Transcript
VENT-AXIA BIFURCATED CASE AXIAL FAN WIRING DIAGRAMS THREE PHASE FAN CONNECTED TO A 415V COIL D.O.L. STARTER 3 Phase Supply (380-415V 50Hz).
THREE PHASE FAN CONNECTED TO A STAR / DELTA STARTER 3 Phase Supply (380-415V 50Hz).
STAR / DELTA Starter with current overload protection and a 415 volt coil.
L3 E
L2
L1
BIFURCATED CASE AXIAL FAN WIRING DIAGRAMS
L1
L2
L3 E
A1
415 Volt D.O.L. Starter A suitable sized overload relay must be fitted to provide motor protection.
A1
5
3
1
E
A2
6
4
2
23
96
24
A2 23
95
24
96
STAR / DELTA STARTER
2
4
1
3
5
2
4
6
6
E L3
L2
L1
U1
V1
U2
W1
BIF500/2/3/18-26˚ BIF 800/4/3/8-18˚
BIF 250/4/3/8-32˚ BIF 315/4/3/8-32˚ BIF 400/4/3/8-32˚ BIF 500/4/3/8-30˚ BIF 630/4/3/8-26˚
THREE PHASE FAN CONNECTED TO A 415V COIL D.O.L. STARTER & A 1.4, 4.0, 7.0 OR 11.0 AMP AUTO TRANSFORMER CONTROLLER 3 Phase Supply (380-415V 50Hz). N L1 L2 L3 E
THREE PHASE FAN CONNECTED TO A 240V COIL D.O.L. STARTER 415 Volt D.O.L. Starter A suitable sized overload relay must be fitted to provide motor protection.
3 Phase Supply (380-415V 50Hz).
L3
L2
N
E
A1
E
5
3
1
V2
FAN TERMINAL
V2
BIF 250/2/3/8-32˚ BIF 315/2/3/8-32˚ BIF 400/2/3/8-28˚
240 Volt D.O.L. Starter A suitable sized overload relay must be fitted to provide motor protection.
V1
E
FAN TERMINAL
L1
U1
U2
W1
E W2
W2
A1
E
5
3
1
A2
N.B. Links between terminals 1 to A1, 5 to 95 must be fitted and the link between terminals 24 to 96 must be FITTED.
6
4
2
95
23
96
24
A2
N.B. Links between terminals 5 to 95 and 24 to 96 must be fitted.
6
4
2
95
23
96
24
103 14 301 103 14 304 103 14 307 103 14 311
E
TK TK W1 V1 U1 N L 3 L 2 L 1
E
L3
L2
L1
3 Phase Auto Transformer Speed Controller.
E U1
V1
W1
E W2
U2
V2
FAN TERMINAL
BIF 250/2/3/8-32˚ BIF 315/2/3/8-32˚ BIF 400/2/3/8-28˚
118
BIF 250/4/3/8-32˚ BIF 315/4/3/8-32˚ BIF 400/4/3/8-32˚ BIF 500/4/3/8-30˚ BIF 630/4/3/8-26˚
U1
V1
W1
W2
U2
V2
E
NOTE: If a Auto Transformer is being used to control the fan speed, the manual reset facility must be disabled. Contact Vent-Axia's Technical Support line for details.
FAN TERMINAL
BIF 250/4/3/8-32˚ BIF 315/4/3/8-32˚ BIF 400/4/3/8-32˚ BIF 500/4/3/8-30˚ BIF 630/4/3/8-28˚
119
E
BIFURCATED CASE AXIAL FANS (BIF)
N.B. Links between terminals 5 to 95 and 24 to 96 must be fitted.
95
E
VENT-AXIA BIFURCATED CASE AXIAL FAN WIRING DIAGRAMS THREE PHASE FAN SINGLE PHASE IN - THREE PHASE (240V) OUT LC FAN CONNECTED TO AN INVERTER SPEED CONTROLLER KIT (103 20 101)
BIFURCATED CASE AXIAL FAN WIRING DIAGRAMS
THREE PHASE FAN SINGLE PHASE IN - THREE PHASE (240V) OUT LC FAN CONNECTED TO AN INVERTER SPEED CONTROLLER KIT (103 20 102 OR 103 20 103)
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
1 Phase Supply (220 - 240V). E
E
RELAY FW RE 12V SP RS 10V Vi 0V FM
RELAY FW RE 12V SP RS 10V Vi 0V FM
FW 12V 10V Vi 0V
E
Ferrite Coil
Ferrite Coil (Loop the fan supply cable around the ferrite coil 3 times).
(WRAP WITH INSULATION TAPE).
Connector
Shielded Cable
Shielding
Shielding (WRAP WITH INSULATION TAPE DO NOT CONNECT TO THE EARTH TERMINAL).
3 PHASE SUPPLY (230 - 240 Volts) V1
W1
W2
U2
V2
3 PHASE SUPPLY (230 - 240 Volts) E
FAN TERMINAL
BIF 250/2/3/8-32˚ BIF 315/2/3/8-30˚
U1
V1
W1
W2
U2
V2
FAN TERMINAL
BIF 250/4/3/8-32˚ BIF 315/4/3/8-32˚ BIF 400/4/3/8-32˚
BIF 400/2/3/8-22˚ BIF 500/2/3/8-20˚
120
Inverter 455559
1 6 8 10 11
R S T
B1 B2 U V W - B1 /P /R
E
RA RB RC
1 6 8 10 11
BIF 500/4/3/8-32˚ BIF 630/4/3/8-26˚
R S T
B1 B2 U V W - B1 /P /R
RA RB RC
User Fan Speed Controller ILVC 2 (103 20 602)
User Fan Speed Controller ILVC 2 (103 20 602)
L1 L2 L3 E
L1 L2 L3 E
Ferrite Coil
L1 L2 L3 E
Shielding
Filter 103 20 505 103 20 512
Connector
(WRAP WITH INSULATION TAPE).
Shielded Cable
Ferrite Coil
L1 L2 L3 E
(Loop the fan supply cable around the ferrite coil 3 times).
(Loop the fan supply cable around the ferrite coil 3 times).
Shielding
Filter 103 20 512
Connector
(WRAP WITH INSULATION TAPE).
Shielded Cable
L1 L2 L3 E
L1 L2 L3 E
50m Maximum Distance from the Inverter to the Fan (shielded cable required).
(WRAP WITH INSULATION TAPE DO NOT CONNECT TO THE EARTH TERMINAL).
U1
E
Shielding
Shielded Cable
50m Maximum Distance from the Inverter to the Fan (shielded cable required).
Inverter 455556, 455557, 455558 or 103 20 303
(Loop the fan supply cable around the ferrite coil 3 times).
Metal Enclosure & Wiring by others.
SC 1 3 5 7 VIN AIN AUX DO1 DO2 DOG IP12 A(+) A(-) E 2 4 6 8 +15V GND GND AO1 AO2 E IG12 S(+) S(-)
L1 L3 T1 T2 T3 (L) L2 (N) P R (U) (V) (W)
Shielding
E
SC 1 3 5 7 VIN AIN AUX DO1 DO2 DOG IP12 A(+) A(-) E 2 4 6 8 +15V GND GND AO1 AO2 E IG12 S(+) S(-)
User Fan Speed Controller ILVC 1 (103-20-601)
(WRAP WITH INSULATION TAPE).
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
3 Phase Supply (380-415V 50Hz)
Shielding
3 Phase Supply (380-415V 50Hz)
(WRAP WITH INSULATION TAPE DO NOT CONNECT TO THE EARTH TERMINAL).
Shielding (WRAP WITH INSULATION TAPE DO NOT CONNECT TO THE EARTH TERMINAL).
50m Maximum Distance from the Inverter to the Fan (shielded cable required).
50m Maximum Distance from the Inverter to the Fan (shielded cable required).
E
U1
V1
W1
W2
U2
V2
E
FAN TERMINAL
BIF 250/2/3/8-32˚ BIF 315/2/3/8-30˚ BIF 400/2/3/8-22˚ BIF 500/2/3/8-20˚
U1
V1
W1
W2
U2
V2
FAN TERMINAL
BIF 250/4/3/8-32˚ BIF 315/4/3/8-32˚ BIF 400/4/3/8-32˚ BIF 500/4/3/8-32˚ BIF 630/4/3/8-26˚
BIF 800/4/3/8-18˚
121
BIFURCATED CASE AXIAL FANS (BIF)
L1 L2 T1 T2 T3 (L) (N) P R (U) (V) (W)
Connector
Metal Enclosure & Wiring by others.
FW 12V 10V Vi 0V
Inverter 455553 or 455554
User Fan Speed Controller ILVC 1 (103 20 601)
Metal Enclosure & Wiring by others.
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
L~ N
Inverter 455552 E
Metal Enclosure & Wiring by others.
1 Phase Supply (220 - 240V).
L~ N
THREE PHASE FAN THREE PHASE IN - THREE PHASE OUT BIFURCATED AXIAL FAN CONNECTED TO AN INVERTER SPEED CONTROLLER KIT (103 20 350)
THREE PHASE FAN THREE PHASE IN - THREE PHASE OUT BIFURCATED AXIAL FAN CONNECTED TO AN INVERTER SPEED CONTROLLER KIT (103 20 301, 103 20 302, 103 20 303 OR 103 20 305)