Preview only show first 10 pages with watermark. For full document please download

User Manual - Intec Controls

   EMBED


Share

Transcript

PolyGard“ CO AT-1110 Electrochemical analog carbon monoxide transmitters serial no. EC-C 003 User Manual June 14, 2005 PolyGard£ is a registered trademark of MSR Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com GAAT1110I04 Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 2 Electrochemical analog carbon monoxide transmitters 1 General Overview ..................................................................................................................... 3 2 Description ................................................................................................................................... 3 3 Installation .................................................................................................................................... 5 3.1 3.2 4 Electrical Connection ............................................................................................................ 6 4.1 4.2 4.3 5 Assembly information ................................................................................................................ 5 Enclosure................................................................................................................................... 5 Instructions ................................................................................................................................ 6 Wiring connection ...................................................................................................................... 6 Mounting optional relay package AT-2R .................................................................................. 7 Start-up operation .................................................................................................................... 7 5.1 Calibration ................................................................................................................................. 7 5.2 Control span voltage calculation ............................................................................................... 8 5.3 Commissioning optional relay package AT-2R ........................................................................ 8 5.3.1 Selection of open-circuit or closed-circuit operation.............................................................. 8 5.3.2 Select switching differential ................................................................................................... 8 5.3.3 Adjust switching voltage ........................................................................................................ 9 5.3.4 Calculation of the switching voltage (Uthreshold)....................................................................... 9 6 Inspection and Service ....................................................................................................... 10 6.1 6.2 6.3 7 Inspection ................................................................................................................................ 10 Calibration ............................................................................................................................... 10 Replacing of the sensor element............................................................................................. 10 Troubleshooting ..................................................................................................................... 11 7.1 7.2 Diagnostics of the transmitter.................................................................................................. 11 Diagnostics of optional relay package AT-2R ......................................................................... 11 8 Cross-sensitivity Data 9 Specifications ........................................................................................................................... 13 10 Wiring Configuration and Enclosure Dimensions ........................................... 15 11 Notes and General Information ................................................................................... 18 11.1 11.2 11.3 11.4 11.5 ........................................................................................................ 12 Intended product application ................................................................................................... 18 Installers` responsibilities ........................................................................................................ 18 Maintenance ............................................................................................................................ 18 Limited warranty ...................................................................................................................... 18 Return instructions................................................................................................................... 18 PolyGard£ is a registered trademark of MSR Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com GAAT1110I04 Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 3 Electrochemical analog carbon monoxide transmitters 1 General Overview The PolyGard“CO analog gas transmitter is used for detection of carbon monoxide in the ambient air to warn of the presence of Carbon Monoxide gas. 2 Description The sensor portion of the PolyGard£ AT-1110 analog gas transmitter is a micro-fuel cell, which is completely sealed. The measurement is a gas-in-liquid chemical reaction rather than a surface area measurement. With no surface area to coat, this sensor retains its sensitivity to carbon monoxide even after prolonged exposure to clean air. The cell consists of a diffusion barrier, O-ring seal, electrolyte reservoir and three electrodes: sensing, counter and reference. The target gas, carbon monoxide, enters the cell through a diffusion barrier. The chemical process of the measurement is one of oxidation where one molecule of the target gas is exchanged for one molecule of oxygen. The reaction drives the oxygen molecule to the counter electrode, generating a DC microampere signal between the sensing and counter electrodes. This signal is linear to the volume concentration of the sensed gas rather than the partial pressure. The integrated two-wire transformer converts this DC microampere signal to a standard 4-20 mA signal. In some cases, biasing is required to maintain a voltage differential between the reference and sensing electrode in order to facilitate the necessary reaction in the cell. The transmitter electronics will provide the necessary bias voltage when configured for one of these sensor types. Most sensors produce a small amount of baseline current in clean air. This is adjusted out with the zero potentiometer on the transmitter. This oxidation at the electrodes causes wear of the sensor. Typical life for this sensor is approximately five years in normal operation. This will vary somewhat from sensor to sensor, with some working lifetimes less than five years and some greater than 5 years. This wear also changes the characteristics of the sensor, requiring periodic re-calibration. It is recommended that the sensor accuracy be verified every six months and recalibrated as necessary. Caution! Replacement sensor elements, which are not bias types, are shipped with a tiny spring of wire shorting the sensor and reference electrodes. This spring MUST BE REMOVED prior to installing the element into the sensor assembly. PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 4 Optional relay package AT-2R Ĭ: The PolyGard® AT-2R relay package is used in conjunction with the AT-1110 CO analog gas transmitter. The AT-2R provides the transmitters with two relay outputs with adjustable trip/setpoints, switching differential. Once plugged on the master PCB transmitter the relay outputs will change and notify if gas concentration exceeds the adjusted trip/setpoint. If the gas concentration falls below the adjusted trip/setpoint and switching differential the relays again will change state and fall back into their starting position. The relay will trigger on depending on its adjusted power mode. If de-energized it will trigger on. If energized it will trigger off (fail-safe mode) with increasing value. LED number 9 for relay R9 and LED number 10 for relay R10 indicates status of each relay. PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 5 3 Installation Note: x x Avoid any force (e.g. by thumb) during operation or installation on the sensor element. This could destroy the element. Electronics can be destroyed through static electricity. Therefore, do not work on the equipment without a wrist strap connected to earth ground or standing on conductive floor. 3.1 Assembly information x x x x x x x The specific weight of carbon monoxide is almost the same as that of air (factor 0.967). Location of the sensor must conform to the layout of the area being monitored. Disregard the ventilation ratio! Do not mount sensor in the center of the airflow. In larger rooms, it might be necessary to install two or more transmitters where there is not adequate air movement. Do not mount in corners or directly in front of air inlets (e.g. doors, windows, open ramps, dampers, etc.). In areas with undefined air movement, it might be necessary to distribute several transmitters in a vertical and horizontal direction over the whole area to be monitored. Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might be possible. Mounting height is five feet above floor (max. 6 feet). Provide adequate space around sensor for maintenance and calibration work. Duct model 4 mounting: Mount only in a straight section of duct with minimum air vortex. Keep a minimum distance of 3.5 feet (1m) from any curve or obstacle. Mount only in a duct system with a maximum air velocity of 2000 ft/min or less. Mounting must be made so that the airflow is in line with probe openings. (see Fig. 6, page 16) 3.2 Enclosure  Un-screw cover of enclosure.  Carefully unplug the basic PCB mounted on fixed terminal blocks.  Screw the base vertically on wall or on a single gang electrical box. (see Fig. 5, page 16).  For duct model Ĭ mounting: Cut a hole in the duct and install the probe in the hole. (see Fig. 7, page 16) Screw the housing to the duct using the mounting holes inside enclosure.  Plug in the basic PCB and replace the cover after wiring connection is completed (see 4.2 wiring connection). PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 6 4 Electrical Connection 4.1 Instructions Note: Electrostatic discharge (ESD) may damage electronic components. During wiring, open the cover only when completely grounded via grounding strap or standing on conductive floor. x x x x x x Connections should be made without any power applied to conductors. Installation of the electrical wiring should be according to the connection diagram and only performed by a trained specialist. Avoid any influence from external interference by using a shielded cable. Recommended cable: 18 AWG shielded, maximum resistance 20.8 :/1000 ft (73 :/1000 m) Cable for Relay Package AT-2R Ĭ: Does not need to be shielded. Cable insulation: Since the PCB mounts on top of the wiring terminations, it is important to ensure that the wire shields or any bare wires do not short to the PCB. Terminal strip X4 Connector 3 Connector 4 Connector 5 Connector 2 Terminal strip X5: Power supply (+) 24 VDC, 17 – 28 VDC Signal 4 – 20 mA Shield 0 VDC (DC common, only needed with option relay package AT-2R4). (functions only with option relay package AT-2R) Ĭ. Connector 1-3 Connector 4-5 Potential free relay contact (R9) Potential free relay contact (R10) 4.2 Wiring connection x x Unscrew cover of enclosure. Unplug basic PCB from terminal blocks. For single gang electrical box mounting: x Pull through cable via hole in base; connect cable leads on terminal block X4. x Snap the ferrite core on the cable into the enclosure (see Fig.1, page 15). For surface mounting (cable entry always from the top) and also for duct mounting: x Remove cover to access cable. x Connect cable leads on terminal block X4. x Snap the ferrite core on the cable into the enclosure. (see Fig.1, page 15). x Plug the PCB on fixed terminal blocks on base. x Screw cover on base. Optional Relay package AT-2R Ĭ: x Connect cable leads on terminal X5 x Snap the ferrite core also on the cable into the enclosure. (see Fig.1, page 15). (This ferrite core is delivered with the relay package) Note: (Ferrite core installation) Prior to terminating the wire, secure enough cable length within the enclosure to snap-on the supplied ferrite core. The ferrite core must be within the enclosure and located such that the PCB can be installed. PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 7 4.3 Mounting optional relay package AT-2R Ĭ Static Electricity (see section 4.1). x x x x Unplug basic PCB from the terminal blocks fixed on base. Plug Relay Package female header X2 on basic PCB. (see Fig. 3, page 15) Secure on back of PCB the washer and nut. Plug basic PCB into terminal blocks on base. 5 Start-up operation Only trained technicians should perform the following: Check mounting location. Check airflow direction for duct mounting. Check power voltage. Check PCB EC-C for proper mounting at X4 and X5. Check for correct sensor element (7 MSR) at terminal X3 PCB EC-C. Optional relay package AT-2R Ĭ: x Check proper mounting of relay package AT-2R at board EC-C. x Select the desired hysteresis and relay function. x Adjust threshold value if not ordered from the factory with setpoint calibrated. x Verify transmitter operation (sensor/transmitter was factory calibrated). x x x x x x Note: If calibration is necessary, the sensor element must be powered and be fully stabilized for at least 1 hour. Required instruments to calibrate the transmitter: x Test gas bottle with synthetic air. x Test gas bottle with 200 ppm CO. x Gas pressure regulator with flow meter to control the gas flow to 150-300 ml/min. x Sensor head calibration adapter with tubing. x Digital voltmeter with range 0 – 2 VDC, accuracy 1% and a small screwdriver. Note: Please observe proper handling procedures for test gas bottles! 5.1 Calibration Zero adjustment Zero-point calibration (4mA): (After sensor warm-up) x Connect digital voltmeter to test pins – and + (with a range selected that will display 2 VDC max.). x Connect the calibration adapter to sensor element. x Apply sensor element zero calibration gas, (150-300 ml/min; 14.5 psi ± 10%), or other clean air source. x Wait two minutes until the signal is stable, adjust signal with zero potentiometer ”Zero” until the signal is 200 mV ± 2 mV and stable. x Remove calibration adapter carefully by turning lightly. PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 8 Span adjustment Notes: CO calibration gas is toxic, never inhale the gas! Symptoms: Dizziness, headache and nausea. Procedure if exposed: Bring into fresh air at once, consult doctor. x x x x Connect calibration adapter to the sensor element. Apply sensor element span calibration gas (200 ppm CO), (150-300 ml/min; 14.5 psi ± 10%). Wait two minutes until the signal is stable, adjust signal with span potentiometer ”Span” until the signal reads the appropriate mVDC (± 3mV, see calculation for control voltage 5.2) and is stable. Remove calibration adapter with a careful light turn. Inspect the seating of the sensor element! 5.2 Control span voltage calculation 800 (mV) x test gas concentration (ppm) Measuring range CO (ppm) + 200 (mV) Example Measuring range CO concentration Test gas concentration Control voltage 800 (mV) x 200 (ppm) + 200 (mV) = 250 (ppm) 250 ppm 200 ppm 840 mV 840 mV 5.3 Commissioning optional relay package AT-2R Ĭ 5.3.1 Selection of open-circuit or closed-circuit operation. Each relay can be configured for normally de-energized operation or normally energized operation (fail-safe) via jumper. Operation Relay R9 Jumper pos. Relay R10 Jumper pos. Normally de-energized operation 9 to 11 18 to 20 Normally energized operation 10 to 12 19 to 21 Factory setting is for closed-circuit operation. 5.3.2 Select switching differential Switch threshold calculation format: Uout = Uthreshold - Udifferential (see section 5.3.4 for Uthreshold calculations) Two different values of switching differential can be selected via jumper per relay. The jumpers need to be plugged into the correct position to select either 5% or 10% of the transmitters full range as switching differential. (see table for jumper positions). PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 9 Threshold calculation Voltage (V) Switch differential (%) Relay R9 Jumper pos. Relay R10 Jumper pos. 1.00 – 3.50 5 10 7 5 16 14 3.51 – 6.50 5 10 4* 6 13 * 15 6.51 – 9.00 5 10 5 8 14 17 Note: At a voltage below 1.50 V it is not allowed to have a switching differential of 10%. The triggered alarm trip/setpoint would not allow the relay to return to ist starting position. * Factory set 5.3.3 Adjust switching voltage Required instruments: x x Digital multimeter with 0 – 10 VDC range, 1% accuracy Small screwdriver Switching voltage can range from 1 V – 9 V, 10% - 90% CO concentration by adjustment. Adjust switching voltage for relay R 9 x x Connect digital multimeter at X9 + and -. Adjust potentiometer P9, calculate the switching voltage ± 10 mV, (see section 5.3.4). Adjust switching voltage for relay R 10 x x Connect digital multimeter at X10 + and X9-. Adjust potentiometer P10, calculate the switching voltage ± 10 mV, (see section 5.3.4). 5.3.4 Calculation of the switching voltage (Uthreshold) Uthreshold = 8 (V) x Alarm threshold (ppm) Measuring range CO (ppm) + 2 (V) Example Measuring range CO Alarm threshold Uthreshold 8 (V) x 50 (ppm) 250 ppm CO 50 ppm CO + 3.6 V + 2 (V) = 3.6 V 250 (ppm) PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 10 6 Inspection and Service 6.1 Inspection Inspection and service of the transmitters should be done by a trained technician and executed on a periodic interval. It is recommended that the sensor operation be verified at least every six months. 6.2 Calibration (See part 5.1 and 5.2) x Service at periodic intervals is to be decided by the person responsible for the gas detection system. x If span calibration voltage of 840 mV (see note below) is no longer attainable when applying 200 ppm Carbon Monoxide in air, then the sensor element has to be replaced. After the sensor element has been replaced a calibration is required. Note: If using a different level of span test gas ppm, or different sensor range, then the mV needs to be calculated. 6.3 Replacing of the sensor element Static electricity (see section 4.1). Sensor should always be installed without power applied: x x x x x x x Unplug basic PCB EC-C carefully from the terminal blocks on the base. Unplug old sensor element out from the PCB EC-C. Take new sensor element out of original packing and remove the shorting wire on the sensor element contacts. Plug sensor element in the PCB EC-C. Plug the PCB EC-C in terminal block X4, X5 carefully. After sensor warm-up, turn potentiometer “Span” to its center position. (Turn the pot 25 rotations counter-clockwise, then 11 rotations clockwise to get centered.) Calibrate (see section 5.1). PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 11 7 Troubleshooting 7.1 Diagnostics of the transmitter Trouble Reason Solution Output signal 0 mA and control voltage 0 V Power not applied Basic PCB EC-C X4 and X5 not plugged in correctly Measure power voltage terminal block X4 terminal 3 (+) and 4 for 17 – 28 VDC Plug in the basic PCB EC-C into X4 and X5 correctly Output signal less then 4 mA Sensor element not calibrated Calibrate sensor element output Control current signal not correct Sensor span not attainable Replace sensor element 7.2 Diagnostics of optional relay package AT-2R 4 Trouble Reason Solution No relay switching Board AT-2R not installed correctly Jumper JP 9 – 12 and 18 - 21 not installed correctly Plug AT-2R 4 correctly into board No or incorrect relay switching See section 5.3.1 for correct setting No relay switching at Switching voltage not calculated threshold setting adjusted correctly Check switching voltage (see section 5.3.4) Relay return differential too Differential jumper not correct long Check jumper position (see section 5.3.2) PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 12 8 Cross-sensitivity Data Ĭ This table shows the typical response to be expected from the sensor when exposed to the following gases. Gas Chemical mark Gas concentration Tolerance ppm CO Acetone (CH3)CO(CH3) 200 ppm < 0.46 ppm Ammonia NH3 100 ppm 0 pmm Chlorine CL2 1 ppm 0 ppm Ethanol C2H5OH 200 ppm 0 ppm Ethylene C2H4 100 ppm d 100 ppm Hydrogen H2 100 ppm  60 ppm Hydrogen chloride HCI 5 ppm 0 ppm Hydrogen cyanide HCN 10 ppm < 2 ppm Hydrogen sulphide H2S 15 ppm  0.3 ppm Nitric oxide NO 35 ppm d 7 ppm Nitrogen dioxide NO2 5 ppm d - 1 ppm Sulphur dioxide SO2 5 ppm 0 ppm Toluene C6H5CH3 200 ppm 0 ppm Trichloraethane C2HCL2 200 ppm < 10 ppm PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 13 9 Specifications Electrical Power supply: Power consumption: - w/relay package 4 RFI/EMI protection Sensor Performance Gas detected Sensor element Range Stability & resolution Repeatability Long term output drift Response time Sensor life expectancy 4 Sensor coverage Mounting height Type of Control Analog output signal Option 4 Operating Environment Working temperature Ĭ Storage temperature Humidity Pressure range Physical characteristics Enclosure material Enclosure color Wall mounting Installation Dimensions (HxWxD) Cable entry Wire connection Wire size Wire distance Weight Approvals/Listings Warranty PolyGard£ is a registered trademark of MSR 17-28 VDC (polarity protected) 22 mA, (0.6 VA), max. 35 mA, (1.0 VA), max. 5.0 W @1 ft. (0.31 m) radiated Carbon monoxide (CO) Electrochemical, diffusion 0 – 250 ppm factory set 0 - 150 to 0 – 300 ppm, adjustable via calibration ± 0.5 ppm of reading ± 1% of reading  0.4% signal loss/month t90 d 30 sec. 5 year, normal operating environment 5,000 sq.ft., (465 m2), to10,000 sq.ft. (930 m2) under “ideal conditions” 5 to 6 ft. (1.5 to 1.8 m) above floor Proportional, 4 – 20 mA, load d 450 : (2) relay contacts, potential free, max. 30 VAC/DC 0.5 A 14 °F to 104 °F (-10 °C to + 40 °C) -4 °F to 104 °F (-20 °C to + 40 °C) 15 to 95% RH non-condensing Atmospheric ±10% Galvanized Steel w/zinc coating, corrosion resistant Light gray NEMA1 (IP 42) Wall (surface) mounted or single gang electrical box 5.59 x 5.59 x 2.48 in. (142x142x63 mm) 1 hole for ½ in. conduit for wall (surface) mounting, and 1 hole on back side of base plate for single gang electrical box mounting Terminal blocks, screw type for lead wire Min. 24 AWG (0.25 mm2), max. 14 AWG (2.5 mm2) Max. loop resist. 450 : (= wire resist. + controller input resist.) 0.7 Ibs. ( 0.3 kg ) UL Recognized sensor City of Los Angeles CE VDI 2053 EMV-compliance 89/336/EWG Two years material and workmanship Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Options Enclosures Duct mounted 4 - w/probe - cable entry Wall mounted 4 - material - color Dimensions (HxWxD) Relay Package Ĭ Type Contact rating Setpoint Switching differential Relay mode Status indicator Heater, built-in Ĭ Power supply Power consumption For ambient temperature Thermostatic control PolyGard£ is a registered trademark of MSR Page 14 NEMA 3 (IP 44) 7/8 in. (22 mm) diameter and 7.16 in. (182 mm) length 1 hole for ½ in. conduit NEMA 4X w/splash guard (IP 65) ABS UL94V0 Light gray 4.8 x 4.72 x 3.42 in. (122 x 120 x 87 mm) (1) SPDT (R9), (1) SPST (R10) 30 VAC/DC, 0.5 A max. Adjustable setting for each relay within 10-90% of full range Jumper selectable, 5% or 10% of full range Jumper select., de-energized or energized (fail-safe) for each relay (2) LED’s, one for each relay 24 VAC/DC ± 5%, 50/60 Hz 1.0 A (24 VAC), max. - 40 °F (-40 °C) 32 °F (0 °C) ± 5 °F (3 °C) Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 15 10 Wiring Configuration and Enclosure Dimensions Wiring Configuration Fig. 1 3-wire configuration with -Optional relay package Power supply 17 - 28V/DC + Snap ferrite core shield 4-20mA 0V/DC - Transmitter AT-1100 X4 1 X5 R10 2 0V DC 5 3 24V DC 4 3 4 4-20mA 2 5 Shield R9 1 6 Shield 7 Shield X1 2 1 Controller Snap ferrite core Optional heater 24V AC/DC 1A 0V Shield: Connect Shield to either terminal 5, 6 or 7. Shield should be grounded at either the sensor or controller. DO NOT ground Shield at both ends. For stand-alone relay operation (w/o controller) place 220….330 : resistor between terminals 2 (common) and 4 (signal). Printed circuit board EC-C Fig. 2 Option relay package AT 2R Ĭ Fig. 3 + 1 - 1 X4 S X3 R Sensor Position Jumper No. C JP7 EC-C 003 230398 X6 Position Jumper No. X2 1 Position Jumper No. X5 VR3 Span VR2 Zero Platin31 PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Assembly Fig. 4 Page 16 Dimensions Fig. 5 7 1 + 1 5 R X5 X4 VR3 Span X5 S X3 Sensor 1 C 1 X4 JP7 EC-C 003 230398 - 3.3 in. (84 mm) Hole for mounting 5.59 in. (142 mm) Cable entry 2.48 in. (63 mm)0.83 in. (21 mm) 1 X2 K10 X9 - X10 D=0.88 in. (22,5 mm) K9 X2 9 P9 + P10 + X6 D=0.16 in. (4 mm) K9 PCB EC-C K10 2R-AT 001 170299 option AT-2R gas outlet (closed with duct enclosure) 5.59 in. (142 mm) 2.75 in. (70 mm) VR2 Zero d=0.16 in. (4 mm) Platin31 gehaem10 Gehaem12 gas inlet (closed with duct enclosure) Duct mounting enclosure Ĭ Fig. 6 Cutout for duct model Ĭ Fig. 7 2.48 in. (63 mm) 0.83 in. (21 mm) D=0.16 in. (4 mm) D=0.88 in. (22.5 mm) 7.16 in. (182 mm) Gehäuse1 gehaem20 D=0.16 in. (4 mm) PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 17 Splash guard enclosure Ĭ Fig. 8 4.8 in. (122 mm) X2 3.54 in. (90 mm) + 1 EC-C 003 230398 X6 C 1 X4 S X3 Sensor R JP7 4.72 in. (120 mm) 1 0.63 in. (16 mm) 4.33 in. (110 mm) X5 VR3 Span VR2 Zero Platin31 0.63 in. (16 mm) at11splash 3.34 in. (85 mm) Splash guard enclosure Ĭ Fig. 9 at11splash1 PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806 User Manual - PolyGard® CO AT-1110 Page 18 11 Notes and General Information It is important to read this user manual thoroughly and clearly understand the information and instructions. The PolyGard® transmitters must be used within product specification capabilities. The appropriate operating and maintenance instructions and recommendations must be followed. Due to ongoing product development, MSR reserves the right to change specifications without notice. The information contained herein is based upon data considered to be accurate. However, no guarantee is expressed or implied regarding the accuracy of this data. 11.1 Intended product application The PolyGard® CO AT-1110 transmitters are designed and manufactured for control applications for energy savings and OSHA air quality compliance in commercial buildings and manufacturing plants (i.e.,detection and automatic exhaust fan control for automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses with forklifts, fire stations, tunnels, etc.). 11.2 Installers` responsibilities It is the installer`s responsibility to ensure that all PolyGard® transmitters are installed in compliance with all national and local codes and OSHA requirements. Installation should be implemented only by individuals familiar with proper installation techniques and with codes, standards and proper safety procedures for control installations and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential to strictly follow all instructions as provided in the user manual. 11.3 Maintenance It is recommended that the PolyGard® transmitter performance check is done on a routine schedule. Any performance deviations may be serviced based on needed requirements. Re-calibration and part replacement may be implemented in the field by a qualified individual and with the appropriate tools. Alternatively, the easily removable plug-in transmitter card with the sensor may be returned for service to INTEC Controls. 11.4 Limited warranty MSR and INTEC Controls warrant the PolyGard® transmitters for a period of two (2) years from the date of shipment against defects in material or workmanship. Should any evidence of defects in material or workmanship occur during the warranty period, MSR or INTEC Controls will repair or replace the product at their own discretion, without charge. This warranty does not apply to units that have been altered, had repair attempted, or been subjected to abuse, accidental or otherwise. The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned. The above warranty is in lieu of all other express warranties, obligations or liabilities. This warranty extends only to the PolyGard® transmitter. MSR and INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard® transmitters. 11.5 Return instructions If the PolyGard® transmitter needs to be returned to INTEC Controls for service, an RMA number must be obtained prior to sending. PolyGard£ is a registered trademark of MSR Ĭ Not evaluated by UL GAAT1110I04 Phone: (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Specification subject to change without notice. Printed in USA 040806