Transcript
Zelio RXG interface relay Essentials All-in-1 Document
2014
Schneider Electric - Industry Business – H2I – Relays Business
1
Zelio RXG presentation Presentation Zelio RXG interface relay is widely used in PLC interface application, for its reliable installation, easy test & maintenance, slim and spacing saving. The RXG interface relay range comprises: 1.10 A relays with 1C/O contact and 5 A relays with 2C/O contacts. 2.Sockets with separate contact terminals with Screw connector connection, 35mm DIN rail mounting and Panel mounting. 3.Protection modules(diode, diode + LED, RC circuit, or varistor + LED) common to all RXG and RSB sockets. 4.A plastic maintaining clamp is supplied together for all RXG sockets. 5.Clip-in legends for all RXG and RSB sockets.
5* 2
1
4
*common with RSB range. Schneider Electric - Industry Business – H2I – Relays Business
3*
2
Zelio RXG relay description Presentation 1.Spring return pushbutton for testing the contacts (green: dc, red: ac). 2.Mechanical “relay status” indicator for the outputs. 3.Lock-down door enabling forced maintaining of the contacts for test sequences or maintenance purposes. 4.LED (depending on version) indicating the relay status for the power. 5.Removable legend for relay identification. 6.Five, or eight Fast-on type pins. 7.Clear cover type.
5
6
4 2 1 3
7
Schneider Electric - Industry Business – H2I – Relays Business
3
Zelio RXG socket description Presentation Sockets with separate contact terminals (1) 1.Connection by connector. 2.Five or eight female contacts for the relay pins. 3.A fixing hole for panel mounting. 4.Location for protection modules. 5.Locking components for plastic maintaining clamp. 6.Locating slot for mounting on DIN rail. (1) The inputs and outputs are separated from the relay supply.
1 Input(s) 6 Outputs
2 5 3 4
Relay supply
Schneider Electric - Industry Business – H2I – Relays Business
4
Zelio RXG relay Specification General Characteristics Standard Certification and compliance Pollution Degree Overvoltage Category Ambient temperature
IEC 61810-1, UL 508, CSA C22-2 No 14, CE, cURus, UL listed, CSA, EAC, RoHS, REACH, China RoHS 2 III
Storage Operation
Relative Humidity Vibration resistance
In operation Not operation
Degree of protection Shock resistance
In operation Not operation
Protection category Mounting Position
-40 to +85 deg C -40 to +70 deg C Operating: 10% to 85% 3 gn (10…150Hz), 1.5mm DA 10-55Hz 5 gn (10…150Hz), 1.5mm DA 10-55Hz IP40 20 gn 100 gn RT I Any Mounting Position
Relay Type Insulation Characteristics IEC UL, CSA Rated Impulse Withstand Voltage Between coil & contact Between polest Between contacts Between Terminal & Product Surface Dielectric Strength Between coil & contact Between polest Between contacts Between Terminal & Product Surface Rated Insulation Voltage Ui
Insulation Resistance
Schneider Electric - Industry Business – H2I – Relays Business
1-Pole 2-Pole V kV kV kV kV
250 300 6 --
4
2.5 2.5 5000 VAC --3000 VAC 1000 VAC 3000 1000 Megohms @ 500 VDC
5
Zelio RXG relay Specification Contact Characteristics Contact Configure Contact material Contact Resistance Conventional thermal current <=55oC Nominal Load (resistive) AC Nominal Load (resistive) DC Rated operational current(IEC) Rated operational current(UL)
Switching Voltage(Maximum) Switching Capacity (Maximum) AC Switching Capacity (Maximum) DC Switching Current(Minimum) Switching Voltage(Minimum) Switching Capacity (Minimum) Maximum Operating Rate (No Load)
mΩ
1 C/O (SPDT) 2 C/O (DPDT) AgSnO 100 mOhm
A A A A A
10 5 10A /250VAC 5A /250VAC 10A /30VDC 5A /30VDC NO 10 5 NC 10 5 10A/300VAC 5A /300VAC 10A /30VDC 5A /30VDC 1/2 hp @ 240 Vac 1/3 hp @ 240 Vac A 1/3 hp @ 120 Vac 1/6 hp @ 120 Vac IEC 250 VAC / 125VDC UL, CSA V 300V VA 2500 1250 W 300 150 mA 100 10 VDC 5 mW 500 50 18000 Operating cycles/hour
Maximum Operating Rate (Under Load) Utilization coefficient Mechanical durability AC Coil DC Coil Electrical durability Resistive Inductive
Million Million Million Million
1800 Operating cycles/hour Continuous / 20% 10 10 0.1 0.1
Coil Characteristics Average Consumption (AC)
VA
1.0 @ 60Hz
Average Consumption (DC)
W
0.53W
Drop out Voltage Threshold (AC)
>=0.30Uc@min ambient temperature
Drop out Voltage Threshold (DC)
>=0.10Uc@ min ambient temperature
Operating Range (AC)
0.8~1.1Uc@ max ambient temperature
Operating Range (DC) Coil Insulation Pickup time Release time Control Voltage
0.75~1.1Uc@ max ambient temperature Class "F" 20 Max(With LED) 20 Max(With LED) 24/48/120/220/230 6/12/24/48/60/110
mS mS AC DC
Schneider Electric - Industry Business – H2I – Relays Business
6
Zelio RXG socket Specification Socket type General Characteristics Conforming to standard Certification and compliance (2012) Rated Current(IEC) Rated Voltage(IEC/UL) Degree of protection Overvoltage category Degree of pollution Environment Ambient Temperature Storage temperature Relative Humidity (RH)
Terminal Type of terminal Screw Size Terminal referencing Maximum torque Maximum Wire Pull Force
Terminal Connection
2 Pole
IEC 61984, UL508, CSA C22.2 No. 14 CE, cURus, CSA, EAC, RoHS, REACH, China RoHS A 10 5 V 250V/300V 250V/300V IP20 III 3
oC oC
%
Insulation Rated insulation voltage (Ui) Rated impulse voltage (1.2/50us)
Dielectric Strength (RMS)
1 Pole
-40~+70 -40~+85 Operating: 10% to 85%
Between Contacts Between Adjacent Terminals Between Output and input terminals Between terminals and Din Rail Between Contacts Between Adjacent Terminals Between Output and input terminals Between terminals and Din Rail
N.m Min wire size, 0.2mm² N Max wire size, 1.5mm² N Max wire size, 2.5mm² N
V Kv Kv Kv Kv VAC VAC VAC VAC
250V 2.5 --
4
6 4 2500 -3000 5000 3000
Screw M3 IEC & NEMA 0.8 10 40 50
Flexible with cable end 1 wire 2 wires
0.2…2.5 mm², 22…14 AWG 0.2…1.0 mm², 22…17 AWG
Solid without cable end 1 wire 2 wires
0.5…2.5 mm², 20…14 AWG 0.5…1.5 mm², 20…16 AWG
Installation and Compatibility Mounting Panel mounting screw torque Panel mounting screw size (max) Schneider Electric - Industry Business – H2I – Relays Business
N.m mm
35mm Din Rail and Panel 0.8 3.5
7
Zelio RXG Differentiation
Complete offer Simple selection within wide offer range, onestop shopping covering all coil voltages.
Easy to use The only product in the market that allows to perform test without tool, thanks to the onestep lockable “test” button.
Flexible to adapt Easy and economic replacement and inventory, thanks to the optional separate protection modules.
Zelio RXG conforms with lots of industrial standards below: Estimated obtaining date is Mar 2014.
Schneider Electric - Industry Business – H2I – Relays Business
8
Zelio RXG Selection guide With test button
Relay
RXG●1 ●●
Socket
With test button and LED
RXG●2 ●●
1 C/O 10A
2 C/O 5A
1 C/O 10A
2 C/O 5A
24VAC
RXG11B7
RXG21B7
RXG12B7
RXG22B7
48VAC 120VAC
RXG11E7 RXG11F7
RXG21E7 RXG21F7
RXG12E7 RXG12F7
RXG22E7 RXG22F7
220VAC
RXG11M7
RXG21M7
RXG12M7
RXG22M7
230VAC
RXG11P7
RXG21P7
RXG12P7
RXG22P7
6VDC 12VDC
RXG11RD RXG11JD
RXG21RD RXG21JD
RXG12RD RXG12JD
RXG22RD RXG22JD
24VDC 48VDC 60VDC
RXG11BD RXG11ED RXG11ND
RXG21BD RXG21ED RXG21ND
RXG12BD RXG12ED RXG12ND
RXG22BD RXG22ED RXG22ND
110VDC
RXG11FD
RXG21FD
RXG12FD
RXG22FD
Screw connector
RGZE1S35M
RGZE1S48M RGZE1S35M
With LED
Relay
RXG●3 ●●
Socket
RXG●5 ●●
1 C/O 10A
RGZE1S48M
Clear cover 2 C/O 5A
1 C/O 10A
2 C/O 5A
24VAC
RXG13B7
RXG23B7
RXG15B7
RXG25B7
48VAC 120VAC
RXG13E7 RXG13F7
RXG23E7 RXG23F7
RXG15E7 RXG15F7
RXG25E7 RXG25F7
220VAC 230VAC
RXG13M7 RXG13P7
RXG23M7 RXG23P7
RXG15M7 RXG15P7
RXG25M7 RXG25P7
6VDC
RXG13RD
RXG23RD
RXG15RD
RXG25RD
12VDC
RXG13JD
RXG23JD
RXG15JD
RXG25JD
24VDC 48VDC 60VDC
RXG13BD RXG13ED RXG13ND
RXG23BD RXG23ED RXG23ND
RXG15BD RXG15ED RXG15ND
RXG25BD RXG25ED RXG25ND
110VDC
RXG13FD
RXG23FD
RXG15FD
RXG25FD
Screw connector
RGZE1S35M
Schneider Electric - Industry Business – H2I – Relays Business
RGZE1S48M RGZE1S35M
RGZE1S48M 9
Zelio RXG Selection guide Protection modules for all RXG sockets Description
Voltage (V)
Reference
Diode
6...230 VDC
RZM 040W
RC circuit
24…60 VAC 110...240 VAC
RZM 041BN7 RZM 041FU7
6…24 VDC
RZM 031RB
24…60 VDC 110…230 VDC
RZM 031BN RZM 031FPD
6…24 VAC/DC 24…60 VAC/DC
RZM 021RB RZM 021BN
110…230 VAC/DC
RZM 021FP
Diode + Green LED
Varistor + Green LED
Accessories Description
Reference
Legend
RGZL520
RXG* Relay
Plastic maintaining clamp
RGZR215
RGZ* Socket
Legend
RSZ L300
RGZ* Socket
Schneider Electric - Industry Business – H2I – Relays Business
For Use with
10