Transcript
DC Powered Relay Module Installation Instructions Jumper 1
Jumper 2
DO/D2/D3/D4/P3
CO J1
RL1
RL2
RL3
RL4
RL5
COM NO NC COM NO NC COM NO NC COM NO NC TB1 TB2 TB3 TB4
ZL-RRL16-24
RL6
Cable Connector
RL7
RL8
COM NO NC COM NO NC COM NO NC COM NO NC TB5 TB6 TB7 TB8
RL9
CO
DO/D2/D3/D4/P3
J2 RL10
RL11
RL12
COM NO NC COM NO NC COM NO NC COM NO NC TB9 TB10 TB11 TB12
RL13
RL14
RL15
RL16
COM NO NC COM NO NC COM NO NC COM NO NC TB13 TB14 TB15 TB16
Typical Internal Circuit Jumper Settings
Cable Connector
2.18” (55.5mm)
2.14” 54.3mm)
2.7K
I/O Module Series
J1
J2
DirectLOGIC +V
CLICK Productivity 3000
COM NO
35mm DIN RAIL
Terminal NC Block
General Specifications Description Mechanical Life Electrical Life Operating Frequency
16 Output Relay module with LEDs, 24 VDC coil 10,000,000 Operations at no load condition 1000,000 Operations at rated resistive load 20 cycles per minute electrical 300 cycles per minute mechanical
Contact Specifications Current Rating Contact Type Contact Voltage (per point)
10A @ 250VAC/30VDC
Maximum Power Inductive
2500VA General Use
1 Form C (SPDT) 250VAC/30VDC
Isolation Coil to Contact Isolation NC Contact to NO Contact Same Relay Isolation Between Relays LED Indicator State Relay Operating Temperature Range Humidity Range Vibration Resistance
2500VAC for 1 minute
Maximum Power Resistive
AC 2500VA, DC 300W
1000VAC for 1 minute
Maximum Switching Voltage
250VAC, 110VDC
1000VAC for 1 minute
Minimum Load Contact Resistance Contact Material
10mA @ 5VDC
10 to 55 Hz dual amplitude width 1.5mm
Input Voltage Rating
24VDC (±10%)
Shock Resistances
1000m/s² endurance 100m/s² operation Copper alloy, tin-lead plated
Maximum Continuous Coil Voltage
31.2VDC
Rated Current Coil Resistance Power Consumption per Relay Coil Supply Current Max. Pick Up Current Max. Drop-Out Voltage Min. Pick-Up Voltage Max. Off to On/On to Off Response Time
16.7mA (±10%) @ 24 VDC
Terminal Block Contacts Wire Range Wire Strip Length Screw Torque Dimensions (LxWxH) Replacement Relays Approvals Clearance Requirements
Red (on=relay on, off= relay off) 32 to 140°F (0 to 60°C)
0.24-0.27” (6-7mm) 4.4 in-lbs (0.5 Nm) 11.8” x 3.38” x 2.20” (300mm x 86mm x 55.88mm) ZL-RELAY-24X4, 1 Form C (SPDT) Qty. 4/pkg UL 508 4.00” (101.6mm) top and bottom
AgNi
Coil Specifications
45 to 85% RH
12-24AWG Solid or Stranded Conductor
100mΩ Max @ 1A, 6VDC
1440Ω (±10%) 0.4W 293mA (Total 16 relays) 15mA 1.2VDC 19.2VDC 8ms/12ms
ZL-RRL16-24
DC Powered Relay Module Installation Instructions
Remove or Install Relay
1
Rotate retaining clip away from relay.
DIN Rail Installation and Removal To install ZIPLink module, insert upper tab into DIN rail. Note: For clearance requirements see specifications.
2
Remove relay from module.
Rotate until firmly seated
Click and locked on DIN rail.
To remove ZIPLink module, insert screwdriver between Tab 1 and module.
Reverse procedure to replace relay.
WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes. Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation. If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call us at 770-844-4200. This publication is based on information that was available at the time it was printed. At AutomationDirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without any obligation. This publication may also discuss features that may not be available in certain revisions of the product.
Tab Pry up 1 to release clip from DIN rail.
Tab 2
Repeat for Tab 2.
ZIPLink Cable Removal
2
Pull connector from socket.
1 Push tab on raised tip and hold.
3505 Hutchinson Road, Cumming GA 30040 1-800-633-0405 www.automationdirect.com Copyright 2008, AutomationDirect.com Incorporated/All Rights Reserved Worldwide
4/25/2008 Document # ZL-LTB16-24 Rev1