Transcript
West Chicago, IL 60185 Phone: 630-562-2700 www.triadboiler.com
TRIAD BOILER SYSTEMS, INC. SERIES 900 HIGH PRESSURE STEAM BOILER
69"
Note: Dimensions subject to change without notice.
TRIAD BOILER SYSTEMS, INC. SERIES 900 HP STEAM (Model 900 HP) The Series 900 is a steel vertical firetube packaged boiler with a water-backed combustion chamber equipped with highefficiency turbulators. Boilers come fully wired, and fit through a 34” doorway. STANDARD EQUIPMENT: Low/High/Low Power Burner (UL Listed) L404F Honeywell Pressuretrol Controller L4079B Honeywell Pressuretrol Limit Control 150 Water Level Control 750 M&M Low Water Cut-Off, Manual Reset Honeywell Control Relay Gauge Glass Assembly Pressure Gauge Relief Valve Lifting Lugs UL, FM and CSD-1 Compliance Vessel Pressure Rating of 150 PSI
OPTIONAL EQUIPMENT: Gas Fired (NG or Propane), Oil Fired, or Dual Fuel Burners UL, IRI, FM and CSD-1 Compliance Modulating Gas Trains Sealed Combustion Air Intake Barometric Dampers
SPECIFICATIONS: Input BTU/Hr
Output BTU/Hr
Efficiency
HP Rating
Steam lbs./hr
600,000
486,000
81.0%
13.8
478
700,000
567,000
81.0%
16.2
558
800,000
648,000
81.0%
18.5
637
900,000
729,000
81.0%
23.1
717
Note: Typical for Natural Gas. - Oil or LP burner data may vary.
CLEARANCES & CONNECTIONS: Consult local codes for front, rear, and side clearances. 1” feed water, 1” blow down, 3/4” relief valve outlet 15-50 psi 4” FL steam outlet, 51-100 psi 3” FL steam outlet, 101-150 psi 2” TH steam outlet
CONTROL: The Series 900 can operate on its own controls, but a TRIAD microprocessor control panel is recommended for sequencing more than two boilers to minimize run-time and fuel usage.
POWER: 120V, 60Hz, Single Phase, fused for 30 amps. Min / Max gas pressure, typically 5.6” / 14” WC
WEIGHT/VOLUME: Shipping Weight – 1,400 lbs. Operating Weight - 1,885lbs. Volume – 55 gallons
ALL BURNER EQUIPMENT UL APPROVED
TRIAD BOILER REPRESENTATIVE:
TRIAD Boiler Systems, Inc. West Chicago, IL 60185 Phone: 630-562-2700 Fax: 630-562-2800 Web: www.triadboiler.com