Vigilon The Vigilon analogue addressable fire detection and alarm system from Gent offers medium to large sized building owners the latest in system flexibility and control panel aesthetics. LPCB approved to EN 54: Parts 2 & 4, Vigilon 1-4 loop control panels can accommodate up to 200 devices on each loop, including repeat panels, interfaces, call points, sensors and sounders. Up to 31 panels may be connected in a secure network, whilst multi layer networks can be created using a domain bridge architecture. Vigilon’s backlit LCD display presents clear indication of Fire or Fault location and the control panel’s innovative 8 -line x 40 character display with push-button keypad is simple to use. Fire Plans can be tailored to precisely meet site requirements. Vigilon’s software allows network areas to be sectored to evacuate or alert status, or configured with pre-set delays.
Repeat Panel
Fully compatible with Gent’s innovative new S-Quad - a combined Multi-Sensor range with speech, sounder and strobe in one intelligent unit.
Manual Call Point
l
l
l
l
l
Because all Vigilon devices connect onto the same 2-core loop, separate sounder or repeater panel wiring circuits are not required. Selection of sensors to suit each building’s use will reduce false alarms and Vigilon’s comprehensive range includes heat, dual angle optical / heat and CO multi sensors, beam and duct smoke detectors. Optical or heat combined sensor/sounder/ strobe can also be deployed to boost alarm sound levels without costly additional wiring. In the event of a Fire or Fault, Vigilon’s analogue addressable technology will provide an entire historic log of the system’s management information. Vigilon allows full integration with additional outstations such as Supervisor graphics terminals and Vigilon Voice alarm systems. To meet the requirements of BS5839 Part 1: 2002 the Vigilon is supplied with integral zonal indication, visible at access level 1. This comprises of 32 fire LED’s (secret till lit), which enables ‘at a glance’ overview indication, without the need for manual intervention by fire fighters.
T-breaker
Sprinkler
Interface Units
Max Loop Length 1000m
Alarm Sounder
Additional features l
Spur
Door Release or Plant Shutdown S-Quad Sensor Sounder
Beam Transmitter
Beam Receiver
S-Quad Sounder Strobe
Supervisor
Loop 1
Manned Centre Link to Fire Station
Via Node to Trend Building Management Network
Loop 2 Loop 3 Loop 4
Secure 3500 Fibre Network (up to 64 panels) Node
ACU
Secure 3500 Copper Network (up to 31 Panels)
Node
Loop 2 Loop 3 Loop 4
Node
Secure Fibre Optic Loop 2 Loop 3 Domain Loop 4 (Max 200 panels per system)
MIC
Loop 1
S-Quad Sensor
Up to 200 Devices per Loop DAU A4 Mimic Panel
S-Quad Sensor/Speech Strobe
by Honeywell
Vigilon Dimensions (mm)
A
B
C
Control Panel
408
539
151
Battery Box
382
309
112
Repeat Panel
338
403
101
A4 Mimic Display
330
276
73
A4 Mimic Control Panel
483
385
78
A4 Mimic
PANELS Type Max No of Loops Loop Capacity Batteries Battery Standby
Approx Weight
Control Panel
Repeat panel
A4 Mimic
4
N/A
N/A
200
N/A
N/A
4 x 12V @ 12AH
1 x 12V @ 6AH
4 x 12V @ 6AH
24 hours standby +
24 hours standby +
24 hours standby +
30 minutes alarm
30 minutes alarm
30 minutes alarm
upgradeable to 72 hours
upgradeable to 72 hours
updradeable to 72 hours
16.2 Kg
6.2 Kg
Sensors
Display 2.3 Kg Control Panel 10.4 Kg
0°C to 45°C
Operating Temp
Cable Entry
Beam Sensors (pair)
EN54 pt 2+4
Relevant Standard Top and rear knockins
Top or rear knockins
Rear
LPCB approved to EN54: Parts 2&4
Approvals
Repeat panel
Electronic Alarm Sounder
A2 Mimic panel
Manual Call Point by Honeywell Waterside Road E-mail
Hamilton Industrial Park
gent_enquir
[email protected]
Leicester
L E5 1T N
Website
United Kingdom
Te l
+ 4 4 ( 0 ) 11 6 2 4 6 2 0 0 0
w w w.gent.co.uk
Fax
+ 4 4 ( 0 ) 11 6 2 4 6 2 3 0 0 L i t e r a t u r e r e f : G E N 010