UPS Power Battery LCP12-36 (12V36 W) Specification Nominal Voltage
12V
Nominal Capacity(10HR)
8.2Ah at 1.80V/cell @250C/770F
Watts(15min Rated)
36.0 Watts/cell at 1.67V/cell @250C/770F
Dimension
Length Width Container Height Total Height (with Terminal)
151±2mm (5.95 inches) 65±1mm (2.56 inches) 93.5±1mm (3.68 inches) 99±1mm (3.90 inches)
Ma int en
an ce -fr
ee Se
LC P1 2-
36 (1 2V 36
ale d Le CO NS ad -ac id TA NT VO Sta ndb LTAG E y CH AR use : GE Cy cle 13. 5-1 3.8 use : Init ial 14. 4-1 5.0 cur ren t: Warn ing: Risk of Les s tha fire, expl heat abov osio n, n or burn e the 2.4 50 O C, or s. Do not incin erate disa ssem . ble,
W)
Ba tte ry V V 0A
MH2 6866
LEOCH
BATTER
MADE IN Y CO.,LTD. CHINA
Non-s BATTERY MUSTpillable BE RECYCLED
Approx 2.40 kg (5.29lbs)
Approx Weight Terminal
T2
Container Material
ABS
Rated Capacity
8.72 8.20 8.00 6.51 6.02
Max. Discharge Current
105A (5s)
Internal Resistance
Approx 20.0mΩ
Operating Temp.Range
Discharge : -15~500C (5~1220F) Charge : 0~400C (32~1040F ) Storage : -15~400C (5~1040F) 0
Applications
(20hr,1.80V/cell,250C/770F) (10hr,1.80V/cell,250C/770F) (8hr,1.75V/cell,250C/770F) (3hr,1.75V/cell,250C/770F) (1hr,1.60V/cell,250C/770F)
AH/0.436A AH/0.820 A AH/1.00 A AH/2.17A AH/6.02A
UPS (High rate) Emergency power supply Banks & Financial Markets Hospitals & Testing Laboratories Industrial Process Control Facilities Date & Network Operations Centers
Compliant Standards
0
Nominal Operating Temp. Range
25±3 C (77±5 F )
Cycle Use
Initial Charging Current less than 2.40A. Voltage 14.4V~15.0V at 250 C(770 F)Temp. Coefficient -30mV/0C
Standby Use
No limit on Initial Charging Current Voltage 13.5V~13.8V at 250 C(770 F)Temp. Coefficient -20mV/0C
Capacity affected by Temperature
40o C 25o C 0o C
Self Discharge
Leoch LCP series batteries may be stored for up to 9 months at 250 C(770F) and then a freshening charge is required. For higher temperatures the time interval will be shorter.
(104o F) ( 77o F ) ( 32o F )
IEC60896-21/22:2004 BS 6290 Part 4
103% 100% 86%
VdS
t est ed
9
Germany
Constant Current Discharge (Amperes) at 25 0C (77 0F ) F.V/Time
5min
10min
15min
20min
30min
45min
1h
2h
3h
4h
5h
6h
8h
1.85V/cell
23.5
18.0
14.6
12.2
8.88
6.26
4.87
2.72
1.94
1.55
1.30
1.15
0.90
10h
20h
0.749
0.418
1.80V/cell
25.9
19.9
16.0
13.4
9.55
6.76
5.26
2.92
2.09
1.67
1.40
1.25
0.99
0.820
0.436
1.75V/cell
30.8
22.5
18.1
14.5
10.2
7.14
5.53
3.06
2.17
1.72
1.43
1.27
1.00
0.828
0.439
1.70V/cell
32.6
23.4
18.8
14.9
10.5
7.34
5.71
3.14
2.23
1.75
1.46
1.29
1.02
0.836
0.443
1.67V/cell
35.0
24.5
19.5
15.4
10.9
7.62
5.90
3.22
2.27
1.78
1.48
1.30
1.03
0.841
0.444
1.60V/cell
36.7
25.4
20.0
15.8
11.1
7.75
6.02
3.28
2.31
1.80
1.49
1.31
1.04
0.848
0.446
8h
10h
20h
Constant Power Discharge (Watts) at 25 0C (77 0F ) F.V/Time
5min
10min
15min
20min
30min
45min
1h
2h
3h
4h
5h
6h
1.85V/cell
44.4
34.4
28.1
23.9
17.5
12.4
9.74
5.47
3.92
3.14
2.63
2.28
1.80
1.50
0.840
1.80V/cell
48.3
37.7
30.6
26.0
18.7
13.4
10.5
5.84
4.21
3.38
2.84
2.47
1.97
1.64
0.872
1.75V/cell
56.6
42.0
34.4
27.8
19.9
14.0
11.0
6.10
4.36
3.46
2.89
2.51
1.99
1.65
0.878 0.885
1.70V/cell
59.0
43.2
35.2
28.3
20.3
14.3
11.3
6.24
4.46
3.52
2.95
2.54
2.01
1.66
1.67V/cell
62.2
44.4
36.0
28.9
20.8
14.8
11.6
6.38
4.52
3.56
2.98
2.56
2.01
1.67
0.886
1.60V/cell
63.8
45.3
36.2
29.3
21.0
14.9
11.7
6.44
4.57
3.58
2.99
2.58
2.04
1.68
0.890
Specifications subject to change without notice.
1
Dimensions T2 Terminal
7.95 (0.313)
0.83 (0.033)
3.4 (0.134)
65±1 43
99±1 93.5±1
6.35(0.25)
Unit: mm [inches]
151±1
Discharge Characteristics
Float Charging Characteristics
6V Battery 12V Battery V V 13.0 6.5
Charge Volume
Temperature:25 0 C
Terminal Voltage(V)
6.0
12.0
5.5
11.0 0.22C 0.10C
0.052C
Charging Current
(A)
%
Charging Voltage
120
0.10C
2.4
100
0.08C
2.3
80
0.06C
2.2
60
0.04C
2.1
40
0.02C
2.0
20
0C
Charged Volume
0.7C 0.4C 5.0
Charge Voltage (Constant 2.25V/cell)
1.2C
10.0
After 50% Discharge
2.1C 4.5
9.0
4.0
8.0 3C 7C
10C 1
2
4
6 810 S
40 60
20
After 100% Discharge
4C 2
Charging Current 6 8 10 min
4
20
40 60
2
4 6 8 10 H
20
0
Discharge Time
8
12
16
20
24
28
32
36
Effect of Temperature on Long Term Float Life
120
15
100
12 9
C 0.1 0 C 0.2 2
80
4
Charging Time(Hours)
Temperature Effects in Relation to Battery Capacity
Capacity (%)
0
0.1CA-2.25V/cell temperature25 C
(V/cell)
Charging voltage : 2.25V/cell
6 3
60
1.0C 40
2
2. 0 C
20
0
0 -20
-10
0
10
30
20
40
20 68
50
0
Temperature( C )
40 104
50 122
0
C F
O
Battery temperature
100 100C
Remaining Capacity(%)
30 86
Self Discharge Characteristics
A
80 250C
60
B
300C
A
No supplementary charge required (Carry out supplementary charge before use if 100% capacity is required.)
B
Supplementary charge required before use.Optional charging way as below: 1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell. 2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell. 3.Charged for 8~10hours at limted current 0.05CA .
C
Supplementary charge may often fail to recover the capacity. The battery should never be left standing till this is reached.
0
40 C
40
C
20 0 0
2
6
4
8
10
12
Storage Time(Months)
Sales Office China sales office:
HongKong sales office:
Singapore sales office:
North America sales office:
Europe sales office:
Add:5th Floor,Xinbaohui Bldg.,Nanhai Blvd., Nanshan,Shenzhen, China. 518052 Tel: +86-755-86036060 (100 lines) Fax: +86-755-26067269 E-mail:
[email protected] Http://www.leoch.com
Add: Workshop C, 33/F, TML Tower, No. 3 Hoi Shing Road, Tsuen Wan, New Territories, Hong Kong Tel: +852 35786666 Fax: +852 21170016 E-mail:
[email protected]
Add: No. 1 Tech Park Crescent, Singapore 638131 Tel: +65 6863 6078(5 lines) Fax: +65 6863 6079 Email
[email protected]
Add: 19751 Descartes, Unit A, Foothill Ranch, CA 92610, USA Tel: 949-588-5853 Fax: 949-588-5966 E-mail:
[email protected] Http://www.leoch.us
Add: 9B Wheatstone Court. Waterwells Business Park, Gloucester, GL2-2AQ, UK United Kingdom Tel: +44(0) 1452 729428 / 1452 729696 Fax: +44 (0)1452-690125 E-mail:
[email protected]
2
Publication No.:LB-03-17