Transcript
VENTILATED FLOOR GRID FAM 3000 PV - 48 VDC
Fig. 1 - Typical application of FAM 3000 PV Warm air
Warm air
Plenum
Warm air
(optional)
Warm air
CDZ Rack A
Rack B
FAM 3000PV
Cold air
Rack A: User cooled directly by CDZ
Rack B: Users located in areas unfavourable because of obstructions
Fig. 2 - Layout of Mobile Room - Air Circuit Example: application of n° 5 Unit FAM 3000PV, installed under the raised floor. N.B. Quantity and position of Grilles and FAM must be defined in the design phase, as a function of required air flow.
By-Pass RACK “n”
RACK 4
FAM
FAM
RACK 3
RACK 2
RACK 1
Fig. 3a - Layout of FAM electrical connections with Potentiometer Example: application of n° 5 Unit FAM 3000PV, installed under the raised floor. N.B. Quantity and position of Grilles and FAM must be defined in the design phase, as a function of required air flow.
CDZ: Air Conditioning Unit
Warm air corridor
Minimum 250 mm
RACK “n ”
RACK 4
RACK 3
RACK 2
RACK 1
RACK 6
RACK 5
CDZ: Air Conditioning Unit
CDZ: Air Conditioning Unit
RACK 7
RACK 6
RACK 5
Warm air corridor
RACK 3
RACK 2
RACK 1
CDZ: Air Conditioning Unit
RACK 4
RACK 8
RACK 7
Potentiometer on board of FAM to adjust manually the Fan speed
Fig. 4 - Different grilles application for FAM 3000 PV
(Interconnections with modulating signal 0 - 10 VDC to regulate the fan speed)
RACK “n ”
48 VDC
Optional Applications
Fig. 3a - Layout of FAM electrical connections with Microprocessor
Connection QE-FAM with shielded cables 2 x 1,5 mm² /each FAM
FAM
48 VDC
RACK “n ”
By-Pass = Grilles (optional) with air flow regulation, to adapt the flow of CDZ with actual demand of Racks.
Optional Application
FAM
48 VDC
CDZ: Air Conditioning Unit
RACK 8
RACK “n” By-Pass
FAM
CDZ: Air Conditioning Unit
By-Pass
Potentiometers: N° 1/each FAM
Cold air corridor
FAM
CDZ: Air Conditioning Unit Warm air Warm air Warm air
Plenum (optional)
FAM 3000PV
48 VDC
FAM 3000PV
48 VDC
RACK “n ”
RACK 8
48 VDC
RACK 7
RACK 6
RACK 5
ST
QE
Optional applications
SC
CDZ: Air Conditioning Unit
FAM 3000PV
48VDC
QE = Electrical panel with Microprocessor
ST
Temperature Probe/s (Position and quantities to be fixed)
SC = Customer Supervisor
CDZ
1
2
Rack B
Rack B
Rack B
(see Fig.1)
(see Fig.1)
(see Fig.1)
FAM 3000PV
FAM 3000PV
Installation and connections
The module is placed always under a raised floor in a horizontal position. The air, supplied by the air conditioner (Fig. 1 and 4) after being treated, is conveyed under floor and, by the FAM, to the Users (Racks)
Description of FAM 3000 PV
The module is made by a structure of sheet steel, oven painted that includes: a) Axial fan, directly coupled to a variable speed motor (0-10 VDC) to obtain heads and flow rates suitable for the application in place. It is equipped with internal thermal protection, with automatic reset, that intervenes in case of malfunctions of ventilator. b) Air supply through grilles placed above the safety net fixed to the FAN. c) Air intake, through perforated protective plate located under the FAN.
TECHNICAL CHARACTERISTICS OF FAM 3000 PV - 48 VDC Characteristics
Unit of measure
Value
Nominal Air flow (at 21 °C, density = 1.2 kg/m³)
m3 / h
3000
Available head pressure at nominal air flow
Pa
100
Fan speed at nominal air flow Axial Fan
rpm N°
Electric Supply (VAC +/- 10%) (EN 60204 - 1)
VDC
Max Operative Power input (at 3000 mc/h - 190 Pa)
W
Control of: Speed / Head pressure / Air flow
Max Electric absorption FLA (at 3000 mc/h - 190 Pa) Weight (without grilles)
Limits of use: Temp. (with protection IP 44)
1830 1
48
VDC
36 - 57
A
1,9
kg
min. - max.°C
80
18,5
-25 °C /+60 °C
Electrical Diagram FAM 3000PV / 48-VDC + earth @J?AI
JGEFR @JSC
D_l
+.
)
£ ]
£ £ £ £
{
EQ8 qugraf `pc_icp /.?
OPTIONAL Electrical diagram FAM 3000 - 48 VDC
Cjcarpga_j qsnnjw 26 TBA ) c_prf A_`jc 1v/*3 kk¼ Jclerf ; 3 k &msp qsnnjw'
Fan speed Regulator
FAN 48VDC
RED YELLOW WHITE (not used) LIGHT BLUE
trimmer
Power provided by the user. It is recommended to protect the FAM with adequate breaker
Note: The speed regulator is protected by an eernal fuse
STOP
MAX
Manual Speed regulator
FAN SPEED REGULATOR Connection V+ / VVoltage
Connection IN / VMinimum (*) Regulation Voltage (*) Output impedance STOP function
(*) NOTE Voltage value are referred to no load present to IN / V-
Fan speed regulator At the potentiometric command for adjusting voltage is slaved a switch which stops the power. With a trimmer you can adjust the minimum value the speed or power. The trimmer is accessible from the outside, with screwdriver.
V+/V-
36÷52 VDC
VMIN IN/VRIN
0÷5 VDC VMIN÷10 VDC 5 kOhm max Opened