UFC SERIES FlatPakTM 400Hz GROUND POWER UNIT 90kVA
APPLICATION: Since its beginning in 1960, Unitron has specialized in the design and development of reliable, solid-state power systems. Through an innovative design, advanced self-diagnostic systems (BITE) and modular construction, Unitron products assure maximum power availability and minimal repair time. The FlatPakTM Series includes 400Hz converters specifically designed for installation where space is limited. The units mount “flat” against a wall, and offer the smallest size to power rating ratio in the industry. Also, by using noise reduction technology, Unitron converters are quiet enough to be located close to the equipment they serve. No special soundproofing or other insulation is required. Output power ratings for the 400Hz FlatPak Converter range from 20kVA to 400kVA. In addition to fixed units, Unitron offers 400Hz, 28VDC and combination AC/DC converters in mobile and towable configurations.
OPTIONS: ■■ ■■
FIXED CONFIGURATION (Shown with standard digital panel and paint)
STANDARD FEATURES: ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
UL 1012 Listed 3 Phase, 380-480VAC input ≤ 5% Input Current Distortion Automatic Input Line Monitoring Advanced Integrated Display (AID™) Console 8000 Event Log / Diagnostics TCP/IP/Ethernet Interface (Modbus) Internal Communication Ports - USB, RJ45 (Ethernet), RS485 (Modbus), & RS232 External Communication Ports - RJ45 (Ethernet) & USB 15% Automatic Line Drop Compensation Emergency Power “OFF” Switch I/O Voltage, Current, & Frequency Monitoring Elapsed Time Meter Front Panel Summary Fault Indicators Forklift Tubes - 4 Inch Input High Voltage Transient Protection Multi Language (Romanization) Display English, French, German, Italian, Portuguese, Russian and Spanish, Others - Specify
This product was manufactured in a plant whose quality management system is registered to ISO 9001:2008.
■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
IP55 Output Universal Aircraft Safety Interlock Circuit Disconnect (Single or Dual) Output Safety Disconnect Second 28VDC output Indoor Touch Screen Panel Alternate Output Voltages (120/208V, 575V) Input/Output Contactor Auto Restart Parallelable (grid expansion) Redundant (N+1/Hot Swap) Custom Paint & Decals (Standard Color - White) Ground Fault Monitor Lockable Front Door CE Mark certified No Break Power Transfer Compatible Stand - 4, 12 or 18 Inch Neutral Interrupt Protection Universal Safety Interlock
MECHANICAL SPECIFICATIONS: Size: Weight: Enclosure: Cooling:
See Figure 1 See Figure 1 NEMA 3RX Forced Convection
SPECIFICATIONS / STANDARDS:
EN 61000-6-2* Electromagnetic compatibility Immunity standard for industrial environments EN 61000-6-4* Electromagnetic compatibility Emission standard for industrial environments 2006/95/EC* Low Voltage Directive ISO 1540 Characteristics of aircraft electrical system ISO 6858 Aircraft ground support electrical supplies SAE ARP 5015 Ground equipment 400Hz ground power performance requirement MIL-STD-704F Aircraft electric power characteristics MIL-STD-1472 Human Engineering Design Criteria DFS-400 Specification for 400Hz aircraft power supply
*Defined Basis of CE Mark Certification
GENERAL SPECIFICATIONS INPUT:
OUTPUT:
Input Current Distortion
≤ 5%, typically 3%
Voltage 380 to 480 volts, +10%, -15%, 3Ø, 3 wire plus ground (Alternate voltages - specify)
Power Rating
90 kVA
Power Factor Range
0.5 lagging to 0.8 leading
Overload
100% continuous 110% for 60 min 125% for 10 min 150% for 2 min 200% for 20 sec 300% for 6 sec (60+ kVA)
Voltage**
115/200 volts, 3Ø, 4 wire, grounded neutral
Crest Factor
1.414 ± 3%
Frequency
50 - 60 Hz ± 10%
Phase Rotation
Any
Protection
Over/undervoltage, loss of phase, overcurrent, short circuit. Voltage transient protection IAW IEEE C62.41.1, Location Cat. B/C
Inrush Current
No greater than 100% of full load current
Voltage Regulation
± 1.0% under all conditions of line, balanced loads and temperature
Acoustical Noise
< 65 dBA at 5 feet (1.5m) (60 dBA typical)
Voltage Transients
IAW MIL-STD-704F
Temperature Range
-40°C to +55°C 10 - 95%
Frequency Regulation
400 Hz ± 0.01% under all conditions of line, load and temperature
Type 3RX, IP54
Frequency Transients
None
Phase Angle Regulation
± 1° for balanced loads; ± 2° for unbalanced loads
Harmonic Distortion
2.0% maximum
Protection
Overload, short circuit, over/undervoltage and safety disconnect
Automatic Line Drop Compensation (ALDC)
15%
ENVIRONMENTAL:
Relative Humidity
Ingress of Water
ENERGY FACTORS: Efficiency
94% typical at full load, 92% typical at half load; varies depending on configuration
Energy Efficiency Ratio
20.0 typical
FIGURE 1
Weight*: 90.0kVA = 1,040lbs. (472kg.) *Weight varies with options
NOTE: **Alternate output voltage of 120/208 volt available when specifiedw
UFC FlatPakTM SERIES GROUND POWER UNIT (GPU) REV. NC
UFC SERIES FlatPakTM 400Hz GROUND POWER UNIT 125-200kVA
APPLICATION:
Since its beginning in 1960, Unitron has specialized in the design and development of reliable, solid-state power systems. Through an innovative design, advanced self-diagnostic systems (BITE) and modular construction, Unitron products assure maximum power availability and minimal repair time. The FlatPakTM Series includes 400Hz converters specifically designed for installation where space is limited. The units mount “flat” against a wall, and offer the smallest size to power rating ratio in the industry. Also, by using noise reduction technology, Unitron converters are quiet enough to be located close to the equipment they serve. No special soundproofing or other insulation is required. Standard output power ratings for the 400Hz FlatPak Converter range from 20kVA to 400kVA. For higher system ratings to 2MW, contact factory. In addition to fixed units, Unitron offers 400Hz, 28VDC and combination AC/DC converters in mobile and towable configurations. Also available are 270VD outputs at various power ratings.
OPTIONS:
FIXED CONFIGURATION (Shown with standard digital front panel and optional privacy panel)
STANDARD FEATURES: ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
UL 1012 Listed 3 Phase, 4 wire, 380/200 to 480/277VAC input (Specify) 50/60 Hz input ≤ 5% Input Current Distortion Automatic Input Line Monitoring Advanced Integrated Display (AID™) Console 8000 Event Log / Diagnostics TCP/IP/Ethernet Interface (Modbus) Internal Communication Ports - USB, RJ45 (Ethernet), RS485 (Modbus), & RS232 External Communication Ports - RJ45 (Ethernet) & USB 15% Automatic Line Drop Compensation Emergency Power “OFF” Switch I/O Voltage, Current, & Frequency Monitoring Elapsed Time Meter Front Panel Summary Fault Indicators Forklift Tubes - 4 Inch Input High Voltage Transient Protection Multi Language (Romanization) Display English, French, German, Italian, Portuguese, Russian and Spanish, Others - Specify
MECHANICAL SPECIFICATIONS: Size: Weight: Enclosure: Cooling:
See Figure 1 See Figure 1 NEMA 3RX Forced Convection
■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
IP55 Second 28VDC output Alternate 3-phase, Input Voltage (600/345V) Alternate Output Voltages (120/208V, 575V, 440V) Input/Output Contactor Input and/or Output Circuit Breaker Auto Restart Parallelable (grid expansion), Redundant (N+1/Hot Swap) Custom Paint & Decals (Standard Color - White) Ground Fault Monitor Lockable Front Door CE Mark certified No Break Power Transfer Compatible (Aircraft Load) Touch Screen Front Panel Stand - 4, 12 or 18 Inch Neutral Interrupt Protection Universal Aircraft Safety Interlock (Single or Dual) 28 VDC Aircraft Safety Interlock (Single or Dual) Anti-Condensation Heater(s)
SPECIFICATIONS / STANDARDS:
EN 61000-6-2* Electromagnetic compatibility Immunity standard for industrial environments EN 61000-6-4* Electromagnetic compatibility Emission standard for industrial environments 2006/95/EC* Low Voltage Directive ISO 1540 Characteristics of aircraft electrical system ISO 6858 Aircraft ground support electrical supplies SAE ARP 5015 Ground equipment 400Hz ground power performance requirement MIL-STD-704F Aircraft electric power characteristics MIL-STD-1472 Human Engineering Design Criteria DFS-400 Specification for 400Hz aircraft power supply Defined Basis of CE Mark Certification * This product was manufactured in a plant whose quality management system is registered to ISO 9001:2008.
GENERAL SPECIFICATIONS OUTPUT:
INPUT: Input Current Distortion
≤ 5%, typically 3%
Voltage 380/200V to 415/240V or 480/277V, +10%, -15%, 3Ø, 4 wire plus ground (Specify) Frequency
50 - 60 Hz ± 10%
Phase Rotation
Any
Protection
Over/undervoltage, loss of phase, overcurrent, short circuit. Voltage transient protection IAW IEEE C62.41.1, Location Cat. B/C
Inrush Current
No greater than 100% of full load current
ENVIRONMENTAL: Acoustical Noise
< 65 dBA at 5 feet (1.5m) (60 dBA typical)
Temperature Range
-40°C to +55°C
Relative Humidity
10 - 95% (100% with anti- condensation option)
Ingress of Water
Type 3RX, IP54
ENERGY FACTORS: Efficiency
94% typical at full load, 92% typical at half load; varies depending on configuration
Standard Power Ratings (Specify)
125, 156.5, 187.5, 200 kVA (Others upon request)
Power Factor Range
0.5 lagging to 0.8 leading
Overload
100% continuous 110% for 60 min 125% for 10 min 150% for 2 min 200% for 20 sec 300% for 6 sec
Voltage**
115/200 volts, 3Ø, 4 wire, grounded neutral
Crest Factor
1.414 ± 3%
Voltage Regulation
± 1.0% under all conditions of line, balanced loads and temperature
Voltage Transients
IAW MIL-STD-704F
Frequency Regulation
400 Hz ± 0.01% under all conditions of line, load and temperature
Frequency Transients
None
Phase Angle Regulation
± 1° for balanced loads; ± 2° for unbalanced loads
Harmonic Distortion
2.0% maximum
Protection
Overload, short circuit, over/undervoltage and safety disconnect
Automatic Line Drop Compensation (ALDC)
15%
NOTE: **Alternate output voltages available when specified
Weight*: 125kVA - 1,580lbs (717kg.)
156.5kVA - 1,673lbs (759kg.)
*Weight varies with options
187.5kVA - 1,765lbs (801kg.) 200kVA - 1,820lbs (826kg.)
FIGURE 1 REV. D
UFC SERIES FlatPakTM 400Hz GROUND POWER UNIT 250-400kVA
APPLICATION:
Since its beginning in 1960, Unitron has specialized in the design and development of reliable, solid-state power systems. The FlatPak™ Series includes 400Hz converters specifically designed for installation where space is limited. The units mount “flat” against a wall, and offer the smallest size to power rating ratio in the industry. Each of the two identical power bays which each operate in paralleled harmony to give the desired power grid rating. Each of the bays can be located in near proximity (side by side or back to back) or in different areas of a utility room depending upon "niche" space available. For those applications desiring (N+1)/Hot Swap Redundancy, the FlatPak Series can also be provided with an optional centrally located I/O Power Distribution Unit (PDU) to facilitate a more economical solution than requiring separately furnished PDUs.
FIXED CONFIGURATION (Shown with digital front panel)
STANDARD FEATURES: ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
UL 1012 Listed 3 Phase, 4 wire, 380/200 to 480/277VAC input (Specify) Indoor/Outdoor (Hangar/Ramp) Use 50/60 Hz input ≤ 5% Input Current Distortion Automatic Input Line Monitoring Advanced Integrated Display (AID™) Console 8000 Event Log / Diagnostics TCP/IP/Ethernet Interface (Modbus) Internal Communication Ports - USB, RJ45 (Ethernet), RS485 (Modbus), & RS232 External Communication Ports - RJ45 (Ethernet) & USB 15% Automatic Line Drop Compensation Emergency Power “OFF” Switch I/O Voltage, Current, & Frequency Monitoring Elapsed Time Meter Sleep Mode Front Panel Summary Fault Indicators Forklift Tubes - 4 Inch Single Input Connection Input High Voltage Transient Protection Multi Language (Romanization) Display English, French, German, Italian, Portuguese, Russian and Spanish, Others - Specify
MECHANICAL SPECIFICATIONS: Size: Weight: Enclosure: Cooling:
See Figure 1 See Figure 1 NEMA 3RX Corrosion Resistant Forced Convection
This product was manufactured in a plant whose quality management system is registered to ISO 9001:2008.
Output power ratings for the 400Hz FlatPak™ Converter range from 20kVA to 400kVA in a single bay configurations and up to 800kVA in (N+1)/Hot Swap fully redundant systems where critical loads are involved. Additionally, the redundant configurations can be provided with "Load Management" to assure the most efficient level of operation for various load conditions. Contact factory for more details on Redundant Configurations.
OPTIONS: ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
300% Overload for 6 sec. Touch Screen Panel Alternate Output Voltages (208/120V, 600/345V) Input/Output Contactor Input and/or Output Circuit Breaker Auto Restart Parallelable (grid expansion) Redundant (N+1/Hot Swap) Custom Paint & Decals (Standard Color - White) Ground Fault Monitor Lockable Front Door CE Mark certified Stand - 4, 12 or 18 Inch Neutral Interrupt Protection Universal Aircraft Safety Interlock (Single or Dual) Anti-Condensation Heater(s)
SPECIFICATIONS / STANDARDS:
ISO 1540 Characteristics of aircraft electrical system ISO 6858 Aircraft ground support electrical supplies SAE ARP 5015 Ground equipment 400Hz ground power performance requirement MIL-STD-704F Aircraft electric power characteristics MIL-STD-1472 Human Engineering Design Criteria DFS-400 Specification for 400Hz aircraft power supply EN 61000-6-2* Electromagnetic compatibility Immunity standard for industrial environments EN 61000-6-4* Electromagnetic compatibility Emission standard for industrial environments 2006/95/EC* Low Voltage Directive *Defined Basis of CE Mark Certification
GENERAL SPECIFICATIONS OUTPUT:
INPUT: Input Current Distortion
Standard Power Ratings 250, 312, 375, 400 kVA (specify)
≤ 5%, typically 3%
Voltage 380 to 480 volts, +10%, -15%, 3Ø, 3 wire plus ground (Alternate voltages - specify) Frequency
50 - 60 Hz ± 10%
Phase Rotation
Any
Protection
Over/undervoltage, loss of phase, overcurrent, short circuit. Voltage transient protection IAW IEEE C62.41.1, Location Cat. B/C
Inrush Current
No greater than 100% of full load current
Power Factor Range
0.5 lagging to 0.8 leading
Overload
100% continuous 110% for 60 min 125% for 10 min 150% for 2 min 200% for 20 sec
Voltage**
575 volts, 3Ø, 3 wire
Crest Factor
1.414 ± 3%
Voltage Regulation
± 1.0% under all conditions of line, balanced loads and temperature
Voltage Transients
IAW MIL-STD-704F
Frequency Regulation
400 Hz ± 0.01% under all conditions of line, load and temperature
Frequency Transients
None
Phase Angle Regulation
± 1° for balanced loads; ± 2° for unbalanced loads
ENERGY FACTORS:
Harmonic Distortion
2.0% maximum
Efficiency
Protection
Overload, short circuit, over/undervoltage and safety disconnect
Automatic Line Drop Compensation (ALDC)
15%
ENVIRONMENTAL: Acoustical Noise
< 65 dBA at 5 feet (1.5m) (60 dBA typical)
Temperature Range
-40°C to +55°C
Relative Humidity
10 - 95% (100% with anti- condensation option)
Ingress of Water
Type 3RX, IP55 94% typical at full load, 92% typical at half load; varies depending on configuration
NOTE: **Alternate output voltages available when specified
118in 2997mm
36in 914mm MAINTENANCE CLEARANCE
REMOVABLE LIFTING EYES
29in 749mm
74in 1883mm
Unitron
POWER SYSTEMS
UFC-400F
FORKLIFT TUBES
(OPTIONAL PRIVACY PANEL SHOWN)
Weight*:
250kVA - 3,410lbs (1,547kg.) 312kVA - 3,596lbs (1,631kg.)
*Weight varies with options
375kVA - 3,780lbs (1,715kg.) 200kVA - 3,890lbs (1,764kg.)