Transcript
Installation and operating instructions for contractors
Vitobloc BACnet/IP Gateway CHP unit accessory for VITOBLOC 200 50 to 530 kW el
5671 514-1
01/2015
Imprint
NOTE The Vitobloc 200 CHP unit is not suitable for 60 Hz operation. It is therefore not available for the American and Canadian markets in particular.
Note: This technical guide contains instructions for design engineers regarding the design, use and operating conditions of a CHP unit. For technical details please refer to the individual product catalogue, or for implementation planning, refer to the relevant technical unit description. For assistance with preliminary work during the project planning phase please contact our advisers. Subject to technical modifications. Continuing development may result in minor differences in the illustrations, operating steps and specifications. Updating the documentation Please let us know if you have any suggestions for improving our documentation, or if you have noticed any errors. Manufacturer’s address Viessmann Werke GmbH & Co.KG D-35107 Allendorf Telephone +49 (0)6452 70-0
Fax: +49 (0)6452 70-2780 www.viessmann.de
5671 514-1
Publication date: 01/2015
2
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Table of contents
Table of contents 1.
Safety instructions
................................................................................................................ 4
2.
Function
................................................................................................................ 5
3.
Type
................................................................................................................ 5
4.
Installation
4.1 4.2 4.3 4.4
5.
BACnet / IP
5.1 Data points.......................................................................................11 5.2 Sensor assignment by type of CHP unit .........................................16
6.
Commissioning
...............................................................................................................18
7.
Maintenance
...............................................................................................................18
8.
Disposal
...............................................................................................................18
5671 514-1
Mounting rail installation .................................................................. 6 Power supply ................................................................................... 8 Connecting the floating digital outputs ............................................. 9 Connecting the interfaces................................................................10
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
3
Safety instructions
1
Safety instructions
General
These operating instructions contain general information that must be observed during installation, operation and maintenance. They must therefore be read by the installer and relevant qualified technician(s) prior to installation and commissioning. They must always be available at the system.
Identification of safety instructions
Failure to observe the safety instructions identified with this hazard symbol in these installation and operating instructions may result in risks to personnel. Caution
Failure to observe the safety instructions identified with this symbol may result in risks for the device or the system and its functions.
Note
This symbol indicates information that will simplify work and ensure safe operation.
Personnel qualifications
The personnel designated to operate, maintain, inspect and install this equipment must have the appropriate qualifications for such work. The system operator is responsible for ensuring that this is the case. The safety instructions listed in these operating instructions must be observed, as must all applicable national regulations for accident prevention and any in-house working, operating or safety instructions issued by the operator.
Risks from failure to observe the safety instructions
Failure to observe the safety instructions may result in risks to personnel as well as to the environment and the system. LIABILITY The manufacturer will not accept any liability if these safety instructions are not observed. In particular, failure to observe these instructions may pose the following risks: Failure of important system functions Failure of prescribed methods of service and maintenance Risks to personnel due to electrical and mechanical effects Electrical hazards Hazards arising from electrical current, e.g. as a result of removing safety covers, must be prevented.
Safety instructions for maintenance, inspection and installation work
The operator must ensure that all maintenance, inspection and installation work is carried out by authorised, qualified personnel who have used the operating instructions to acquaint themselves with the device. In principle, work may only be carried out on the device when the CHP unit is in an idle state and isolated from the power supply. Directly after work has been completed, all safety and protective equipment must be replaced and returned to full function.
5671 514-1
Safety instructions for the operator (risk analysis according to EN 12100)
4
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Function
Unauthorised modifications and production of spare parts
Alterations or modifications to the device are only permissible following consultation with the manufacturer. Original spare parts and accessories authorised by the manufacturer are important to ensure safety. Use of other parts can void the liability for any resulting losses.
Impermissible operation
The device may only be used for the specified purpose. Any installation for an unspecified purpose is strictly prohibited.
2
Function
General
The device makes the data from a Vitobloc 200 CHP unit, which is read via the RS-232, available on the BACnet/IP.
On-site connection (building management system)
CHP unit
Fig. 1 Schematic diagram of the device
3
Version The device is a compact unit for installation on a mounting rail. The mounting rail and fittings are included in the standard delivery of the device.
5671 514-1
Standard delivery
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
5
Installation
4
Installation The device is always installed in a de-energised state with the wiring disconnected.
General operating conditions
In order to ensure fault-free operation of the device, the following conditions must be met and maintained: Do not use in locations with aggravated operating conditions, such as
corrosive steam or gas, dust formation or high ionising radiation Permissible ambient temperature during operation 0 °C to +55 °C Any installation position Permissible ambient temperature during storage -25 °C to +85 °C Permissible relative humidity during storage 95 %, without condensation Caution
4.1
An earth terminal is required on the profile rail.
Mounting rail installation After removing the packaging, check the device for any transport damage. Mount the top-hat rail on a clean surface and do not place it under stress.
General
Caution
Drilling swarf, screws and other foreign bodies must be prevented from entering the device.
Install it away from thoroughfares, but ensure there is still easy access. Protect the device from direct insolation. Caution
Installing the mounting rail
Ensure there is adequate heat transfer.
With unit types EM-18/36, EM-20/39, EM-50/81 and EM-70/115, the Vitobloc Gateway must be installed in an external terminal box. With larger CHP units that have ratings of 140 kW el or more, the mounting rail may be installed in the control panel of the CHP unit.
Fig. 3 Gateway in the control panel door of the EM-238/363 CHP unit 5671 514-1
Fig. 2 Gateway on the side panel of the EM-140/207 CHP unit control panel
6
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Installation
Installing the Gateway
Pull the white tabs on the underside of the device downwards until they latch into place Push the device onto the top-hat rail Caution
Do not apply pressure to the display as this risks damaging it
Push the white tabs back into their original positions Once the device has been successfully installed, connect it according to the connection diagram, taking account of the safety instructions Removing the Gateway The Vitobloc Gateway is always removed in a de-energised state with the wiring disconnected.
5671 514-1
Pull the white tabs on the underside of the device downwards until they unlock Pull out the orange tabs on the right-hand side of all the terminals in order to release them from the mounting rail Grip the terminals simultaneously with your thumb and index finger at the top and bottom of the ribbed casing surfaces and pull from the mounting rail
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
7
Installation 4.2
Power supply Before switching on the power supply, ensure that the components are clean and have been mounted in the correct order on the top-hat rail. Order from left to right: CX 9000 KL 2794 KL 9010
Fig. 4 BACnet / IP Gateway Caution
The device requires a voltage of 24 V DC (-15 %/+20 %), connected to an isolated power source protected by a max. 4 A fuse.
Connecting the power supply
Fig. 5 Power supply of the Vitobloc BACnet / IP Gateway
5671 514-1
The 24 V DC power supply for the Gateway is connected via the contacts labelled 24 V and 0 V as well as the + and - contacts. The spring-loaded terminals are designed for wires with a cross-section of between 0.08 and 2.5 mm² (stripped back by 8 to 9 mm).
8
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Installation
4.3
Connecting the floating digital outputs
KL 2794
The KL 2794 has 4 floating digital outputs. Output 1 switches terminals 1 and 2; output 2 terminals 5 and 6; output 3 terminals 3 and 4; and output 4 terminals 7 and 8 to continuity. The 4 outputs can be used freely (e.g. for calling the CHP unit)
Signal-LED1
Signal-LED2
Signal-LED3
Signal-LED4
Output 1
Output 2
Output 1 Power contact + 24 V
Output 2
Output 3 Power contact 0 V
Output 4
Output 3
Output 4
Plan view
Contact allocation
5671 514-1
Fig. 6 KL 2794
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
9
Installation 4.4
Connecting the interfaces
RS232 interface
The RS232 interface is marked COM1 and is connected with the RS232 interface of the CHP unit via the null modem cable provided.
Connecting cable between CHP unit and Gateway CHP unit Sub-D 9-pole socket
GATEWAY Sub-D 9-pole socket
2: RxD
3: TxD
3: TxD
2: RxD
5: GND
5: GND
Tab. 1 Connecting cable between CHP unit and Gateway Note
Ethernet interface
Cable to RS232 standard.
The CHP unit data is supplied to the BACnet / IP via the Ethernet interface. The device has 2 RJ-45 Ethernet ports, designated X001 and X002. The two ports behave like a switch. Thus the Ethernet cable can be routed further to an additional device. A commercially available Ethernet cable can be used to make the connection (4x2 Category 5 twisted pair copper cable – max. cable length 100 m). The following IP settings are factory-set: IP address: 192.168.4.78 Subnet mask: 255.255.255.0 To change the IP settings, the "cerhost" program is required; this can be downloaded from the Beckhoff website. Link to the latest version: ftp://ftp.beckhoff.com/Software/embPCControl/CE/Solutions/RemoteDisplay/CeRemDispHost.zip
5671 514-1
This is a remote desktop software program which enables the installed Windows Ce user interface to be operated. The network settings in Windows Ce are performed in exactly the same way as in Windows XP.
10
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
BACnet / IP
5
BACnet / IP The Gateway makes all data points of the CHP unit's RS232 interface available on the BACnet / IP. Four floating digital outputs for switching purposes (e.g. for calling the CHP unit) are also provided.
5.1
Data points
Designation
BACnet type
Content / remark
Mode
Multistate input
1: OFF 2: manual 3: auto
Status
Multistate input
1: OFF 2: ready 3: start 4. operation 5: fault
Operating mode
Multistate input
1: OFF 2: manual 3: mains substitute 4: --5: selection 100 % 6: set value 0-100 %
Set_value_modulating_operation
Analogue input Multistate input
Fault Hours run
Analogue input
Minutes run
Analogue input
Starts
Analogue input
Maintenance interval
Analogue input
Unit lockout
Analogue input
Advance warning time
Analogue input
The first fault reported during a malfunction until all faults have been acknowledged again.
Analogue input
Indicates when the next service is due, expressed in hours run. (Next_service - hours run = number of hours run until next service)
NiCrNi_A
Analogue input
*1
NiCrNi_B
Analogue input
*1
NiCrNi_C
Analogue input
*1
NiCrNi_D
Analogue input
*1
5671 514-1
Next_service
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
11
BACnet / IP
Designation
BACnet type
Content / remark
PT100_1
Analogue input
*1
PT100_2
Analogue input
*1
PT100_3
Analogue input
*1
PT100_4
Analogue input
*1
PT100_5
Analogue input
*1
PT100_6
Analogue input
*1
Battery voltage
Analogue input
Oil pressure
Analogue input
Lambda probe voltage
Analogue input
Speed
Analogue input
Temperature_controller
Analogue input
Temperature_enabling
Analogue input
Mains_voltage_L1
Analogue input
Mains_voltage_L2
Analogue input
Mains_voltage_L3
Analogue input
Gen._voltage_L1
Analogue input
Gen._voltage_L2
Analogue input
Gen._voltage_L3
Analogue input
Gen._current_L1
Analogue input
Gen._current_L2
Analogue input
Gen._current_L3
Analogue input
Mains_voltage_total
Analogue input
Generator_voltage_total
Analogue input
Gen._current_total
Analogue input
Output
Analogue input
Mains frequency
Analogue input
Gen._frequency
Analogue input
CosPhi
Analogue input
Communication fault
Binary input
Digital_output1
Binary output
Freely usable floating digital output
Digital_output2
Binary output
Freely usable floating digital output
Digital_output3
Binary output
Freely usable floating digital output
Digital_output4
Binary output
Freely usable floating digital output
5671 514-1
*1 The temperatures for NiCrNi and PT 100 are assigned differently, depending on the unit type. (See chapter "Sensor assignment by type of CHP unit")
Tab. 2 BACnet data point list
12
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
BACnet / IP 5.1.1 Multistate faults
5671 514-1
Value
Designation
1
No fault
2
Emergency stop
3
Min. oil level
4
Min. coolant pressure
5
Min. gas pressure
6
Safety temperature
7
Generator temperature
8
Silencer hood temperature
9
Fan fault
10
Coolant pump fault
11
Max. exhaust gas back pressure
12
Feed-in switch
13
External fault
14
Speed too high
15
Coolant temperature
16
Max. exhaust gas temperature
17
Min. exhaust gas temperature
18
Min. oil pressure
19
Max. gas pressure
20
Heating water pump fault
21
Start-up speed <50 rpm
22
Ignition speed
23
Speed window
24
Speed <1200 rpm
25
Start-up fault
26
Synchronisation fault
27
Speed <50 per pickup
28
Max. oil level
29
Max. temperature Pt100_2
30
Max. temperature Pt100_3
31
Max. output
32
Reverse output
33
Output controller fault
34
Lambda controller fault
35
Generator contactor fault
36
Ignition fault
Comments
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
13
BACnet / IP
14
Designation
Comments
37
Oil pressure fault
38
Lambda start position
39
Knocking ON
40
Knocking OFF
41
Time switch deselection
Disabled
42
Time switch enabling
Disabled
43
Mains fault F <
Disabled
44
Mains fault F >
Disabled
45
Mains fault U+F <>
Disabled
46
Min. knocking output
47
Max. knocking output
48
Mains coupling switch
49
Knocking fault
50
Mains OK
Disabled
51
Mains fault
Disabled
52
Temperature deselection
Disabled
53
Temperature enabling
Disabled
54
Service overdue
55
Safety shutdown
56
Engine not idle
57
Battery undervoltage
58
Generator undervoltage
59
Generator overvoltage
60
Generator overcurrent
61
Generator out-of-balance load
62
Tightness test fault
63
Mains circuit breaker fault
64
Sensor fault
65
Max. exhaust gas temperature A
66
Min. exhaust gas temperature A
67
Max. exhaust gas temperature B
68
Min. exhaust gas temperature B
69
Max. exhaust gas temperature C
70
Min. exhaust gas temperature C
71
Max. exhaust gas temperature D
72
Min. exhaust gas temperature D
73
Exhaust gas temp. differential A/B
CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
5671 514-1
Message
BACnet / IP
Message
Designation
74
Reserve
75
Max. return temp. PT100/2
76
Max. heating water temp. PT100/3
77
Max. engine oil temp.
78
Max. gas mixture temp.
79
Max. coolant mixture temp.
Comments
Tab. 3 Fault messages
5.1.2 EDE files
5671 514-1
The EDE files are available on request.
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
15
BACnet / IP
5.2
Sensor assignment by type of CHP unit
Sensor
EM-18/36 / EM-20/39
EM-50/81
EM-70/115
EM-140/207
NiCrNi / A
Exhaust gas temperature Exhaust gas temperature Exhaust gas temperature Exhaust gas temperature
NiCrNi / B
--------------
--------------
--------------
--------------
NiCrNi / C
--------------
--------------
--------------
--------------
NiCrNi / D
--------------
--------------
--------------
--------------
PT 100 / 1
Coolant
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
Heating water
PT 100 / 4
--------------
--------------
--------------
--------------
PT 100 / 5
--------------
--------------
--------------
--------------
PT 100 / 6
--------------
--------------
--------------
--------------
EM-199/263
EM-199/293
EM-238/363
EM-363/498
Exhaust gas upstream of turbo
Exhaust gas upstream of turbo
Exhaust gas A
Exhaust gas upstream of turbo A
Exhaust gas B
Exhaust gas upstream of turbo B
Tab. 4 Sensor assignment overview
Sensor NiCrNi / A NiCrNi / B
Exhaust gas downstream Exhaust gas downstream of turbo of turbo
NiCrNi / C
Exhaust gas downstream Exhaust gas downstream Exhaust gas downstream of cat. of cat. of cat.
Exhaust gas upstream of cat.
--------------
--------------
--------------
Exhaust gas downstream of cat.
PT 100 / 1
Coolant
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
Heating water
PT 100 / 4
Engine oil temperature
Engine oil temperature
Engine oil temperature
Engine oil temperature
--------------
Gas mixture temperature
--------------
Coolant mixture inlet
PT 100 / 5
PT 100 / 6
Gas mixture temperature Gas mixture temperature
Coolant mixture inlet
Coolant mixture inlet
09/2012
NiCrNi / D
5671 514
Tab. 5 Sensor assignment overview
ESS Energie Systeme & Service GmbH 16
Amendments a CHP unit accessory • Vitobloc BACnet/IP Gateway
BACnet / IP Sensor
EM-401/549
BM-36/66
BM-55/80
NiCrNi / A
Exhaust gas upstream of turbo A
Exhaust gas temperature
Exhaust gas temperature
NiCrNi / B
Exhaust gas upstream of turbo B
--------------
--------------
NiCrNi / C
Exhaust gas upstream of cat.
--------------
--------------
NiCrNi / D
Exhaust gas downstream of cat.
--------------
--------------
PT 100 / 1
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
PT 100 / 4
Engine oil temperature
--------------
--------------
PT 100 / 5
Gas mixture temperature
--------------
--------------
PT 100 / 6
Coolant mixture inlet
--------------
--------------
Tab. 6 Sensor assignment overview
Sensor
BM-190/238
BM-366/437
NiCrNi / A
Exhaust gas upstream of turbo
Exhaust gas upstream of turbo A
NiCrNi / B
Exhaust gas downstream of turbo
Exhaust gas upstream of turbo B
NiCrNi / C
--------------
Exhaust gas downstream of turbo
NiCrNi / D
--------------
--------------
PT 100 / 1
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
PT 100 / 4
Engine oil temperature
Engine oil temperature
PT 100 / 5
Gas mixture temperature
Gas mixture temperature
PT 100 / 6
Coolant mixture inlet
Coolant mixture inlet
5671 514-1
Tab. 7 Sensor assignment overview
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
17
Commissioning
6
Commissioning The device is commissioned as part of the general commissioning of the CHP plant or, in the case of retrofitting, by the CHP unit manufacturer's technical service personnel.
7
Maintenance This accessory is maintenance-free.
8
Disposal
5671 514
09/2012
This product and its components must be disposed of in an environmentally responsible manner. Use public or private waste disposal companies.
ESS Energie Systeme & Service GmbH 18
Amendments a CHP unit accessory • Vitobloc BACnet/IP Gateway
5671 514-1
Notes
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway
19
Subject to technical modifications.
Viessmann Werke GmbH & Co KG D-35107 Allendorf Telephone +49 (0)6452 70-0
Fax: +49 (0)6452 70-2780 www.viessmann.de
5671 514-1
20
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Tel: +44 1952 675000 Fax: +44 1952 675040 E-mail:
[email protected]
! n e lt a h e b ro v n e g n u r e d n Ä e h c is n h c Te