Transcript
YIF series Indoor Units DAF009 DAF012 DAF018 DAF024 DAF030
FAF012 FAF018 FAF024 FAF030
CAF012 CAF018 CAF024 CAF030
DAF036
FAF036
CAF036
DAF042 DAF060
FAF042
CAF042
Outdoor Units YIF009 YIF012 YIF018 YIF024 YIF030 YIF036 YIF036T YIF042T YIF060T
REFRIGERANT R410A SM YIFSER 2-A.1 GB Version:2
HEAT PUMP JAN - 2012
LIST OF EFFECTIVE PAGES
LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Total number of pages in this publication is 171 consisting of the following: Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title........................... 1 A .............................. 1 i................................. 1 1-1 -1-4……………… 1 2-1 - 2-23……………. 2 3-1…………………….1 4-1 - 4-4…………….. 1 5-1-5-19……………… 1 6-1 -6-4………………. 1 7-1 -7-13…………….. 2 8-1-8-2………………. 1 9-1- 9-12……………. 1 10-1-10-1……………. 1 11-1…………..............1 12-1 -12-6………….... 1 13-1 - 13-3……………1 14-1- 14-49…………. 2 * Zero in this column indicates an original page.
A
SM YIF 2-A.1 GB
TABLE OF CONTENTS
Table of Contents 1.
INTRODUCTION ............................................................................................................................. 1-1
2.
PRODUCT DATA SHEET............................................................................................................... 2-1
3.
RATING CONDITIONS ................................................................................................................... 3-1
4.
OUTLINE DIMENSION ................................................................................................................... 4-1
5.
PERFORMANCE DATA ................................................................................................................. 5-1
6.
AIRFLOW CURVES........................................................................................................................ 6-1
7.
SOUND LEVEL CHARACTERISTICS ........................................................................................... 7-1
8.
ELECTRICAL DATA....................................................................................................................... 8-1
9.
WIRING DIAGRAM......................................................................................................................... 9-1
10.
REFRIGERATION DIAGRAMS ...................................................................................................... 10-1
11.
TUBING CONNECTIONS ............................................................................................................... 11-1
12.
CONTROL SYSTEM ....................................................................................................................... 12-1
13.
TROUBLESHOOTING.................................................................................................................... 13-1
14.
EXPLODED VIEW & SPARE PART LIST...................................................................................... 14-1
15.
APPEDDIX ...................................................................................................................................... 15-1
SM YIF 2-A.1 GB
i
INTRODUCTION
1.
INTRODUCTION
1.1
General The YIF series range comprises RC (heat pump) models. The whole range covers nominal cooling capacity from 9kBtu/h to 60kBtu/h which matching following indoors, as follows: IDU: Ducted(8 Models): DAF009 DAF012 DAF018 DAF024 DAF030 DAF036 DAF042 DAF060 Floor/Ceiling(4 Models): FAF012 FAF018 FAF024 FAF030 FAF036 FAF042 Cassette(6 Models): CAF012 CAF018 CAF024 CAF030 CAF036 CAF042 ODU: 1 Ph(6 Models): YIF009 YIF012 YIF018 YIF024 YIF030 YIF036 3 Ph(3 Models): YIF036 YIF042 YIF060
1.2
Main Features The YIF series benefits from the most advanced technological innovations, namely: • Auto mode • Cooing/Heating/Dehumidification • Sleep mode (from remote control) • ON/OFF Timer • Auto swing • 4-dimension swing (Cassette only) • Energy saving • Intelligent Deicing • Memory from power failure • Cold air prevention in heating • Self diagnostic (Error indications) for ease of maintenance
SM YIF 2-A.1 GB
1-1
INTRODUCTION
1.3
Indoor Unit The indoor unit is calling mounted, and can be easily fitted to many types of residential and commercials applications. It is major designed for light commercial air-conditioning needs. It includes: • Coil with hydrophilic aluminum fins. • Advanced electronic control box assembly • Mounting plate
1.4
Filtration The YIF series presents several types of air filters: • Easily accessible, and re-usable pre-filters (mesh)
1.5
Control The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. For further details, please refer to the Operation Manual, Appendix.
1.6
Outdoor Unit The outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. For further information, please refer to the Product Data Sheet, Chapter 2. It includes : • Compressor mounted in a soundproofed compartment : • Axial fan. • Outdoor coil with hydrophilic louver fins for RC units. • Outlet air fan grill. • Interconnecting wiring terminal block.
1.7
Tubing Connections Flare type interconnecting tubing to be produced on site. For further details, please refer to the Installation Manual, Chapter 10.
1-2
SM YIF 2-A.1 GB
INTRODUCTION
1.8
Accessories RCW Wall Mounted Remote Control The RCW remote control is mounted on the wall, and controls the unit either as an infrared remote control or as a wired controller. The wired remote control with larger LCD display provides the following functions • Interconnecting wiring terminal block. • On/OFF unit • Choose the operating mode (Heating-Cooling-Dehumidification-Fan or
Automatic mode), • Increase or decrease the setting temperature. • Adjust the fan speeds (Auto/High/Medium/Low) • Setting ON-OFF timer within 0.5hr-24hrs • Air exchange (Fresh air) settings • Sleep mode saves energy by preventing overcooling or overheating during night
time • Energy saving function • Technician functions
- Display of Outdoor Ambient Temperature - Power-fail Memory Function Setting - Setting of Ambient Temp. Sensor - Setting of Fan Speed - Failure Display For further details, please refer to the Technical Service Manual.
1.9
Inbox Documentation Each unit is supplied with its own installation, operation and remote control manuals.
SM YIF 2-A.1 GB
1-3
INTRODUCTION
1.10
Matching Table
INDOOR UNITS OUTDOOR UNITS
DAF009
YIF009
√
YIF012 YIF018 YIF024 YIF030
DAF018 CAF018 FAF018
DAF024 CAF024 FAF024
DAF030 CAF030 FAF030
DAF036 CAF036 FAF036
DAF060
√ √ √ √
YIF036T
√
YIF060T
DAF042 CAF042 FAF042
√
YIF036
YIF042T
1-4
DAF012 CAF012 FAF012
√ √
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2. 2.1
PRODUCT DATA SHEET DAF009 / YIF009
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Capacity (4)
PRELIMINARY PRODUCT DATA SHEET DAF009 YIF009 ducted Units Btu/hr kW kW W/W
Cooling 8870 2.6 1.00 2.6
Heating 9720 2.85 0.97 2.93
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 4.5 4.3 Starting current A Circuit breaker rating (IDU/ODU) A 6/10 Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 830/640/550 Air flow (1) H/M/L m3/hr 550/470/400 External static pressure Min-Max Pa 25(0~25) Sound power level (2) H/M/L dB(A) 47/46/44 Sound pressure level(3) H/M/L dB(A) 37/36/34 Moisture removal l/hr 1 Condenstate drain tube I.D mm 20 Dimensions WxHxD mm 913x220x680 Weight kg 27 Package dimensions WxHxD mm 995x258x750 Packaged weight kg 32 Units per pallet units Stacking height units Refrigerant control Capillary Compressor type, model Rotary Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 2800 Sound power level H/L dB(A) 65 Sound pressure level(3) H/L dB(A) 55 Dimensions WxHxD mm 848x540x320 Weight kg 32 Package dimensions WxHxD mm 878x590x360 Packaged weight kg 37 Units per pallet Units Stacking height units Refrigerant type R410A Refrigerant chargeless distance kg/m 1.1/5 Additional charge per 1 meter g/m 30g/m Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53) Connections between units Max.tubing length m. Max.20 m. Max.15 Max.height Operation control type Remote control Heating elements (Option) kW Others (1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-1
PRODUCT DATASHEET
2.2
DAF012 / YIF012
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
DAF012 YIF012 ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 11940 3.5 1.2 2.91
220-240V/Single/50Hz 5.4 4.9 6/13 Centrifugal x 2 1110/910/760 600/540/490 25(0~25) 50/48/46 40/38/36 1.3 20 913x220x680 27 995x258x750 32
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 12280 3.6 1.1 3.27
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 848x540x320 32 878x590x360 37
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.0/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-2
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.3
DAF018 / YIF018
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
DAF018 YIF018 ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 17060 5.0 2.1 2.38
220-240V/Single/50Hz 9.4 8.1 6/20 Centrifugal x 2 1000/920/780 840/750/680 25(0~25) 52/50/48 42/40/38 1.9 30 1012x266x736 36 1120x308x795 39
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 19450 5.7 1.8 3.16
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 848x540x320 40 878x590x360 45
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.5/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-3
PRODUCT DATASHEET
2.4
DAF024 / YIF024
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
DAF024 YIF024 ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Cooling 23880 7.0 2.66 2.63
Heating 27300 8.0 2.51 3.18
220-240V/Single/50Hz 11.9 11.3 6/25 Centrifugal x 2 1250/1220/1060 1400/1350/1220 25(0~80) 54/52/50 44/42/40 2.4 20 1270x268x504 37 1345x268x594 45
Capillary Rotary Propeller(direct) x 1 940 3200 69 59 1018x700x412 59 1100x755x450 64
kg/m g/m In.(mm) In.(mm) m. m.
R410A 2.2/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-4
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.5
DAF030 / YIF030
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, mode Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
DAF030 YIF030 ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units kg/m g/m In.(mm) In.(mm) m. m.
Cooling 28320 8.3 3.00 2.76
Heating 31050 9.1 3..00 3.03
220-240V/Single/50Hz 13.4 13.4 6/30 Centrifugal x 2 1250/1220/1060 1400/1320/1200 37(0~50) 54/52/50 44/42/40 2.5 20 1270x268x530 37 1345x283x594 43
Capillary Rotary Propeller(direct) x 1 780 4200 69 59 980x790x427 70 1080x840x485 75
R410A 3.6/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-5
PRODUCT DATASHEET
2.6
DAF036 / YIF036
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
DAF036 YIF036 ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 34120 10.0 4.00 2.50
220-240V/Single/50Hz 17.9 15.7 10/40 Centrifugal x 2 1320/1090/910 2000/1650/1380 37(0~150) 60/58/56 50/48/46 2.9 20 1251x290x744 57 1335x290x834 67
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 37530 11.0 3.50 3.14
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-6
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.7
DAF036 / YIF036T
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
DAF036 YIF036T ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units kg/m g/m In.(mm) In.(mm) m. m.
Cooling 34120 10.0 4.00 2.50
Heating 37530 11.0 3.50 3.14
380-415V/3 Ph/50Hz
10/16 Centrifugal x 2 1320/1090/910 2000/1650/1380 37(0~150) 60/58/56 50/48/46 2.9 20 1251x290x744 57 1335x290x834 67
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-7
PRODUCT DATASHEET
2.8
DAF042 / YIF042
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
DAF042 YIF042T ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Cooling 40940 12.0 5.3 2.26
Heating 47770 14.0 4.9 2.85
380-415V/3 Ph/50Hz
10/20 Centrifugal x 2 1320/1090/910 2000/1650/1380 37(0~150) 60/58/56 50/48/46 4.3 20 1251x290x744 57 1335x290x834 67
Capillary Scroll Propeller(direct) x 2 840 6000 70 60 950x1250x412 112 1110x1385x450 123
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.55/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-8
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.9
DAF060 / YIF060
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
DAF060 YIF060T ducted Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 54590 16.0 6.5 2.46
380-415V/3 Ph/50Hz
10/20 Centrifugal x 2 1320/1090/910 2500/-/37(0~150) 63/60/58 53/50/48 4.7 20 1251x330x788 66 1334x330x882 76
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 63120 18.5 5.5 3.36
Capillary Scroll Propeller(direct) x 2 940 6000 74 64 950x1250x412 123 1110x1385x450 134
kg/m g/m In.(mm) In.(mm) m. m.
R410A 5.0/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-9
PRODUCT DATASHEET
2.10
FAF012 / YIF012
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condensate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF012 YIF012 Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling Heating 11940 12280 3.5 3.6 1.17 1.10 2.99 3.27 C C 220-240V/Single/50Hz 5.24 4.93 6/16 Centrifugal x 2 790/670/550 790/670/550 0 56/54/51 46/44/41 1.2 20 836/238/695 27 935/295/805 35.5
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 840x540x320 32 878x590x360 37
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.0/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-10
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.11
FAF018 / YIF018
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condensate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF018 YIF018 Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling Heating 17060 19450 5.0 5.7 2.03 2.07 E E 1.10 1.23 220-240V/Single/50Hz 1.10 1.23 6/20 Centrifugal x 2 1070/970/870 1070/970/700 0 64/60/56 54/50/46 1.9 20 836x238x695 27 935x295x805 35.5
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 848x540x320 40 878x590x360 45
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.5/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-11
PRODUCT DATASHEET
2.12
FAF024 / YIF024
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF024 YIF024 Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 23880 7.0 2.61 2.68
220-240V/Single/50Hz 11.7 11.6 6/25 Centrifugal x 2 1360/1280/1240 1170/1080/1000 0 60/58/56 50/48/46 2.35 20 1300X188X600 32 1414X248X724 36
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 27300 8.0 2.59 3.08
Capillary Rotary Propeller(direct) x 1 940 3200 69 59 1018x700x412 59 1100x755x450 64
kg/m g/m In.(mm) In.(mm) m. m.
R410A 2.2/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-12
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.13
FAF030 / YIF030
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF030 YIF030 Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 30030 8.8 3.00 2.93
220-240V/Single/50Hz 13.4 12.8 6/30 Centrifugal x 2 1025/965/890 1600/1450/1300 0 62/61/59 52/51/49 2.3 20 1420×245×700 50 1545×330×825 59
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 33440 9.8 2.85 3.43
Capillary Rotary Propeller(direct) x 1 780 4200 69 59 980x790x427 70 1080x840x485 75
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.6/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-13
PRODUCT DATASHEET
2.14
FAF036 / YIF036
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF036 YIF036 Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling Heating 34120 37530 10.0 11.0 3.60 3.30 2.50 3.14 2.77 3.33 220-240V/Single/50Hz 16.1 14.8 6/40 Centrifugal x 2 1100/1000/930 1800/1630/1520 0 64/61/58 54/51/48 2.9 20 1590X238X695 42 1714X330X830 51
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-14
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.15
FAF036 / YIF036T
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
FAF036 YIF036T Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 34120 10.0 3.60 2.77
380-415V/3 Ph/50Hz 16.1 14.8 6/16 Centrifugal x 2 1100/1000/930 1800/1630/1520 0 64/61/58 54/51/48 2.9 20 1590X238X695 42 1714X330X830 51
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 36780 10.78 3.30 3.26
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-15
PRODUCT DATASHEET
2.16
FAF042 / YIF042
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
FAF042 YIF042T Floor / Ceiling Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Cooling 40940 12.0 4.8 2.50
Heating 47770 14.0 4.7 2.97
380-415V/3 Ph/50Hz 21.5 21.1 6/16 Centrifugal x 2 1100/1000/930 1800/1630/1520 0 64/61/58 54/51/48 4.3 20 1590X238X695 42 1714X330X830 51
Capillary Scroll Propeller(direct) x 2 840 6000 70 60 950x1250x412 112 1110x1385x450 123
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.55/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-16
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.17
CAF012 / YIF012
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
CAF012 YIF012 Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 11940 3.5 1.17 2.99
220-240V/Single/50Hz 5.2 4.9 6/13 Centrifugal x 1 820/720/620 550/490/420 0 57/55/53 47/45/43 1.1 20 600×230×600 20 848×310×678 27
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 12280 3.6 1.1 3.27
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 848x540x320 32 878x590x360 37
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.0/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-17
PRODUCT DATASHEET
2.18
CAF018 / YIF018
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
CAF018 YIF018 Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling Heating 17060 19450 5.0 5.7 2.00 1.90 2.38 3.16 2.50 3.00 220-240V/Single/50Hz 9.0 8.5 6/20 Centrifugal x 1 820/720/620 550/490/420 0 57/55/53 47/45/43 1.9 20 600×230×600 20 848×310×678 27
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Capillary Rotary Propeller(direct) x 1 900 2800 66 56 848x540x320 40 878x590x360 45
kg/m g/m In.(mm) In.(mm) m. m.
R410A 1.5/5 30g/m 1/4"(6.35) 1/2"(12.7) Max.20 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-18
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.19
CAF024 / YIF024
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
CAF024 YIF024 Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units kg/m g/m In.(mm) In.(mm) m. m.
Cooling 23200 6.8 2.62 2.63
Heating 25590 7.5 2.50 3.18
220-240V/Single/50Hz 11.7 11.2 6/25 Centrifugal x 1 600/550/500 1180/1080/1000 0 57/55/53 47/45/43 2.35 20 840×260×840 30 960×310×960 38
Capillary Rotary Propeller(direct) x 1 940 3200 69 59 1018x700x412 59 1100x755x450 64
R410A 2.2/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-19
PRODUCT DATASHEET
2.20
CAF030 / YIF030
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
CAF030 YIF030 Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 28320 8.3 2.90 2.86
220-240V/Single/50Hz 13.0 14.1 6/30 Centrifugal x 1 670/620/570 1400/1270/1170 0 61/59/58 51/49/48 2.7 20 840×260×840 27 960×310×960 36
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 30030 8.8 3..15 2.79
Capillary Rotary Propeller(direct) x 1 780 4200 69 59 980x790x427 70 1080x840x485 75
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.6/5 60g/m 3/8"(9.53) 5/8"(15.88) Max.30 Max.15 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-20
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.21
CAF036 / YIF036
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
CAF036 YIF036 Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 34120 10.0 3.60 2.77
220-240V/Single/50Hz 16.1 14.8 6/40 Centrifugal x 1 710/660/610 1660/1570/1500 0 63/61/58 53/51/48 2.9 20 840X320X840 38 960X394X960 46
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 37530 11.0 3.30 3.33
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-21
PRODUCT DATASHEET
2.22
CAF036 / YIF036T
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height Operation control type Heating elements (Option) Others
CAF036 YIF036T Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Cooling 34120 10.0 3.60 2.77
Heating 37530 11.0 3.10 3.54
380-415V/3 Ph/50Hz 16.1 13.9 6/16 Centrifugal x 1 710/660/610 1660/1570/1500 0 63/61/58 53/51/48 2.9 20 840X320X840 38 960X394X960 46
Capillary Scroll Propeller(direct) x 1 900 4000 70 60 1018x840x412 90 1110x985x450 100
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.2/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-22
SM YIF 2-A.1 GB
PRODUCT DATASHEET
2.23
CAF042 / YIF042
R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics
PRELIMINARY PRODUCT DATA SHEET
Capacity (4)
OUTDOOR
INDOOR
Power input (4) EER (Cooling) or COP(Heating) (4) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating (IDU/ODU) Fan type & quantity Fan speeds H/M/L Air flow (1) H/M/L External static pressure Min-Max Sound power level (2) H/M/L Sound pressure level(3) H/M/L Moisture removal Condenstate drain tube I.D Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant control Compressor type, model Fan type & quantity Fan speeds H/L Air flow H/L Sound power level H/L Sound pressure level(3) H/L Dimensions WxHxD Weight Package dimensions WxHxD Packaged weight Units per pallet Stacking height Refrigerant type Refrigerant chargeless distance Additional charge per 1 meter Liquid line Suction line Connections between units Max.tubing length Max.height difference Operation control type Heating elements (Option) Others
CAF042 YIF042T Flared Units Btu/hr kW kW W/W V/Ph/Hz A A A
Cooling 40940 12.0 4.8 2.50
380-415V/3 Ph/50Hz 21.5 22.4 6/20 Centrifugal x 1 710/660/610 1650/1570/1500 0 63/61/58 53/ 51/48 4.3 20 840X320X840 38 960X394X960 46
RPM m3/hr Pa dB(A) dB(A) l/hr mm mm kg mm kg units units
RPM m3/hr dB(A) dB(A) mm kg mm kg Units units
Heating 47770 14.0 5.0 2.80
Capillary Scroll Propeller(direct) x 2 840 6000 70 60 950x1250x412 112 1110x1385x450 123
kg/m g/m In.(mm) In.(mm) m. m.
R410A 3.55/5 120g/m 1/2"(12.7) 3/4"(19.05) Max.50 Max.30 Remote control
kW
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM YIF 2-A.1 GB
2-23
RATING CONDITIONS
3.
RATING TING CONDITIONS Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1
Operating Limits R410A
Operating Limits
Cooling Heating Voltage
SM YIF 2-A.1 GB
Upper limit Lower limit Upper limit Lower limit 1 Ph 3 Ph
Indoor 32℃ DB 23℃ WB 21℃ DB 15℃ WB 27℃ DB 20℃ DB 198 – 264 V -
Outdoor 43℃ 18℃ 24℃ DB 18℃ WB -7℃ DB -8℃ WB 198 – 264 V 360 – 440 V
3-1
OUTLINE DIMENSION
OUTLINE DIMENSION
4. 4.1
Indoor Units: DAF009, DAF012, DAF018, DAF024, DAF036, DAF042, DAF060
Unit:mm Model
A
B
C
D
E
F
G
H
I
J
856
571
515
790
913
680
750
100
172
220
932
627
738
894
1012
736
738
125
207
266
1101
395
820
1159
1270
504
1002
160
235
268
1011
635
820
1115
1251
744
980
160
231
290
1015
679
820
1115
1251
788
980
160
261
330
DAF009 DAF012 DAF018 DAF024 DAF030 DAF036 DAF042 DAF060
SM YIF 2-A.1 GB
4-1
OUTLINE DIMENSION
4.2
Indoor Units: FAF012, FAF018, FAF024, FAF036, FAF042
Unit: mm
4-2
Model
A
B
C
D
E
FAF012/018
836
238
745
695
260
FAF024/030
1300
188
1202
600
260
FAF036/042
1590
238
1491
695
260
SM YIF 2-A.1 GB
OUTLINE DIMENSION
4.3
Indoor Units: CAF012, CAF018, CAF024, CAF036, CAF042
Unit: mm Model CAF012
H
A
B
C
D
E
245
650
400
606
440
66
275
950
680
840
720
76
345
950
680
840
720
76
CAF018 CAF024 CAF030 CAF036 CAF042
SM YIF 2-A.1 GB
4-3
OUTLINE DIMENSION
4.4
Outdoor Units:
YIF009/012/018/024/030/036
4-4
SM YIF 2-A.1 GB
OUTLINE DIMENSION YIF042/060
Unit:mm Model
A
B
C
H
D
848
320
540
540
286
YIF024
1018
412
572
695
378
YIF030
980
427
610
790
395
1018
412
572
840
378
1032
412
572
1250
378
YIF009 YIF012 YIF018
YIF036 YIF036T YIF042T YIF060T
SM YIF 2-A.1 GB
4-5
PERFORMANCE DATA & PRESSURE CURVES
5.
PERFORMANCE DATA
5.1
YIF009
5.1.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC)
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
15
20
25
30
35
40
46
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 2.65 2.81 2.94 3.07 3.17 1.71 1.81 1.91 1.87 1.90 0.71 0.71 0.71 0.72 0.72 2.63 2.78 2.91 3.04 3.15 1.87 1.99 2.10 2.04 2.09 0.77 0.77 0.78 0.78 0.78 2.52 2.70 2.86 2.99 3.09 1.66 1.78 1.88 1.85 1.90 0.83 0.84 0.84 0.85 0.85 2.37 2.55 2.76 2.86 2.96 1.58 1.71 1.84 1.81 1.88 0.90 0.91 0.92 0.93 0.93 2.18 2.37 2.73 2.83 2.60 1.49 1.62 1.75 1.82 1.77 0.97 0.98 1.01 1.01 1.00 1.98 2.16 2.39 2.52 2.63 1.38 1.52 1.67 1.65 1.73 1.04 1.06 1.08 1.09 1.10 1.72 1.90 2.13 2.26 2.37 1.26 1.39 1.57 1.54 1.61 1.15 1.16 1.18 1.20 1.21
LEGEND TC SC PI WB DB ID OU
5.1.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW)
SM YIF 2-A.1 GB
5-1
PERFORMANCE DATA & PRESSURE CURVES
ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
1.50
0.78
1.44
0.83
1.38
0.87
-7
1.61
0.80
1.55
0.84
1.50
0.88
-2
1.71
0.81
1.65
0.85
1.60
0.90
2
2.08
0.84
2.00
0.90
1.91
0.95
6
2.94
0.91
2.85
0.97
2.75
1.03
10
3.19
0.96
3.11
1.02
3.02
1.09
15
3.45
1.00
3.36
1.08
3.28
1.14
20
3.63
1.03
3.55
1.12
3.45
1.20
LEGEND TH PI WB DB ID OU
5.1.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating 5-2
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.2
YIF012
5.2.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC) 15
20
25
30
35
40
46
SM YIF 2-A.1 GB
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 3.57 3.78 3.96 4.13 4.27 2.30 2.44 2.57 2.51 2.55 0.85 0.85 0.85 0.86 0.86 3.54 3.75 3.92 4.10 4.24 2.52 2.68 2.83 2.75 2.81 0.92 0.93 0.93 0.94 0.94 3.40 3.64 3.85 4.03 4.17 2.24 2.40 2.53 2.49 2.55 0.99 1.00 1.01 1.02 1.02 3.19 3.43 3.71 3.85 3.99 2.13 2.30 2.48 2.43 2.53 1.08 1.09 1.10 1.11 1.11 2.94 3.19 3.68 3.82 3.50 2.00 2.18 2.35 2.45 2.38 1.16 1.18 1.21 1.21 1.20 2.66 2.91 3.22 3.40 3.54 1.86 2.05 2.25 2.22 2.32 1.25 1.27 1.29 1.31 1.32 2.31 2.56 2.87 3.05 3.19 1.69 1.87 2.11 2.07 2.17 1.37 1.40 1.42 1.44 1.45 5-3
PERFORMANCE DATA & PRESSURE CURVES LEGEND TC SC PI WB DB ID OU
5.2.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW) ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
1.89
0.88
1.82
0.94
1.75
0.98
-7
2.03
0.90
1.96
0.95
1.89
1.00
-2
2.16
0.91
2.09
0.97
2.02
1.02
2
2.63
0.96
2.52
1.02
2.41
1.08
6
3.71
1.03
3.60
1.10
3.47
1.17
10
4.03
1.09
3.92
1.16
3.82
1.24
15
4.36
1.13
4.25
1.22
4.14
1.30
20
4.59
1.17
4.48
1.27
4.36
1.36
LEGEND TH PI WB DB ID OU
5.2.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling
5-4
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
SM YIF 2-A.1 GB
5-5
PERFORMANCE DATA & PRESSURE CURVES
5.3
YIF018
5.3.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC)
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
15
20
25
30
35
40
46
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 5.10 5.40 5.65 5.90 6.10 3.30 3.50 3.68 3.60 3.66 1.49 1.49 1.50 1.50 1.51 5.05 5.35 5.60 5.85 6.05 3.60 3.83 4.04 3.93 4.01 1.61 1.62 1.63 1.64 1.64 4.85 5.20 5.50 5.75 5.95 3.21 3.43 3.63 3.57 3.66 1.74 1.75 1.77 1.78 1.79 4.55 4.90 5.30 5.50 5.70 3.05 3.29 3.55 3.48 3.62 1.88 1.90 1.93 1.94 1.95 4.20 4.55 5.25 5.45 5.00 2.87 3.12 3.37 3.51 3.41 2.03 2.07 2.12 2.13 2.10 3.80 4.15 4.60 4.85 5.05 2.66 2.93 3.23 3.18 3.33 2.19 2.23 2.27 2.29 2.31 3.30 3.65 4.10 4.35 4.55 2.42 2.69 3.02 2.97 3.11 2.40 2.44 2.49 2.52 2.55
LEGEND TC SC PI WB DB ID OU
5-6
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
5.1.3
Heating Capacity (kW) ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
2.99
1.44
2.88
1.53
2.76
1.61
-7
3.22
1.48
3.11
1.56
2.99
1.64
-2
3.42
1.49
3.31
1.58
3.19
1.67
2
4.16
1.57
3.99
1.67
3.82
1.76
6
5.87
1.68
5.70
1.80
5.50
1.91
10
6.38
1.78
6.21
1.90
6.04
2.03
15
6.90
1.85
6.73
2.00
6.56
2.12
20
7.27
1.91
7.10
2.07
6.90
2.23
LEGEND TH PI WB DB ID OU
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
5.1.4 Curves Cooling Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating SM YIF 2-A.1 GB
5-7
PERFORMANCE DATA & PRESSURE CURVES Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.4
YIF024
5.4.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC) 15
20
25
30
35
40
46
5-8
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 7.14 7.56 7.91 8.26 8.54 4.61 4.89 5.15 5.03 5.12 1.89 1.89 1.89 1.90 1.91 7.07 7.49 7.84 8.19 8.47 5.04 5.36 5.66 5.50 5.62 2.04 2.05 2.06 2.07 2.08 6.79 7.28 7.70 8.05 8.33 4.48 4.80 5.08 4.99 5.12 2.20 2.22 2.24 2.26 2.26 6.37 6.86 7.42 7.70 7.98 4.26 4.60 4.97 4.87 5.07 2.38 2.41 2.44 2.46 2.47 5.88 6.37 7.35 7.63 7.00 4.01 4.36 4.71 4.91 4.77 2.58 2.62 2.68 2.69 2.66 5.32 5.81 6.44 6.79 7.07 3.73 4.10 4.51 4.44 4.66 2.78 2.82 2.87 2.90 2.92 4.62 5.11 5.74 6.09 6.37 3.39 3.76 4.23 4.15 4.35 3.05 3.10 3.15 3.19 3.22 SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES LEGEND TC SC PI WB DB ID OU
5.4.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW) ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
4.20
2.01
4.04
2.14
3.88
2.25
-7
4.52
2.06
4.36
2.17
4.20
2.29
-2
4.80
2.08
4.64
2.21
4.48
2.33
2
5.84
2.18
5.60
2.32
5.36
2.46
6
8.24
2.35
8.00
2.51
7.72
2.67
10
8.96
2.48
8.72
2.65
8.48
2.83
15
9.68
2.59
9.44
2.79
9.20
2.96
20
10.20
2.66
9.96
2.89
9.68
3.11
LEGEND TH PI WB DB ID OU
5.4.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling
SM YIF 2-A.1 GB
5-9
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.5
YIF030
5.5.1
Cooling Capacity (kW)
5-10
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
Entering Air DB OD Coil(oC)
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
15
20
25
30
35
40
46
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 8.47 8.96 9.38 9.79 10.13 5.46 5.79 6.10 5.96 6.06 2.13 2.13 2.14 2.15 2.15 8.38 8.88 9.30 9.71 10.04 5.98 6.35 6.71 6.52 6.66 2.30 2.31 2.33 2.34 2.35 8.05 8.63 9.13 9.55 9.88 5.31 5.69 6.02 5.91 6.06 2.48 2.51 2.53 2.55 2.55 7.55 8.13 8.80 9.13 9.46 5.05 5.45 5.89 5.77 6.00 2.69 2.72 2.76 2.78 2.79 6.97 7.55 8.72 9.05 8.30 4.75 5.17 5.58 5.81 5.65 2.91 2.95 3.02 3.04 3.00 6.31 6.89 7.64 8.05 8.38 4.41 4.86 5.34 5.26 5.52 3.13 3.18 3.24 3.27 3.29 5.48 6.06 6.81 7.22 7.55 4.01 4.45 5.01 4.92 5.15 3.44 3.49 3.55 3.60 3.64
LEGEND TC SC PI WB DB ID OU
5.5.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW)
SM YIF 2-A.1 GB
5-11
PERFORMANCE DATA & PRESSURE CURVES
ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
4.25
2.40
4.09
2.56
3.93
2.69
-7
4.58
2.46
4.41
2.60
4.25
2.74
-2
4.86
2.49
4.70
2.64
4.54
2.79
2
5.91
2.61
5.67
2.78
5.43
2.94
6
8.34
2.81
8.10
3.00
7.82
3.19
10
9.07
2.96
8.83
3.17
8.59
3.38
15
9.80
3.09
9.56
3.33
9.32
3.54
20
10.33
3.18
10.08
3.45
9.80
3.72
LEGEND TH PI WB DB ID OU
5.5.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
o
Outdoor Temp.( C DB)
Heating 5-12
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.6
YIF036
5.6.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC) 15
20
25
30
35
40
46
SM YIF 2-A.1 GB
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
Entering Air WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 10.20 10.80 11.30 11.80 6.58 6.98 7.36 7.19 2.84 2.84 2.85 2.86 10.10 10.70 11.20 11.70 7.20 7.65 8.09 7.85 3.07 3.08 3.10 3.12 9.70 10.40 11.00 11.50 6.40 6.86 7.25 7.12 3.31 3.34 3.37 3.40 9.10 9.80 10.60 11.00 6.08 6.57 7.09 6.95 3.58 3.63 3.68 3.70 8.40 9.10 10.50 10.00 5.73 6.23 6.73 6.81 3.88 3.94 4.03 4.00 7.60 8.30 9.20 9.70 5.32 5.86 6.44 6.34 4.18 4.24 4.32 4.36 6.60 7.30 8.20 8.70 4.84 5.36 6.04 5.92 4.58 4.66 4.74 4.80
23/32 12.20 7.31 2.87 12.10 8.02 3.13 11.90 7.30 3.40 11.40 7.23 3.72 10.90 7.01 4.05 10.10 6.65 4.39 9.10 6.21 4.85 5-13
PERFORMANCE DATA & PRESSURE CURVES LEGEND TC SC PI WB DB ID OU
5.6.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW) ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
5.78
2.80
5.56
2.98
5.34
3.13
-7
6.22
2.87
6.00
3.03
5.78
3.19
-2
6.60
2.91
6.38
3.08
6.16
3.26
2
8.03
3.05
7.70
3.24
7.37
3.43
6
11.33
3.27
11.00
3.50
10.62
3.72
10
12.32
3.45
11.99
3.69
11.66
3.95
15
13.31
3.61
12.98
3.89
12.65
4.13
20
14.03
3.71
13.70
4.03
13.31
4.34
LEGEND TH PI WB DB ID OU
5.6.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling
5-14
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.7
YIF042
5.7.1
Cooling Capacity (kW)
SM YIF 2-A.1 GB
5-15
PERFORMANCE DATA & PRESSURE CURVES
Entering Air DB OD Coil(oC)
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
15
20
25
30
35
40
46
15/21 12.24 7.90 3.76 12.12 8.64 4.07 11.64 7.68 4.39 10.92 7.30 4.75 10.08 6.87 5.14 9.12 6.38 5.53 7.92 5.80 6.07
Entering Air WB/DB ID Coil(oC) 17/24 19/27 21/29 12.96 13.56 14.16 8.38 8.83 8.62 3.77 3.77 3.79 12.84 13.44 14.04 9.18 9.70 9.42 4.09 4.11 4.13 12.48 13.20 13.80 8.22 8.70 8.54 4.43 4.47 4.50 11.76 12.72 13.20 7.88 8.51 8.34 4.81 4.87 4.91 10.92 12.60 12.00 7.47 8.07 8.17 5.22 5.34 5.30 9.96 11.04 11.64 7.03 7.73 7.61 5.62 5.72 5.78 8.76 9.84 10.44 6.43 7.25 7.11 6.17 6.28 6.36
23/32 14.64 8.77 3.81 14.52 9.63 4.14 14.28 8.76 4.51 13.68 8.68 4.92 13.08 8.41 5.36 12.12 7.98 5.82 10.92 7.44 6.42
LEGEND TC SC PI WB DB ID OU
5.7.2
5-16
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW)
SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
7.35
3.92
7.07
4.17
6.79
4.39
-7
7.91
4.02
7.63
4.24
7.35
4.47
-2
8.40
4.07
8.12
4.31
7.84
4.56
2
10.22
4.26
9.80
4.53
9.38
4.80
6
14.42
4.58
14.00
4.90
13.51
5.20
10
15.68
4.84
15.26
5.17
14.84
5.53
15
16.94
5.05
16.52
5.44
16.10
5.78
20
17.85
5.19
17.43
5.64
16.94
6.08
LEGEND TH PI WB DB ID OU
5.7.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
o
Outdoor Temp.( C DB)
Heating SM YIF 2-A.1 GB
5-17
PERFORMANCE DATA & PRESSURE CURVES Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5.8
YIF060
5.8.1
Cooling Capacity (kW)
Entering Air DB OD Coil(oC) 15
20
25
30
35
40
46
5-18
Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
15/21 16.32 10.54 4.62 16.16 11.52 4.99 15.52 10.25 5.38 14.56 9.73 5.82 13.44 9.17 6.30 12.16 8.52 6.79 10.56 7.74 7.44
Entering Air WB/DB ID Coil(oC) 17/24 19/27 21/29 17.28 18.08 18.88 11.17 11.77 11.51 4.62 4.63 4.65 17.12 17.92 18.72 12.24 12.94 12.56 5.01 5.04 5.07 16.64 17.60 18.40 10.97 11.61 11.40 5.43 5.48 5.52 15.68 16.96 17.60 10.51 11.35 11.13 5.90 5.97 6.02 14.56 16.80 16.00 9.97 10.77 10.90 6.40 6.55 6.50 13.28 14.72 15.52 9.37 10.31 10.15 6.89 7.01 7.09 11.68 13.12 13.92 8.58 9.67 9.48 7.57 7.70 7.80
23/32 19.52 11.70 4.67 19.36 12.84 5.08 19.04 11.69 5.53 18.24 11.58 6.04 17.44 11.21 6.58 16.16 10.64 7.14 14.56 9.93 7.88 SM YIF 2-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES LEGEND TC SC PI WB DB ID OU
5.8.2
– – – – – – –
Total Cooling Capacity, kW Sensible Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Heating Capacity (kW) ENTERING AIR DB ID COIL(Oc) 15
20
25
ENTERING WB OD COIL(oC)
TH
Pl
TH
Pl
TH
Pl
-10
9.71
4.40
9.34
4.69
8.97
4.92
-7
10.45
4.51
10.08
4.76
9.71
5.02
-2
11.10
4.57
10.73
4.84
10.36
5.12
2
13.51
4.79
12.95
5.09
12.40
5.39
6
19.06
5.14
18.50
5.50
17.85
5.84
10
20.72
5.43
20.17
5.80
19.61
6.20
15
22.39
5.67
21.83
6.11
21.28
6.49
20
23.59
5.83
23.03
6.33
22.39
6.82
LEGEND TH PI WB DB ID OU
5.8.3
– – – – – –
Total Heating Capacity, kW Power Input, kW Wet Bulb Temp., (oC) Dry Bulb Temp., (oC) Indoor Outdoor
Curves
Cooling
SM YIF 2-A.1 GB
5-19
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Suction Pressure(Bar)
11.0
9.0
15/21(WB/DB) 17/24(WB/DB) 19/27(WB/DB) 21/29(WB/DB) 23/32(WB/DB)
7.0
5.0 15
20
25
30
35
40
46
Outdoor Temp.(o C DB)
Heating Discharge Pressure VS.Outdoor Temp
Discharge Pressure(Bar)
40.0
30.0
20.0 25 C DB 20 C DB 15 C DB
10.0 -10
-7
-2
2
6
10
15
20
Outdoor Temp.(o C WB)
5-20
SM YIF 2-A.1 GB
AIRFLOW CURVES
6.
AIRFLOW CURVES
6.1
DAF009 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed Medium Speed
30 Performance test point at 25 Pa
Low Speed
External Static Pressure (Pa)
25
20
Operating Range
15
10
5
0 200
300
400
500
600
700
Airflow Rate,(m ³/ hr)
6.2
Model: DAF012 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
30
Medium Speed
Performance test point at 25 Pa
Low Speed
External Static Pressure (Pa)
25
Operating Range
20
15
10
5
0 200
300
400
500
600
700
800
Airflow Rate,(m ³/ hr)
SM YIF 2-A.1 GB
6-1
AIRFLOW CURVES
6.3
Model: DAF018 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
30
Medium Speed
Performance test point at 25 Pa
Low Speed
External Static Pressure (Pa)
25
Operating Range
20
15
10
5
0 200
300
400
500
600
700
800
900
1000
1100
Airflow Rate,(m ³/ hr)
6.4
Model: DAF024 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
100
Medium Speed Low Speed
External Static Pressure (Pa)
90 80
Operating Range
70 60 50
Performance test point at 25 Pa
40 30 20 10 0 400
600
800
1000
1200
1400
1600
Airflow Rate,(m ³/ hr)
6-2
SM YIF 2-A.1 GB
AIRFLOW CURVES
6.5
Model: DAF030 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
120
Medium Speed
110
Low Speed
External Static Pressure (Pa)
100
Operating Range
90 80
Performance test point at 37 Pa
70 60 50 40 30 20 10 0 400
600
800
1000
1200
1400
1600
Airflow Rate,(m ³/ hr)
6.6
Model: DAF036 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
160
Medium Speed Low Speed
External Static Pressure (Pa)
140
Operating Range
120 100
Performance test point at 37 Pa
80 60 40 20 0 400
600
800
1000
1200
1400
1600
1800
2000
2200
2400
Airflow Rate,(m ³/ hr)
SM YIF 2-A.1 GB
6-3
AIRFLOW CURVES
6.7
Model: DAF042 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
150
Medium Speed
External Static Pressure (Pa)
Low Speed 120
Operating Range
90
Performance test point at 37Pa
60
30
0 400
600
800
1000
1200
1400
1600
1800
2000
2200
2400
Airflow Rate,(m ³/ hr)
6.8
Model: DAF060 Nominal System Curve Max System Curve
Airflow Vs. External Static Pressure
High speed
150
Medium Speed
External Static Pressure (Pa)
Operating Range
Low Speed
120 Performance test point at 50Pa 90
60
30
0 400
600
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
Airflow Rate,(m ³/ hr)
6-4
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
7. 7.1
SOUND LEVEL CHARACTERISTICS Sound Pressure Level
SM YIF 2-A.1 GB
7-1
SOUND LEVEL CHARACTERISTICS
7.2
Ducted IDU Sound Pressure Level (measured as figure 3) DAF 009 Cooling
DAF 009 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
0 63
125
250
500
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10 0
1000 2000 4000 8000
63
Octave Band Center Frequencies [Hz]
FAN SPEED
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
LINE
HI ME LO
DAF 012 Cooling
DAF 012 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65
60
NC60 NC55 NC50
50
NC45 NC40 NC35
40 30
NC30
20
NC25
10
NC20 NC15
0
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70 NC65 NC60
60
NC55 NC50 NC45
50 40
NC40 NC35
30
NC30
20
NC25
10
NC20 NC15
0 63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
FAN SPEED
63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
LINE
HI ME LO
7-2
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
DAF 018 Cooling
DAF 018 Heating Noise spectrum & NC Curves
Noise spectrum & NC Curves 90 80
80
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
90
70 NC65 NC60
60
NC55
50
NC50 NC45 NC40
40
NC35
30
NC30
20
NC25 NC20
10
NC15
70
125
250
500
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
0 63
NC65
60
0
1000 2000 4000 8000
63
Octave Band Center Frequencies [Hz]
FAN SPEED
125 250 500 1000 2000 4000 8000 Octave Band Center Frequencies [Hz]
LINE
HI ME LO
DAF 024 Cooling
DAF 024 Heating Noise spectrum & NC Curves
Noise spectrum & NC Curves 90
90
Octave Band Sound Pressure Level [dB re 20 mPa]
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
63
125 250 500 1000 2000 4000 Octave Band Ce nter Frequencies [Hz]
FAN SPEED
8000
63
125 250 500 1000 2000 4000 8000 Octave Band Center Frequencies [Hz]
LINE
HI ME LO
SM YIF 2-A.1 GB
7-3
SOUND LEVEL CHARACTERISTICS
DAF 030 Cooling
DAF 030 Heating Noise spectrum & NC Curves 90
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves 90
NC15
10
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
DAF 036 Cooling
DAF 036 Heating Noise spectrum & NC Curves
Noise spectrum & NC Curves 90
90
Octave Band Sound Pressure Level [dB re 20 mPa]
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 250 500 1000 2000 4000 Octave Band Ce nter Frequencies [Hz]
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
7-4
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
DAF 042 Cooling
DAF 042 Heating Noise spectrum & NC Curves
Noise spectrum & NC Curves
90
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
80
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
70
0
0 63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
DAF 060 Cooling
DAF 060 Heating 90
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves 90
Noise spectrum & NC Curves
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 250 500 1000 2000 4000 Octave Band Cen ter Frequencies [Hz]
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
SM YIF 2-A.1 GB
7-5
SOUND LEVEL CHARACTERISTICS
7.3
Cassette IDU Sound Pressure Level (measured as figure 4) CAF012 Cooling
CAF012 Heating
Noise spectrum & NC Curves
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
90
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
70
0
0 63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
CAF018 Cooling
CAF018 Heating
Noise spectrum & NC Curves
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
2000 [Hz] 4000 125 500 10 equencies Octave250 Band Center Fr 00
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
7-6
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
CAF024 Cooling
CAF024 Heating
Noise spectrum & NC Curves
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
70
0
0 63
125 500 1000 2000 [Hz] 4000 Octave250 Band Center Frequencies
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
CAF030 Cooling
CAF030 Heating
Noise spectrum & NC Curves
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
2000 [Hz] 4000 125 500 ter 1000 Frequencies Octave250 Band Cen
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
SM YIF 2-A.1 GB
7-7
SOUND LEVEL CHARACTERISTICS
CAF036 Cooling
CAF036Heating
Noise spectrum & NC Curves
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
70
0
0 63
125 500 1000 2000 [Hz] 4000 Octave250 Band Center Frequencies
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
CAF042 Cooling
CAF042 Heating
Noise spectrum & NC Curves
90
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
70
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 500 er 1000 2000 [Hz] 4000 Octave250 Band Cent Frequencies
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
7-8
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
7.4
Floor Ceiling IDU Sound Pressure Level (measured as figure 2) FAF012 Cooling
FAF012 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10 0
0 63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
FAN SPEED
63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
LINE
HI ME LO
SM YIF 2-A.1 GB
7-9
SOUND LEVEL CHARACTERISTICS
FAF018 Cooling
FAF018 Heating Noise spectrum & NC Curves
90
90
80
80
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10 0
0 63
125
250
500
63
1000 2000 4000 8000
FAN SPEED
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Center Frequencies [Hz]
LINE
HI ME LO
FAF024 Cooling
FAF024 Heating
Noise spectrum & NC Curves
90
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
70
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 500 1000 ncies 2000 [Hz] 4000 Octave250 Band Center Freque
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
7-10
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
FAF030 Cooling 90
FAF030 Heating 90
Noise spectrum & NC Curves
80 Octave Band Sound Pressure Level [dB re 20 mPa]
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
NC65
60
0
0 63
125 250 500 1000 2000 [Hz] 4000 Octave Band Center Frequencies
FAN SPEED
63
8000
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
FAF036 Cooling 90
FAF036 Heating 90
Noise spectrum & NC Curves
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80 Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125Octave 250 500 ter Frequencies 1000 2000 [Hz] 4000 Band Cen
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
SM YIF 2-A.1 GB
7-11
SOUND LEVEL CHARACTERISTICS
FAF042 Cooling 90
FAF042 Heating 90
Noise spectrum & NC Curves
Noise spectrum & NC Curves
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
80
80
70
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125Octave 250 500 1000 2000 [Hz]4000 Band Center Frequencies
FAN SPEED
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
LINE
HI ME LO
7.5
Outdoor units MODEL Indoor Outdoor YIF009 YIF012 YIF018 YIF024 YIF030 YIF036 YIF036T YIF042 YIF060
SPL dB(A) SPW dB(A) Cooling/Heating Cooling/Heating 55/55 65/65 56/56 66/66 56/56 66/66 59/59 69/69 59/59 69/69 60/60 70/70 60/60 70/70 60/60 70/70 64/64 74/74
Figure 5. Microphone Distance from Unit 7-12
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS
7.6
Sound Pressure Level Spectrum (Measured as Figure 5) YIF009 Cooling
YIF009 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
0 63
125
250
500
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10 0
1000 2000 4000 8000
63
Octave Band Center Frequencies [Hz]
125
90
80
80
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
30
NC25 NC20 NC15
20 10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
40
1000 2000 4000 8000
YIF012 Heating
Noise spectrum & NC Curves
50
500
Octave Band Center Frequencies [Hz]
YIF012 Cooling
60
250
70 NC65 NC60 NC55 NC50 NC45 NC40 NC35 NC30
60 50 40 30
NC25 NC20 NC15
20 10 0
0 63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
SM YIF 2-A.1 GB
63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
7-13
SOUND LEVEL CHARACTERISTICS YIF018 Cooling
YIF018 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65
60
NC60 NC55 NC50
50
NC45
40
NC40
30
NC35 NC30
20
NC25 NC20
10
NC15
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70 NC65 NC60 NC55
60 50
NC50 NC45 NC40 NC35 NC30
40 30 20
NC25 NC20
10
NC15
0
0 63
125
250
500
1000 2000
63
4000 8000
YIF024 Cooling
500
1000 2000 4000 8000
Noise spectrum & NC Curves
90
90
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
250
YIF024 Heating
Noise spectrum & NC Curves
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
7-14
125
Octave Band Center Frequencies [Hz]
Octave Band Center Frequencies [Hz]
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
63
125 250 500 1000 2000 4000 8000 Octave Band Center Frequencies [Hz]
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS YIF030 Cooling
YIF030 Heating Noise spectrum & NC Curves
90
90
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
70 60
NC65 NC60
50
NC55 NC50
40
NC45 NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
63
8000
500
1000 2000 4000 8000
YIF036 Heating Noise spectrum & NC Curves
Noise spectrum & NC Curves 90
80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
250
Octave Band Center Frequencies [Hz]
YIF036 Cooling 90
125
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
SM YIF 2-A.1 GB
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
7-15
8000
SOUND LEVEL CHARACTERISTICS YIF036T Cooling
YIF036T Heating
Noise spectrum & NC Curves
90
Noise spectrum & NC Curves 90 80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
80
NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
NC15
10
70
0
0 63
125 500 1000 2000 [Hz] 4000 Octave250 Band Center Frequencies
63
8000
YIF042 Cooling
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
7-16
8000
YIF042 Heating
Noise spectrum & NC Curves
90
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
125 500 1000 2000 [Hz] 4000 Octave250 Band Center Frequencies
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
8000
SM YIF 2-A.1 GB
SOUND LEVEL CHARACTERISTICS YIF060 Cooling
YIF060 Heating
Noise spectrum & NC Curves
90 80
80
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10
Octave Band Sound Pressure Level [dB re 20 mPa]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
90
70 NC65
60
NC60 NC55
50
NC50 NC45
40
NC40 NC35
30
NC30 NC25
20
NC20 NC15
10 0
0 63
125 500 1000 2000 [Hz] 4000 Octave250 Band Center Frequencies
SM YIF 2-A.1 GB
8000
63
125 250 500 1000 2000 4000 Octave Band Center Frequencies [Hz]
7-17
8000
ELECTRICAL DATA
8. 8.1
ELECTRICAL DATA Indoor units Ducted Model
8.2
8.3
Power Supply (V,Ph,Hz)
(A)
Power Supply Wiring No. X Cross Section (mm2)
Circuit Breaker
DAF009
220-240,1,50
6
3 X1.5
DAF012
220-240,1,50
6
3 X1.5
DAF018
220-240,1,50
6
3 X1.5
DAF024
220-240,1,50
6
3 X1.5
DAF030
220-240,1,50
6
3 X1.5
DAF036
220-240,1,50
10
3 X1.5
DAF042
220-240,1,50
10
3 X1.5
DAF060
220-240,1,50
10
3 X1.5
Indoor units Floor/Ceiling Model
Power Supply (V,Ph,Hz)
Capability of Air Switch (A)
Minimum Sectional Area of Earth Wire (mm2)
FAF012
220-240,1,50
6
3 X1.5
FAF018
220-240,1,50
6
3 X1.5
FAF024
220-240,1,50
6
3 X1.5
FAF030
220-240,1,50
6
3 X1.5
FAF036
220-240,1,50
6
3 X1.5
FAF042
220-240,1,50
6
3 X1.5
Indoor units Cassette
SM YIF 2-A.1 GB
Model
Power Supply (V,Ph,Hz)
(A)
Minimum Sectional Area of Earth Wire (mm2)
CAF012
220-240,1,50
6
3 X1.5
CAF018
220-240,1,50
6
3 X1.5
CAF024
220-240,1,50
6
3 X1.5
CAF030
220-240,1,50
6
3 X1.5
CAF036
220-240,1,50
6
3 X1.5
CAF042
220-240,1,50
6
3 X1.5
Capability of Air Switch
8-1
ELECTRICAL DATA
8.4
Outdoor units Model
Power Supply (V,Ph,Hz)
(A)
Power Supply Wiring No. X Cross Section (mm2)
Circuit Breaker
Interconnecting Cable Model No. X Cross Section (mm2)
YIF009
220-240,1,50
10
3 X2.5
2 X0.75
YIF012
220-240,1,50
13
3 X2.5
2 X0.75
YIF018
220-240,1,50
20
3 X2.5
2 X0.75
YIF024
220-240,1,50
25
3 X2.5
2 X0.75
YIF030
220-240,1,50
30
3 X6.0
2 X0.75
YIF036
220-240,1,50
40
3 X6.0
2 X0.75
YIF036T
380-415,3,50
16
5 X4.0
2 X0.75
YIF042T
380-415,3,50
20
5 X4.0
2 X0.75
YIF060T
380-415,3,50
20
5 X4.0
2 X0.75
NOTE Power wiring cord should comply with local laws and electrical regulations requirements.
8-2
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.
WIRING DIAGRAM
9.1
Indoor unit
9.1.1
Ducted type: for all models
SM YIF 2-A.1 GB
9-1
WIRING DIAGRAM
9.1.2
9-2
Floor ceiling type: for all models
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.1.3
Cassette type: for CAF012 018 024
9.1.4
Cassette type: for CAF 030 036 042
SM YIF 2-A.1 GB
9-3
WIRING DIAGRAM
9.2
Outdoor unit
9.2.1
YIF009
9-4
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.2.2
YIF012
SM YIF 2-A.1 GB
9-5
WIRING DIAGRAM
9.2.3
9-6
YIF018
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.2.4
YIF024
SM YIF 2-A.1 GB
9-7
WIRING DIAGRAM
9.2.5
9-8
YIF030
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.2.6
YIF036
SM YIF 2-A.1 GB
9-9
WIRING DIAGRAM
9.2.7
9-10
YIF036T
SM YIF 2-A.1 GB
WIRING DIAGRAM
9.2.8
YIF042
SM YIF 2-A.1 GB
9-11
WIRING DIAGRAM
9.2.9
9-12
YIF060
SM YIF 2-A.1 GB
REFRIGERATION DIAGRAMS
10.
REFRIGERATION DIAGRAMS
10.1
Cooling and Dry Mode
10.2
Heating Mode
SM YIF 2-A.1 GB
10-1
TUBING CONNECTIONS
11.
TUBING CONNECTIONS
When the outdoor unit is installed above the indoor unit, an oil trap is required every 5m along the suction line at the lowest point of the riser. In case the indoor unit is installed above the outdoor, no trap is required.
SM YIF 2-A.1 GB
11-1
CONTROL SYSTEM
12. 12.1
CONTROL SYSTEM OPERATION FLOWCHART
Cooling/Dry Operation Power On
Unit start and running at cool or dry mode
Indoor fan run
Satisfying open Comp. condition
N
Y
Comp. and outdoor fan run
Temp of indoor
N
≤Set temp Y
Comp. and outdoor fan stop
Y
SM YIF 2-A.1 GB
Comp. stop for 3 min
N
12-1
CONTROL SYSTEM Heating Operation
12.2
12-2
MAIN LOGIC
SM YIF 2-A.1 GB
CONTROL SYSTEM
12.2.1
Cooling Mode
When RAT≥SPT +1℃, the unit begins cooling operation, the compressor and the outdoor fan are running, the indoor fan is running at a set speed. When RATt≤SPT -1℃, the unit is in the cooling idle state, the compressor and the outdoor fan stop running, the indoor fan is running at a set speed. When SPT -1℃<RAT.<SPT+1℃, the unit keeps in the operation state.
12.2.2
Dry Mode
When RAT≥SPT+2℃, the unit begins cooling operation ,the compressor and the outdoor fan are running, the indoor fan is running at a low speed.
SM YIF 2-A.1 GB
12-3
CONTROL SYSTEM When RAT≤SPT-2℃, the unit is in the cooling shutdown state, the compressor and the outdoor fan stop running. When SPT-2℃<RAT<SPT+2℃, the unit is in the six-minute stop and four-minute operation state, that is, the compressor runs for 6 minutes and then stops for 4 minutes, in such cycle repeatedly; and the indoor fan operates at a low speed.
12.2.3
Heating Mode
When RAT.≤SPT-1℃, the unit begins heating operation, the compressor and the outdoor fan are running, the indoor fan is running at a set speed according to anti cold prevention conditions. When RAT≥SPT+1℃, the compressor and the outdoor fan stop running and the four-way valve keeps energized; and the indoor fan is running according to afterheat blowing conditions. When SPT-1℃<RAT<SPT+1℃, the unit keeps in the previous operation state.
12.2.4
Fan Mode
In this mode, the indoor fan may run at high, medium, low and automatic speed. The indoor fan runs at a fast speed for 5s and then runs at a set speed. The compressor, outdoor fan and 4-way valve will be OFF. In this mode, the range of setting temperature is 16~30C In Auto Fan user setting, fan speed will be adjusted automatically according to the difference between actual room temperature (RAT) and user set point temperature (SPT). Indoor Fan Speed RAT-SPT
12-4
High
Med
Low
Cooling
>=2
(0,2)
<=0
Heating
<=0
(1,3]
>3 SM YIF 2-A.1 GB
CONTROL SYSTEM
12.3
Protections
12.3.1
Indoor Coil Defrost Protection
When the unit has been running for refrigeration or dehumidification for a period and the ICT< -2℃, the unit will report a fault and stops the compressor and the outdoor unit. The unit will begin to operate after ICT≥10℃ and the compressor will run again after 3 minutes stop. 12.3.2
Deicing Protection
Defrosting start conditions: After the heating operation runs for an accumulated period of 44 minutes and the compressor continues to operate for 4 mins and 50 seconds, and a one-minute duration of OCT.≤-5℃is detected, the unit begins defrosting. If an auxiliary heater is available, it must be stopped firstly, and after 10 seconds, the four-way valve, the indoor fan, the outdoor fan and the compressor will run compulsively. Defrosting completion conditions: When defrosting runs 10 minutes or OCT≥10℃, defrosting will be completed. In such case, the four-way valve is running, the outdoor fan is running, the compressor is running compulsively, and the indoor fan operates according to anti cold prevention conditions.
12.3.3
Compressor over Heating Protection
After the compressor is started, if CTT>= 130 degree for continuous 30 seconds, E4 will be displayed, all loads (except for the four way valve) will be shut off, the compressor will stop for 3 minutes. The complete system will restart after CTT<90 degree. If such fault is reported for successive three times, the protection can not be restored itself.
12.3.4
Compressor high pressure Protection
When high pressure protection is detected for continuous 3 seconds, all loads are shut off (except for the four way valve), all buttons and remote control signals except for button ON/OFF are shielded. It cannot recover automatically, the unit should be powered off and on, or failure should be removed after power supply is restored.
12.3.5
Compressor low pressure Protection
When the unit is started or at standby (detection will begin 3 minutes after the compressor is started up) and detected breakdown of the low pressure switch for continuous 30 seconds, a fault is reported. The unit can be recovering automatically after the first 2 reported faults within 30 minutes. The third reported fault and so on can not be recovered automatically.
12.3.6
Compressor over load Protection
SM YIF 2-A.1 GB
12-5
CONTROL SYSTEM After the compressor is started, if the overload switch of the compressor is detected to shut off, the fault is reported. All loads (except for the four way valve) are shut off, the fault is displayed, and the compressor will stop for 3 minutes. If the fault is removed, the compressor can be restarted to run. If successive three compressor overload protection faults are detected within 30 minutes, the unit can not be restored itself and the buzzer will give out an alarm. Push the ON/OFF button to shut off the unit. Then push ON/OFF button again, if over load protection disappears, operation will restore. Otherwise, the fault is displayed.
12.3.7
Water Over Flow Protection
Water Over Flow is detected for continuous 8 seconds after the system is powered on, the water full protection is initiated and the indicator is twinkling (or E9 is displayed). In cooling and dry mode, the outdoor fan and the compressor are shut off and the indoor fan stops after 1 minute delay. In heating mode, the outdoor fan and the compressor are shut off, the four way valve keeps at the previous status, and the indoor fan stops after 1 minute delay. In fan mode, the load of indoor unit remains.
12.3.8
Indoor overheating in heating mode
During Heat Mode, the protection of indoor overheating prevents abnormal high pressure. When ICT reaches 58C, OFAN will stop operating and resume operating if the ICT go to normal.
12-6
SM YIF 2-A.1 GB
TROUBLESHOOTING
13.
TROUBLESHOOTING
13.1
TROUBLE TABLE
Trouble
Origin of Trouble Name
Code
Control Description Trouble Signal If water full protection continues for 2 hours and fails to restore, it is
E0
Pump Failure
Pump
believed that the water pump is at fault and all loads are shut off and fail to restore automatically. When high pressure protection is detected for continuous 3 seconds, all loads are shut off (except for the four way valve), all
E1
Compressor High
High pressure
Pressure Protection
switch
buttons and remote control signals except for button on/off are shielded and fail to restore automatically, the unit should be powered off and on, or failure should be removed after power supply is restored. When the unit has been running in cool and dry mode for a period
E2
IDU Freezing Protection
ICT
and ICT is lower than -2℃, the unit will report a fault and stops the compressor and the outdoor unit. The unit will begin to operate after ICT ≥10℃, the compressor will run again after 3 minutes stop. When the unit is started or at standby (detection will begin 3 minutes after the compressor is started up) and detected
E3
Compressor Low
Low pressure
Pressure Protection
switch
breakdown of the low pressure switch for continuous 30 seconds, a fault is reported. The unit can be restored automatically after the first 2 reported faults within 30 minutes. The third reported fault and so on can not be restored automatically. After the compressor is started, if CTT is detected to be more than or equal to 130 degree for continuous 30 seconds, E4 will be
E4
Compressor Over Heating Protection
CTT
displayed, all loads (except for the four way valve) will be shut off, the compressor will stop for 3 minutes and the complete system will restore after CTT is lower than 90 degree. If such fault is reported for successive three times, the protection can not be restored itself. After the compressor is started, if the overload switch of the compressor is detected to shut off, the fault is reported. All loads (except for the four way valve) are shut off, the fault is displayed,
E5
Compressor Overload Protection
and the compressor will stop for 3 minutes. If the fault is removed, Overload protector the compressor can be restarted to run. If successive three compressor overload protection faults are detected within 30 minutes, the unit can not be restored itself and the buzzer will give out an alarm. Push the ON/OFF button to shut off the unit. Then push ON/OFF button again, if the protection disappears, operation
SM YIF 2-A.1 GB
13-1
TROUBLESHOOTING Trouble
Origin of Trouble Name
Code
Control Description Trouble Signal will restore. Otherwise, the fault is displayed. When outdoor unit is energized and fails to receive data of indoor unit within 30 seconds, an indoor unit communication fault is reported. The compressor and the outdoor unit will be shut off, and the four way valve will be stopped 2 minutes after the compressor
E6
Communications Failure
outage in heating state. Communication
If indoor unit fails to receive information of outdoor unit, a communication fault is reported. The indoor unit is shut off and an indicator is twinkling. If the display board fails to receive information of outdoor unit, a communication fault is determined and displayed and the unit does not actuate. After communication becomes normal, the system can restore to the previous running state itself. If fan overload protection is detected for continuous 3 seconds, relevant compressor and fan shall be shut off immediately and a
E8
Indoor Fan Protection
Indoor unit
fault code E8 is displayed, and at the same time, the buzzer gives out an alarm. Push the ON/OFF key, if the fault disappears, clear the fault display and push the ON/OFF key for restarting the system. Water full is detected for continuous 8 seconds after the system is powered on, the water full protection is initiated and the indicator is twinkling (or E9 is displayed). Under refrigeration and
E9
Full Water Protection
dehumidification mode, the outdoor fan and the compressor are Liquid level switch shut off and the indoor fan stops after 1 minute delay; under heating mode, he outdoor fan and the compressor are shut off, the four way valve keeps at the previous status, and the indoor fan stops after 1 minute delay; under air supply mode, the load of indoor unit remains. When RAT failure is detected for continuous 5 seconds, RAT will be set compulsively at 24 degree, the system does not take any measure, and only the indicator is twinkling or fault code F0 is
F0
Failure of RAT
RAT
displayed. After the fault is removed, the system can restore operation by itself. In FAN mode, only the fault is displayed and the indoor fan is running normally. The fault display disappears when the fault is removed. When ICT failure is detected for continuous 5 seconds, in cool and dry mode, the system will be shut off. In heating mode, all loads
F1
Failure of ICT
ICT
except for the four way valve are shut off. The indicator is twinkling or fault code F1 is displayed. The system can restore by itself and display fault elimination after the fault is removed. Under FAN
13-2
SM YIF 2-A.1 GB
TROUBLESHOOTING Trouble
Origin of Trouble Name
Code
Control Description Trouble Signal mode, only the fault is displayed and the indoor unit is running normally. The fault display disappears when the fault is removed. When OCT failure is detected for continuous 5 seconds, in cool and dry mode, the system will be shut off. In heating mode, all loads except for the four way valve are shut off. The indicator is twinkling or fault code F2 is displayed. The system can restore by itself and
F2
Failure of OCT
OCT
display fault elimination after the fault is removed. Under FAN mode, only the fault is displayed and the indoor unit is running normally. The fault display disappears when the fault is removed. For other types of refrigeration machines except for air duct machine, condenser thermal bulb is not detected. When OAT failure is detected for continuous 5 seconds, in cool and dry mode, the system will be shut off. In heating mode, all loads except for the four way valve are shut off. The indicator is twinkling
F3
Failure of OAT
OAT
or fault code F3 is displayed. The system can restore by itself and display fault elimination after the fault is removed. Under FAN mode, only the fault is displayed and the indoor unit is running normally. The fault display disappears when the fault is removed. After the compressor is started, CTT failure is detected for continuous 5 seconds,. Under cool and dry mode, all loads will be shut off. Under heating mode, all loads except for the four way valve are shut off. The indicator is twinkling or fault code F4 is displayed. And the buzzer gives out an alarm. After the fault is removed, the
F4
Failure of CTT
CTT
system will restore by itself and clear the fault code. If CTT is short circuited, under cool and dry mode, all loads will be shut off. Under heating mode, all loads except for the four way valve are shut off. The indicator is twinkling or fault code F4 is displayed. And the buzzer gives out an alarm. After the fault is removed, the system will restore by itself and clear the fault code. When RAT(at RCW) failure is detected for continuous 5 seconds, RAT will be set compulsively at 24 degree, the system does not take any measure, and only the indicator is twinkling or fault code
F5
Failure of RAT( at RCW)
RCW
F0 is displayed. After the fault is removed, the system can restore operation by itself. Under FAN mode, only the fault is displayed and the indoor fan is running normally. The fault display disappears when the fault is removed.
13.2
FLOW CHART OF TROUBLESHOOTING
SM YIF 2-A.1 GB
13-3
TROUBLESHOOTING Service personnel shall collect the malfunction information as much as possible and research them thoroughly, list these electrical parts which may cause malfunction, service personnel shall be able to determine the specific reason and solve the faulted parts. z
Observe the status of the complete device and do not observe the partial
z
It is advised to start from the simple operation during analyzing ,judging and confirming malfunction reason, then conduct the complicated operations such removal of device, part replacement and refrigerant filling.
z
Find the malfunction reason carefully as unit may occur several malfunction at the same time and one malfunction may develop into several malfunction, so entire system analysis shall be established to make the judged result exact and credible .
13-4
SM YIF 2-A.1 GB
TROUBLESHOOTING
Malfunction display: E1 Compressor High Pressure Protection
SM YIF 2-A.1 GB
13-5
TROUBLESHOOTING
Malfunction display: E3 Compressor Low Pressure Protection
13-6
SM YIF 2-A.1 GB
TROUBLESHOOTING
Malfunction display: E4 Compressor Exhaust High Temperature(CTT) Protection Compressor Exhaust High Temperature Protection
Check if the air exhaust temperature has reached 130℃?
No Check if the resistance value of the sensor is correct?
Yes check if the liquid bypass plug is connected when the air exhaust temperature of the compressor exceeds 115℃?
No replace the corresponding
discharge temperature sensor
Yes No
Replace the main board of the outdoor unit
No
Replace the liquid bypass parts
No
refer to capacity code
Yes check if the liquid bypass parts are in good conditions, for examples, if the solenoid valve works properly or the capillary is clogged?
Yes Check if the capacity output of the outdoor unit meets with the capacity requirement of the indoor unit?
Yes Repair if system tube is leaking and add refrigerant of the same quality
SM YIF 2-A.1 GB
13-7
TROUBLESHOOTING
Malfunction display: E5 Compressor Overload
Compressor Overheat
if the compressor cable is properly connected
No
adjust the compressor cable connection
Yes if the current value is higher than the set value of the protector
No replace over-current protector
Yes No
if the high pressure of the assembly is ok
refer to “E1”
Yes No if the voltage is ok
contact power supplier
Yes communication is resumed
13-8
SM YIF 2-A.1 GB
TROUBLESHOOTING
Malfunction display: E6 Communications Failure
Communications Failure No Check if the communication cable of the indoor unit is ok
check the directions of the plug and the socket
Yes No check if the communication cable is through
replace communication cable
Yes No check the connection of the communication cable for the indoor and outdoor units
check the directions of the plug and the socket
Yes No Check if the magnetic rings are on both ends of the communication cable?
please attach the supplied magnetic rings
Yes check if power has been supplied to the outdoor unit?
No connect power to magnetic rings
Yes check if the address code of the outdoor unit has been repeated?
No correct the repeated address code
Yes check if the address code of the cable remote controller meets the address code of the indoor unit?
SM YIF 2-A.1 GB
No correct the address code of the cable remote controller
13-9
TROUBLESHOOTING
Malfunction display: E9 Water Full Protection Full Water Protection No
check if water overflows?
No
check if the voltage of liquid level switch end is ok?
replace the main board of the indoor unit
Yes
check the liquid level switch
Yes No
check if the water drainage pump works?
No
replace the main board of the indoor unit
check if the voltage for the water drainage pump end is ok?
check the cables of water drainage pump
Yes Yes check if the water drainage pipe is jammed or if water flows smoothly?
No adjust the water drainage pipe
Yes check the water drainage pipe
13-10
SM YIF 2-A.1 GB
TROUBLESHOOTING
Malfunction display: F0 Failure of RAT
Failure of Indoor Room Sensor at Air Intake check if the plug of the temperature sensor is correctly connected with socket on the main board?
No
check the directions of the plug and socket
Yes Remove the sensor to check if the resistance value is ok?
No replace temperature sensor
Yes replace main board of the indoor unit
Malfunction display: F1 Failure of ICT
Failure of Condenser Temp. Sensor
Check if the plug of the temperature sensor is correctly connected with socket on the main board?
No
check the directions of the plug and the socket
Yes Remove the temperature sensor to check if the resistance value is ok?
No
replace the temperature
Yes Remove the temperature sensor to check if the resistance value is ok?
SM YIF 2-A.1 GB
13-11
TROUBLESHOOTING
Malfunction display: F3 Failure of OAT
Failure of Outdoor Ambient Sensor
Check if the plug of the temperature sensor is correctly connected with socket on the main board?
No
check the directions of the plug and the socket
No
replace the temperature sensor
Yes Remove the temperature sensor to check if the resistance value is ok?
Yes replace the main board of the indoor unit
Malfunction display: F4 Failure of Exhaust Temp. Sensor(CTT)
Failure of Exhaust Temp. Sensor
Check if the plug of the temperature sensor is correctly connected with socket on the main board?
No
check the directions of the plug and the socket
No
replace the temperature sensor
Yes Remove the temperature sensor to check if the resistance value is ok?
Yes replace the main board of the outdoor unit
13-12
SM YIF 2-A.1 GB
TROUBLESHOOTING
Malfunction display: F5 Failure of RAT at RCW
Failure of Indoor Room Sensor at Wire Controller
Check if the plug of the temperature sensor is correctly connected with socket on the main board?
No
check the directions of the plug and the socket
No
replace the temperature sensor
Yes Remove the temperature sensor to check if the resistance value is ok?
Yes replace the main board of the outdoor unit
SM YIF 2-A.1 GB
13-13
EXPLODED VIEW & SPARE PART LIST
14. 14.1
EXPLODED VIEW & SPARE PART LIST Exploded view of Indoor unit: for DAF all models
SM YIF 2-A.1 GB
14-1
EXPLODED VIEW & SPARE PART LIST
14.2 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
14-2
Spare part list of Indoor Unit DAF009 Part Code 11725201 01499051 01259051 3900012123G 390001921G 01395768 30228205 43110239 33010020 420101851 42010194 30294219_K38101 01279051 01259054 10319051 1570520102 01339095 150024011 010087043 01309054 06320020 02112446 70819522 70819521 01719521 01425269 01498783 01499053 01078770 42020063 11120011 11120012 22202029 22202030 01079055 01079056 76712455 30510460
Part Description Filter Sub-Assy Seal of Left Side Plate Top Cover Plate Temperature Sensor Tube Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Assy Lower Cover Plate Sub-Assy Centrifugal Fan Fan Motor Fan Fixed Plate Motor Sub-Assy Evaporator Assy Right Side Plate Assy Pipe Connection Nut accessories Hook Bar Clasp Hoop Motor Support Electric Box Cover Side Plate of Air outlet Seal of Connection Pipe Upper Cover Plate of Evaporator Sensor Insert Filter Sub-Assy Filter Sub-Assy Rear Snail Shell Front Volute Casing Left Evaporator Support Evaporator Support Choke Plug of Drain Pipe Remote controller YX1F1
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 4 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.3 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Spare part list of Indoor Unit DAF012 Part Code 11725201 01499051 01259051 3900012123G 390001921G 01395767 30228205 43110239 33010027 420101851 42010194 30294219_K38101 01279051 01259054 10319051 1570520103 01339095 10319051 010090583 01309054 70819521 01719521 01845221 01498783 22202029 22202030 01499053 01078770 42020063 76515202 01079055 01079056 30510460 76712455 01425269 70819522 02112446 06320020
SM YIF 2-A.1 GB
Part Description Filter Sub-Assy Seal of Left Side Plate Top Cover Plate Temperature Sensor Tube Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor CBB611A(3uF/450V) Terminal Board Terminal Board Display Board Water Tray Assy Lower Cover Plate Sub-Assy Centrifugal Fan Fan Motor Fan Fixed Plate Centrifugal Fan Evaporator Assy Right Side Plate Assy Hoop Motor Support Electrical Retaining Plate Side Plate of Air outlet Rear Snail Shell Front Volute Casing Seal of Connection Pipe Upper Cover Plate of Evaporator Sensor Insert Cable-Cross Loop Left Evaporator Support Evaporator Support Remote controller YX1F1 Choke Plug of Drain Pipe Electric Box Cover Bar Clasp Hook Pipe Connection Nut accessories
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 4 4 1
14-3
EXPLODED VIEW & SPARE PART LIST
14.4 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
14-4
Spare part list of Indoor Unit DAF018 Part Code 11725202 01315295 01259064 3900012123G 390001921G 01395766 30228205 43110239 33010027 420101851 42010194 30294219_K38101 01278633 01265296 15002401 1570520201 01339058 10319051 01025312 01308670 22202029 22202030 01425269 01258650 01498641 02118504 76712454 01498640 01498644 30510460 01845221 02225234
Part Description Filter sub-assy Left Side Plate Assy Upper Cover Plate Assy Temperature Sensor Tube Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor CBB611A(3uF/450V) Terminal Board Terminal Board Display Board Water Tray Sub-Assy Bottom Cover Motor Sub-Assy Fan Motor Fan Fixed Plate Centrifugal Fan Evaporator Assy Right Side Plate Assy Rear Snail Shell Front Volute Casing Electric Box Cover Cover of Air Intake Air Intake Assy Hook Choke Plug of Water Pipe Seal of Connection Pipe 1 Seal of Connection Pipe 2 Remote controller YX1F1 Electrical Retaining Plate Side Plate of Air intake
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.5 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Spare part list of Indoor Unit DAF024 Part Code 11125303 01315343 01265301 3900012123G 3900012121G 01395765 30228205 43110239 33010014 420101851 42010194 30294219_K38101 01285317 01265304 15012458 15705304 01325301 15012454 01025366 01315304 01495304 76712455 43138220 15405302 01425269 02112446 450127011 30510460 01495302
SM YIF 2-A.1 GB
Part Description Filter Sub-assy Left Side Plate Sub-Assy Top Cover Temperature Sensor Temperature Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Foam Bottom Cover Fan (right) SYP-160/200J Fan motor Fan Fixed Plate Fan (left) SYP-160/200J Evaporator Assy Right Side Plate Seal of Connection Pipe Choke Plug of Drain Pipe Water Pump Water Pump Assy Electric Box Cover Hook Water Level Switch Remote controller YX1F1 Seal of Connection Pipe
qty 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1
14-5
EXPLODED VIEW & SPARE PART LIST
14.6
Spare part list of Indoor Unit DAF030 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
14-6
Part Code 11125303 01315343 01265301 3900012123G 3900012121G 01395765 30228205 43110239 33010014 420101851 42010194 30294219_K38101 01285317 01265304 15012458 15705304 01325301 15012454 01025297 01315304 01495304 76712455 43138220 15405302 01425269 02112446 30510460 450127011 01495302
Part Description Filter Sub-assy Left Side Plate Sub-Assy Top Cover Temperature Sensor Temperature Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Foam Bottom Cover Fan (right) SYP-160/200J Fan motor Fan Fixed Plate Fan (left) SYP-160/200J Evaporator Assy Right Side Plate Seal of Connection Pipe Choke Plug of Drain Pipe Water Pump Water Pump Assy Electric Box Cover Hook Remote controller YX1F1 Water Level Switch Seal of Connection Pipe
qty 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.7 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Spare part list of Indoor Unit DAF036 Part Code 111253031 01315306 01265306 3900012123G 390001921G 01395764 30228205 43110239 33010734 420101851 42010194 30294219_K38101 01285323 15265301 15018603 15705305 01325220 15018604 01025249 01315341 01495306 01495304 01375301 76712455 43138220 15405302 450127011 018953022 30510460 02112466 01845221 01425269
SM YIF 2-A.1 GB
Part Description air filter Left Side Plate Top Cover Temperature Sensor Tube Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Components Bottom Cover Fan Fan Motor Fixing Plate Sub-assy Fan Evaporator Assy Right Side Plate Sub-Assy Seal of Connection Pipe Seal of Connection Pipe Side Plate of Air intake Choke Plug of Drain Pipe Water Pump Water Pump Assy Water Level Switch Evaporator Support Plate Remote controller YX1F1 Hook Electrical Retaining Plate Electric Box Cover
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1
14-7
EXPLODED VIEW & SPARE PART LIST
14.8 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
14-8
Spare part list of Indoor Unit DAF042 Part Code 111253031 01315306 01265306 3900012123G 390001921G 01395764 30228205 43110239 33010734 420101851 42010194 30294219_K38101 01285323 15265301 15018604 15705305 01325220 15018603 0102524901 01315341 15405302 450127011 0102525001 01425269 01495304 01375301 76712455 30510460 02112466 01495306 01845221 43138220
Part Description air filter Left Side Plate Top Cover Temperature Sensor Tube Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Components Bottom Cover Fan Fan Motor Fixing Plate Sub-assy Fan Evaporator Assy Right Side Plate Sub-Assy Water Pump Assy Water Level Switch Evaporator Assy Electric Box Cover Seal of Connection Pipe Side Plate of Air intake Choke Plug of Drain Pipe Remote controller YX1F1 Hook Seal of Connection Pipe Electrical Retaining Plate Water Pump
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.9 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Spare part list of Indoor Unit DAF060 Part Code 111253032 01309108 01259111 3900012123G 3900012121G 01395764 30228205 43110239 33010734 420101851 42010194 30294219_K38101 01279114 01259114 15019066 15705305 01339110 15019065 01025331 01315339 450127011 76712707 76712708 43138220 01845221 15405302 01709070 01425269 01495304 76712454 30510460 02112466
SM YIF 2-A.1 GB
Part Description Filter Sub-assy Left Side Plate Top Cover Temperature Sensor Temperature Sensor Electric Box Assy Main PCB2 Z8235 Transformer Capacitor Terminal Board Terminal Board Display Board Water Tray Assy Bottom Cover Fan (right) SYP-200/190J-3 Fan Motor Fan Fixed Plate Fan (left) SYP-200/190J-3 Evaporator Assy Right Side Plate Sub-Assy Water Level Switch Pump Gasket 1 Pump Gasket 2 Water Pump Electrical Retaining Plate Water Pump Assy Motor Support Sub-Assy Electric Box Cover Seal of Connection Pipe Choke Plug of Water Pipe Remote controller YX1F1 Hook
qty 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 4
14-9
EXPLODED VIEW & SPARE PART LIST
14.10
14-10
Exploded view of Indoor unit: FAF012, FAF018
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.11 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Spare part list of Indoor Unit FAF012 Part Code 01302013 26232001 261124152 0130201501 1051953202 261124162 10512026 24212019 10512025 24212018 10512027 10582009 10582008 26152006 01072411 12312404 01332404 26112027 0107243701 33010020 43110237 0140240701 30227021 42011159 24253001 46010013 01412408 70812001 05235433 30545654 20102138 26252002 11122013 22412010 26252003 201620041 01532001P 01272205P 01709532 26112028 01332405 12312403 01072410 26112026 15212402 26152005 01032467 03222519
SM YIF 2-A.1 GB
Part Description Rear Side Plate Handle Decorate Plate Rear side plate assy Guide Louver Decorate Plate Shaft of Guide Louver II Guide Louver Support Shaft of Guide Louver I Louver Fixer Air Louver Swing Lever Swing Lever Right Support Plate Right Fixing Plate of Evaporator Foam Of Right Side Plate Assy Mounting Plate Right Decorative Board Pipe Clamp Plate Capacitor CBB61 Transformer Electric Box Main Board Terminal Board Wire Base Fuse Electric Box Cover Pipe Hoop Drainage Pipe Sub-assy Display Board Display Box Front Grill Clip1 Filter Sub-Assy Front Grill Front Grill Clip Button Panel Sub-Assy Front Panel Sub-assy Water Tray Panel Motor Support Left Decorative Board Mounting Plate Foam Sub-assy Left Fixing Plate of Evaporator Motor Clamp Step Motor Left Fixing Plate Evaporator Sub-Assy Liquid-intake Pipe Components
qty 1 4 1 1 1 1 2 2 1 1 12 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 4 1 1 1 1
14-11
EXPLODED VIEW & SPARE PART LIST 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
14-12
39000194 42020063 01362001 01072409 01708763 10312401 22202032 22202031 70819522 70819521 15707302
4001023214 24253002 03533425 30294219 30510136
Outdoor Tube Sensor Sensor Insert Water Lead Panel Cover Of Evaporator Fixed Mount Centrifugal Fan Propeller Housing Front Volute Casing Axes Connector Bar Clasp Hoop Fan Motor Remote Controller Connecting Cable Connecting Cable Signal Wire Wire Clamp Air Collecting Pipe Components Display Board Remote Controller
1 1 1 1 1 2 2 2 0 4 1 1 0 0 0 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.12 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25.1 25.2 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
Spare part list of Indoor Unit FAF018 Part Code 01302013 26232001 261124152 0130201501 1051953202 261124162 10512026 24212019 10512025 24212018 10512027 10582009 10582008 26152006 01072411 12312404 01332404 26112027 0107243701 33010027 43110237 0140240701 30227021 42011159 24253001 24253002 46010013 01412408 70812001 05235433 30545654 20102138 26252002 11122013 22412010 26252003 201620041 01532001P 01272205P 01709532 26112028 01332405 12312403 01072410 26112026 15212402 26152005 01032468
SM YIF 2-A.1 GB
Part Description Rear Side Plate Handle Decorate Plate Rear side plate assy Guide Louver Decorate Plate Shaft of Guide Louver II Guide Louver Support Shaft of Guide Louver I Louver Fixer Air Louver Swing Lever Swing Lever Right Support Plate Right Fixing Plate of Evaporator Foam Of Right Side Plate Assy Mounting Plate Right Decorative Board Pipe Clamp Plate Capacitor CBB61 Transformer Electric Box Main Board Terminal Board Wire Base Wire Clamp Fuse Electric Box Cover Pipe Hoop Drainage Pipe Sub-assy Display Board Display Box Front Grill Clip1 Filter Sub-Assy Front Grill Front Grill Clip Button Panel Sub-Assy Front Panel Sub-assy Water Tray Panel Motor Support Left Decorative Board Mounting Plate Foam Sub-assy Left Fixing Plate of Evaporator Motor Clamp Step Motor Left Fixing Plate Evaporator Sub-Assy
qty 1 4 1 1 1 1 2 2 1 1 12 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 4 1 1 1
14-13
EXPLODED VIEW & SPARE PART LIST 48.1 48.2 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
14-14
03222520 03533428 39000194 42020063 01362001 01072409 01708763 10312401 22202032 22202031 70819522 70819521 157073024
4001023214 30294219 30510136
Liquid-intake Pipe Components Air Collecting Pipe Components Outdoor Tube Sensor Sensor Insert Water Lead Panel Cover Of Evaporator Fixed Mount Centrifugal Fan Propeller Housing Front Volute Casing Axes Connector Bar Clasp Hoop Fan Motor Remote Controller Connecting Cable Connecting Cable Signal Wire Display Board Remote Controller
1 1 1 1 1 1 1 2 2 2 0 4 1 1 0 0 0 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.13
Exploded view of Indoor unit: FAF024
SM YIF 2-A.1 GB
14-15
EXPLODED VIEW & SPARE PART LIST
14.14 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52
14-16
Spare part list of Indoor Unit FAF024 Part Code 261124172 10512025 0133242202 24212020 24222016 1051241001 10512026 261124212 26152407 015324104 20102138 30545654 20162004 26152408 15212402 26112026 0127241401 01272403 05235433 26232001 12312407 01332404 01792408 01792409 26112033 01072438 01399620 420101851 42011159 30227021 76512210 43110237 01412408 10312401 73012401 33010027 1501240601 01722409 01702405 73012403 01332426 22202031 22202032 01302429 01702410 11122012 01362401 22412401 26252003 010024052 26252002
Part Description Decorative Board Shaft of Louver Mounting Plate Sub-Assy of Swing Vane Louver Support Louver Fixer Air Guider Assy Shaft of Louver Decorative Board Left mounting plate(Louver Motor ) Front Panel Assy Display Box Display Board Button Panel Sub-Assy Right mounting plate(Louver Motor ) Stepping Motor Motor Clamp Water Tray Assy Auxiliary Water Tray Drain Pipe Sub-Assy Handle Right side board foam sub-assy Mounting Plate Support Of Motor Bearing Fixer of Motor Support Right Decoration Panel Outlet pipe press board sub-assy (evaporator) Electric Box Assy Terminal Board Terminal Board Main PCB Z7A251B Fan Bearing Transformer 57X25C Electric Box Cover Centrifugal Fan Rotary Axis Assy Capacitor CBB611A(3uF/450V) Motor FN100B Motor Clip Motor Press Plate Joint Slack Motor Mounting Plate Sub-Assy Front Volute Casing Rear Volute Casing Rear Side Plate Motor Support Sub-Assy Filter Water Lead Plate Front Grill Assy Front Grill Clip Evaporator Assy Front Grill Clip
qty 1 2 1 3 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 2 1 1 1 1 1 1 1 2 1 1 4 2 1 1 1 2 2 1 4 4 1 1 1 1 2 2 1 2
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST 53 54 55 56 57 58 59 60 61 62 63
39000186 390001215G 01072417 26112032 01332405 12312406 01332428 01302418 10582008 10582009 10512028 30294219 30510460
SM YIF 2-A.1 GB
Temperature Sensor(15K black) Temperature Sensor Evaporator Cover Left Decoration Panel Mounting Plate Left side board foam sub-assy Bearing Mounting Plate Sub-Assy Rear Side Plate assy of Air Outlet Swing Lever Swing Link Lever Air Louver Display Board Remote controller YX1F1
1 1 1 1 1 1 1 1 3 2 22 1 1
14-17
EXPLODED VIEW & SPARE PART LIST
14.15
14-18
Exploded view of Indoor unit: FAF030
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.16 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
Spare part list of Indoor Unit FAF030 Part Code 10512025 0133242202 1051241001 26152407 015324104 30545654 26152408 15212402 0127241401 05235433 26232001 26112033 01332428 01399620 42011159 46010013 30227021 76512210 43110237 01412408 10312401 33010027 1501240601 73012403 22202031 22202032 01302429 01702410 01362401 22412401 01029414 390001215G 26112032 10582008 10512028 15212402 01792408 10512026 420101851 01072417 30294219 01332405 24222016 01722409 01702405 01072438 30510460 01332404 73012401
SM YIF 2-A.1 GB
Part Description Shaft of Louver Mounting Plate Sub-Assy of Swing Vane Air Guider Assy Left mounting plate(Louver Motor ) Front Panel Assy Display Board Right mounting plate(Louver Motor ) Stepping Motor Water Tray Assy Drain Pipe Sub-Assy Handle Right Decoration Panel Bearing Mounting Plate Sub-Assy Electric Box Assy Terminal Board Fuse 5A/250V Main PCB Z7A251B Fan Bearing Transformer 57X25C Electric Box Cover Centrifugal Fan Capacitor CBB611A(3uF/450V) Motor FN100B Joint Slack Front Volute Casing Rear Volute Casing Rear Side Plate Motor Support Sub-Assy Water Lead Plate Front Grill Assy Evaporator Assy Temperature Sensor Left Decoration Panel Swing Lever Air Louver Stepping Motor Support Of Motor Bearing Shaft of Louver Terminal Board Evaporator Cover Display Board Mounting Plate Louver Fixer Motor Clip Motor Press Plate Outlet pipe press board sub-assy (evaporator) Remote controller YX1F1 Mounting Plate Rotary Axis Assy
qty 2 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 2 1 1 4 1 1 2 4 4 1 1 1 2 1 1 1 3 22 1 2 2 1 1 1 1 2 1 2 1 1 1 2
14-19
EXPLODED VIEW & SPARE PART LIST 42020063 01792409 76512404 01702405 24222016 22412011 11122012 39000186 10582009
14-20
Sensor Insert Fixer of Motor Support O-Gasket of Bearing Motor Press Plate Louver Fixer Grille Filter Temperature Sensor(15K black) Swing Link Lever
1 1 2 1 2 1 1 1 2
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.17
Exploded view of Indoor unit: FAF036/042
SM YIF 2-A.1 GB
14-21
EXPLODED VIEW & SPARE PART LIST
14.18 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 49 50 51
14-22
Spare part list of Indoor Unit FAF036 Part Code 261124152 10512025 0133241802 24212019 24212018 1051240602 10512026 261124162 26152405 015324091 20102138 30545654 201620041 26152406 15212402 26112026 0127240802 01272409 05235433 26232001 12312404 01332404 01792408 01792407 26112027 01072437 01399619 420101851 42011159 30227021 76512210 43110237 01412408 10319051 73012402 33010037 15012405 01722410 01702405 73012403 01332425 22202030 22202029 01302431 01702411 11122013 01362407 22412010 22412012 26252003 01029610
Part Description Left Decoration Plate Shaft of Louver Swing Louver Fixer sub-assy Guide Louver Holder Louver Fixer Guide Louver Shaft of Louver Right Decoration Plate Left Swing Motor Fixer Front Panel Assy Display Box Display Board Button Panel Sub-Assy Right Swing Motor Fixer Stepping Motor Motor Clamp Water Tray Sub-Assy Water Tray Drain Pipe Sub-Assy Handle Foam of Right Side Plate Mounting Plate Support Of Motor Bearing Shoe Plate of Motor Support Decorative Board Evaporator outlet tube press plate sub-assy Electric Box Assy Terminal Board Terminal Board Main PCB Z7A251B Fan Bearing Transformer 57X25C Electric Box Cover Centrifugal Fan Rotary Axis Sub-Assy Capacitor Fan Motor Motor Fixer Motor Press Plate Joint Slack Motor Mounting Plate Sub-Assy Front Volute Casing Rear Snail Shell Rear Side Plate Assy Motor Support Sub-Assy Filter Water Lead Plate Sub-Assy Grille Front Grill Front Grill Clip Evaporator Assy
qty 1 3 1 4 3 1 2 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 2 2 1 4 4 1 1 1 1 1 4 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST 52 53 54 55 56 57 58 59 60 61 62 63
26252002 39000194G 39000186 01072409 26112028 01332405 12312403 01332417 01302417 10582008 10582009 10512027 45020051 01722405 30294219 30510460
SM YIF 2-A.1 GB
Front Grill Clip Temp Sensor (20K) Temperature Sensor(15K black) Cover Of Evaporator Decorative Board Mounting Plate Left Side Foam Bearing Mounting Plate Assy Rear Side Plate Sub-Assy Swing Lever Swing Link Lever Air Louver Dial Switch of Three-way Retaining Plate of Capacitor Display Board Remote controller YX1F1
1 1 1 1 1 1 1 1 1 2 4 26 1 1 1 1
14-23
EXPLODED VIEW & SPARE PART LIST
14.19 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 49
14-24
Spare part list of Indoor Unit FAF042 Part Code 261124152 10512025 0133241802 24212019 24212018 1051240602 10512026 261124162 26152405 015324091 20102138 30545654 201620041 26152406 15212402 26112026 0127240802 01272409 05235433 26232001 12312404 01332404 01792408 01792407 26112027 01072437 01399619 420101851 42011159 30227021 76512210 43110237 01412408 10319051 73012402 33010037 15012405 01722410 01702405 73012403 01332425 22202030 22202029 01302431 01702411 11122013 01362407 22412010 22412012
Part Description Left Decoration Plate Shaft of Louver Swing Louver Fixer sub-assy Guide Louver Holder Louver Fixer Guide Louver Shaft of Louver Right Decoration Plate Left Swing Motor Fixer Front Panel Assy Display Box Display Board Button Panel Sub-Assy Right Swing Motor Fixer Stepping Motor Motor Clamp Water Tray Sub-Assy Water Tray Drain Pipe Sub-Assy Handle Foam of Right Side Plate Mounting Plate Support Of Motor Bearing Shoe Plate of Motor Support Decorative Board Evaporator outlet tube press plate sub-assy Electric Box Assy Terminal Board Terminal Board Main PCB Z7A251B Fan Bearing Transformer 57X25C Electric Box Cover Centrifugal Fan Rotary Axis Sub-Assy Capacitor Fan Motor Motor Fixer Motor Press Plate Joint Slack Motor Mounting Plate Sub-Assy Front Volute Casing Rear Snail Shell Rear Side Plate Assy Motor Support Sub-Assy Filter Water Lead Plate Sub-Assy Grille Front Grill
qty 1 3 1 4 3 1 2 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 2 2 1 4 4 1 1 1 1 1 4
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST 50 51 52 53 54 55 56 57 58 59 60 61 62 63
26252003 01029612 26252002 39000194G 39000186 01072409 26112028 01332405 12312403 01332417 01302417 10582008 10582009 10512027 45020051 01722405 30294219 30510460
SM YIF 2-A.1 GB
Front Grill Clip Evaporator Assy Front Grill Clip Temp Sensor (20K) Temperature Sensor(15K black) Cover Of Evaporator Decorative Board Mounting Plate Left Side Foam Bearing Mounting Plate Assy Rear Side Plate Sub-Assy Swing Lever Swing Link Lever Air Louver Dial Switch of Three-way Retaining Plate of Capacitor Display Board Remote controller YX1F1
1 1 1 1 1 1 1 1 1 1 1 2 4 26 1 1 1 1
14-25
EXPLODED VIEW & SPARE PART LIST
14.20
14-26
Exploded view of Indoor unit: CAF012/018
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.21
Spare part list of Indoor Unit CAF012
NO.
Part Code
Part Description
qty
1
30297301
Display Board Z7A351
1
2
10312702
Centrifugal Fan
1
3
15012707
Fan Motor
1
4
01029608
Evaporator Assy
1
5
01702702
Motor Mounting Rack
1
9
01382719
Tube Exit Plate Assy
1
10
01399418
Electric Box Assy
1
11
42010258
Terminal Board
1
12
43110233
Transformer 48X26G
1
13
33010026
Capacitor CBB61
1
14
30227110
Main PCB Z71351D
1
15
01412723
Electric Box Cover
1
18
390000592
Tube Sensor
1
20
450127011
Water Level Switch
1
21
05232722
Drain Pipe for Water Pump
1
22
43130320
Water Pump
1
23
39000191
Ambient Temperature Sensor
1
01362704
Right baffle Assy
1
01332708
Pump Support Assy
1
20182704
Water Tray Assy
1
20182703
Water Tray
1
45020051
Dial Switch of Three-way
1
49010252
Radiator
1
40030079
Connecting Wire
1
420101851
Terminal Board
1
40010232
4-core Cable
1
SM YIF 2-A.1 GB
14-27
EXPLODED VIEW & SPARE PART LIST
14.22
Spare part list of Indoor Unit CAF018
NO.
Part Code
Part Description
qty
1
30297301
Display Board Z7A351
1
2
10312702
Centrifugal Fan
1
3
15012707
Fan Motor
1
4
01029408
Evaporator Assy
1
5
01702702
Motor Mounting Rack
1
9
01382719
Tube Exit Plate Assy
1
10
01399408
Electric Box Assy
1
11
42010258
Terminal Board
1
12
43110233
Transformer 48X26G
1
13
33010026
Capacitor CBB61
1
14
30227110
Main PCB Z71351D
1
15
01412723
Electric Box Cover
1
18
390000592
Tube Sensor
1
20
450127011
Water Level Switch
1
22
43130320
Water Pump
1
23
39000191
Ambient Temperature Sensor
1
14-28
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.23
Exploded view of Indoor unit:CAF024/036/042
SM YIF 2-A.1 GB
14-29
EXPLODED VIEW & SPARE PART LIST
14.24 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
14-30
Spare part list of Indoor Unit CAF024 Part Code 01382715 01332701 01302718 01302715 01222701 01302714 01702701 15012703 10312705 01074042 390001921G 010027101 20182701 01412721 10372701 01399533 42010258 43110226 20122054 390001911 20122055 30227111 33010010 01072703 10312701 43130324 45010201 05230026 01302716 01252713 30294219 420101851 05232702 30510460
Part Description Tube Exit Plate Assy Major Mounting Plate Front Side Plate Left Side Plate Assy Base Plate Assy Rear Side Plate Motor Mounting Rack Fan Motor Centrifugal Fan Connection Sheet Assy Tube Sensor Evaporator Assy Water Tray Assy Electric Box Base Plate Flow Guide Loop Electric Box Assy Terminal Board Transformer Electric Box Cover Sub-Assy1 Ambient Temperature Sensor Electric Box Cover Sub-Assy2 Main PCB Z71351E Capacitor CBB61 3.5kuF/450V Evaporator of Fixed Mount Fan Fixer Water Pump Water Level Switch Drain Pipe for Water Pump Right Side Plate Pump Backup Cover Plate Assy Display Board Terminal Board Drain Hose Assy Remote Controller
qty 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.25 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Spare part list of Indoor Unit CAF036 Part Code 01382715 01332701 01302713 01302711 01222701 01302709 01702701 15012706 10310101 01072732 390001921G 01029402 20182701 01412721 10372722 01399531 42010258 43110226 20122054 390001911 20122055 30227111 33010012 01072707 10312701 43130324 45010201 05230026 01302712 01252713 30294219 420101851 01332751 05232702 30510460
SM YIF 2-A.1 GB
Part Description Tube Exit Plate Assy Major Mounting Plate Front Side Plate Left Side Plate Assy Base Plate Assy Rear Side Plate Motor Mounting Rack Fan Motor Centrifugal Fan Evaporator Linkage Tube Sensor Evaporator Assy Water Tray Assy Electric Box Base Plate Flow Guide Loop Electric Box Assy Terminal Board Transformer Electric Box Cover Sub-Assy1 Ambient Temperature Sensor Electric Box Cover Sub-Assy2 Main PCB Z71351E Capacitor Evaporator of Fixed Mount Fan Fixer Water Pump Water Level Switch Drain Pipe for Water Pump Right Side Plate Assy Pump Backup Cover Plate Assy Display Board Terminal Board Water Pump Assy Drain Hose Assy Remote controller YX1F1
qty 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1
14-31
EXPLODED VIEW & SPARE PART LIST
14.26 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
14-32
Spare part list of Indoor Unit CAF042 Part Code 01382715 01332701 01302713 01302711 01222701 01302709 01702701 15012706 10310101 01072732 390001921G 01029405 20182701 01412721 10372722 01399530 42010258 43110226 20122054 390001911 20122055 30227111 33010012 01072707 10312701 01332751 45010201 05230026 01302712 01252713 30294219 420101851 05232702 05232044 43130324 30510460
Part Description Tube Exit Plate Assy Major Mounting Plate Front Side Plate Left Side Plate Assy Base Plate Assy Rear Side Plate Motor Mounting Rack Fan Motor Centrifugal Fan Evaporator Linkage Tube Sensor Evaporator Assy Water Tray Assy Electric Box Base Plate Flow Guide Loop Electric Box Assy Terminal Board Transformer Electric Box Cover Sub-Assy1 Ambient Temperature Sensor Electric Box Cover Sub-Assy2 Main PCB Z71351E Capacitor Evaporator of Fixed Mount Fan Fixer Water Pump Assy Water Level Switch Drain Pipe for Water Pump Right Side Plate Assy Pump Backup Cover Plate Assy Display Board Terminal Board Drain Hose Assy Drain Hose Water Pump Remote controller YX1F1
qty 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.27
Exploded view of Indoor unit: CAF030
SM YIF 2-A.1 GB
14-33
EXPLODED VIEW & SPARE PART LIST
14.28 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
14-34
Spare part list of Indoor Unit CAF030 Part Code 01382715 01332701 01302718 01302715 01222701 01302714 01702701 15709404 10312705 01074042 390001921G 01029415 20182701 01412721 10372701 01399532 42010258 43110226 20122054 390001911 30510460 20122055 30227111 33010010 05232702 01072703 10312701 43130324 45010201 05230026 01302716 01252713 30294219
Part Description Tube Exit Plate Assy Major Mounting Plate Front Side Plate Left Side Plate Assy Base Plate Assy Rear Side Plate Motor Mounting Rack Fan Motor Centrifugal Fan Connection Sheet Assy Tube Sensor Evaporator Assy Water Tray Assy Electric Box Base Plate Flow Guide Loop Electric Box Assy Terminal Board Transformer Electric Box Cover Sub-Assy1 Ambient Temperature Sensor Remote controller YX1F1 Electric Box Cover Sub-Assy2 Main PCB Z71351E Capacitor CBB61 3.5kuF/450V Drain Hose Assy Evaporator of Fixed Mount Fan Fixer Water Pump Water Level Switch Drain Pipe for Water Pump Right Side Plate Pump Backup Cover Plate Assy Display Board
qty 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.29
Exploded view of Outdoor unit: YIF009/012
SM YIF 2-A.1 GB
14-35
EXPLODED VIEW & SPARE PART LIST
14.30 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
14-36
Spare part list of Outdoor Unit YIF009 Part Code 22413007 200020153 10333413 15013067 01703068 01125241 01253443 01473014 33010743 01395761 70410523 430004022 71010103 04635715 0130200404 26233433 07100003 01713041 00120145 01239052 01195701P 3900012128G 30224058 43110233 42011103 none 420111531 430004002 33010026 07100005 00180084 76710205 06123401 420101851
Part Description Grille Front Panel Sub-Assy Axial-flow Fan Fan Motor Motor Support Condenser Assy Top Cover Plate Rear Grill Capacitor CBB65 Electric Box Assy Isolation Washer 4-Way Valve Fixed Clamp discharge pipe Right Side Plate Assy Big Handle Cut-off Valve (1/4) Valve Support Compressor and Fittings Clapboard Chassis sub-assy Tube sensor Main Board Transformer 48X26G Terminal Board 2-8 AC Contactor Connection Board 4-way Valve Accessory Capacitor CBB61 2.5uF/450V Cut-off Valve (3/8) Overload Protector Compressor Gasket 4CYC00188 Drainage Connecter Terminal Board
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 3 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.31 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Spare part list of Outdoor Unit YIF012 Part Code 22413433 200020153 10333004 15013071 01703086 01125244 01253443 01473014 33010743 01395763 70410523 430004032 71010103 04635715 0130200404 26233433 07100003 01713041 00120139 01239052 01195702P 3900012128G 30224058 43110233 42011103 none 420111531 430004002 33010027 07100006 00180255 76710272 420101851 06123401
SM YIF 2-A.1 GB
Part Description Front grill Front Panel Sub-Assy Axial Flow Fan Motor FW48G motor support Condenser Assy Top Cover Plate Rear Grill Capacitor CBB65 Electric Box Assy Isolation Washer 4-way Valve Fixed Clamp discharge pipe Right Side Plate Assy Big Handle Cut-off Valve (1/4) Valve Support Compressor and Fittings Clapboard Metal Base Tube sensor Main Board Transformer 48X26G Terminal Board 2-8 AC Contactor Connection Board 4-way Valve Accessory Capacitor CBB611A(3uF/450V) Cut-off Valve Overload Protector Compressor Gasket Terminal Board Drainage Connecter
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 3 1 1
14-37
EXPLODED VIEW & SPARE PART LIST
14.32 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
14-38
Spare part list of Outdoor Unit YIF018 Part Code 22413007 01533012 10333413 15013071 01703391 01125252 01253443 01473014 33000039 01395758 70410523 430004032 71010103 04635331 0130200401 26233433 07100004 01713041 00103702 01245244 01203144 3900012128G 30224058 43110233 42011103 none 420111531 430004002 33010027 07100006 00180157 76710202 420101851 06123401
Part Description Grille Front Panel Axial-flow Fan Motor FW48G Motor Support Condenser Assy Top Cover Plate Rear Grill Capacitor Electric Box Assy Isolation Washer 4-way Valve Fixed Clamp discharge pipe Right Side Plate Assy Big Handle Cut-off Valve Valve Support Compressor and Fittings Clapboard Underpan Sub-Assy Tube sensor Main Board Transformer 48X26G Terminal Board 2-8 AC Contactor Connection Board 4-way Valve Accessory Capacitor CBB611A(3uF/450V) Cut-off Valve Overload Protector Compressor Gasket 4CYC00008 Terminal Board Drainage Connecter
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 3 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.33
Exploded view of Outdoor unit: YIF024
SM YIF 2-A.1 GB
14-39
EXPLODED VIEW & SPARE PART LIST
14.34 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
14-40
Spare part list of Outdoor Unit YIF024 Part Code 22414102 26235401 01433017P 01303251P 26235253 10335253 150154512 01705103 01255013P 01125262 01233024 430004002 04145220 01395744 44010222 30224058 420111451 01303115 01473028 420101851 43110233 33010013 33000039 01715001 07103030 00103709 01205201 06813401 06123401 430004032 46020007 460200061 00180253 76710238 01703027 04324001 01173021 07130209 42011103 3900012121G 765152121 01413047 3900012132G
Part Description Panel Grille Small Handle Front Plate Front Side Plate Handle Axial-flow Fan Motor LW92H Motor Support Top Cover Condenser Assy Mid Clapboard Sub-Assy 4-way Valve Accessory 4-way Valve Assy Electric Box Assy Double Pole AC Contactor Main Board Terminal Board Rear Side Plate Sub-Assy Mesh Enclosure Terminal Board Transformer 48X26G Capacitor CBB61 Capacitor Valve Support Sub-Assy Gas Valve Sub-Assy Compressor ATH290CV-C9LU Underpan Sub-Assy Choke Plug Drainage Connecter 4-way Valve Low Pressure Switch Pressure Switch Overload Protector Compressor Gasket Motor Support One-way Valve Condenser support plate Cut-off Valve Terminal Board 2-8 Temperature Sensor Electric Heating Strip Electric Box Cover Plate Ambient Temperature Sensor
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.35
Exploded view of Outdoor unit: YIF030
SM YIF 2-A.1 GB
14-41
EXPLODED VIEW & SPARE PART LIST
14.36 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
14-42
Spare part list of Outdoor Unit YIF030 Part Code 01305043P 01475008 10335005 01125339 01705016 01255007 01235061 04145321 07133157 071302391 01195236P 00103105 1501506207 26235001 01715012P 01305044P 26235401 01305072P 22415003 01435004P 33000039 43110233 44010222 01395631 420111451 420101851 30224058 33010009 06123401 01175037 42011147 00180270 76812206 02141375 4300008201 460200061 46020007 06813401 765152123 390001921G 42010157 390002062G 20113003 430004002 39000017G
Part Description Left Side Plate Rear Grill Axial Flow Fan Condenser Assy Motor Support Sub-Assy Top Cover Sub-Assy Clapboard 4-way Valve Assy Cut-off Valve Cut-off Valve Chassis Sub-assy Compressor Fan Motor Big Handle Valve Support Sub-Assy Right Side Plate Small Handle Front Side Plate Front Grill Cabinet Capacitor Transformer 48X26G Double Pole AC Contactor Electric Box Assy Terminal Board Terminal Board Main Board Capacitor CBB61 7uF/450V Drainage Connecter Condenser support plate Terminal Board Overload Protector Compressor Gasket Capacitor Clamp 4-way Valve Pressure Switch Low Pressure Switch Choke Plug electrical heater Tube Sensor Terminal Temperature Sensor Insulating Plate of Electric box Cover 4-way Valve Accessory Temperature Sensor
qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 3 1 1 2 1 1 1 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.37
Exploded view of Outdoor unit: YIF036
SM YIF 2-A.1 GB
14-43
EXPLODED VIEW & SPARE PART LIST
14.38 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
14-44
Spare part list of Outdoor Unit YIF036 Part Code 22265401 01435103P 01475401 01255012P 01305402 26235253 01715402 01205402 01305406 10335401 01125245 01705402 150154011 01235403 43000338 430004002 00205226 07130212 07130210 460200061 3900012128G 01395757 420101851 4311023302 420111451 30224058 33010013 44010254 42011147 33000039 39000017G 26235401 06123401 46020007 04675735 07255403 42020063 06813401 76515404 76710209 01175402
Part Description Front Grill Housing Rear Grill Top Cover Rear Side Plate Sub-Assy Handle Valve Support Sub-Assy Underpan Sub-Assy Front Side Plate Sub-Assy Axial-flow Fan Condenser Assy Motor Support Sub-Assy Motor LW92D Clapboard Sub-Assy 4-way Valve 4-way Valve Accessory Compressor Cut-off Valve Cut-off Valve Pressure Switch Tube sensor Electric Box Assy Terminal Board Transformer Terminal Board Main Board Capacitor CBB61 AC Contactor Terminal Board Capacitor Temperature Sensor Small Handle Drainage Connecter Low Pressure Switch Inhalation Tube Sub-Assy Vapor Liquid Separator Components Sensor Insert Choke Plug Electric Heater Band Compressor Gasket M-0101-DSB Condenser support assy
qty 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 3 1
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.39 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
Spare part list of Outdoor Unit YIF036T Part Code 22265401 01435103P 01475401 01255012P 01305402 26235253 01715402 01205403 01305403 10335401 01125245 01705402 150154011 01235403 43000338 430004002 00129050 07130212 07130210 460200061 3900012128G 01395511 420101851 4311023302 42011103 30224058 33010013 44010226 76515202 42011147 42011043 46020052 07220016 04675735 76710209 76515404 3900012132G 39000017G 42010157 01175402 06813401 07255403 01305406 26235401 06123401 46020115 05212423 49010252 46020007
SM YIF 2-A.1 GB
Part Description Front Grill Housing Rear Grill Top Cover Rear Side Plate Sub-Assy Handle Valve Support Sub-Assy Underpan Assy Front Side Plate Axial-flow Fan Condenser Assy Motor Support Sub-Assy Motor LW92D Clapboard Sub-Assy 4-way Valve 4-way Valve Accessory Compressor and Fittings Cut-off Valve Cut-off Valve Pressure Switch Tube sensor Electric Box Assy Terminal Board Transformer Terminal Board 2-8 Main Board Capacitor CBB61 AC Contactor Cable-Cross Loop Terminal Board Terminal Board Anti-phase Protector Bidirection Strainer Inhalation Tube Sub-Assy Compressor Gasket M-0101-DSB Electric Heater Band Ambient Temperature Sensor Temperature Sensor Terminal Condenser support assy Choke Plug Vapor Liquid Separator Components Front Side Plate Sub-Assy Small Handle Drainage Connecter Over Current Protector Tube Sensor Bushing Radiator Low Pressure Switch
qty 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 3 1 1 1 2 1 2 1 1 1 1 1 1 1 1
14-45
EXPLODED VIEW & SPARE PART LIST
14.40
14-46
Exploded view of Outdoor unit: YIF042
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.41 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 21 22 23 24 25 26 27 28 30 31 33 34 36 37 38 39
Spare part list of Outdoor Unit YIF042 Part Code 22414102 01435436 01475432 01255013P 01303712 26235253 01715001 01205433 01305430 10338731 01125246 01705433 15013110 01235440 07225018 43000338 04145228 00129051 07130212 76710209 460200061 3900012129G 3900012121G 39000285 01395748 420101851 43110171 42011043 46020112 30224058 44010226 46020052 33010010 42011103 06123401 06813401 43110242 46020007 430004002 071302392 01895203 04675319 76515404
SM YIF 2-A.1 GB
Part Description Panel Grille Front Plate Rear Grill Top Cover Rear Side Plate Sub-Assy Handle Valve Support Sub-Assy Underpan Sub-Assy Front Side Plate Sub-Assy Axial Flow Fan φ472X165 Condenser Assy Motor Support Sub-Assy Fan Motor Clapboard Sub-Assy Gas-liquid Separator Sub-Assy 4-way Valve 4-way Valve Sub-Assy Compressor and Fittings Cut-off Valve Compressor Gasket M-0101-DSB Pressure Switch Discharge sensor Temperature Sensor Temperature Sensor Electric Box Assy Terminal Board Transformer Terminal Board Over Current Protector Main Board AC Contactor Anti-phase Protector Capacitor CBB61 3.5kuF/450V Terminal Board 2-8 Drainage Connecter Choke Plug Power Transformer Low Pressure Switch 4-way Valve Accessory "Valve 1/2""" Condenser support sub-assy Inhalation Tube Sub-Assy Electric Heater Band
qty 2 1 1 1 1 3 1 1 1 2 1 1 2 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 3 1 1 1 1 1 1 1
14-47
EXPLODED VIEW & SPARE PART LIST
14.42
14-48
Exploded view of Outdoor unit: YIF060
SM YIF 2-A.1 GB
EXPLODED VIEW & SPARE PART LIST
14.43 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 21 22 23 24 25 26 27 28 30 31 33 34 36 37 38 39
Spare part list of Outdoor Unit YIF060 Part Code 22414102 01435436 01475432 01255472 01303712 26235253 01715001 01205472 01305431 10335253 01125292 01705471 15701108 01235473 07225016 43000338 04145277 00129052 07130212 76710209 460200061 3900012121G 3900012129G 39000285 01395746 420101851 43110171 42011043 46020103 30224058 44010213 46020052 33010037 42011103 06123401 49010252 06813401 42010157 43110242 036390664 430004002 07130210 49010104 02145435 46020007 76515404
SM YIF 2-A.1 GB
Part Description Panel Grille Front Plate Rear Grill Top Cover Rear Side Plate Sub-Assy Handle Valve Support Sub-Assy Underpan Sub-Assy Front Side Plate Axial-flow Fan Condenser Assy Motor Support Sub-Assy Motor LW92R Mid Clapboard Sub-Assy Gas-liquid Separator Assy 4-way Valve 4-way Valve Sub-Assy Compressor and Fittings Cut-off Valve Compressor Gasket M-0101-DSB Pressure Switch Temperature Sensor Discharge sensor Temperature Sensor Electric Box Assy Terminal Board Transformer Terminal Board Over Current Protector Main Board AC Contactor Anti-phase Protector Capacitor Terminal Board 2-8 Drainage Connecter Radiator Choke Plug Terminal Power Transformer Inhalation Tube Sub-Assy 4-way Valve Accessory Cut-off Valve Magnetic Ring Liquid Accumulator Clamp Low Pressure Switch Electric Heater Band
qty 2 1 1 1 1 3 1 1 1 2 1 1 2 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 3 2 1 1 1 1 1 1 1 1
14-49
APPENDIX
15.
APPEDDIX
APPENDIX
SM YIF 2-A.1 GB
15-1