AIR CONDITIONERS
XC15
DAVE LENNOX SIGNATURE® COLLECTION R−410A − SilentComfortt Technology ENGINEERING DATA
Bulletin No. 210456 January 2007 Supersedes June 2006
SEER − up to 17.0 2 to 5 Tons Cooling Capacity − 22,000 to 56,000 Btuh MODEL NUMBER IDENTIFICATION
X C 15 − 036 − 230 − 2 Refrigerant Type X = R−410A Unit Type C = Air Conditioner Series
Minor Revision Number Voltage 230 = 208/230V−1ph−60hz Nominal Cooling Capacity 024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons
FEATURES CONTENTS ARI Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 9 − 23 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 2 − 4 Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 Indoor Coil / Air Handler Substitution . . . . . . . . . . . Page 8 Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . Page 7 Model Number Identification . . . . . . . . . . . . . . . . . . Page 1 Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Equipment Warranty Compressor − limited warranty for ten years in residential installations and five years in non-residential installations. All other covered components − ten years in residential installations and one year in non-residential installations. Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details. ApplicationS SEER up to 17.0. 2 through 5 ton. Single phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Matching add−on furnace indoor coils or air handlers provide a wide range of cooling capacities and applications. See ARI Ratings tables. See Indoor Coils and Air Handlers tab sections for data. Units shipped completely factory assembled, piped, and wired. Each unit is test operated at the factory insuring proper operation. Installer must set air conditioner, connect refrigerant lines, and make electrical connections to complete job. Approvals Certified in accordance with USE certification program which is based on ARI Standard 210/240. Tested in the Lennox Research Laboratory environmental test room. Rated according to U.S. Department of Energy (DOE) test procedures. Condensing units and components within bonded for grounding to meet safety standards for servicing required by UL and CEC. Units are UL and ULC listed. ISO 9001 Registered Manufacturing Quality System. ENERGY STAR® certified units are designed to use less energy, help save money on utility bills, and help protect the environment. Many Lennox home comfort systems meet ENERGY STAR requirements when used with matching components. For expanded ratings, see www.lennoxdavenet.com.
XC15 − 2 to 5 Ton Air Conditioner / Page 2
J
B
I
C HG
L E F
D
K
REFRIGERATION SYSTEM Refrigerant Non−chlorine, ozone friendly, R−410A. Unit pre−charged with refrigerant. See Specification table. Condenser Fan with SilentComfortt Technology B Specially−designed, SilentComfort fan guard uses Passive Vortex Suppression to reduce air noise. Corrosion−resistant PVC (polyvinyl chloride) coated steel wire. Specially designed fan blades reduce operating sound levels. Direct drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity. Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. Fan motor is inherently protected. Motor totally enclosed for maximum protection from weather, dust and corrosion. Fan service access accomplished by removal of fan guard. Copper Tube/Enhanced Fin Coil C Lennox designed and fabricated coil. Ripple−edged aluminum fins. Copper tube construction. Lanced fins provide maximum exposure of fin surface to air stream resulting in excellent heat transfer. Fin collars grip tubing for maximum contact area. Flared shoulder tubing connections/silver soldering construction. Coil is factory tested under high pressure to insure leakproof construction. Entire coil is accessible for cleaning.
FEATURES REFRIGERATION SYSTEM (CONTINUED) D High Pressure Switch Shuts off unit if abnormal operating conditions cause the discharge pressure to rise above setting. Protects compressor from excessive condensing pressure. Manual reset. Low Pressure Switch E Shuts off unit if suction pressure falls below setting. Provides loss of charge and freeze-up protection. Automatic reset. Hi-Capacity Liquid Line Drier F Factory installed in the liquid line, the drier traps moisture or dirt that could contaminate the refrigerant system. 100% molecular−sieve bead type drier.
COMPRESSOR
G Scroll Compressor
OPTIONS
Expansion Valve Kits Must be ordered extra and field installed on certain evaporator units. See ARI Ratings tables. Chatleff style fitting. Freezestat Installs on or near the discharge line of the evaporator or on the suction line. Senses suction line temperature and cycles the compressor off when suction line temperature falls below it’s setpoint. Opens at 29°F and closes at 58°F. Refrigerant Line Kits Refrigerant lines (suction & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized, and sealed at factory. Suction line fully insulated. L15 lines are stubbed at both ends. See Specifications table for selection. Not available for −060 model and must be field fabricated.
H
Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. During compression, one scroll remains stationary while the other scroll orbits around it. Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. Compressor is installed in the unit on resilient rubber mounts for vibration free operation. Factory installed crankcase heater. Crankcase Heater Crankcase heater prevents migration of liquid refrigerant into compressor and ensures proper compressor lubrication. Compressor Sound Cover A Lennox−exclusive, sand−filled, polypropylene copolymer, compressor cover dramatically reduces compressor sound levels.
XC15 − 2 to 5 Ton Air Conditioner / Page 3
FEATURES CONTROLS
I Lennox System Operations Monitor
Provides detailed information for proper preventive maintenance and fast, easy servicing. Displays the most common fault conditions through indicator LED’s: Monitor detects both mechanical and electrical system problems. Monitors only and does not provide safety protection. When an abnormal condition is detected, communicates the specific condition through the ALERT and TRIP lights. POWER LED (green) − indicates voltage within the range of 19−28VAC is present at the power connection. ALERT LED (yellow) − communicates an abnormal system condition through a unique flash code. The ALERT LED will flash a number of times consecutively, pause and then repeat the process. The number of consecutive flashes, defined as the Flash Code, correlates to a particular abnormal condition. The codes can indicate one of the following: long run time, system pressure trip (discharge or suction pressure out−of−limits or compressor overloaded), short cycling, locked rotor, open circuit, open start circuit (current present only in run circuit), open run circuit (current present only in start circuit), welded contactor (compressor runs continuously), or low voltage (control circuit < 17VAC). TRIP LED (red) − indicates there is a demand signal from the thermostat but no current to the compressor is detected by the monitor.
OPTIONS
Compressor Hard Start Kit Single−phase units are equipped with a PSC compressor motor. This type of motor normally does not need a potential relay and start capacitor. In conditions such as low voltage, kit may be required to increase the compressor starting torque. Compressor Time−Off Control Kit prevents compressor short−cycling and allows time for suction and discharge pressure to equalize. Permits compressor start−up in an unloaded condition. Automatic reset with 5 minute delay between compressor shut−off and start−up. Indoor Blower Off Delay Relay Delays the indoor blower−off time during the cooling cycle. See ARI Rating Tables for usage. Low Ambient Kit Air conditioners will operate satisfactorily down to 45_F outdoor air temperature without any additional controls. Kit can be added in the field enabling unit to operate properly down to 30_F. A freezestat should be installed on compressors equipped with a low ambient kit. A compressor lock−out thermostat should be added to terminate compressor operation below recommended operation conditions (on/off operation, 30°F or modulating operation, 0°F). Thermostat Thermostat not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book. XC15 − 2 to 5 Ton Air Conditioner / Page 4
J Cabinet
K
Heavy−gauge steel construction Pre−painted cabinet finish. Painted base section. Control box is conveniently located with all controls factory wired. Large removable panel provides service access. Drainage holes are provided in base section for moisture removal. High density polyethylene unit support feet raise the unit off of the mounting surface, away from damaging moisture. SmartHinget Louvered Coil Protection Steel louvered panels provides complete coil protection. Panels are hinged to allow easy cleaning and servicing of coils. Panels may be completely removed. Interlocking tabs and slots assure tight fit on cabinet.
Refrigerant Line Connections, Electrical Inlets and Service Valves Suction and liquid lines are located on corner of unit cabinet and are made with sweat connections. See dimension drawing. L Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Suction valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. Suction and liquid line service valves and gauge ports are located inside the cabinet. Refrigerant line connections and field wiring inlets are located in one central area of the cabinet. See dimension drawing.
SPECIFICATIONS Model No. XC15−024
XC15−030
XC15−036
XC15−042
XC15−048
XC15−060
2
2.5
3
3.5
4
5
Liquid line (o.d.) − in.
3/8
3/8
3/8
3/8
3/8
3/8
Suction line (o.d.) − in.
3/4
3/4
3/4
7/8
7/8
1−1/8
General D t Data
Nominal Tonnage
Connections (sweat)
1 R−410A
Refrigerant Outdoor Coil
charge furnished 8 lbs. 10 oz. 8 lbs. 10 oz.
9 lbs. 2 oz.
9 lbs. 13 oz. 12 lbs. 2 oz. 13 lbs. 0 oz.
Net face area − sq. ft. Outer coil
20.73
20.73
20.73
20.73
27.21
27.21
Inner coil
20.08
20.08
20.08
20.08
26.36
26.36
Tube diameter − in.
5/16
5/16
5/16
5/16
5/16
5/16
Outdoor Fan
No. of rows
2
2
2
2
2
2
Fins per inch
22
22
22
22
22
22
Diameter − in.
26
26
26
26
26
26
No. of blades
3
3
3
3
3
3
Motor hp
1/15
1/15
1/12
1/12
1/5
1/5
Cfm
2100
2100
2300
2300
3910
3910
Rpm
825
825
825
825
825
825
Watts
100
100
112
112
212
212
273
274
276
299
346
351
208/230V− 1ph
208/230V− 1ph
208/230V− 1ph
208/230V− 1ph
208/230V− 1ph
208/230V− 1ph
30
30
35
40
50
60
Shipping Data − lbs. 1 pkg. ELECTRICAL DATA Line voltage data − 60hz 2 Maximum
overcurrent protection (amps) 3 Minimum
circuit ampacity
17.4
18.1
21.5
23.1
28.4
34.1
Rated load amps
13.5
14.1
16.7
17.9
21.8
26.4
Locked rotor amps
58.3
73.0
79.0
112.0
117.0
134.0
Power factor
0.97
0.97
0.98
0.93
0.96
0.98
Full load amps
0.5
0.5
0.65
0.65
1.1
1.1
Locked rotor amps
0.8
0.8
1.1
1.1
2.1
2.1
Compressor
Outdoor Fan Motor
OPTIONAL ACCESSORIES − must be ordered extra Compressor Hard Start Kit
88M91
S
S
S
S
S
S
Compressor Low Ambient Cut−Off
45F08
S
S
S
S
S
S
Compressor Time−Off Control
47J27
S
S
S
S
S
S
Freezestat
3/8 in. tubing
93G35
S
S
S
S
S
S
5/8 in. tubing
50A93
S
S
S
S
S
S
34M72
S
S
S
S
S
S
L15−41−20 L15−41−30
L15−41−40 L15−41−50
S
S
S
L15−65−30
L15−65−40 L15−65−50
S
S
Low Ambient Kit Refrigerant Line Sets
S
Field Fabricate Indoor Blower Off Delay Relay
58M81
S
S
S
S
S
S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage. 1 Refrigerant charge sufficient for 15 ft. length of refrigerant lines. 2 HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
XC15 − 2 to 5 Ton Air Conditioner / Page 5
DIMENSIONS INCHES (mm)
COIL DRAIN OUTLETS (Around perimeter of base) UNIT SUPPORT FEET
13−1/2 (343)
10−1/2 (267)
18 (457)
11 (279) TOP VIEW
TOP VIEW BASE SECTION
39−1/2 (1003) AIR
SUCTION LINE INLET LIQUID LINE INLET
37 (940) (−024, −030, −036, −042) 47 (1194) (−048, −060)
DISCHARGE
35−1/2 (902) ELECTRICAL INLETS
4−1/2 (114)
18−1/2 (470)
8 (203) 1 (25) SIDE VIEW
XC15 − 2 to 5 Ton Air Conditioner / Page 6
ACCESS VIEW
INSTALLATION CLEARANCES
NOTES:
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ See NOTES
One of these three sides must be 36 in. (914 mm). One of the two remaining sides may be 12 in. (305 mm). The remaining side may be 6 in. (152 mm).
Service See NOTES
See NOTES
Service Clearance − 30 in. (762 mm) 48 in. (1219 mm)clearance required on top of unit 24 in. (610 mm) required between two units
See NOTES
FIELD WIRING DISCONNECT SWITCH (By Others)
DISCONNECT SWITCH (By Others)
THERMOSTAT (Optional)
D
B
A
A Two Wire Power (not furnished) B Two Power (not furnished) See Electrical Data
C
LENNOX AIR CONDITIONER
C Four Wire Low Voltage (not furnished) 18 ga. minimum LENNOX HEATING UNIT OR AIR HANDLER
D Six Wire Low Voltage (not furnished) 18 ga. minimum All wiring must conform to NEC or CEC and local electrical codes.
OUTDOOR SOUND DATA 1 Unit U it
Model No. No XC15−024 XC15−030 XC15−036 XC15−042 XC15−048 XC15−060
125 39.0 39.0 57.5 58.0 59.5 60.0
Octave Band Sound Power Levels dBA, re 10−12 Watts Center Frequency − HZ 250 500 1000 2000 4000 46.5 54.5 57.0 57.5 52.5 46.5 54.5 57.5 58.0 49.5 58.0 62.0 61.5 59.0 53.5 59.0 62.0 59.5 58.0 53.0 61.0 65.0 63.0 60.0 5530 62.0 64.5 63.5 60.5 56.0
1Sound S d
8000 44.5 51.0 49.0 46.0 48.0 49.5
Rating R ti Number (dB) 64 65 68 68 70 70
NOTE − the octave sound power data does not include tonal correction. 1 Tested according to ARI Standard 270-95 test conditions.
XC15 − 2 to 5 Ton Air Conditioner / Page 7
ARI RATINGS − INDOOR COIL / AIR HANDLER SUBSTITUTION Substituting Coils in the ARI Tables Most R−22 and R−410A indoor coils and air handlers are the same except for the factory installed expansion device. C33 coils can be used in place of the CX34 coils, CB26UH, CB27UH, CB30M and CB31MV air handlers can be used in place of the CBX26UH, CBX27UH, CBX32M and CBX32MV, respectively.
The expansion device is based on the size of the outdoor unit. The factory installed RFC or TXV on the C33/CB26UH/CB27UH/CB30M/CB31MV must be replaced to correspond to the outdoor unit. The correct TXV’s are: 1.5−2.5 ton air conditioners 37L51 3−3.5 ton air conditioners 39L72 4−5 ton air conditioners 91M02 Example: A four−ton air conditioner is being installed. The ARI table shows that CBX32MV−048 is a matching air handler. A CB31MV−51 with a 91M02 TXV can be used in its place.
UP−FLOW COILS
AIR HANDLERS
R−410A CX34−18/24A−6F CX34−18/24B−6F CX34−18/24C−6F CX34−19A−6F CX34−25A−6F CX34−25B−6F CX34−30A−6F CX34−30B−6F CX34−30C−6F CX34−31A−6F CX34−31B−6F CX34−36A−6F CX34−36B−6F CX34−36C−6F CX34−38A−6F CX34−38B−6F CX34−42B−6F CX34−43B−6F CX34−43C−6F no equivalent CX34−44/48B−6F CX34−44/48C−6F CX34−49C−6F CX34−50/60C−6F CX34−60D−6F CX34−62C−6F CX34−62D−6F
R−22 = = = = = = = = = = = = = = = = = = =
C33−24A−2 C33−24B−2 C33−24C−2 C33−19A−2 C33−25A−2 C33−25B−2 C33−30A−2 C33−30B−2 C33−30C−2 C33−31A−2 C33−31B−2 C33−36A−2 C33−36B−2 C33−36C−2 C33−38A−2 C33−38B−2 C33−42B−2 C33−43B−2 C33−43C−2
= = = = = = =
C33−44C−2 C33−48B−2 C33−48C−2 C33−49C−2 C33−50/60C−2 C33−60D−2 C33−62C−2 C33−62D−2
XC15 − 2 to 5 Ton Air Conditioner / Page 8
R−410A CBX26UH−018 CBX26UH−024 CBX26UH−030 CBX26UH−036 CBX26UH−042 CBX26UH−048 CBX26UH−060 CBX27UH−018/024 CBX27UH−030 CBX27UH−036 CBX27UH−042 CBX27UH−048 CBX27UH−060 CBX32M−018/024 CBX32M−030 CBX32M−036 CBX32M−042 CBX32M−048 CBX32M−060 CBX32MV−018/024 CBX32MV−024/030 CBX32MV−036 CBX32MV−048 CBX32MV−060 CBX32MV−068
R−22 CB26UH−018 CB26UH−024 CB26UH−030 CB26UH−036 CB26UH−042 CB26UH−048 CB26UH−060 CB27UH−018/024 CB27UH−030 CB27UH−036 CB27UH−042 CB27UH−048 CB27UH−060 CB30M−21/26 CB30M−31 CB30M−41 CB30M−46 CB30M−51 CB30M−65 no equivalent no equivalent = CB31MV−41 = CB31MV−51 = CB31MV−65 no equivalent
= = = = = = = = = = = = = = = = = = =
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−024
2 TON
Up-Flow Indoor Coils 22,800 22,800 23,200
Up−Flow Coils 14.00 14.00 14.20
11.50 11.50 11.70
1985
3 CX34−18/24A/B−6F
Factory TXV
1985
3 CX34−30A/B−6F
Factory TXV
1985
3 CX34−19A−6F
Factory TXV Factory TXV
23,400
14.20
11.70
2000
3 CX34−36A/B−6F
23,600
14.50
12.00
1965
3 CX34−25A/B−6F
Factory TXV
23,800
14.70
12.00
1985
3 CX34−31A/B−6F
Factory TXV
12.20
1985
3 CX34−38A/B−6F
Factory TXV
12.50
1840
24,200
14.70
Up-Flow Indoor Coils + Furnace 23,000 23,200
15.00 15.00
12.20
1900
Up−Flow Coils
+ Furnace
5 CX34−18/24A−6F
4 G60UHV−36A−070
Factory TXV
CX34−18/24B−6F
4 G61MPV−36B−045
Factory TXV Factory TXV
23,200
15.20
12.50
1855
CX34−18/24B−6F
4 G61MPV−36B−070
23,200
15.20
12.50
1855
CX34−30A−6F
4 G60UHV−36A−070
Factory TXV
23,200
15.20
12.50
1855
CX34−30B−6F
4 G61MPV−36B−045
Factory TXV
CX34−30B−6F
4 G61MPV−36B−070
Factory TXV
CX34−18/24B−6F
4 G60UHV−36B−090
Factory TXV Factory TXV
23,200 23,200
15.20 15.50
12.50 12.70
1855 1825
23,400
15.50
12.70
1845
CX34−30B−6F
4 G60UHV−36B−090
23,600
15.50
12.70
1860
CX34−19A−6F
4 G60UHV−36A−070
Factory TXV
CX34−36B−6F
4 G61MPV−36B−045
Factory TXV
CX34−25A−6F
4 G60UHV−36A−070
Factory TXV Factory TXV
24,000 24,000
15.70 15.70
12.70 13.00
1890 1845
24,000
15.70
13.00
1845
CX34−36B−6F
4 G61MPV−36B−070
24,000
15.70
13.20
1820
CX34−36A−6F
4 G60UHV−36A−070
Factory TXV
24,000
16.00
13.20
1820
CX34−36B−6F
4 G60UHV−36B−090
Factory TXV
CX34−25B−6F
4 G61MPV−36B−045
Factory TXV
CX34−25B−6F
4 G61MPV−36B−070
Factory TXV Factory TXV
24,200 24,200
15.70 15.70
13.00 13.00
1860 1860
24,200
16.20
13.20
1835
CX34−25B−6F
4 G60UHV−36B−090
24,400
16.00
13.00
1875
CX34−31A−6F
4 G60UHV−36A−070
Factory TXV
CX34−31B−6F
4 G61MPV−36B−045
Factory TXV
CX34−31B−6F
4 G61MPV−36B−070
Factory TXV Factory TXV
24,400 24,400
16.00 16.00
13.00 13.20
1875 1850
24,400
16.50
13.50
1805
CX34−31B−6F
4 G60UHV−36B−090
24,600
16.00
13.20
1865
CX34−38B−6F
4 G61MPV−36B−045
Factory TXV
24,600
16.00
13.20
1865
CX34−38B−6F
4 G61MPV−36B−070
Factory TXV
CX34−38A−6F
4 G60UHV−36A−070
Factory TXV
CX34−38B−6F
4 G60UHV−36B−090
Factory TXV
24,600 24,600
16.20 16.50
13.20 13.50
1865 1820
Down-Flow Indoor Coils
Down−Flow Coils
23,200
14.20
11.70
1985
3 CR33−24A−F
2 37L51
23,400
14.50
12.00
1950
3 CR33−48B−F
2 37L51
23,800
14.50
12.00
1985
3 CR33−30/36A/B−F
2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 9
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−024 Down-Flow Indoor Coils + Furnace 23,400 14.70 12.20 23,800 15.20 12.50 24,200 15.70 13.00 24,200 15.70 13.00 24,400 15.70 13.00 Horizontal Indoor Coils 22,000 13.50 11.20 22,400 13.70 11.50 23,000 14.00 11.70 23,000 14.20 11.70 23,200 14.20 11.70 23,400 14.20 12.00 23,400 14.50 12.00 23,600 14.50 12.00 24,000 14.70 12.00 Horizontal Indoor Coils + Furnace 22,600 14.70 12.20 22,600 14.70 12.20 22,600 14.70 12.20 22,600 15.20 12.50 22,800 15.00 12.50 22,800 15.00 12.50 22,800 15.20 12.50 22,800 15.50 12.70 23,400 15.20 12.50 23,600 15.50 12.70 23,600 15.50 12.70 23,600 15.70 12.70 23,600 15.70 13.00 23,800 16.00 13.20 24,000 15.50 13.00 24,000 15.70 13.00 24,000 15.70 13.00 24,000 15.70 13.00 24,000 15.70 13.00 24,000 15.70 13.00 24,000 16.00 13.20 24,000 16.20 13.20 24,200 15.70 13.00 24,600 16.00 13.00 24,600 16.00 13.20 24,600 16.00 13.20 24,600 16.00 13.20 24,800 16.50 13.50
2 TON 1920 1905 1860 1860 1875 1965 1950 1965 1965 1985 1950 1950 1965 2000 1850 1850 1850 1810 1825 1825 1825 1795 1870 1860 1860 1860 1815 1805 1845 1845 1845 1845 1845 1845 1820 1820 1860 1890 1865 1865 1865 1835
Down−Flow Coils CR33−18A−F CR33−24A−F CR33−30/36B−F CR33−30/36B−F CR33−30/36A−F Horizontal Coils 3 CH23−21 3 CH23−31 3 CH33−24/30A−2F 3 CH33−19A−2F 3 CH23−41 3 CH33−36A/B−2F 3 CH33−25B−2F 3 CH33−25A−2F 3 CH33−31A/B−2F Horizontal Coils CH23−21 CH23−21 CH23−21 CH23−21 CH23−31 CH23−31 CH23−31 CH23−31 CH33−24/30A−2F CH23−41 CH33−19A−2F CH23−41 CH23−41 CH23−41 CH33−36B−2F CH33−25B−2F CH33−25B−2F CH33−25B−2F CH33−36A−2F CH33−36B−2F CH33−36B−2F CH33−25B−2F CH33−25A−2F CH33−31A−2F CH33−31B−2F CH33−31B−2F CH33−31B−2F CH33−31B−2F
+ Furnace 4 G60DFV−36A−070 4 G60DFV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60DFV−36A−070
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
+ Furnace 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G60UHV−36A−070 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−071 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−071 4 G60UHV−36B−090
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 10
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−024
2 TON
Air Handlers
Air Handlers
23,400
14.50
12.00
1950
3 CB30U−21/26
2 37L51
23,400
14.50
12.00
1950
3 CBX32M−018/024
23,800
15.50
12.70
1875
4 CBX32MV−018/024
24,000
15.00
12.50
1920
3 CB30U−41/46
(Up−Flow)
2 37L51
24,000
15.00
12.50
1920
3 CBX32M−036
(Multi−Position)
Factory TXV
24,000
15.20
12.70
1890
3 CBX32M−030
(Multi−Position)
Factory TXV
24,000
15.50
12.70
1890
3 CB30U−31
24,200
16.20
13.50
1795
4 CBX32MV−024/030
24,400
16.70
13.70
1780
4 CBX27UH−024
(Up−Flow / Horizontal)
Factory TXV
24,600
17.00
14.00
1755
4 CBX27UH−030
(Up−Flow / Horizontal)
Factory TXV
24,800
16.50
13.50
1835
4 CBX32MV−036
(Multi−Position)
Factory TXV
(Up−Flow) (Multi−Position) (Multi−Position)
Factory TXV Factory TXV
2 37L51
(Up−Flow) (Multi−Position)
Factory TXV
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular match−up.
XC15 − 2 to 5 Ton Air Conditioner / Page 11
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−030 Up-Flow Indoor Coils 28,400 29,200 29,200 29,400 29,800 30,000 30,200 30,400
2.5 TON 11.20 11.70 11.70 11.70 11.70 12.00 12.00 12.00
2535 2495 2495 2515 2545 2500 2515 2535
Up−Flow Coils 3 CX34−30A/B−6F 3 CX34−42B−6F 3 CX34−36A−6F 3 CX34−25A/B−6F 3 CX34−31A/B−6F 3 CX34−44/48B−6F 3 CX34−38A−6F 3 CX34−43B−6F
Up-Flow Indoor Coils + Furnace 28,800 14.00 28,800 14.20 28,800 14.20 28,800 14.50 29,400 15.20 29,600 14.70 29,600 14.70 29,800 14.50 29,800 14.50 29,800 14.70 29,800 14.70 29,800 14.70 29,800 15.20 29,800 15.20 30,000 15.20 30,200 15.00 30,200 15.20 30,400 15.00 30,400 15.00 30,400 15.00 30,400 15.50 30,400 15.50 30,600 15.00 30,600 15.20 30,600 15.20 30,600 15.70 30,800 15.00 30,800 15.20 30,800 15.70
11.70 12.00 12.00 12.20 12.70 12.50 12.50 12.20 12.20 12.20 12.50 12.50 12.70 12.70 12.70 12.50 12.70 12.50 12.50 12.70 13.00 13.00 12.50 12.70 12.70 13.00 12.70 12.70 13.00
2460 2400 2400 2360 2315 2370 2370 2445 2445 2445 2385 2385 2345 2345 2360 2415 2380 2430 2430 2395 2340 2340 2450 2410 2410 2355 2425 2425 2370
Up−Flow Coils CX34−30B−6F CX34−30A−6F CX34−30B−6F CX34−30B−6F 5 CX34−36A−6F CX34−36B−6F CX34−42B−6F CX34−36B−6F CX34−42B−6F CX34−25B−6F CX34−25A−6F CX34−25B−6F CX34−36B−6F CX34−42B−6F CX34−25B−6F CX34−31B−6F CX34−31A−6F CX34−31B−6F CX34−44/48B−6F CX34−44/48B−6F CX34−31B−6F CX34−44/48B−6F CX34−38B−6F CX34−38B−6F CX34−38A−6F CX34−38B−6F CX34−43B−6F CX34−43B−6F CX34−43B−6F
Down-Flow Indoor Coils 29,200 14.00 29,600 14.00
11.70 11.70
2495 2530
Down−Flow Coils 3 CR33−48B−F 3 CR33−30/36A/B−F
13.50 13.70 13.70 13.70 14.00 14.00 14.20 14.20
Factory TXV 2 37L51 Factory TXV Factory TXV Factory TXV 2 37L51 Factory TXV 2 37L51 + Furnace 4 G61MPV−36B−045 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G61MPV−36B−070 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36A−070 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090
Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV 2 37L51 Factory TXV 2 37L51 Factory TXV Factory TXV Factory TXV Factory TXV 2 37L51 Factory TXV Factory TXV Factory TXV Factory TXV 2 37L51 2 37L51 Factory TXV 2 37L51 Factory TXV Factory TXV Factory TXV Factory TXV 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular match−up.
XC15 − 2 to 5 Ton Air Conditioner / Page 12
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−030 Down-Flow Indoor Coils + Furnace 29,600 15.00 12.50 29,800 14.70 12.20 29,800 15.20 12.70 30,000 14.70 12.20 30,000 14.70 12.50 30,000 14.70 12.50 30,200 15.20 12.70 Horizontal Indoor Coils 27,400 13.00 11.00 27,800 13.20 11.00 29,000 13.70 11.50 29,200 13.70 11.70 29,200 13.70 11.70 29,400 13.70 11.70 29,600 14.00 11.70 29,800 14.00 11.70 30,000 14.00 11.70 30,200 14.20 12.00 30,400 14.20 12.00 30,800 14.20 12.00 Horizontal Indoor Coils + Furnace 27,800 14.00 11.70 27,800 14.00 11.70 28,000 13.70 11.50 28,000 14.20 12.00 28,200 14.20 12.00 28,400 14.00 11.70 28,400 14.20 12.00 28,400 14.70 12.20 28,800 14.20 12.00 29,400 14.50 12.20 29,400 14.70 12.50 29,400 14.70 12.50 29,600 14.50 12.20 29,600 14.70 12.50 29,600 15.20 12.70 29,600 15.20 12.70 29,800 14.50 12.20 29,800 14.70 12.50 29,800 14.70 12.50 29,800 14.70 12.50 30,000 14.50 12.20 30,000 15.00 12.70 30,000 15.00 12.50 30,000 15.20 12.70
2.5 TON 2370 2445 2345 2460 2400 2400 2380 2490 2525 2520 2495 2495 2515 2530 2545 2565 2515 2535 2565 2375 2375 2435 2335 2350 2425 2365 2330 2400 2410 2350 2350 2425 2370 2330 2330 2445 2385 2385 2385 2460 2360 2400 2360
Down−Flow Coils CR33−48B−F CR33−48B−F CR33−48B−F CR33−36B−F CR33−36A−F CR33−36B−F CR33−36B−F Horizontal Coils 3 CH23−21 3 CH23−31 3 CH23−41 3 CH33−25B−2F 3 CH33−36A/B−2F 3 CH33−25A−2F 3 CH23−51 3 CH33−42B−2F 3 CH33−31B−2F 3 CH33−44/48B−2F 3 CH33−43−2F 3 CH33−43B−2F Horizontal Coils CH23−21 CH23−21 CH23−21 CH23−21 CH23−31 CH23−31 CH23−31 CH23−31 CH33−24/30A−2F CH33−36A−2F CH23−41 CH23−41 CH23−41 CH33−36B−2F CH23−41 CH33−36B CH33−36B−2F CH33−25A−2F CH33−25B−2F CH33−25B−2F CH33−25B−2F CH23−51 CH23−51 CH33−25B−2F
+ Furnace 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G60DFV−36B−090 4 G61MPV−36B−045 4 G60DFV−36A−070 4 G61MPV−36B−070 4 G60DFV−36B−090
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
+ Furnace 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36A−070 4 G60UHV−36A−070 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G61MPV−36B−071 4 G61MPV−36B−045 4 G60UHV−36A−070 4 G61MPV−36B−070 4 G60UHV−36B−090
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular match−up.
XC15 − 2 to 5 Ton Air Conditioner / Page 13
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Indoor Unit Model No.
Total Unit Watts
E i Expansion Device
XC15−030
2.5 TON
Horizontal Indoor Coils + Furnace (Continued) 30,200
15.00
12.50
2415
Horizontal Coils
+ Furnace
CH23−51
4 G61MPV−36B−045
2 37L51 2 37L51
30,200
15.50
13.00
2325
CH23−51
4 G60UHV−36B−090
30,400
15.00
12.50
2430
CH33−31A−2F
4 G60UHV−36A−070
2 37L51
30,400
15.00
12.50
2430
CH33−31B−2F
4 G61MPV−36B−071
2 37L51
30,400
15.00
12.50
2430
CH33−31B−2F
4 G61MPV−36B−070
2 37L51
30,600
15.00
12.50
2450
CH33−31B.−2F
4 G61MPV−36B−045
2 37L51 2 37L51
30,600
15.50
13.00
2355
CH33−31B−2F
4 G60UHV−36B−090
30,800
15.50
13.00
2370
CH33−43C−2F
4 G61MPV−36C−090
2 37L51
31,000
15.20
12.70
2440
CH33−43B−2F
4 G61MPV−36B−070
2 37L51
31,000
15.20
12.70
2440
CH33−43B−2F
4 G61MPV−36B−071
2 37L51
CH33−43B−2F
4 G60UHV−36B−090
2 37L51
31,200
15.50
13.00
2400
14.50
12.20
2445
3 CB30U−41/46
Air Handlers 29,800
Air Handlers
29,800
14.70
12.20
2445
3 CB30U−31
29,800
14.70
12.20
2445
3 CBX32M−030
(Up−Flow)
(Up−Flow) (Multi−Position)
2 37L51 2 37L51
Factory TXV
30,000
14.50
12.20
2460
3 CB30U−51
30,000
14.50
12.20
2460
3 CBX32M−036
(Multi−Position)
Factory TXV
(Multi−Position)
2 37L51
(Up−Flow)
30,000
14.50
12.20
2460
3 CBX32M−042
30,000
15.20
12.70
2360
4 CBX32MV−024/030
(Multi−Position)
2 37L51
Factory TXV
30,400
14.70
12.20
2490
3 CBX32M−048
30,400
15.70
13.00
2340
4 CBX27UH−030
(Up−Flow / Horizontal)
Factory TXV
30,400
15.70
13.00
2340
4 CBX32MV−036
(Multi−Position)
Factory TXV
2305
4 CBX27UH−036
(Up−Flow / Horizontal)
2 37L51
30,400
15.70
13.20
(Multi−Position)
2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular match−up.
XC15 − 2 to 5 Ton Air Conditioner / Page 14
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−036 Up-Flow Indoor Coils 33,600 13.70 11.20 33,600 13.70 11.20 34,800 14.00 11.70 34,800 14.00 11.70 35,200 14.20 11.70 35,200 14.20 11.70 35,400 14.20 11.70 Up-Flow Indoor Coils + Furnace 33,800 14.20 11.70 33,800 14.20 11.70 34,000 14.00 11.50 34,000 14.00 11.50 34,000 14.00 11.70 34,000 14.50 12.00 34,200 14.50 12.00 34,200 14.50 12.00 34,400 14.50 12.00 35,000 14.50 12.00 35,200 14.20 12.00 35,200 15.20 12.70 35,400 14.50 12.00 35,400 14.50 12.00 35,400 14.70 12.20 35,400 15.00 12.50 35,400 15.00 12.50 35,600 14.50 12.00 35,600 14.70 12.20 35,800 15.20 12.70 36,000 15.20 12.70 36,000 15.20 12.50 36,200 15.20 12.70 36,600 15.50 12.70 37,000 15.70 13.00 Down-Flow Indoor Coils 33,600 13.50 11.20 34,200 13.70 11.50 Down-Flow Indoor Coils + Furnace 33,800 14.00 11.50 33,800 14.20 11.70 34,000 14.70 12.20 34,400 14.00 11.50 34,400 14.20 11.70 34,600 14.70 12.20
3 TON 3000 3000 2975 2975 3010 3010 3025 2890 2890 2955 2955 2905 2835 2850 2850 2865 2915 2935 2770 2950 2950 2900 2830 2830 2965 2920 2820 2835 2880 2850 2880 2845 3000 2975 2940 2890 2785 2990 2940 2835
Up−Flow Coils 3 CX34−36A/B−6F 3 CX34−42B−6F 3 C33−44C 3 CX34−44/48B/C−6F 3 CX34−38A/B−6F 3 CX34−50/60C−6F 3 CX34−43B/C−6F Up−Flow Coils + Furnace 4 G61MPV−36B−070 CX34−36B−6F 4 G61MPV−36B−070 CX34−42B−6F 4 G61MPV−36B−045 CX34−36B−6F 4 G61MPV−36B−045 CX34−42B−6F 4 G60UHV−36A−070 CX34−36A−6F 4 G61MPV−36C−090 CX34−36C−6F 4 G60UHV−36B−090 CX34−36B−6F 4 G60UHV−36B−090 CX34−42B−6F 4 G61MPV−60C−090 CX34−36C−6F 4 G61MPV−36B−070 CX34−44/48B−6F 4 G61MPV−36B−045 CX34−44/48B−6F 5 CX34−38B−6F 4 G60UHV−36B−090 4 G60UHV−36A−070 CX34−38A−6F 4 G61MPV−36B−045 CX34−38B−6F 4 G61MPV−36B−070 CX34−38B−6F 4 G60UHV−36B−090 CX34−44/48B−6F 4 G61MPV−60C−090 CX34−44/48C−6F 4 G61MPV−36B−045 CX34−43B−6F 4 G61MPV−36B−070 CX34−43B−6F 4 G61MPV−36C−090 CX34−43C−6F 4 G60UHV−36B−090 CX34−43B−6F 4 G61MPV−60C−090 CX34−50/60C−6F 4 G61MPV−60C−090 CX34−43C−6F 4 G61MPV−60C−090 CX34−49C−6F 4 G61MPV−60C−090 CX34−62C−6F Down−Flow Coils 3 CR33−48B/C−F 3 CR33−30/36B/C−F Down−Flow Coils + Furnace 4 G61MPV−36B−045 CR33−48B−F 4 G61MPV−36B−070 CR33−48B−F 4 G60DFV−36B−090 CR33−48B−F 4 G61MPV−36B−045 CR33−30/36B−F 4 G61MPV−36B−070 CR33−30/36B−F 4 G60DFV−36B−090 CR33−30/36B−F
Factory TXV 2 37L51 2 37L51 2 37L51 Factory TXV 2 37L51 2 37L51 Factory TXV 2 37L51 Factory TXV 2 37L51 Factory TXV Factory TXV Factory TXV 2 37L51 Factory TXV 2 37L51 2 37L51 Factory TXV Factory TXV Factory TXV Factory TXV 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 15
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−036
3 TON
Horizontal Indoor Coils 33,400 13.50 33,600 13.50 34,200 13.70 34,200 13.70 34,600 14.00 35,200 14.20 35,200 14.20 35,600 14.20 35,800 14.20 36,000 14.20
11.20 11.20 11.50 11.50 11.50 11.70 11.70 11.70 12.00 11.70
2980 3000 2975 2975 3010 3010 3010 3045 2985 3075
Horizontal Coils 3 CH23−41 3 CH33−36B−2F 3 CH23−51 3 CH33−36C−2F 3 CH33−42B−2F 3 CH33−44/48B−2F 3 CH33−48C−2F 3 CH33−43C−2F 3 CH33−50/60C−2F 3 CH33−43B−2F
Horizontal Indoor Coils + Furnace 33,600 13.70 33,600 14.00 33,800 14.00 33,800 14.20 33,800 14.50 34,000 14.50 34,400 14.20 34,400 14.20 34,600 14.70 34,800 14.20 34,800 14.50 35,200 14.70 35,400 14.50 35,600 14.50 35,600 15.00 35,800 15.20 36,200 14.50 36,200 14.70 36,200 14.70 36,600 15.20
11.50 11.70 11.50 11.70 12.00 12.00 11.70 12.00 12.20 11.70 12.00 12.20 12.20 12.00 12.50 12.50 12.00 12.20 12.20 12.70
2920 2870 2940 2890 2815 2835 2940 2865 2835 2975 2900 2885 2900 2965 2850 2865 3015 2965 2965 2880
Horizontal Coils CH23−41 CH23−41 CH33−36B−2F CH33−36B−2F CH23−41 CH33−36B−2F CH23−51 CH23−51 CH23−51 CH33−42B−2F CH33−42B−2F CH33−42B−2F CH33−44/48B−2F CH33−44/48B−2F CH33−44/48B−2F CH33−43C−2F CH33−43B−2F CH33−43B−2F CH33−43B−2F CH33−43B−2F
Air Handlers 34,000 34,200 34,600 34,600 34,600 34,800 35,000 35,000 35,200 35,600 36,000 36,000
12.00 11.70 12.00 12.00 12.20 12.20 12.50 12.70 12.20 12.20 13.00 13.00
2835 2925 2885 2885 2835 2850 2800 2755 2885 2920 2770 2770
Air Handlers 3 CB30U−31 (Up−Flow) 3 CBX32M−030 (Multi−Position) 3 CBX32M−036 (Multi−Position) 3 CB30U−41/46 (Up−Flow) 4 CBX32MV−024/030 (Multi−Position) 3 CBX32M−042 (Multi−Position) 4 CBX32MV−036 (Multi−Position) 4 CBX27UH−036 (Up−Flow / Horizontal) 3 CB30U−51 (Up−Flow) 3 CBX32M−048 (Multi−Position) 4 CBX32MV−048 (Multi−Position) 4 CBX27UH−042 (Up−Flow / Horizontal)
14.50 14.20 14.20 14.50 15.00 14.70 15.00 15.20 14.70 14.70 16.00 16.00
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
+ Furnace 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G61MPV−36B−070 4 G61MPV−36B−045 4 G60UHV−36B−090 4 G61MPV−36C−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−071 4 G60UHV−36B−090
2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51 2 37L51
Factory TXV Factory TXV 2 37L51 Factory TXV 2 37L51 Factory TXV Factory TXV 2 37L51 2 37L51 2 37L51 Factory TXV
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay.
XC15 − 2 to 5 Ton Air Conditioner / Page 16
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−042 Up-Flow Indoor Coils 38,500 40,000 40,500 40,500 40,500
3.5 TON 10.60 10.90 11.00 11.00 11.00
3630 3670 3680 3680 3680
Up−Flow Coils 3 CX34−42B−6F 3 CX34−44/48B/C−6F 3 CX34−38A/B−6F 3 CX34−50/60C−6F 3 CX34−43B−6F
Up-Flow Indoor Coils + Furnace 38,500 13.20 40,000 13.00 40,000 13.00 40,000 13.50 40,000 13.50 40,000 13.70 40,000 14.20 40,500 13.00 40,500 13.20 40,500 13.20 40,500 13.20 40,500 13.70 40,500 13.70 40,500 13.70 40,500 14.00 40,500 14.20 41,000 14.00 41,000 14.00 41,000 14.00 41,000 14.00 41,000 14.20 41,000 14.20 41,000 14.20 41,000 14.20 41,000 14.20 42,000 14.70 42,500 14.50
10.90 10.80 10.80 11.00 11.20 11.20 11.50 10.90 10.90 11.00 11.00 11.20 11.20 11.20 11.20 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.50 11.70 11.70 12.00 12.00
3530 3705 3705 3635 3635 3570 3480 3715 3715 3680 3680 3615 3615 3615 3615 3520 3565 3565 3565 3565 3565 3565 3565 3505 3505 3495 3545
Up−Flow Coils CX34−42B−6F CX34−44/48B−6F CX34−44/48B−6F CX34−44/48C−6F CX34−44/48C−6F CX34−44/48B−6F 5 CX34−44/48C−6F CX34−38B−6F CX34−43B−6F CX34−38B−6F CX34−43B−6F CX34−38B−6F CX34−44/48C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−44/48C−6F CX34−43B−6F CX34−43C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−43C−6F CX34−43C−6F CX34−43C−6F CX34−43C−6F CX34−50/60C−6F CX34−62C−6F CX34−62C−6F
Down-Flow Indoor Coils 38,000 13.00 39,500 13.20
10.50 10.80
3620 3655
Down−Flow Coils 3 CR33−48B/C−F 3 CR33−50/60C−F
13.00 13.20 13.20 13.20 13.50
2 39L72
Factory TXV 2 39L72 2 39L72 Factory TXV + Furnace 4 G60UHV−36B−090 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36C−090 4 G61MPV−60C−090 4 G60UHV−36B−090 4 G60UHV−60C−110 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−070 4 G60UHV−36B−090 4 G61MPV−60C−110 4 G61MPV−36C−090 4 G61MPV−60C−090 4 G60UHV−60C−090 4 G60UHV−36B−090 4 G61MPV−36C−090 4 G60UHV−60C−110 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−090 4 G60UHV−60C−090 4 G60UHV−60C−090 4 G60UHV−60C−110
2 39L72
Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV 2 39L72 Factory TXV 2 39L72 Factory TXV 2 39L72 Factory TXV 2 39L72 2 39L72 Factory TXV Factory TXV Factory TXV 2 39L72 2 39L72 Factory TXV Factory TXV Factory TXV Factory TXV 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 17
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−042 Down-Flow Indoor Coils + Furnace 38,000 13.20 10.70 38,000 13.50 10.80 38,500 13.50 11.00 38,500 13.50 11.00 38,500 13.70 11.00 38,500 13.70 11.20 39,500 13.70 11.00 40,000 14.00 11.20 40,000 14.00 11.20 40,000 14.20 11.50 40,000 14.20 11.50 40,000 14.20 11.50 40,000 14.20 11.50 Horizontal Indoor Coils 39,000 13.00 10.80 39,500 13.20 10.80 40,000 13.20 10.90 40,500 13.20 11.00 40,500 13.50 11.00 40,500 13.50 11.00 41,000 13.50 11.00 41,000 13.50 11.00 41,000 13.50 11.00 41,000 13.50 11.00 41,500 13.50 11.00 41,500 13.50 11.20 Horizontal Indoor Coils + Furnace 39,000 13.00 10.70 39,000 13.50 11.00 39,000 13.70 11.00 39,000 13.70 11.00 39,500 13.00 10.60 39,500 13.00 10.70 39,500 13.00 10.70 39,500 13.20 10.80 39,500 13.50 11.00 39,500 13.50 11.00 39,500 13.70 11.20 39,500 13.70 11.20 39,500 13.70 11.20 40,000 13.70 11.20 40,000 13.70 11.20 40,000 13.70 11.20 40,000 14.00 11.20 40,000 14.00 11.20 40,500 13.00 10.90 40,500 13.20 10.90 40,500 13.20 11.00
3.5 TON 3550 3520 3500 3500 3500 3440 3590 3570 3570 3480 3480 3480 3480 3610 3655 3670 3680 3680 3680 3725 3725 3725 3725 3775 3705 3645 3545 3545 3545 3725 3690 3690 3655 3590 3590 3525 3525 3525 3570 3570 3570 3570 3570 3715 3715 3680
Down−Flow Coils CR33−48C−F CR33−48C−F CR33−48B−F CR33−48C−F CR33−48C−F CR33−48C−F CR33−50/60C−F CR33−50/60C−F CR33−50/60C−F CR33−50/60C−F CR33−50/60C−F CR33−60D−F CR33−60D−F Horizontal Coils 3 CH23−51 3 CH23−65 3 CH33−42B−2F 3 CH33−44/48B−2F 3 CH23−68 3 CH33−48C−2F 3 CH33−43C−2F 3 CH33−50/60C−2F 3 CH33−60D−2F 3 CH33−62D−2F 3 CH33−43B−2F 3 CH33−49C−2F Horizontal Coils CH23−51 CH23−51 CH23−51 CH23−51 CH33−42B−2F CH23−65 CH33−42B−2F CH23−65 CH23−51 CH23−65 CH23−51 CH23−51 CH23−65 CH23−65 CH23−65 CH33−42B−2F CH23−65 CH23−65 CH33−44/48B−2F CH23−68 CH33−44/48B−2F
+ Furnace 4 G61MPV−36C−090 4 G61MPV−60C−090 4 G60DFV−36B−090 4 G61MPV−60C−110 4 G60DFV−60C−090 4 G60DFV−60C−110 4 G61MPV−36C−090 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60DFV−60C−090 4 G60DFV−60C−110 4 G60DFV−60D−135 4 G61MPV−60D−135
2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72
+ Furnace 4 G61MPV−36B−070 4 G61MPV−36C−090 4 G60UHV−36B−090 4 G61MPV−60C−110 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−070 4 G61MPV−36B−070 4 G61MPV−60C−090 4 G61MPV−36C−090 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G60UHV−36B−090 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−36B−090 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−36B−045 4 G61MPV−36B−045 4 G61MPV−36B−070
2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay.
XC15 − 2 to 5 Ton Air Conditioner / Page 18
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−042 Horizontal Indoor Coils + Furnace (Continued) 40,500 13.50 11.00 40,500 13.70 11.20 40,500 13.70 11.20 41,000 14.00 11.20 41,000 14.00 11.20 41,000 14.00 11.50 41,000 14.00 11.50 41,000 14.00 11.50 41,000 14.00 11.50 41,000 14.20 11.50 41,000 14.20 11.50 41,500 13.20 10.90 41,500 13.20 11.00 41,500 13.20 11.00 41,500 14.00 11.50 41,500 14.00 11.50 41,500 14.00 11.50 41,500 14.20 11.50 41,500 14.20 11.50 41,500 14.20 11.50 41,500 14.20 11.50 41,500 14.20 11.70 41,500 14.20 11.50 41,500 14.20 11.50 41,500 14.20 11.70 41,500 14.50 11.70 41,500 14.50 11.70 42,000 14.00 11.50 42,000 14.00 11.50 42,000 14.20 11.50 42,000 14.00 11.50 42,000 14.20 11.70 42,000 14.20 11.50 42,000 14.20 11.70 42,000 14.50 11.70 Air Handlers 39,500 13.50 11.00 39,500 13.50 11.00 39,500 13.50 11.00 39,500 13.70 11.00 40,500 13.70 11.20 40,500 14.00 11.20 41,000 14.70 12.00 41,000 14.70 11.70 41,000 14.70 11.70
3.5 TON 3680 3615 3615 3660 3660 3565 3565 3565 3565 3565 3565 3805 3775 3775 3610 3610 3610 3610 3610 3610 3610 3545 3610 3610 3545 3545 3545 3650 3650 3650 3650 3590 3650 3590 3590 3590 3590 3590 3590 3615 3615 3505 3505 3505
Horizontal Coils + Furnace 4 G61MPV−36B−070 CH23−68 4 G60UHV−36B−090 CH33−44/48B−2F 4 G61MPV−36C−090 CH33−48C−2F 4 G61MPV−36C−090 CH23−68 4 G61MPV−60C−090 CH23−68 4 G60UHV−36B−090 CH23−68 4 G60UHV−60C−090 CH33−48C−2F 4 G60UHV−60C−110 CH33−48C−2F 4 G61MPV−60C−110 CH33−48C−2F 4 G60UHV−60C−110 CH23−68 4 G61MPV−60C−110 CH23−68 4 G61MPV−36B−045 CH33−43B−2F 4 G61MPV−36B−070 CH33−43B−2F 4 G61MPV−36B−071 CH33−43B−2F 4 G61MPV−60C−090 CH33−50/60C−2F 4 G61MPV−36C−090 CH33−43C−2F 4 G61MPV−36C−090 CH33−49C−2F 4 G61MPV−60C−090 CH33−43C−2F 4 G61MPV−60C−090 CH33−49C−2F 4 G61MPV−60C−111 CH33−49C−2F 4 G60UHV−60C−090 CH23−68 4 G60UHV−60C−090 CH33−43C−2F 4 G60UHV−60C−090 CH23−68 4 G61MPV−60C−110 CH33−50/60C−2F 4 G60UHV−60C−110 CH33−50/60C−2F 4 G60UHV−60C−090 CH33−49C−2F 4 G60UHV−60C−090 CH33−49C−2F 4 G60UHV−36B−090 CH33−43B−2F 4 G61MPV−60C−091 CH33−43C−2F 4 G60UHV−60C−110 CH33−43C−2F 4 G61MPV−60C−091 CH33−49C−2F 4 G60UHV−60C−090 CH33−50/60C−2F 4 G61MPV−60C−110 CH33−43C−2F 4 G61MPV−60C−110 CH33−49C−2F 4 G60UHV−60C−110 CH33−49C−2F Air Handlers 3 CB30U−41/46 (Up−Flow) 3 CBX32M−036 (Multi−Position) 3 CBX32M−042 (Multi−Position) 4 CBX32MV−036 (Multi−Position) 3 CB30U−51 (Up−Flow) 3 CBX32M−048 (Multi−Position) 4 CBX32MV−048 (Multi−Position) 4 CBX27UH−042 (Up−Flow / Horizontal) 4 CBX27UH−048 (Up−Flow / Horizontal)
2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72 2 39L72
Factory TXV 2 39L72
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay.
XC15 − 2 to 5 Ton Air Conditioner / Page 19
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−048 Up-Flow Indoor Coils 46,500 14.00 11.50 47,000 14.20 11.70 48,000 14.50 11.70 48,500 14.50 12.00 48,500 14.50 12.00 Up-Flow Indoor Coils + Furnace 47,000 14.20 11.70 47,000 14.20 11.70 47,000 14.50 12.00 47,500 14.20 11.70 47,500 14.50 12.00 47,500 14.50 12.00 47,500 14.70 12.00 47,500 15.00 12.20 48,500 14.70 12.20 48,500 14.70 12.20 48,500 15.00 12.20 48,500 15.00 12.50 48,500 15.20 12.50 49,000 15.00 12.50 49,000 15.20 12.70 49,000 15.20 12.50 Down-Flow Indoor Coils 45,500 13.50 11.20 47,000 14.20 11.50 47,000 14.20 11.70 Down-Flow Indoor Coils + Furnace 45,500 13.70 11.20 45,500 13.70 11.20 45,500 14.00 11.50 46,000 14.00 11.50 47,500 14.50 12.00 47,500 14.50 12.00 47,500 14.70 12.00 47,500 14.70 12.20 47,500 15.00 12.20 47,500 15.00 12.20 Horizontal Indoor Coils 46,000 13.70 11.20 47,000 14.00 11.50 47,500 14.20 11.70 47,500 14.20 11.70 48,000 14.50 11.70 48,000 14.50 11.70 48,500 14.50 12.00 48,500 14.50 12.00
4 TON 4045 4015 4105 4040 4040 4015 4015 3915 4060 3960 3960 3960 3895 3975 3975 3975 3880 3880 3920 3860 3920 4065 4085 4015 4065 4065 3955 4000 3960 3960 3960 3895 3895 3895 4105 4085 4060 4060 4105 4105 4040 4040
Up−Flow Coils 3 CX34−44/48C−6F 3 CX34−50/60C−6F 3 CX34−60D−6F 3 CX34−49C−6F 3 CX34−62D−6F Up−Flow Coils CX34−44/48C−6F CX34−44/48C−6F CX34−44/48C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−50/60C−6F 5 CX34−50/60C−6F CX34−49C−6F CX34−49C−6F CX34−49C−6F CX34−60D−6F CX34−60D−6F CX34−49C−6F CX34−62D−6F CX34−62D−6F Down−Flow Coils 3 CR33−48C−F 3 CR33−60D−F 3 CR33−50/60C−F Down−Flow Coils CR33−48C−F CR33−48C−F CR33−48C−F CR33−48C−F CR33−50/60C−F CR33−50/60C−F CR33−50/60C−F CR33−60D−F CR33−50/60C−F CR33−60D−F Horizontal Coils 3 CH23−51 3 CH23−65 3 CH33−48C−2F 3 CH33−60D−2F 3 CH33−50/60C−2F 3 CH33−62D−2F 3 CH23−68 3 CH33−49C−2F
Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV + Furnace 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G61MPV−60C−090 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G60UHV−60D−135 4 G60UHV−60C−090 4 G60UHV−60D−135 4 G61MPV−60D−135
Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV 2 91M02 2 91M02 2 91M02
+ Furnace 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60DFV−60C−090 4 G60DFV−60C−110 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60DFV−60C−110 4 G61MPV−60D−135 4 G60DFV−60C−090 4 G60DFV−60D−135
2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 20
ARI RATINGS 1 ARI
Cooling Capacity Btuh
Standard 210/240 Ratings Efficiency SEER EER
Total Unit Watts
Indoor Unit Model No.
Expansion Device
XC15−048 Horizontal Indoor Coils + Furnace 46,500 14.00 46,500 14.00 46,500 14.20 46,500 14.50 46,500 14.50 46,500 14.50 47,000 14.20 47,000 14.20 47,000 14.50 47,000 14.70 47,000 14.70 47,500 14.50 47,500 14.50 47,500 14.50 47,500 14.70 48,000 14.70 48,000 15.00 48,000 15.20 48,500 14.50 48,500 14.50 48,500 14.70 48,500 14.70 48,500 14.70 48,500 14.70 48,500 14.70 48,500 14.70 48,500 14.70 48,500 14.70 48,500 15.00 48,500 15.00 48,500 15.00 48,500 15.00 48,500 15.00 48,500 15.00 48,500 15.20 49,000 15.00 49,000 15.00 49,000 15.20 49,000 15.20 49,000 15.20 49,000 15.50
4 TON 11.70 11.70 11.70 11.70 11.70 12.00 11.70 11.70 12.00 12.20 12.00 11.70 12.00 12.00 12.00 12.20 12.20 12.50 12.00 12.00 12.00 12.00 12.20 12.20 12.20 12.20 12.20 12.20 12.20 12.50 12.20 12.20 12.20 12.50 12.50 12.20 12.20 12.50 12.50 12.50 12.70
3975 3975 3975 3975 3975 3875 4015 4015 3915 3850 3915 4060 3960 3960 3960 3935 3935 3840 4040 4040 4040 4040 3975 3975 3975 3975 3975 3975 3975 3880 3975 3975 3975 3880 3880 4015 4015 3920 3920 3920 3860
Horizontal Coils CH23−51 CH23−51 CH23−51 CH23−51 CH23−51 CH23−51 CH23−65 CH23−65 CH23−65 CH23−65 CH23−65 CH33−48C−2F CH23−65 CH33−48C−2F CH33−48C−2F CH33−48C−2F CH33−60D−2F CH33−60D−2F CH33−49C−2F CH33−49C−2F CH33−50/60C−2F CH33−62D−2F CH33−62D−2F CH33−49C−2F CH33−49C−2F CH33−49C−2F CH33−49C−2F CH33−50/60C−2F CH33−49C−2F CH33−62D−2F CH33−50/60C−2F CH33−50/60C−2F CH33−62D−2F CH33−62D−2F CH33−62D−2F CH23−68 CH23−68 CH23−68 CH23−68 CH23−68 CH23−68
+ Furnace 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G61MPV−60D−135 4 G60UHV−60D−135 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G60UHV−60D−135 4 G61MPV−60D−135 4 G61MPV−60C−110 4 G60UHV−60C−090 4 G61MPV−60C−090 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G61MPV−60D−135 4 G60UHV−60D−135 4 G61MPV−60C−091 4 G61MPV−60C−111 4 G61MPV−60C−110 4 G61MPV−60C−091 4 G61MPV−60C−090 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G61MPV−60C−110 4 G61MPV−60C−111 4 G61MPV−60C−090 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G60UHV−60D−135 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G60UHV−60D−135
2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 21
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−048 Air Handlers 45,500 45,500 47,000 47,500 48,000 48,000 48,000 48,000 48,500 48,500
4 TON 13.70 14.00 14.20 15.20 14.70 14.70 15.00 15.20 15.20 15.20
11.50 11.50 11.70 12.20 12.00 12.20 12.20 12.50 12.50 12.50
3955 3955 4015 3895 4000 3935 3935 3840 3880 3880
Air Handlers 4 CBX32MV−036 (Multi−Position) 3 CBX32M−042 (Multi−Position) 3 CB30U−51 (Up−Flow) 4 CBX27UH−060 (Up−Flow / Horizontal) 3 CB30U−65 (Up−Flow) 3 CBX32M−060 (Multi−Position) 3 CBX32M−048 (Multi−Position) 4 CBX27UH−048 (Up−Flow / Horizontal) 4 CBX32MV−048 (Multi−Position) 4 CBX32MV−060 (Multi−Position)
2 91M02
Factory TXV 2 91M02 Factory TXV 2 91M02 Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV
XC15−060 Up-Flow Indoor Coils 53,000 13.20 10.90 54,500 13.50 11.20 55,000 13.20 11.00 56,000 13.50 11.20 Up-Flow Indoor Coils + Furnace 53,000 13.00 10.70 53,000 13.00 10.80 53,500 13.00 10.80 53,500 13.00 10.80 53,500 13.20 10.80 54,000 13.20 11.00 55,000 13.50 11.20 55,500 13.50 11.20 55,500 13.50 11.20 55,500 13.50 11.20 55,500 13.50 11.20 56,000 13.70 11.20 56,000 13.70 11.20 56,000 14.00 11.50 Down-Flow Indoor Coils 53,000 13.00 10.80 53,000 13.00 10.80 Down-Flow Indoor Coils + Furnace 53,000 13.00 10.70 53,000 13.00 10.70 53,000 13.20 10.80 53,500 13.20 10.90 53,500 13.20 10.90 53,500 13.20 10.90 Horizontal Indoor Coils 53,000 13.00 10.80 53,000 13.20 10.90 54,000 13.50 11.00 54,500 13.20 11.00 55,000 13.50 11.00 55,500 13.50 11.00
5 TON 4860 4865 5000 5000 4955 4905 4955 4955 4955 4910 4910 4955 4955 4955 4955 5000 5000 4870 4905 4905 4955 4955 4905 4910 4910 4910 4905 4860 4910 4955 5000 5045
Up−Flow Coils 3 CX34−50/60C−6F 3 CX34−49C−6F 3 CX34−60D−6F 3 CX34−62D−6F Up−Flow Coils CX34−44/48C−6F CX34−44/48C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−50/60C−6F CX34−60D−6F CX34−49C−6F CX34−49C−6F CX34−49C−6F CX34−49C−6F CX34−60D−6F CX34−62D−6F 5 CX34−62D−6F Down−Flow Coils 3 CR33−50/60C−F 3 CR33−60D−F Down−Flow Coils CR33−50/60C−F CR33−50/60C−F CR33−60D−F CR33−50/60C−F CR33−50/60C−F CR33−60D−F Horizontal Coils 3 CH23−65 3 CH33−48C−2F 3 CH33−50/60C−2F 3 CH33−60D−2F 3 CH23−68 3 CH33−62D−2F
Factory TXV Factory TXV Factory TXV Factory TXV + Furnace 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G61MPV−60D−135 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60D−135 4 G61MPV−60D−135 4 G60UHV−60D−135
Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV Factory TXV 2 91M02 2 91M02
+ Furnace 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G61MPV−60D−135 4 G60DFV−60C−090 4 G60DFV−60C−110 4 G60DFV−60D−135
2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 22
ARI RATINGS 1 ARI
Standard 210/240 Ratings Efficiency Cooling Capacity Btuh EER SEER
Total Unit Watts
Indoor Unit Model No.
E i Expansion Device
XC15−060
5 TON
Horizontal Indoor Coils + Furnace 52,000 13.00 52,500 13.00 52,500 13.00 53,000 13.00 53,000 13.00 53,000 13.00 53,000 13.20 53,000 13.20 53,000 13.20 53,500 13.00 53,500 13.20 54,000 13.00 54,000 13.00 54,000 13.00 54,500 13.20 54,500 13.20 54,500 13.20 54,500 13.50 55,000 13.00 55,000 13.20 55,000 13.50 55,000 13.50 55,000 13.50 55,000 13.50 55,000 13.70 55,000 13.70 55,500 13.50 55,500 13.50 55,500 13.50 55,500 13.70 55,500 13.70 55,500 13.70 56,000 13.50 56,000 13.70 Air Handlers 53,000 54,000 54,500 55,000 55,500 55,500 55,500
13.50 13.50 13.70 13.70 13.50 13.70 14.00
10.70 10.80 10.80 10.80 10.80 10.90 10.90 10.90 10.90 10.70 11.00 10.80 10.90 10.90 10.90 10.80 11.00 11.00 11.00 11.00 11.00 11.00 11.00 11.20 11.20 11.20 11.20 11.20 11.20 11.20 11.20 11.20 11.20 11.20 11.00 11.00 11.20 11.20 11.00 11.20 11.50
4860 4860 4860 4905 4905 4860 4860 4860 4860 5000 4865 5000 4955 4955 5000 5045 4955 4955 5000 5000 5000 5000 5000 4910 4910 4910 4955 4955 4955 4955 4955 4955 5000 5000
Horizontal Coils CH23−51 CH23−51 CH23−51 CH23−65 CH23−65 CH23−51 CH23−65 CH23−65 CH23−65 CH33−48C−2F CH23−65 CH33−48C−2F CH33−48C−2F CH33−48C−2F CH33−50/60C−2F CH33−50/60C−2F CH33−50/60C−2F CH33−60D−2F CH33−62D−2F CH33−50/60C−2F CH33−62D−2F CH23−68 CH23−68 CH33−60D−2F CH23−68 CH23−68 CH33−62D−2F CH33−62D−2F CH33−62D−2F CH33−62D−2F CH33−62D−2F CH23−68 CH33−62D−2F CH23−68
+ Furnace 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G61MPV−60D−135 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60D−135 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G61MPV−60C−090 4 G60UHV−60D−135 4 G61MPV−60C−110 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G61MPV−60C−091 4 G60UHV−60C−090 4 G61MPV−60C−090 4 G61MPV−60C−090 4 G61MPV−60C−110 4 G60UHV−60D−135 4 G60UHV−60C−110 4 G61MPV−60D−135 4 G61MPV−60C−110 4 G61MPV−60C−111 4 G61MPV−60D−135 4 G60UHV−60C−090 4 G60UHV−60C−110 4 G60UHV−60C−090 4 G60UHV−60D−135 4 G60UHV−60D−135
4820 4910 4865 4910 5045 4955 4825
Air Handlers 3 CB30U−51 (Up−Flow) 3 CBX32M−048 (Multi−Position) 4 CBX27UH−060 (Up−Flow / Horizontal) 4 CBX32MV−048 (Multi−Position) 3 CB30U−65 (Up−Flow) 3 CBX32M−060 (Multi−Position) 4 CBX32MV−060 (Multi−Position)
2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02 2 91M02
Factory TXV Factory TXV Factory TXV 2 91M02 Factory TXV Factory TXV
1
Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air with 25 ft. of connecting refrigerant lines.
2
Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
3 4 5
Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation. Blower control must be set for a time−off blower delay. Most popular indoor coil.
XC15 − 2 to 5 Ton Air Conditioner / Page 23
Visit us at www.lennox.com For the latest technical information, www.lennoxdavenet.com Contact us at 1−800−4−LENNOX NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2007 Lennox Industries Inc.