Project Name: _______________________________________________________ Date: ________________________ Location: ________________________________________________________________________________________ Engineer: ________________________________________________________________________________________ Contractor: __________________________________________________________ Rep: ________________________
1 – GENERAL SPECIFICATIONS Product Features:
Factory Supplied Items
VM110P SA240-S43932 Stainless Steel Heat Exchanger ASME “H” stamped boiler, designed and constructed in compliance with the ASME Boiler and Pressure Vessel Code Section IV Maximum operating pressure 30 psi [206.8 kPa] Modulating burner, 6.5 turndown ratio Direct Spark Ignition Built-in Tank Sensor Wall (standard) or floor mounting (w/ opt. kit, NTI part # 84624) Zero clearance to combustibles 110 MBH [110,000 BTU] Field conversion from Natural Gas (factory) to Propane Optional Sidewall vent kits Vents with PVC/CPVC/PP/SS Built-in diverter valve Built-in 3 speed circulator Built-in 16 gallon indirect water heater 120VAC outlet for condensate pump On/Off switch
Vertical Firetube Boiler
Indirect Tank
10K thermistor outdoor sensor 150PSI [1034 kPa] ASME Temperature/Pressure Relief Valve 30PSI [206.8 kPa] ASME Relief Valve 60PSI [413.7 kPa] Pressure Gauge Low-loss Header Condensate Trap Control Features Integral microprocessor safety control Domestic Hot Water Priority Outdoor Reset Warm weather shut down Freeze protection Cascade up to 16 VM110T series boilers 3 Circulator outputs Outdoor reset temperature boost Service reminder Adjustable pump post purge Run time accumulation Night setback option Lockout and error history
Circulator Low-loss Header
NY Thermal Inc.
NY Thermal Inc. 30 Stonegate Drive, Saint John, NB E2H 0A4 Canada 2014-07-14 Rev. 0
Technical Service: 1-800-688-2575 Fax: 1-506-432-1135 Web: http:// www.nythermal.com NY Thermal Inc. reserves the right to change these specifications without notice
.
VM110P SUBMITTAL Section 1 – General Specifications Section 2 – Product Dimensions Section 3 – Field Wiring
THE FUTURE OF HOME HEATING NY THERMAL INC.
Model Specifications
Water Conn. Model NPT, in. VM110P
Gas Connection NPT, in.
Vent/Air-Intake Pipe Diameter in.
½ (Male)
2 or 3
1 (Sweat)
Vent/ Air-Inlet Max. Length, Ft. 2 in. Venting
Approx. Wt. w/Water lb.
3 in. Venting
100
150
275
100
Heating Specifications
Model
Input Min BTU/hr
Max BTU/hr
Heating Capacity BTU/hr
AFUE %
VM110P
17,000
110,000
101,000
95
NET I=B=R Rating BTU/hr 88,000
Domestic Hot Water Specifications
1st Hour Rating* (GPH)
Continuous Rating* (GPH)
218
205
Domestic Inlet / Outlet 3/4"
Domestic Capacity (Gal.) 16
*Domestic performance based on average water temperature of 108ºF at mixing valve outlet and 50ºF inlet
Performance Specifications
VM110P Performance 120
0.1 Delta T curve
0.08
100
Head loss curve
80
0.06
60
0.04
40
0.02
20
0
0 2
3
4
5
6
7 8 Flow (USGPM)
9
10
11
Temperature (ºF)
Head Loss (ft.)
0.12
12
* Head loss values calculated for factory supplied Low-Loss Header.
NY Thermal Inc.
NY Thermal Inc. 30 Stonegate Drive, Saint John, NB E2H 0A4 Canada 2014-07-14 Rev. 0
Technical Service: 1-800-688-2575 Fax: 1-506-432-1135 Web: http:// www.nythermal.com NY Thermal Inc. reserves the right to change these specifications without notice
.
VM110P SUBMITTAL Section 1 – General Specifications Section 2 – Product Dimensions Section 3 – Field Wiring
THE FUTURE OF HOME HEATING NY THERMAL INC.
2 – PRODUCT DIMENSIONS [IN.] TOP VIEW
BOTTOM VIEW
FRONT VIEW
RIGHT VIEW
RECOMMENDED CLEARANCES [IN.] Front 36
Top 24
Sides 12
Back 0
Bottom 24
NY Thermal Inc.
NY Thermal Inc. 30 Stonegate Drive, Saint John, NB E2H 0A4 Canada 2014-07-14 Rev. 0
Technical Service: 1-800-688-2575 Fax: 1-506-432-1135 Web: http:// www.nythermal.com NY Thermal Inc. reserves the right to change these specifications without notice
Flue Pipe 1
.
VM110P SUBMITTAL Section 1 – General Specifications Section 2 – Product Dimensions Section 3 – Field Wiring
THE FUTURE OF HOME HEATING NY THERMAL INC.
3 -- FIELD WIRING
EXT. LIMIT 120V
DHW PUMP
CH PUMP
BOILER PUMP
SYSTEM SENSOR
CASCADE 2-16 BOILERS / BMS INTERFACE MODULE
9
1
ARGUS LINK -
EXT. LIM
10
2
ARGUS LINK +
DHW PUMP | PUMPE DHW
11
3
COMMON
CH PUMP | PUMPE CH
12
4
SYSTEM | SYSTEME
BOILER PUMP | PUMPE PRIMAIRE
13
5
OUTDOOR | EXTERIEUR
L2 NEUTRAL | NEUTRLE L2
14
6
DHW | ECD AQUASTAT
L2 NEUTRAL | NEUTRLE L2
15
7
THERMOSTAT
L1 120VAC
16
8
THERMOSTAT
GROUND
OUTDOOR DHW DEMAND SENSOR SWITCH/SENSOR
THERMOSTAT / ZONE END SWITCH
SERVICE SWITCH [FIELD SUPPLIED] 120V/1P/60HZ 15A FUSED POWER SUPPLY
NY Thermal Inc.
NY Thermal Inc. 30 Stonegate Drive, Saint John, NB E2H 0A4 Canada 2014-07-14 Rev. 0
Technical Service: 1-800-688-2575 Fax: 1-506-432-1135 Web: http:// www.nythermal.com NY Thermal Inc. reserves the right to change these specifications without notice
.
SENSOR | SONDE
EXT. LIM