VICTORIA Series
Powered by
Submittal Data: GWH12QC-D3DNA1D Job Name Purchaser Submitted To Unit Designation
12,000 BTU/H Wall Mounted Heat- Pump System
Location Engineer Reference For Schedule No.
Date Approval
Construction
GENERAL FEATURES -Compact and Quiet Design -High Efficiency - 16 SEER -DC Inverter Technology -Wireless Remote with LCD Display -Low Ambient Cooling -Comfortable Sleep Mode -Intelligent Defrost -5 year Limited Parts Warranty
Indoor Unit Data
System Ratings Fan Motor
Cooling Rated Capacity Capacity Range Power Input (Max) SEER EER Heating at 47° F Rated Capacity Capacity Range Power Input (Max) HSPF COP Heating at 17° F Rated Capacity Capacity (Max) Power Input (Max) COP Operating Range Cooling Heating
12,000 BTU/H 3,100-13,000 BTU/H 1,080 W 22 13.0
(Max) (Min) (Max) (Min)
Power S upply Normal Operational Voltage Voltage Range Main Power Wire Size Interconnecting Cable Wire Size MCA MOCP/Breaker Size
Output Power F LA
20 W 0.2 A
Airflow 171/400 CFM Cooling Wet (Lo/Hi) 171/400 CFM Heating Dry (Lo/Hi) S ound Pres s ure L evel 29/45 db(A) Cooling (Lo/Hi) 13,000 BTU/H 29/45 db(A) Heating (Lo/Hi) 2,400-14,000 BTU/H 1,360 W Dimensions & Weights 33.3 x 11.1 x 8.2-in Unit Dimensions (LxHxD) 10.1 22/27 LBS Weight (Net/Shipping) 11.8 Outdoor Unit Data 7,600 BTU/H Compressor DC Inverter Driven Rotary 11,167 BTU/H Refrigerant Type R410A 1,168 W Fan Motor Output Power 30 W 8.1 F LA 0.2 A Sound Pressure Cooling 54 db(A) 115℉ (48 C) Heating 54 db(A) 0℉ (-18 C) Dimensions & Weights 75℉ (24 C) Unit Dimensions (LxHxD) 33.4 x 23.6 x 12.6-in -4℉ (-20 C) Weight (Net/Shipping) 86/93 LBS R efrigerant Piping Data 3/8-in Gas Pipe Size (OD) 208/230 V, 1 Phase, 60 Hz 1/4-in Liquid Pipe Size (OD) 187 - 253 V Flared Connection Method 14-2 AWG 66-ft M A X R e f r i g e r a n t P i p e L e n g t h 14-4 AWG 10.0 A 10-ft MIN Refrigerant Pipe Length 15 A 33-ft MAX Refrigerant Pipe Height Difference
© C&H Corporation 2015
VICTORIA Series
Powered by
Submittal Data: GWH12QC-D3DNA1D
12,000 BTU/H Wall Mounted Heat- Pump System
EXTENDED RATINGS COOLING PERFORMANCE Outdoor Ambient Temperature (DB)
Indoor Entering Air Temperatures (DB) 50% RH TC
62 F
SHC
TC
67 F
SHC
TC
72 F
SHC
25 F
14,898
11,045
16,102
11,631
17,181
12,381
55 F
13,326
10,288
14,201
10,647
15,221
11,127
35 F 45 F
65 F 75 F 85 F 95 F 105 F 115 F
14,566 13,840 12,869 12,368 11,884 11,267 10,646 10,024
11,026 10,625 9,995 9,651 9,398 9,006 8,644 8,297
15,466 14,800
14,175 13,329 12,737 12,125 11,483 10,663
11,295 10,969
10,736 10,230 9,838 9,650 9,134 8,636
16,250 15,856
15,023 14,314 13,782 13,225 12,448 11,372
11,726 11,477
10,986 10,564 10,334 9,932 9,564 8,879
HEATING PERFORMANCE Outdoor Ambient Temperature (DB) (80% RH) 5F 15 F 25 F 35 F 45 F 55 F 65 F
TC- Total Capacity ( BtuH) SHC- Sensible Capacity (BtuH)
Indoor Entering Air Temperatures (DB) 65 F 70 F 75 F TC SHC TC SHC TC 9,267 9,267 8,706 8,706 8,478 11,656 11,656 11,023 11,023 10,672 11,904 11,904 11,741 11,741 11,533 12,940 12,940 12,705 12,705 12,598 14,266 14,266 14,059 14,059 13,614 14,586 14,586 14,316 14,316 14,199 14,531 14,531 14,447 14,447 14,345
© C&H Corporation 2015
SHC 8,478 10,672 11,533 12,598 13,614 14,199 14,345
VICTORIA Series
Powered by
Submittal Data: GWH12QC-D3DNA1D
12,000 BTU/H Wall Mounted Heat- Pump System
MINIMUM SPACING REQUIREMENTS Units: inch (mm)
Units: inch (mm)
© C&H Corporation 2015
DIMENSIONAL SPECIFICATIONS INDOOR UNIT DIMENSIONS
GWH12QC-D3DNA1D Units: inch (mm) 8.2 (208)
33.3 (846)
Liquid Line Valve Gas Line Valve Drain Connector
OUTDOOR UNIT DIMENSIONS
1/4-in OD Flared 3/8-in OD Flared 5/8-in OD Units: inch (mm)
23.6 (600)
Liquid Line Valve Gas Line Valve
1/4-in OD Flared 3/8-in OD Flared
www.cooperandhunter.us without notice or without incurring obligations. All rights reserved.
© C&H Corporation 2015