INSTALLATION GUIDE
RELAYS TM
V200D
V200D
Dual 10A SPDT Enclosed Relays 10-30 VDC/AC or 208-277 VAC Coil Installer’s Specifications Operating Temperature -40°C to 55°C (-40° to 131°F) Operating Humidity 10-90% non condensing Expected Relay Life Electrical (at rated current): 100,000 cycles Mechanical (unpowered): 10,000,000 cycles Relay Status LED ON=energized Wire Specifications: Lead Length 14” (356mm) min. Gauge UL1015; Coil: 18AWG; Contacts: 16AWG Insulation Class 600VAC RMS Agency Approvals UL508 enclosed device listing
INSTALLATION Disconnect and lock out all power sources before beginning the installation.
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • • • • •
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Turn off all power supplying equipment before working on or inside the equipment. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
NOTICE • • • •
This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure.
DIMENSIONS
1. Using the threaded nipple connect the relay to the desired enclosure through a knock out hole. 2. Secure with the conduit nut provided.
Relay #1
3. Connect Coil: • Choose the coil common lead (white with yellow stripe) and connect it to the (-) source termination point. • Choose either the low voltage (10-30VAC/DC, white with blue stripe) or high voltage (208-277VAC, white with brown stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.* NOTE: When connecting the control side of this device (#18 wires) to power line circuits, provide current limiting at 7 amps max. 4. Connect Relay Contacts: • Choose the relay common wire (yellow) and connect to switched load.
Relay #2
5. Connect Coil: • Choose the coil common lead (white with violet stripe) and connect it to the (-) source termination point. • Choose either the low voltage (10-30VAC/DC, grey with white stripe) or high voltage (208-277VAC, white with orange stripe) lead, depending on the application requirements, and connect it to the (+) source termination point.* NOTE: When connecting the control side of this device (#18 wires) to power line circuits, provide current limiting at 7 amps max.
4.0" (103 mm)
3.8" (97 mm)
2.0" (52 mm)
2.3" (59 mm)
2.5" (64 mm)
6. Connect Relay Contacts: • Choose the relay common wire (violet) and connect to switched load. • Choose the relay N.O. (brown) and/or* N.C. (grey) lead and connect to switched load. 7. Secure the enclosure and reconnect power.
3/4" NPT Nipple
Z203400-0B
PAGE 1
* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e. wire nut.
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 /
[email protected]
02122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
V200D TM
WIRING COLOR CODES CONTROL SYSTEM INPUT White
Relay 1
CONTACT OUTPUT
n ow br
n ow br
HI wht/brown
WIRING EXAMPLE
208-277VAC
White
To Load
CON TAC TS
N.C.
e blu
e blu
LOW wht/blue
Nipple mount directly to a panel
YELLOW
10-30VAC/DC
Common COIL To Controls
White
ORANGE
w llo ye
w llo ye
COMM wht/yellow
N.O.
Common
CONTROL SYSTEM INPUT White
CONTACT OUTPUT
ge an or
ge an or
HI wht/orange
Relay 2
Nipple mount to any 2x or 4x electrical box
GREY
208-277VAC
To Load
CONTACTS
COIL
N.C.
VIOLET
ite
ite
Grey
wh
wh
LOW grey/wht
White
To Controls
BROWN
let vio
let vio
COMM wht/violet
Wire Nut
Common
10-30VAC/DC
Common
N.O.
CONTACT AND COIL SPECIFICATIONS
LED CONFIGURATION Relay 2 Relay 1
10V.......................................... 12V.......................................... 24V.......................................... 30V.......................................... 208V........................................ 277V........................................
AC DC 8 9 154 AC DC 2 3 36 Coil Current AC DC 25mA 14mA 25mA 14mA 31mA 16mA 39mA 18mA 19mA 25mA -
RELAY 1
Pull in Voltage 10-30V..................................... 208-277V................................. Drop Out Voltage 10-30V..................................... 208-277V................................. Voltage
RELAY 2
TYPICAL COIL PERFORMANCE
CONTACT RATINGS Resistive.............. 10A@277VAC, 28VDC Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C. 240VAC, 1/3HP N.O. & 1/6HP N.C. 277VAC, 1/4HP N.O. & 1/8HP N.C. Pilot Duty............. 277VAC, (1.7A), 480VA N.O. Ballast.................. 277VAC, 1.7A Tungsten............... 120VAC, TV3 N.O. TV2 N.C. Gold Flash............. Yes
Z203400-0B
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 /
[email protected]
02122