Preview only show first 10 pages with watermark. For full document please download

Transcript

ELECTRICAL DATA SHEET-DUAL MAINS UPS RATING AT 0.9 PF LAG. NOMINAL INPUT VOLTAGE (FREQUENCY) / BYPASS VOLTAGE (FREQUENCY) NOMINAL OUTPUT VOLTAGE ( FREQUENCY) INPUT WIRING BYPASS WIRING UPS INPUT NOMINAL INPUT CURRENT (A) 225kVA 480V (40-70Hz) / 480V (50/60Hz) 480V (50/60Hz) WIRING : 3 WIRE -3PH+G WIRING : 3WIRE-3PH+G OR 4WIRE- 3PH+N+G 255 MAXIMUM INPUT CURRENT (A) 306 INPUT CURRENT LIMITATION (A) 347 UPS BYPASS NOMINAL CURRENT (A) 271 WIRING : 3WIRE-3PH+G OR 4WIRE- 3PH+N+G OUTPUT WIRING NOMINAL OUTPUT CURRENT (FULL LOAD) (A) NOMINAL BATTERY VOLTAGE (VDC) END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC) BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A) BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A) INPUT THDI OUTPUT THDU MAXIMUM SHORT CIRCUIT WITHSTAND REQUIRED UPSTREAM INPUT BREAKERS 80% RATED/100%RATED REQUIRED UPSTREAM BYPASS BREAKERS 80% RATED/100%RATED REQUIRED UPSTREAM OUTPUT BREAKERS 80% RATED/100%RATED RECOMMENDED INPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS RECOMMENDED BYPASS CABLE SIZE 80% RATED/ 100% RATED BREAKERS RECOMMENDED OUTPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS HEAT DISSIPATION @100% LOAD (BTU/hr) [kW] - NORMAL OPERATION / ECO MODE Air flow @ 100% Load 271 480 384 ELECTRICAL DATA SHEET-SINGLE MAINS UPS RATING AT 0.9 PF LAG. 225kVA NOMINAL INPUT VOLTAGE (FREQUENCY) 480V (50/60Hz) NOMINAL OUTPUT VOLTAGE ( FREQUENCY) 480V (50/60Hz) WIRING : 3WIRE-3PH+G OR 4WIRE- 3PH+N+G 255 INPUT WIRING UPS INPUT NOMINAL INPUT CURRENT (A) MAXIMUM INPUT CURRENT (A) 306 INPUT CURRENT LIMITATION (A) 347 WIRING : 3WIRE-3PH+G OR 4WIRE- 3PH+N+G OUTPUT WIRING NOMINAL OUTPUT CURRENT (FULL LOAD) (A) NOMINAL BATTERY VOLTAGE (VDC) END OF DISCHARGE VOLTAGE (FULL LOAD) (VDC) BATTERY CURRENT AT FULL LOAD AND NOMINAL BATTERY VOLTAGE (A) BATTERY CURRENT AT FULL LOAD AND MINIMUM BATTERY VOLTAGE (A) 441 INPUT THDI 551 OUTPUT THDU < 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD < 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD 65kA @ REQUIRED BREAKER SIZE LJL36600U31X- 600A(350A SETTING)/ LJL36400CU31X-400A(350A SETTING) LJL36400U31X- 400A(300A SETTING)/ LJL36400CU31X-400A(300A SETTING) LJL36400U31X- 400A(300A SETTING)/ LJL36400CU31X-400A(300A SETTING) MAXIMUM SHORT CIRCUIT WITHSTAND REQUIRED UPSTREAM INPUT BREAKERS 80% RATED/100%RATED REQUIRED UPSTREAM OUTPUT BREAKERS 80% RATED/100%RATED RECOMMENDED INPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS RECOMMENDED OUTPUT CABLE SIZE 80% RATED/ 100% RATED BREAKERS HEAT DISSIPATION @100% LOAD (BTU/hr) [kW] - NORMAL OPERATION / ECO MODE (2) 2/0 AWG / (2) 2/0 AWG Air flow @ 100% Load 271 480 384 441 551 < 3%@ 100% LOAD, <4% @ 50% LOAD, <6% @ 25% LOAD < 2%@ 100% LINEAR LOAD, < 3%@ 100% NON-LINEAR LOAD 65kA @ REQUIRED BREAKER SIZE LJL36600U31X- 600A (350A SETTING) / LJL36400CU31X-400A (350A SETTING) LJL36400U31X- 400A (300A SETTING) / LJL36400CU31X-400A (300A SETTING) (2) 2/0 AWG / (2) 2/0 AWG (1) 300 kcmil / (1) 300 kcmil (24870) [7.29] / (3450) [1.01] 3700m³@40°C, 3200m³@30°C, (1) 300 kcmil / (1) 300 kcmil (1) 300 kcmil / (1) 300 kcmil (24870) [7.29] / (3450) [1.01] 3700m³@40°C, 3200m³@30°C, 2800m³@20°C EFFICIENCY DATA AT VARIOUS LOAD LEVELS 25%  50%  75%  100%  MODE \ LOAD LOAD LOAD LOAD LOAD NORMAL OPERATION 95.8% 96.4% 96.5% 96.4% ECOnversion MODE 97.4% 98.6% 98.9% 99.0% ECO MODE 98.5% 99.1% 99.4% 99.5% BATTERY OPERATION 96.3% 96.2% 96.0% 95.7% 2800m³@20°C