Transcript
H800-900
“Go/no” Current Switches
! On/off status for direct-drive fans, pumps, and process motors ■ More reliable for status than relays across auxiliary contacts ■ Ideal for direct-drive units, unit vents, fan coil units, exhaust fans and other fixed loads
H800 Mini
■ Great for lighting status--less expensive than 277 V relays ■ Low 0.5 A turn-on--ideal for small exhaust fans. (Not intended to detect belts breaking) H900 Split-core
Monitor fans, pumps, motors & electrical loads for proper operation LOW-COST STATUS!
■ Split-core H900 for fast retrofit installation ■ Mini solid-core H800 fits in tight enclosures
D ESCRIPTION
■ 100% solid-state, no moving parts to fail
CURRENT STATUS SWITCHES
➢
The H800/900 Go/no current switches provide a cost effective solution for monitoring status on unit vents, exhaust fans, and other fixed loads where belt loss is not a concern.
■ Made in USA; 5 year limited warranty ■ Non-polarity sensitive output
A PPLICATIONS ■ Monitoring on/off status of electrical loads ■ Monitoring direct drive units, exhaust fans and other fixed loads ■ Verifying lighting run times
Ordering INFORMATION
➢
24
Optional Ordering INFORMATION
MODEL
AMPERAGE RANGE
OUTPUT TYPE
OUTPUT RATING
Solid-Core H800
0.5 - 200 A
N.O., Solid State
0.1A @ 30 VAC/DC
Split-Core H900
1.5 - 200 A
N.O., Solid State
1.0A @ 30 VAC/DC
VERIS INDUSTRIES, INC.
®
800.354.8556
MODEL
DESCRIPTION
H700/900-DIN
DIN Rail Mounting Clip Set
800/Brkt
H800 Mounting Bracket
Hawkeye®
H800/H900
A PPLICATIONS/ W IRING DIAGRAM: Hawkeye® 900 ”Go/no” Status Switches
Status In
Motor Control Center
Automation Control Panel
Unit Vent Heater
Starter
Status N.O. 1.0 A@30VAC/DC
Status In Motor
(Heater status optional)
Hawkeye® 800
➢
1.80" (46 mm)
Mounting Bracket .90" (23 mm)
1.90" (48 mm) 2.90" (74 mm)
2.34" (59 mm)
.75"
Self-gripping Iris 900 VERIS INDUSTRIES
Optional DIN Rail Clip
Portland, Oregon 1-800-354-8556
DIN Rail Clip Side View
2.575" (65 mm)
Status N.O. 0.1 A@30V AC/DC
®
Model 800 Current Switch
2.50" (64 mm)
1.04" (26 mm)
1.5" (38 mm)
.87" (22 mm)
#100477-597
3.20" (81 mm)
S PECIFICATIONS Sensor Power .......................................................................................................................... Induced Isolation .................................................................................................................................. 600 VAC rms Temperature Range ................................................................................................................. -15º to 60º C Humidity Range ...................................................................................................................... 0 - 95% non-condensing Dimensions (H900) ................................................................................................................. (L x W x H) 2.90" x 2.575" x 1.04" Sensor Hole Size (H900) ......................................................................................................... (L x W ) 1.90" x .90” Dimensions (H800). ............................................................................................................................. (L x W x H) 2.34" x 1.80" x .87" Sensor Hole Size (H800) ......................................................................................................... 0.75” diameter
25
VERIS INDUSTRIES, INC.
®
800.354.8556
Hawkeye®
CURRENT STATUS SWITCHES