Type P Drilmar® 125-XE VFD Power Cable, 3 Conductors
Crosslinked Polyolefin Insulated, Drilling Rig and Marine Cable, 2000 V
Application
Engineered for easiest installation. Extra flexible stranding meets IEEE, UL, and CSA requirements.
For use in variable frequency AC motor driver (VFD) applications. Flexible conductors for easy handling and installation, with an overall composite shield forme by a copper wire braid and an aluminum foil shield providing a 100% coverage, to contain the VFD EMI emissions, and with grounding conductors distributed symmetrical to reduce induced voltage imbalances and carry common mode noise back to the drive.
Maximum conductor operating temperature: 100 °C as Type P per IEEE, and 110°C as Type X110 per UL and CSA. Meets ampacity ratings per ABS, DNV, LRS, and TCMS. DRILMAR® XLPO Insulation: • Superior oil and chemical resistance. • Sunlight resistant. • Rated at 125 ºC. • Passes Cold Bend at -55 ºC. Heavy Duty CPE Jacket: • Arctic Type XE design. • Abrasion and sunlight resistant. • Rated at 90 ºC. Completed cable offers superior flame resistance meeting: • 70,000 Btu Flame Tests IEEE 1202/FT4, IEEE 383, UL 1685, ICEA T-30-820, and IEC 332 Category A. • 210,000 Btu Flame Test ICEA T-29-520. Arctic Type design meets Cold Bend and Impact Tests at -40 ºC, exceeding the Transport Canada Marine Safety requirements. Cables meet applicable requirements of IEC 92-350.
Standards IEEE 1580-2001 Recommended Practice for Marine Cable for Use on Shipboard and Fixed and Floating Platforms. UL 1309-1995 Marine Shipboard Cable. CSA C22.2 No. 245 Marine Shipboard Cable. IEEE 45-2002 Recommended Practice for Electrical Installations on Shipboard Cable.
Approvals • UL and CSA, as Type P. • UL and CSA, as Type X110. • ABS, American Bureau of Shipping. • DNV, Det Norske Veritas • LRS, Lloyd’s Register of Shipping. • United States Coast Guard. • TCMS, Transport Canada Marine Safey.
Engineering Information 1. Conductor: Soft annealed flexible Tin Coated Copper per IEEE, UL, and CSA. Sizes: 4 AWG up to 535.3 kcmil. 2. Separator Tape: Polyester tape as required.
1 2 3 4 5
6 7 8
3. Insulation: Flame retardant and sunlight resistant Crosslinked Polyolefin (XLPO) per IEEE. Also meets and exceeds the requirements of UL and CSA for Type X110. DRILMAR® 125-XE is a 125 °C XLPO. Rated 2 kV for power cables. 4. Grounding Conductors (x3): Three soft Annealed flexible Tin Coated Copper green insulated conductors symmetrically distributed. Rated 600/1000 volts for grounding conductors. Identification: Power cables Dark Gray with numbers. Grounding conductors Green with numbers. Assembly: Power and grounding conductors cabled round with moisture and flame retardant fillers, as required and binder tape. 5. Shield: Overall tinned copper braid plus aluminum foil/polyester tape providing 100% coverage. A binder tape is used over the shield as required. 6. CPE Jacket: Flame retardant and sunlight resistant Arctic Type Chlorosulfonated Polyethylene (CP) per IEEE, UL and CSA. 7. Armor (optional): StandardBronze. A binder tape is used over the armor as required. Optional - Aluminum or Tinned Copper Braid per IEEE, UL and CSA. 8. Overall Jacket (optional): Flame retardant and sunlight resistant Arctic Type Chlorinated Polyethylene (CPE) per IEEE, UL, and CSA.
CME Wire and Cable | 495 Horizon Drive NE, Suite 100, Suwanee, Georgia 30024 | www.cmewire.com | 770.623.0001 © 2014 CME Wire and Cable, Inc. All Rights Reserved.
July 7, 2017
Drilmar® Marine Cable
Features
Type P Drilmar® 125-XE VFD Power Cable, 3 Conductors, 2000 V Technical Data
Type P VFD Power Cable, 3 Conductors, 2000 V Conductor
Size AWG / kcmil
DTVPCP
Unarmored Nominal OD
Strands
in
mm
Part Number
4
105
1.11
28
2
154
1.23
31
1
224
1.42
1/0
273
2/0
323
3/0
Armored Aluminum
Nominal OD
Net Weight lb/kft
kg/km
in
mm
Part Number
DTVPCP41-3
933
1388
1.16
29
DTVPCP66-3
1243
1850
1.28
33
36
DTVPCP83-3
1651
2457
1.48
1.51
38
DTVPCP105-3
1896
2822
1.63
41
DTVPCP133-3
2178
3241
456
1.89
48
DTVPCP167-3
3084
Bronze Net Weight
Net Weight
lb/kft
kg/km
Part Number
lb/kft
kg/km
DTVPCPA41-3
987
1469
DTVPCPB41-3
1110
1652
DTVPCPA66-3
1303
1939
DTVPCPB66-3
1439
2141
37
DTVPCPA83-3
1720
2560
DTVPCPB83-3
1877
2793
1.56
40
DTVPCPA105-3
1969
2930
DTVPCPB105-3
2136
3179
1.69
43
DTVPCPA133-3
2258
3360
DTVPCPB133-3
2437
3627
4589
1.95
49
DTVPCPA167-3
3176
4726
DTVPCPB167-3
3384
5036
4/0
551
2.21
56
DTVPCP211-3
3783
5630
2.26
57
DTVPCPA211-3
3890
5789
DTVPCPB211-3
4132
6149
262.6
646
2.32
59
DTVPCP262-3
4376
6512
2.37
60
DTVPCPA262-3
4488
6679
DTVPCPB262-3
4742
7057
313.1
779
2.48
63
DTVPCP313-3
5096
7584
2.53
64
DTVPCPA313-3
5216
7762
DTVPCPB313-3
5487
8166
373.7
925
2.62
67
DTVPCP373-3
5809
8645
2.68
68
DTVPCPA373-3
5936
8834
DTVPCPB373-3
6223
9261
444.4
1110
2.80
71
DTVPCP444-3
6701
9972
2.85
72
DTVPCPA444-3
6836
10173
DTVPCPB444-3
7141
10627
535.3
1332
3.11
79
DTVPCP535-3
8106
12063
—
—
—
—
—
—
—
—
The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors and accessories should be verified using actual dimensions of the product. Ampacities: Refer to beginning of section.
Conductor
Armored and Sheathed Aluminum
Size AWG / kcmil
Nominal OD
Bronze Net Weight
Net Weight
Strands
in
mm
Part Number
lb/kft
kg/km
Part Number
lb/kft
kg/km
4
105
1.34
34
DTVPCPAS41-3
1207
1796
DTVPCPBS41-3
1329
1978
2
154
1.46
37
DTVPCPAS66-3
1544
2298
DTVPCPBS66-3
1680
2500
1
224
1.65
42
DTVPCPAS83-3
1995
2969
DTVPCPBS83-3
2152
3203
1/0
273
1.81
46
DTVPCPAS105-3
2372
3530
DTVPCPBS105-3
2538
3777
2/0
323
1.93
49
DTVPCPAS133-3
2689
4002
DTVPCPBS133-3
2869
4270
3/0
456
2.19
56
DTVPCPAS167-3
3670
5462
DTVPCPBS167-3
3878
5771
4/0
551
2.50
64
DTVPCPAS211-3
4459
6636
DTVPCPBS211-3
4700
6994
262.6
646
2.62
66
DTVPCPAS262-3
5084
7566
DTVPCPBS262-3
5338
7944
313.1
779
2.77
70
DTVPCPAS313-3
5849
8704
DTVPCPBS313-3
6120
9108
373.7
925
2.99
76
DTVPCPAS373-3
6797
10115
DTVPCPBS373-3
7083
10541
444.4
1110
3.10
79
DTVPCPAS444-3
7677
11425
DTVPCPBS444-3
7975
11868
The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors and accessories should be verified using actual dimensions of the product. Ampacities: Refer to beginning of section.
CME Wire and Cable | 495 Horizon Drive NE, Suite 100, Suwanee, Georgia 30024 | www.cmewire.com | 770.623.0001 July 7, 2017
© 2014 CME Wire and Cable, Inc. All Rights Reserved.