Approx. 165
TR-N6LH, N6LH/3 5
15
141
60
25
100.5
45.5
14 54.7
Mounting hole 2-M5
30 8.5
Main terminal M6
44
(For 2 element type 4/T2)
41
41
16
74 80
28
*1 140
(For 3 element type 4/T2)
Main (For 2 element type 4/T2) terminal M8
TR-N5L, N5LH/3
19
35
32.5 32
32
18
100 Approx. 165
For TR-N3LH/3 and TR-N3LH type with setting of 45 to 65A *1: :149, *2: 149
TR-N7L, N7L/3
On-contactor mounting
On-contactor mounting
5 Reset button (Stroke 4mm)
32
118 80.8
32 14.5
5
Reset button (Stroke 4mm)
40 4.9
40 17 7
97.5 67.4
32
32 22.5
Aux. terminal M3.5
100 99 *2 146
53.5
50
Reset button (Stroke 4mm)
8.5 12
118 74
8
Mounting hole 2-M4
5
50 20.5 20.5 30
5 Reset button (Stroke 4mm) Aux. terminal M3.5
61 65 69
18
32
32 19
(For 2 element type 4/T2)
74 80
On-contactor mounting 106 76
Main terminal M8
Main terminal M6
24
52.5 56.5 60.5
25
68
30
58
32
Aux. terminal M3.5
98.5 *2 134
Aux. terminal M3.5
32 4.9
7
Reset button 5 (Stroke 4mm)
14.5
109.5 144.5
20.5 20.5 Reset button (Stroke 4mm)
53.5
5
97.5 67.4
TR-N6L, N6L/3
54.5 109.5 144.5
68 25
29.5
*2 123
58
85
9.5
40
Aux. terminal M3.5
Aux. terminal M3.5
52.5 56.5 60.5
(For 2 element type 4/T2) (For 3 element type 4/T2)
16
Main terminal M8
5 41
41
28
*1140
Main terminal M6
For TR-N3LH/3 and TR-N3LH type with setting of 45 to 65A *1: 149, *2: 126
74 80
32 19
(For 2 element type 4/T2)
32
18
100 Approx.165
Note: TR-N10L, N10LH, N12NL, N12LH, N14L and N14LH types have the same dimensions as standard types. See pages 01/105.
■
Mass/Long time operating type
On-contactor mounting Type Mass
Separate mounting Type Mass
On-contactor mounting Type Mass
Separate mounting Type Mass
–
TR-0NLH TR-0NLH/3
0.4kg 0.5kg
TR-N6L TR-N6L/3
1.54kg 1.85kg
TR-N6LH TR-N6LH/3
–
TR-5-1NLH TR-5-1NLH/3
0.42kg 0.52kg
TR-N7L TR-N7L/3
1.54kg 1.85kg
1.6kg 1.91kg
–
TR-N2L TR-N2L/3
0.56kg 0.68kg
TR-N2LH TR-N2LH/3
0.65kg 0.77kg
TR-N10L TR-N10L/3
1.85kg 1.85kg
TR-N10LH TR-N10LH/3
1.5kg 1.5kg
TR-N3L TR-N3L/3
0.63kg 0.77kg
TR-N3LH TR-N3LH/3
0.74kg 0.88kg
TR-N12L TR-N12L/3
2.3kg 2.3kg
TR-N12LH TR-N12LH/3
2.25kg 2.25kg
TR-N5L TR-N5L/3
0.63kg 0.77kg
TR-N14L TR-N14L/3
3.5kg 3.5kg
TR-N14LH TR-N14LH/3
4kg 4kg
–
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
01/97
Thermal Overload Relays TR series
Dimensions, mm Optional accessories Trip indicator SZ-L100 SZ-L200 ■
Reset release button L
SZ-R1 SZ-R2 SZ-R3
Locking nut M10
Panel drilling
10.5 to 11
9
Reset button
23.5
6.5
Type
12 8
SZ-R1 300 SZ-R1 500
26 Approx.140
11
SZ-R4 SZ-R5 SZ-R6
8 3
Approx.440
Panel drilling
Locking nut M10
SZ-R1 700
10.5 to 11 L
9
3.5
L
SZ-L100N2 SZ-L200N2
6.5
Reset button
Type
26
16
SZ-R6 700
Dial cover SZ-DA 11
L
SZ-R4 300 SZ-R5 500
12 8
Approx.250
8
14
Approx.450
2
Characteristic curves These curves show cold starting characteristics. Standard type TR-N2 to N8 TR-0N, 5-1N, TR-N2/3 to N8/3 TR-0N/3, 5-1N/3, TR-N2H, N3H, N6H TR-0NH, 5-1NH, TR-N2H/3, N3H/3, N6H/3 TR-0NH/3, 5-1NH/3
■ ●
Minute
10 8
20
10 8
Tripping time
2 60 40 30 20
5 3
2
2
60 40 30 20
Second
10 8 6 4 3
10 8
3
Tripping time
3
Tripping time
20
5
5
Second
50 30
10 8 6
60 40 30 20
Second
Minute
20
50 30
Minute
50 30
TR-N10 to N14, TR-N10/3 to N14/3, TR-N10H to N14H TR-N10H/3 to N14H/3
4 3
10 8 6 4 3
2
2
2
1 0.8 0.6
1 0.8 0.6
1 0.8 0.6 0.4 0.3
0.4 0.3
0.4 0.3 0.8
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
0.8
15
1.5
2
3
4
5
6
Multiple of current setting
XIn (A)
Wiring diagrams Standard type TR-0N to N8 TR-0N/3 to N8/3 TR-0NH, 5-1NH, N2H, N3H, N6H TR-0NH/3, 5-1NH/3, N2H/3, N3H/3, N6H/3
1
7 8 9 10
15
XIn (A)
0.8
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
15
XIn (A)
■ ●
2-element
3-element
TR-N10 to N14 TR-N10/3 to N14/3 TR-N10H to N14H TR-N10H/3 to N14H/3 2-element
3-element
(with CTs) 1/L1 3/L2
2/T1 4/T2
01/98
(NO) (NC) 5/L3 97 95
6/T3
98 96 (NO) (NC)
1/L1 3/L2 5/L3
(NO) (NC) 97 95
2/T1 4/T2
98 96 (NO) (NC)
6/T3
(with CTs)
1/L1 3/L2 5/L3
(NO) (NC) 97 95
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
98 96 (NO) (NC)
2/T1 4/T2 6/T3
(NO) (NC)
97 95
98 96 (NO) (NC)
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
Thermal Overload Relays TR series
01 Characteristic curves These curves show cold starting characteristics Long time operating type (When setting at the center dial current) TR-N2L to N7L TR-0NL, 5-1NL TR-N2L/3 to N7L/3 TR-0NL/3, 5-1NL/3 TR-N2LH, N3LH, N6LH TR-0NLH, 5-1NLH TR-N2LH/3, N3LH/3, N6LH/3 TR-0NLH/3, 5-1NLH/3 ■ ●
TR-N10L to N14L TR-N10L/3 to N14L/3 TR-N10LH to N14LH TR-N10LH/3 to N14LH/3 50
30
30
20
20
20 10 8
5
3
3
3
2
2
2
5
Tripping time
60 40 30
60 40 30
60 40 30
20
20
10 8 6
10 8 6
4 3
Second
20 10 8 6
Second
Second
10 8
5
Tripping time
Tripping time
10 8
Minute
50
30
Minute
Minute
80 50
4 3
4 3
2
2
2
1 0.8 0.6
1 0.8 0.6
1 0.8 0.6
0.4 0.3
0.4 0.3 0.8
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
0.4 0.3 0.8
15
1
1.5
3
4
5
6
7 8 9 10
Multiple of current setting
xIn (A)
Quick operating type TR-0NQ, 5-1NQ
2
15
0.8
1
1.5
2
3
4
5
6
Multiple of current setting
xIn (A)
7 8 9 10
15
xIn (A)
TR-N2Q, N3Q, N5Q
50
50
30
30
20
20
Minute
Minute
●
10 8
5 3
2
2
60 40 30
60 40 30
20
20
10 8 6
10 8 6
Second
Second
10 8
3
Tripping time
Tripping time
5
4 3
4 3
2
2
1 0.8 0.6
1 0.8 0.6
0.4 0.3
0.4 0.3 0.8
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
15
0.8
1
1.5
xIn (A)
Wiring diagrams Long time operating type TR-0NL to N7L TR-0NL/3 to N7L/3 TR-0NLH, 5-1NLH, N2LH, N3LH, N6LH TR-0NLH/3, 5-1NLH/3, N2LH/3, N3LH/3, N6LH/3
2
3
4
5
6
7 8 9 10
Multiple of current setting
15
xIn (A)
■ ●
2-element 1/L1 3/L2
5/L3
2/T1 4/T2
6/T3
3-element (NO) (NC) 97 95
98 96 (NO) (NC)
1/L1 3/L2
5/L3
2/T1 4/T2
6/T3
(NO) (NC) 97 95
98 96 (NO) (NC)
● Quick operating type TR-0NQ, 5-1NQ TR-N2Q, N3Q, N5Q
TR-N10L to N14L TR-N10L/3 to N14L/3 TR-N10LH to N14LH TR-N10LH/3 to N14LH/3 2-element
3-element
(with CTs)
(with CTs)
1/L1 3/L2 5/L3
(NO) (NC) 97 95
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
98 96 (NO) (NC)
2/T1 4/T2 6/T3
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog Information subject to change without notice
3-element (NO) (NC)
97 95
98 96 (NO) (NC)
1/L1 3/L2 5/L3
(NO) (NC) 97 95
2/T1 4/T2
98 96 (NO) (NC)
6/T3
01/99
Thermal Overload Relays TK series With phase-loss protective device
Thermal overload relays with phase-loss protective device Description
FUJI TK series consists of a 3-heater element thermal overload relay and an phase-loss protective device. These two elements are assembled to make the relay unit. The overload relay characteristics are designed to meet the thermal characteristics of a squirrelcage motors at the time of overload. A FUJI ADL mechanism is also provided to protect from phase-loss. This ADL mechanism is incorporated with the overload relay. The characteristics are coordinated with the temperature rise curve in stator winding at the time of motor phase-loss. They respond quickly to overloads. Other features include the following.
Characteristics
The operating characteristics of a thermal overload relays represents its tripping time and response current starting from cold or hot state. Standard
IEC 105% Ie 60947-4-1
120% Ie (2h max.)
Hot starting characteristics
In cold starting, tripping time is measured from the time when the temperature of the thermal overload relay is equal to the ambient temperature.
In hot starting, tripping time is measured from the time when the thermal overload relay reaches the steady state after non-tripping current flows two hours.
When all poles are not equally energized Operating limit Non-tripping
Tripping Hot start
class 10A 150% Ie 2min max.
class 10A 720% Ie 2 to 10s max.
Not provided
3-phase: 105% Ie
2-phase: 132% Ie
class 10 150% Ie 4min max.
class 10 720% Ie 4 to 10s max.
class 20 150% Ie 8min max.1-phase:
class 20 720% Ie 6 to 20s max.
class 30 150% Ie 12min max.
class 30 720% Ie 9 to 30s max. *
Provided
TK-N2, N3, N5, N6, N7, N8 TK-N2H, N3H, N6H
2-phase: 100% Ie
2-phase: 115% Ie
1-phase: 90% Ie
1-phase: 0 2h max.
TK-N10, N12, N14 TK-N10H, N12H, N14H
50
50
30
30
20
20
20
3-phase characteristic curve (Cold starting)
10 8
Minute
50
10 8
3-phase characteristic curve (Cold starting)
2
2
Tripping time
3
60
3
60 40 30
20
2 60 40 30 20
20
4 3
Second
Open phase (Average) (Cold starting) 3-phase characteristic curve (Hot starting)
2
Open phase (Average) (Cold starting)
10 8 6 4 3
3-phase characteristic curve (Hot starting)
2
1 0.8 0.6
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
Dimensions, mm TK-0N to N14 types: Same as standard types See pages 01/94, 01/95. ■
01/100
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
xIn (A)
0.8
15
1
1.5
2
3
4
5
6
7 8 9 10
Multiple of current setting
xIn (A)
Wiring diagrams TK-0N to N14 types: Same as standard 3-heater element types See pages 01/98. ■
3-phase characteristic curve (Hot starting)
0.4 0.3 0.8
15
4 3
1 0.8 0.6
0.4 0.3 0.8
Open phase (Average) (Cold starting)
10 8 6
2
1 0.8 0.6
0.4 0.3
3-phase characteristic curve (Cold starting)
10 8 5
5
3
20˚C
1-phase: 0 2h max.
30
10 8 6
Ambient temp.
Phase-loss protection
Minute
Minute Tripping time
Cold starting characteristics
Specify the following: 1. Ordering code See pages 01/89.
Locked rotor (cold start)
40 30
Second
Ordering information
■
Overload (hot start)
TK-0N, 5-1N TK-0NH, 5-1NH
5
AF00-141
A trip-free mechanism, wide-range dial ampere adjustment, manual/auto reset chageover lever, operating indicator, and ambient temperature compensators. Types are available ranging from TK-0N to TK-N14.
When all poles are equally energized Operating limit NonTripping tripping
TK-N6
AF88-1380
Tripping time
■
TK-5-1N
Second
■
15
xIn (A)
Ratings of auxiliary contact Same as standard types. See Page 01/93. ■