Preview only show first 10 pages with watermark. For full document please download

Ventilated Floor Grid Fam 3000 Pv - 48 Vdc

   EMBED


Share

Transcript

VENTILATED FLOOR GRID FAM 3000 PV - 48 VDC Fig. 1 - Typical application of FAM 3000 PV Warm air Warm air Plenum Warm air (optional) Warm air CDZ Rack A Rack B FAM 3000PV Cold air Rack A: User cooled directly by CDZ Rack B: Users located in areas unfavourable because of obstructions Fig. 2 - Layout of Mobile Room - Air Circuit Example: application of n° 5 Unit FAM 3000PV, installed under the raised floor. N.B. Quantity and position of Grilles and FAM must be defined in the design phase, as a function of required air flow. By-Pass RACK “n” RACK 4 FAM FAM RACK 3 RACK 2 RACK 1 Fig. 3a - Layout of FAM electrical connections with Potentiometer Example: application of n° 5 Unit FAM 3000PV, installed under the raised floor. N.B. Quantity and position of Grilles and FAM must be defined in the design phase, as a function of required air flow. CDZ: Air Conditioning Unit Warm air corridor Minimum 250 mm RACK “n ” RACK 4 RACK 3 RACK 2 RACK 1 RACK 6 RACK 5 CDZ: Air Conditioning Unit CDZ: Air Conditioning Unit RACK 7 RACK 6 RACK 5 Warm air corridor RACK 3 RACK 2 RACK 1 CDZ: Air Conditioning Unit RACK 4 RACK 8 RACK 7 Potentiometer on board of FAM to adjust manually the Fan speed Fig. 4 - Different grilles application for FAM 3000 PV (Interconnections with modulating signal 0 - 10 VDC to regulate the fan speed) RACK “n ” 48 VDC Optional Applications Fig. 3a - Layout of FAM electrical connections with Microprocessor Connection QE-FAM with shielded cables 2 x 1,5 mm² /each FAM FAM 48 VDC RACK “n ” By-Pass = Grilles (optional) with air flow regulation, to adapt the flow of CDZ with actual demand of Racks. Optional Application FAM 48 VDC CDZ: Air Conditioning Unit RACK 8 RACK “n” By-Pass FAM CDZ: Air Conditioning Unit By-Pass Potentiometers: N° 1/each FAM Cold air corridor FAM CDZ: Air Conditioning Unit Warm air Warm air Warm air Plenum (optional) FAM 3000PV 48 VDC FAM 3000PV 48 VDC RACK “n ” RACK 8 48 VDC RACK 7 RACK 6 RACK 5 ST QE Optional applications SC CDZ: Air Conditioning Unit FAM 3000PV 48VDC QE = Electrical panel with Microprocessor ST Temperature Probe/s (Position and quantities to be fixed) SC = Customer Supervisor CDZ 1 2 Rack B Rack B Rack B (see Fig.1) (see Fig.1) (see Fig.1) FAM 3000PV FAM 3000PV Installation and connections The module is placed always under a raised floor in a horizontal position. The air, supplied by the air conditioner (Fig. 1 and 4) after being treated, is conveyed under floor and, by the FAM, to the Users (Racks) Description of FAM 3000 PV The module is made by a structure of sheet steel, oven painted that includes: a) Axial fan, directly coupled to a variable speed motor (0-10 VDC) to obtain heads and flow rates suitable for the application in place. It is equipped with internal thermal protection, with automatic reset, that intervenes in case of malfunctions of ventilator. b) Air supply through grilles placed above the safety net fixed to the FAN. c) Air intake, through perforated protective plate located under the FAN. TECHNICAL CHARACTERISTICS OF FAM 3000 PV - 48 VDC Characteristics Unit of measure Value Nominal Air flow (at 21 °C, density = 1.2 kg/m³) m3 / h 3000 Available head pressure at nominal air flow Pa 100 Fan speed at nominal air flow Axial Fan rpm N° Electric Supply (VAC +/- 10%) (EN 60204 - 1) VDC Max Operative Power input (at 3000 mc/h - 190 Pa) W Control of: Speed / Head pressure / Air flow Max Electric absorption FLA (at 3000 mc/h - 190 Pa) Weight (without grilles) Limits of use: Temp. (with protection IP 44) 1830 1 48 VDC 36 - 57 A 1,9 kg min. - max.°C 80 18,5 -25 °C /+60 °C Electrical Diagram FAM 3000PV / 48-VDC + earth @J?AI JGEFR @JSC D_l +. ) £ ] £ £ £ £ { EQ8 qugraf `pc_icp /.? OPTIONAL Electrical diagram FAM 3000 - 48 VDC Cjcarpga_j qsnnjw 26 TBA ) c_prf A_`jc 1v/*3 kk¼ Jclerf ; 3 k &msp qsnnjw' Fan speed Regulator FAN 48VDC RED YELLOW WHITE (not used) LIGHT BLUE trimmer Power provided by the user. It is recommended to protect the FAM with adequate breaker Note: The speed regulator is protected by an eernal fuse STOP MAX Manual Speed regulator FAN SPEED REGULATOR Connection V+ / VVoltage Connection IN / VMinimum (*) Regulation Voltage (*) Output impedance STOP function (*) NOTE Voltage value are referred to no load present to IN / V- Fan speed regulator At the potentiometric command for adjusting voltage is slaved a switch which stops the power. With a trimmer you can adjust the minimum value the speed or power. The trimmer is accessible from the outside, with screwdriver. V+/V- 36÷52 VDC VMIN IN/VRIN 0÷5 VDC VMIN÷10 VDC 5 kOhm max Opened