Transcript
WISE-7152 8-channel Isolated Source Type Open Collector Output and 8-channel Isolated Digital Input PoE Module
WISE-7152
Introdu ction WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development. WISE-7152 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7152 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc. This module WISE-7152 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 8-channel isolated open collector outputs and 8-channel isolated wet contact digital inputs. Each output channel supports 650mA current driving +10 ~ 40 VDC and each digital input channel supports counter input.
Features
Built-in Web Server for IF-THEN-ELSE rule setting Built-in IF-THEN-ELSE rule enigne for logic operation No more programming. Just click and get done! Support IO, Counter, Timer, Email operations Modbus/TCP Protocol for SCADA Software Seamless Integration IEEE 802.3af-compliant Power over Ethernet (PoE) 10/100 Base-TX Ethernet 2-way Isolation/ESD Protection DO Type: 8 Isolation Open Collector (Sink Type) DI Type: 8 Isolation Wet Contact (Sink/Source)
H a r d w ar e S p e c i f i c a t i o n s Digital Input Input Channels Input Type On Voltage Level Off Voltage Level Input Impedance Max. Count Counters Max. Input Frequency Min. Pulse Width Overvoltage Protection Digital Output Output Channels Output Type Max Load Current Output Voltage Overvoltage Protection Overload Protection Short Circuit Protection
8 Wet Contact (Sink, Source) +10 VDC ~ +50 VDC +4 VDC Max 10 kΩ 65535 (16 bits) 50 Hz 10 ms +70 VDC 8 Open Collector (Source) 650 mA/channel at 25 °C +10 VDC ~ +40 VDC 47 VDC Yes
System CPU SRAM Flash Memory EEPROM Watchdog Communication PoE Ethernet Port 2 Way Isolation I/O EMS Protection ESD (IEC 61000-4-2) EFT (IEC 61000-4-4) LED Indicators PoE L1 L2 L3 Power Requirements Reserve Polarity Protection Powered from terminal block Powered from PoE Consumption Mechanical Dimensions (W x H x D) Installation Environment Operating Temperature Storage Temperature Humidity
16-bit CPU 512 KB 512 KB 16 KB Yes 10 / 100 Base-TX (With Link, Activity LED Indicator) and Automatic MDI/MDI-X 3750 Vrms 4 kV Contact for each terminal +/-2 kV for Power PoE On System Running Ethernet Link/Act Ethernet 10/100M Speed Yes Yes, 12 ~ 48 VDC Yes, IEEE 802.3af, Class1 4.3 W 72 mm x 123 mm x 35 mm DIN-Rail or Wall mounting -25 ~ +75 °C -30 ~ +80 °C 10 ~ 90% RH, non-condensing
Software Specifications Functions Rule Configuration Website 36 IF-THEN-ELSE Logic Rules 48 Internal Registers 12 Timers 12 Emails 12 CGI Commands 12 Recipes 8 P2P remote modules Modbus/TCP Protocol
IF Conditions DI Channel Internal Register DI Counter DO Counter Timer P2P Rule Status THEN / ELSE Actions DO Channel Internal Register DI Counter DO Counter Timer Email CGI Commands Recipe P2P
Access Web server on WISE controllers to edit and upload logic rules through web browser. 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions Hold temporary variables and read/write data via Modbus/TCP address. Delay / Timing functions. Send Email messages to pre-set Email receivers. Send pre-set CGI commands. Set up THEN/ELSE action groups. Set up the connection information for the remote WISE modules. Real time control and monitoring I/O channels and system status of controllers via SCADA software. ON, OFF, ON to OFF, OFF to ON, Change =, >, <, >=, <=(value) =, >, <, >=, <=(value), Change Timeout, Not Timeout DI, AI, DI counter, DO counter, IR Enable, Disable ON, OFF, Pulse Output Change the value Reset Start, Stop Send Execute DO(On/Off), AO, IR